Installation Instructions Models FDBZ492, FDBZ492-R and FDBZ492-HR

Similar documents
TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector

Installation Instructions Model ABHW-4S

PRODUCT OVERVIEW. SL-2000 AT-A-GLANCE MODEL NUMBER: SL-2000-N 4-Wire Ionization Duct Smoke Detector SL-2000-P 4-Wire Photoelectric Duct Smoke Detector

PRODUCT OVERVIEW SM-501 AT-A-GLANCE

You in Control PRODUCT OVERVIEW

INSTALLATION AND MAINTENANCE

DH100ACDCI Ionization Air Duct Smoke Detector

You in Control PRODUCT OVERVIEW SM-501 AT-A-GLANCE

DH100ACDCI Ionization Air Duct Smoke Detector

Installation Instructions Model CAB-BATT/R

RT-3000 SERIES NEMA 4X TYPE 4X ENCLOSURE WATERTIGHT CORROSION RESISTANT DUCT SMOKE DETECTORS

DH100LP Air Duct Smoke Detector with Extended Air Speed Range

Installation Instructions Model HZM

Installation Instructions Model DLC

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

Installation Instructions

DH400 Air Duct Smoke Detector

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

utomation omponents nc.

SK-Duct Air Duct Smoke Detector

E-PDD Duct Smoke Detector Installation Sheet

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

HS-100 AT-A-GLANCE MODEL NUMBER: HS-100-N 4-Wire Ionization Duct Smoke Detector HS-100-P 4-Wire Photoelectric Duct Smoke Detector

DH500 Intelligent Air Duct Smoke Detector Housing

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Air Duct Housings. Description

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS

DH500ACDC Intelligent Air Duct Smoke Detector Housing

7251DH Intelligent Air Duct Smoke Detector

Duct smoke housing, 2-wire D340/D340P

D2E Duct Smoke Detector

, -9686, -9688, -9755, Duct Detector/Sensor Installation Instructions

DNR Duct Smoke Detector

FX-PDD Duct Smoke Detector Installation Sheet

TS93 EMR WITH SMOKE DETECTOR

DNRECL Eclipse Duct Smoke Detector

DNRHS Intelligent Air Duct Smoke Detector

8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION

D343. Installation Instructions. Air Duct Smoke Housing

Intelligent Detection Devices

Application Data ! WARNING FACTORY INSTALLED SMOKE DETECTORS FOR SMALL AND MEDIUM ROOFTOP UNITS 2TO25TONS TABLE OF CONTENTS PART NUMBERS

DNR Duct Smoke Detector

DUCTSD Duct Smoke Detector

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

DNR-AUS Duct Smoke Detector

ARCHITECT AND ENGINEER SPECIFICATIONS

Model OOHC941 ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that has optical, thermal and CO sensors

Instructions. Duct Mount Accessory Q Rev: 11/

Installation Instructions

Addressable Detectors & Bases

INSTRUCTIONS. Duct Mount Kit Q900. Description. Operation

1400 Direct Wire Ionization Smoke Detector

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

TrueAlarm Analog Sensing

TrueAlarm Analog Sensing

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

Installation Instructions Model CDC-4

MANUAL RESET ALARM RELEASE

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

INSTALLATION INSTRUCTIONS Model FH-2071-UM Enclosure

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

Conventional Releasing Control Panel

SILENT KNIGHT. IntelliKnight Smoke Detector Cleaning and Testing Instruction. Equipment Needed. Testing Equipment. Cleaning Equipment

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

Installation Instruction Venturi-Air Duct Kit. (Part No. S )

MODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload

MANUAL RESET ALARM RELEASE

Installation Instructions Model SSD-C-REM

TECHNICAL DATA OBSOLETE

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Desigo Fire Safety intelligent detectors for complete safety

ESL 500N Series Smoke Detector Installation Sheet

FDBZ290 Air sampling smoke detection kit

RELEASE DEVICE CONTROLS

Duct and Rough Service Carbon Monoxide Sensor

Wiring Instructions (01-09)

MANUAL RESET ALARM RELEASE BOX

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation.

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

FDBZ290 Air sampling smoke detection kit

Desigo Fire Safety Marine Fire and Detection Equipment Models FH-2071-UM, BP-62 and USCG-HPLATE

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Basic Vehicle Fire Protection Manual

OOH740, OOHC740 Automatic fire detectors

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

Transcription:

Installation Instructions Models FDBZ492, FDBZ492R and FDBZ492HR Air Duct Monitoring Housings INTRODUCTION Models FDBZ492, FDBZ492R and FDBZ492HR from, are air duct monitoring housings containing sampling tubes. When used with a compatible smoke detector, smoke and combustion products are detected for shutdown of the duct system and/or operation of supplementary equipment as provided by the system control panel. See the following chart for usage. Model Compatible Detectors F DBZ492 PE11/11C, FP11/11C, HFP11, HFPO11, SFP11*, S FPO11*, 8854, 8713, 8710, OP121, FDO421, FDOOT441, FDOOTC441, OP921, OOH941, OOHC941 Relay No FDBZ492R PE11/11 C, 8854, OP121 Ye s FDBZ492HR F P11/11C, HFP11, HFPO11, S FP11*, SFPO11*, 8713, 8710, FDO421, FDOOT441, FDOOTC441, OP921, OOH941, OOHC941 Yes For compatible control equipment, see char harts on page 11 1 of this manual. TECHNICAL DATA AIR DUCT CONDITIONS Temperature Range: PE11/11C, FP11/11C, HFP11, HFPO11, SFP11*, SFPO11*, 8854, 8710, 8713, FDOOTC441, OOHC941, 32 O F (0 O C) 100 O F (38 O C) per UL 268 OP121, FDOOT441, OOH941, FDO421, OP921, 32 O F (0 O C) 120 O F (49 O C) per UL 268 Altitude Range: FDBZ492, FDBZ492R and FDBZ492HR No altitude limitations Relative Humidity Range: 095% (noncondensing/nonfreezing) Air Duct Velocity Range: 1004000 ft/min FDBZ492, FDBZ492R and FDBZ492HR Sampling Tube Pressure Range of Differences: Greater than 0.01 and less than 1.2 inches of water column These air duct detectors are designed for detection and control of products of combustion in a duct system. They are not to be used for open area protect ection. DO NOT USE air duct detectors with Alarm Verification. *The SFP11 and SFPO11 are approved for use in Canada only. A6V10336866_en_d Building Tec echnologies Division

ASSEMBLY This detector has a cover tamper (removal) switches. Care should be taken when installing the cover. Squarely place the cover on the unit to aviod possible damage to the switches. DO NOT SLIDE COVER INTO POSITION. APPLICATION The duct smoke detectors provide early detection of smoke and products of combustion present in air moving through an HVAC duct supply, return, or both. These devices are designed to prevent the recirculation of smoke in areas by the air handling system s fans and blowers. Complete systems may be shut down in the event of smoke detection. For the correct installation of a duct smoke unit please refer to NFPA 72 (National Fire Alarm Code), NFPA 90A (Standard for Installation of Air Conditioning and Ventilation Systems) and NFPA 92A (Recommended Practice for Smoke Control Systems). OPERATION When the Models FDBZ492, FDBZ492R and FDBZ492HR are operating, a sample of air is drawn from the duct and passed through the sampling chamber by means of the input sampling tube. The air sample passes through the smoke detector mounted in the duct housing and is exhausted back into the duct through the outlet tube. This detector is equipped with cover removal switches (SW1, SW2) that instantly provides a trouble condition upon removal of the clear cover. For all testing and inspection with the cover removed, the cover removal switches (designated as SW1, SW2 on PCB) must be manually depressed to simulate normal operation. LED Indicator The FDBZ492, FDBZ492R and FDBZ492HR contain an LED indicator (located on the smoke detector) capable of flashing either one of three distinct colors: green, yellow, or red. During each flash interval, the microprocessor based detector checks the following: for smoke in its sensing chamber that its critical smoke sensing electronics are operating. Based on the results of these checks, the LED indicator flashes as follows: Flash Interval (Seconds) Flash Color Condition PE11/ PE11C /8854 FP11/FP11C/ HFP11/HFPO11/ SFP11/SFPO11/ 8710/8713 OP121 FDO421/OP921 FDOOT441/ FDOOTC441/ OOH941/ OOHC941 G reen Normal supervisory operation. 7 4 10 8 10 Yellow Detector requires service (cleaning or repair) or is operating beyond its environmental specifications.* 730 4 5 4 4 Red No Flashes Alarm Detector is not powered, repair/replacement. or requires 2½ 4 2½ 1 1 *Note: OP121, FDO421, OP921, FDOOT441, FDOOTC441, OOH941, OOHC941 detectors are not serviceable and need replacement. A6V10336866_en_d 2

TYPE A: CLOSED SYSTEM NO EXHAUST FRESH AIR INTAKE FILTER BLOWER RETURN AIR D PLENUM D SUPPLY AIR C L AIR DUCT HOUSING AIR DUCT HOUSING OUTLET TUBE INPUT SAMPLING TUBE TYPE B: PROVISION FOR EXHAUSTING SOME PERCENTAGE OF RETURN AIR EXHAUST AIR OUTPUT FRESH AIR INTAKE FILTER BLOWER CENTER LINE OF DUCT RETURN D AIR AIR DUCT HOUSING PLENUM D SUPPLY AIR AIR DUCT HOUSING TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER FRESH AIR INTAKE EXHAUST AIR OUTPUT FILTER BLOWER RETURN AIR D PLENUM D SUPPLY AIR RETURN AIR AIR DUCT BLOWER HOUSING AIR DUCT HOUSING Figure 1 Typical Mounting of Duct Housing Figure 2 Recommended Locations in Duct Systems MOUNTING THE AIR DUCT HOUSING Location on Duct System This guideline contains general information on duct smoke detector installation, but does not preclude the NFPA documents listed. assumes no responsibility for improperly installed duct detectors. To determine the correct installation position for a duct smoke detector, the following factors must be considered. 1) A uniform nonturbulent (laminar) airflow between 100 ft/min. to 4,000 ft/ min. must be present in the HVAC duct. To determine duct velocities, examine the engineering specifications that define the expected velocities or use an Alnor model 6000AP velocity meter (or equivalent). 2) To minimize the impact of air turbulence and stratification on performance, a duct smoke detector should be located as far as possible downstream from any obstruction (i.e. deflector plates, elbows, dampers, etc.). In all situations, confirmation of velocity and pressure differential within specifications is required. The pressure differential between the input sampling (high pressure) tube and outlet (low pressure) tube for the smoke duct detector should be greater than 0.01 inches of water and less than 1.2 inches of water. 3) Identify a code compliant location (supply or return side, or both) for the installation of the duct unit that will permit easy access for viewing and serviceability. 4) When installing on the return side, install duct units prior to the air being exhausted from the building or diluted with outside fresh air. A6V10336866_en_d 3

Duct Preparation 5) When installing duct smoke units downstream of filters, fires occurring in the filters will be detected, but if the filters become blocked, insufficient air flow through the duct unit will prevent the correct operation of the duct detector. Duct units installed in the supply air side may monitor upstream equipment and/or filters. 6) Where possible, install duct detectors upstream of air humidifiers and downstream of dehumidifiers. 7) To prevent false alarms, the duct detector should not be mounted in areas of extreme high or low temperatures, in areas where high humidity exists, or in areas where the duct may contain gases or excessive dust. The Air Duct Housings come with an installation kit that contains the following items: Short return (outlet) sampling tube Stopper Two #12 x 3 /4 sheet metal screws Mounting template (packaged separately) Remove mounting template from the installation kit. Remove paper backing from the mounting template and affix it to the duct at the desired location. Using the template as a guide, drill (2) mounting holes, 3/32" (2.5mm) for the #12 X 3 /4 sheet metal screws packaged in the installation kit. Drill or punch (2) 1¼ (32mm) holes for input sampling and outlet tubes, using the template as a guide. Clean all holes. Sampling Tube Installation The duct smoke detectors use a specially notched sampling tube, which may be ordered separately in one of four standard lengths. ST10 For duct widths of 6" to 1.0 ST25 For duct widths of 1.0 to 3.0 ST50 For duct widths of 3.0 to 5.0 (requires support) ST100* For duct widths of 5.0 to 10.0 (requires support) * This model is supplied as two 5 ft. sections with a coupling. Assembly is required for installation. Each model is manufactured with a different number and size of sampling holes. Only the specific tube must be used for the specified duct width. Standard sampling tubes are steel tubes with air intake holes drilled the entire length of the tube. These tubes can be cut to length and must span at least 80% the width of the duct. Sampling tubes over 3.0 must be supported on the opposite side of the duct. To ensure the correct operation, the red stopper (stopper in installation kit) must be inserted in the end of the air input sampling tube. If the input tube protrudes through the opposite side of the duct, the opening around the tube must be sealed. For custom duct widths, always use the next longest standard size and cut down to the exact requirement. A6V10336866_en_d 4

TUBE SUPPORT ONLY FOR DUCTS GREATER THAN 3 FEET WIDE DUCT WIDTH AIR FLOW DIRECTION INSERT RED STOPPER THIS END OF INPUT TUBE INPUT TUBE HOLES FACE AIR FLOW OUTLET TUBE INSTALLED DOWNSTREAM OF AIRFLOW DO NOT INSERT RED STOPPER NOTE: Mountings shown are typical. Detectors can be installed side, bottom or top of duct as long as proper tube operation and flow/pressure performance is maintained. Figure 3 Sampling Tube Orientation Once the airflow direction has been determined (refer to Figure 3), insert the input and outlet tubes into the duct housing. Mounting 1. Remove the cover from the housing. 2. Loosen the screw and rotate the tube retainer until the input tube is inserted and oriented properly. Ensure that the notched end of the tube is inside the housing and that the air input sampling tube is positioned so that the input holes are directly facing the airflow. 3. Once the tube is installed, rotate the retainer back into place and tighten screw. 4. Install the outlet tube in the remaining position. Once the tube is installed, rotate the retainer back into place and tighten screw. After securing the input and outlet tubes to the duct smoke unit, (or initially placing the tubes through the 1¼ holes drilled or punched in the HVAC duct to accept the input and outlet tubes and then attaching them to the duct unit), hold the duct unit assembly in position and use (2) # 12 X 3 /4 sheet metal screws (packaged in the installation kit) to secure the duct smoke detector to the HVAC duct sheet metal. Air Duct Sampling Tube Pressure Measurement The Model PDM3 Pressure Differential Measuring device should be used to ensure that the sampling tube pressure differential is within the specified limits. The differential pressure between the two tubes should be greater than 0.01 inches of water and less than 1.2 inches of water. Qualified personnel should take measurements in accordance with the PDM3 instructions, P/N 315085535. A6V10336866_en_d 5

WIRING Conduit Knockouts Determine knockout size required based upon installation wiring. Refer to Figure 4. Select knockout and remove by placing screwdriver at center of knockout and tap with a hammer until the knockout breaks out. Clean the hole before installing conduit. Figure 4 Removing the Knockouts 1/2 KNOCKOUT 3/4 KNOCKOUTS Wiring The FDBZ492, FDBZ492R and FDBZ492HR should be connected as shown in Figures 5, 6, 7 and 8. Note any limitations on the number of detectors and restrictions on the use of remote devices permitted for each circuit. Installation Of Smoke Detectors The FDBZ492 is used with the 8854, PE11/PE11C, FP11/FP11C and OP121. It is also used with the HFP11/HFPO11, 8710, 8713 detector in the FireFinderXLS, FS 250 or MPC6000, 7000 System. The FDBZ492 is also used with the SFP11/SFPO11 detector in the FS250C System. The FDBZ492 is also used with the FDO421, FDOOT441, FDOOTC441, OP921, OOH941, OOHC941 detector in the Desigo and Cerberus Fire Alarm Systems. The FDBZ492HR must be used for the relay version. Also, all optional accessories in the same loop must be compatible with the detector series being used. These devices should be interconnected as shown in Figure 7 and wired to the DLC, FSDLC or FDLC. (Refer to the DLC Installation Instructions, P/N 315033090, or the FS250, P/N 315049353, or the FS250C Manual, P/N 315 049589C, or the MPC6000/MPC7000 Manual, P/N 315447309, as applicable.) The HFP11, HFPO11, SFP11, SFPO11, 8710, 8713, FDO421, FDOOT441, FDOOTC441, OP921, OOH941, and OOHC941 are polarity insensitive detectors. Line 1 and Line 2 can be either line of the loop. Note any limitations on the number of detectors and restrictions on the use of remote devices permitted for each circuit. When replacing a detector with a different model, be aware that existing detector accessories connected to the base or air duct housing that were compatible with the old detector may not be compatible with the new detector. Always read the Installation Instructions accompanying the detector to determine detector and accessory compatibility. To Install: Remove cover by loosening the four screws. Take off the cover and set it aside. Align detector with base and insert detector. Rotate detector clockwise while gently pressing on it until the detector drops fully into base. Then rotate the detector clockwise until it stops and snaps in place. Replace cover and tighten the four screws. To Remove: Rotate the detector counterclockwise until stop is reached. Pull detector out of base. A6V10336866_en_d 6

TESTING Sensitivity Test Only qualified service personnel should test these units. To assure proper operation of the detector and control panel, both the Sensitivity and the Functional tests should be conducted. The minimum test schedule may be found in the current edition of NFPA 72 for installations in the U.S. and CAN/ULCS537, The Verification of Fire Alarm Systems, for installation in Canada. The PE11/11C, 8854, OP121 detector monitors its smoke sensitivity automatically and requires no test equipment. A green flash of the detector LED indicates that the smoke sensitivity is within its listed limits. The following detector models are analog types that must be programmed for the air duct application using the control unit configuration tool; that is, CSGM, Zeus, FSCT2, Desigo Programming Tool or Cerberus Programming Tool, as applicable. To test the FP11/11C detector refer to its installation instructions. See Table 9. To test the HFP11/HFPO11/SFP11/SFPO11 detector refer to its installation instructions. See Table 9. These tests ensure that the detector is within its listed and marked sensitivity range. For additional instructions on applying the Sensitivities mode, refer to the FireFinder XLS Manual, P/N 315033744, the DPU Manual, P/N 315033260 or the SDPU Manual, P/N 315033260C. Functional Test Smoke Testing Using P/N 500649750 TG11 smoke test canister with testing nozzle model ADTGN P/N 500649717 (purchased separately) available from, insert the test gas nozzle into the hole in the red plug in the unit cover. Press can against cover for about 1 /2 second to release gas into the chamber. DO NOT SPRAY GAS FOR MORE THAN ½ SECOND. OVERUSE OF TEST T GAS MAY RESULT IN DETECTOR CONTAMINA AMINATION. After 15 to 20 seconds the detector will go into alarm, illuminating the detector LED and causing the duct unit functions to operate; alarm relays will change state, and the alarm related remote accessories, if attached, will function. If no test gas is available to conduct functional testing, remove cover and, while holding down the cover removal switch, blow smoke from a smoldering cotton wick or punk directly at the head to cause an alarm. The alarm indicator on the detector should illuminate within one minute. A6V10336866_en_d 7

NOTES: 1. Up to 30 air duct housings can be installed on one initiating circuit, except as noted in Note 2. 2. When an FDBZ492R is used to control a fire safety function, the FDBZ492R must be the ONLY device on the initiating circuit. 3. Do not use looped wire under base terminal. 4. Break wire run to provide supervision of connection. 5. The green grounding screw in the wiring compartment of the air duct housing is not used. 6. Please follow Pin designation in Table 1, 2. If the relay contacts are being used to control 120 VAC operated equipment, ensure that the conduit is properly attached to the internal metal ground strap, using the proper conduit locking nuts. Failure to provide proper grounding may result in fatal electrical shock and violation of national and local codes. Model FDBZ492 For Wiring Information Refer to Table 1 MODEL FDBZ492R For Wiring Information Refer to Table 2 8854 PE11 PE11C OP121 8854 PE11 PE11C OP121 7 6 5 4 3 2 1 2 3 1 4 5 6 7 8 9 NC COM NO Alarm Contacts 125VAC, 24VDC, 2.5A See note 2 Loop Wires + To next detector or See compatible control equipment table + Remote Devices or EOL Device CNTL Loop Wires + See compatible control equipment table CNTL + To next detector or to 2nd remote (See multiple remote devices) or EOL device Pin TABLE 1 Designations Descriptio n 7 Not Use d 6 Device Loop + / Remote + 5 Device Loop + 4 Not Use d 3 Remote Contro l 2 Device Loop 1 Device Loop Remote SEE REMOTE DEVICE INSTRUCTIONS FOR WIRING DETAILS: DEVICE RLC11, RLW11 RSAC11, RSAW11 FDBZ492RTL INSTALLATION INSTRUCTIONS P/N 315094925 P/N 315094926 P/N A610335440 Pin TABLE 2 Designations Descriptio n 1 Device Loop + 2 Not Use d 3 Device Loop 4 Device Loop/Rem 5 Remote Contro l 6 Device Loop Remote + 7 Relay Normally Closed Contact (NC ) 8 Relay Common Contact (COM ) 9 Relay Normally Open Contact (NO ) MULTIPLE REMOTE DEVICES If remote devices are supported by the initiating circuit, each detector/base may have up to 2 remote devices with the following configurations and restrictions only: Remote Device 1 FDBZ492 FDBZ492 FDBZ492 Remote Device 2 RLC11, RLW11 RSAC11, RSAW11 FDBZ492RTL Restrictions See Note 2 See Note 2 See Note 2 Figure 5 Typical Connections for the FDBZ492 / FDBZ492R Using PE11 / PE11C, 8854, or OP121 Detectors / / A6V10336866_en_d 8

NOTES: 1. The relay contacts are shown after a reset pulse, which represents the nonalarm condition. 2. The green grounding screw in the wiring compartment of the air duct housing is not used. 3. Please follow the pin designation on Table 3 4. If the relay contacts are being used to control 120 VAC operated equipment, ensure that the conduit is properly attached to the internal metal ground strap, using the proper conduit locking nuts. Failure to provide proper grounding may result in fatal electrical shock and violation of national and local codes. MODEL FDBZ492 For Wiring Information Refer to Table 3 MODEL FDBZ492HR For Wiring Information Refer to Table 4 FP11 FP11C FP11 FP11C 11 Loop Wires + See compatible control equipment table 7 6 5 4 3 2 1 + + To next addressable detector Optional Remote Alarm Indicator Model RLI1 or RLI2 1 2 3 4 5 6 7 8 9 10 NO NC COM Loop Wires To next + + addressable See compatible control detector equipment table + Optional Remote Alarm Indicator Model RLI1 or RLI2 12 13 Pin TABLE 3 Designations Descriptio n 7 Not Use d 6 Not Use d 5 Remote + 4 Remote 3 Device Loop 2 Device Loop + 1 Not Use d Pin TABLE 4 Designations Descriptio n 1 Not Use d 2 Not Use d 3 Remote + 4 Remote 5 Device Loop 6 Device Loop + 7 Not Use d 8 Relay Normally Closed Contact (NC ) 9 Relay Common Contact (COM ) 10 Relay Normally Open Contact (NO ) 11 Not Use d 12 Not Use d 13 Not Use d Figure 6 Typical Connections for the FDBZ492 / FDBZ492HR Using FP11 / FP11C Detectors Alarm Contacts 125VAC, 24VDC, 2.5A See Note 1 A6V10336866_en_d 9

Loop Wires See compatible control equipment table If the relay contacts are being used to control 120 VAC operated equipment, ensure that the conduit is properly attached to the internal metal ground strap, using the proper conduit locking nuts. Failure to provide proper grounding may result in fatal electrical shock and violation of national and local codes. MODEL FDBZ492 For Wiring Information Refer to Table 5 MODEL FDBZ492HR For Wiring Information Refer to Table 6 HFP11 HFP11 SFP11 SFP11 HFPO11 HFPO11 SFPO11 SFPO11 8710 8710 8713 8713 FDO421 FDO421 FDOOT441 FDOOT441 FDOOTC441 FDOOTC441 OP921 OP921 OOH941 OOH941 OOHC941 OOHC941 Line 1 Line 2 7 6 5 4 3 2 1 Line 1 Line 2 TB2 TB3 To next addressable device Optional Remote Alarm Indicator Model RLHC or RLHW (see notes 2 and 6) Loop Wires See compatible control equipment table Line 1 Line 2 2 3 4 1 6 7 5 8 9 10 Line 1 Line 2 TB2 TB3 11 12 13 For connection to FDBZ492RTL only: NO NC COM Remote (+) Remote Control Remote () To next addressable device Alarm Contacts 125VAC, 24VDC, 2.5A See Note 2 Optional Remote Alarm Indicator Model RLHC or RLHW (see notes 2 and 6) Pin TABLE 5 Designations Descriptio n 7 Not Use d 6 Not Use d 5 Remote TB 1 4 Remote TB 3 3 Line 1 2 Line 2 1 Remote TB 2 Figure 7 Typical Connections for the FDBZ492 / FBDZ492HR Using Compatible Addressable Detectors in Polarity Insensitive Topology Pin TABLE 6 Designations Descriptio n 1 Not Use d 2 Not Use d 3 Remote TB 1 4 Remote TB 3 5 Line 1 6 Line 2 7 Remote TB 2 8 Relay Normally Closed Contact (NC ) 9 Relay Common Contact (COM ) 10 Relay Normally Open Contact (NO ) 11 Connection to + Power terminal of FDBZ492RT L 12 Connection to the Control terminal of FDBZ492RT L 13 Connection to Power terminal of FDBZ492RT L NOTES: 1. The relay contacts are shown after a reset pulse, which represents the nonalarm condition. 2. Refer to the RLHW / RLHC Installation Instructions, P/N 315033230. 3. The green grounding screw in the wiring compartment of the air duct housing is not used. 4. For polarity insensitive topology, follow the pin designation on Table 5, 6 (Figure 7) 5. For connection to FDBZ492RTL only. This allows manual control of the relay output of FDBZ492HR for testing purposes only. The LED on the FDBZ492RTL indicates the status of the relay: GRN in supervisory state; RED in alarm state. 6. When using relay housing with the FDO421, FDOOT441, FDOOTC441, OP921, OOH941, or OOHC941 devices and remote lamp, the RLHW/RLHC cannot be used. Instead, use the ILEDH series programmed to Active Mode. Refer to the ILEDHC/ILEDHW Installation Instructions, P/N 315048637 for details. A6V10336866_en_d 10

Refer to the following Installation Instructions for additional information on testing each of these detectors: TABLE 9 Detector Installation Instruction PE11 315094198 PE11C 315095626 FP11/11C 315095921 HFP11 315033290 HFPO11 315034800 SFP11 315033290C SFPO11 315033290C FDO421 A6V10323926 FDOOT441 A6V10324655 FDOOTC441 A6V10324657 8854 315094198FA OP121 A6V10281367 8710 315033290FA 8713 315033290FA OP921 A6V10323928 OOH941 A6V10324659 OOHC941 A6V10324661 The FP11, HFP11, SFP11, HFPO11, SPFO11, 8710, 8713, FDO421, FDOOT441, FDOOTC441, OP921, OOH941, and OOHC941 detectors can also be tested individually using the DPU. Refer to the DPU Manual, P/N 315033260. The SFP11 and SFPO 11 detectors can be tested individually using the SDPU. Refer to the SDPU Manual, P/N 315033260C. MAINTENANCE The performance of the air duct detector unit may be adversely affected by dirt or foreign matter on the sampling tubes or detector. If the air holes in the input sampling tube become restricted, the unit cannot receive a proper air sample, and performance is impaired. It is recommended that the sampling tubes be checked and cleaned periodically. The detector maintenance program should consist of periodic cleaning of dust from the detector head by using a vacuum cleaner. For cleaning Models PE11, PE11C, FP11, FP11C, HFP11, HFPO11, SFP11 or SFPO11, refer to the detector s Installation Instructions (See Table 9). The cleaning and test program is recommended for 6 month intervals, or more frequently, if needed, depending on the individual detector environment. Consult your local code and AHJ requirements for required maintenance schedules. Under no circumstances is the detector ector portion of the unit to be disassembled by anyone other than an authorized Syst stems Tec echnician. For service, contact your nearest authorized Service Represent epresentat ative. If the fire alarm syst stem em is connected ed to a central stat ation or fire department, or operates es external ernal devices such h as fans, extinguishers, etc., connected, ed, notify appropriate e personnel and disconnect the external ernal devices until il all tests are completed. ed. After er test esting, reset the syst stem, reconnect the devices, and notify the personnel that the syst stem em is operating ing again. ain. COMPATIBLE CONTROL EQUIPMENT FDBZ492 AND FDBZ492R USING PE11/11C/8854/OP121 DETECTOR Module Equipment Compatibility Identifier Module Installation/ Wiring Instructions CDC4 (FireFinderXLS) P/N 3150341008 CP35 (SYSTEM 3) P/N 31508490222 * CZM1B6 (MXL, MXLIQ) P/N 3150953559 CZM4 (MXL, MXLIQ) P/N 31509082610 H ZM ( FireFinderXLS, FS250, FC2050, FC2025, FC2005, FC922, FC924, FC901) P/N 3150348506 SXLEX P/N 3150959978 SZE4X (SXLEX) P/N 3150960188 SZE8AX (SXLEX) P/N 3150960228 * SZM (FS250C) P/N 315034850C4 ZU35 (SYSTEM 3) P/N 31508322218 8705 (MPC6000/MPC7000) P/N 3154473098 A6V10336866_en_d 11

FDBZ492 AND FDBZ492R USING FP11/11C DETECTOR Module Equipment Compatibility Identifier Module Installation/ Wiring Instructions ALD2I (MXL, MXLIQ) P/N 31509146413 MMB2 (MXL) P/N 3150950978 MMB3 (MXL) P/N 3150488607 SMB2 (MXLIQ) P/N 3150959317 FDBZ492 AND FDBZ492HR USING HFP11, HFPO11, 8710, 8713 DETECTOR Module Equipment Compatibility Identifier Module Installation/ Wiring Instructions DLC (FireFinderXLS) P/N 31503309010 FSDLC (FS250) P/N 31504935310 FDLC (MPC6000/MPC7000) P/N 3154473098 FC2050, FC2025 P/N A6V10337045 FC2005 P/N A6V10333722 FC922, FC924 P/N A6V10356958 FC901 P/N A6V10336754 FDBZ492 AND FDBZ492HR USING FDO421, FDOOT441, FDOOTC441, OP921, OOH941, OOHC941 DETECTOR Module Equipment Module Installation/ Compatibility Identifier Wiring Instructions FC2050, FC2025 P/N A6V10337045 FC2005 P/N A6V10333722 FC924, FC922 P/N A6V10356958 FC901 P/N A6V10336754 FDBZ492 AND FDBZ492HR USING SFP11 OR SFPO11 DETECTOR Module Equipment Module Installation/ Compatibility Identifier Wiring Instructions FDLC (FS250C) P/N 315049589C1 The detector model number is the compatibility identifier. *Control equipment does not support remote accessories; e.g., lamps or relays. ELECTRICAL RATINGS FOR PE11/11C, 8854, OP121 Voltage Ripple 1627 VDC 3V peaktopeak S upervisory Current 110 ua max. S tartup Time 50 seconds max. Alarm Current PE11/11C Detector PE11/11C Detector Remote Device 33 50mA 50 70mA + ELECTRICAL RATINGS FOR HFP11, HFPO11, SFP11, SFPO11, 8710, 8713, FDO421, FDOOT441, FDOOTC441, OP921, OOH941, OOHC941 Electrical ratings are not provided here for these detectors. Guidance for detector loop loading, along with loop wire electrical specifications are provided in the applicable control unit instructions given in the above Compatible Control Equipment tables. A6V10336866_en_d 12

Cyber security disclaimer Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept. It is, however, necessary to implement and maintain a comprehensive, stateoftheart security concept that is customized to individual security needs. Such a security concept may result in additional sitespecific preventive action to ensure that the building comfort, fire safety, security management or physical security system for your site are operated in a secure manner. These measures may include, but are not limited to, separating networks, physically protecting system components, user awareness programs, defense in depth, etc. For additional information on building technology security and our offerings, contact your Siemens sales or project department. We strongly recommend customers to follow our security advisories, which provide information on the latest security threats, patches and other mitigation measures. http://www.siemens.com/cert/en/certsecurityadvisories.htm A6V10336866_en_d 13

This page has been left intentionally blank. Florham Park, NJ Siemens Canada, Ltd. 1577 North Service Road East Oakville, Ontario L6H 0H6 Canada P/N A5Q00053166 Document ID A6V10336866_en_d