IFP-2.32 Manual 1) DESCRIPTION ICAS FIRE PANEL IFP 2.32

Similar documents
CU-IQ MANUAL 1. DESCRIPTION Radio Control Panel CU-IQ

Excel-EN Conventional Fire Control Panel

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Installation, Operating and Maintenance Manual

AL600ULADA. NAC Power Extender. Installation Guide

Model 17A00 Expansion Enclosure

Conventional Fire Alarm System 2014 V1.2

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

FEC400 Series. Installation Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

AL800ULADA. NAC Power Extender. Installation Guide

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

MR-2602 Two Zone Fire Alarm Control Panel

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Application, Installation, Operation & Maintenance Manual

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

REPEATER FS5200R INSTRUCTION MANUAL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

Technical Speci fications 220V AC 50Hz or 110V AC 60Hz Accessories operational voltage. 2x 12V / 7Ah sealed lead acid gel batteries

EXTINGUISHING CONTROL PANEL PX2 SERIES

S2000-ASPT. Fire Alarm and Extinguishing Control Panel. Engineer s and User s Manual

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

VAP304 PRO INSTALLATION & OPERATION MANUAL

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

Installation and user manual for the BiWire / Conventional Repeater Panel

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

Two-Channel Gas Controller

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

Interface and EOL Modules 8

TABLE OF CONTENTS TABLE OF CONTENTS 1

QA16 Addressable System

Specification/ Data Sheet

Fire control panel detect 3004 plus and accessories

Fire Control Panel FS5100

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

LF-4000 Series Conventional Fire Alarm Control Unit

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

INSTALLATION MANUAL PC15OO

Multi-Gas-Controller MGC2

Installation Instructions 4 Zone Fire Panel

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

HOME SECURITY MICROPROCESSOR CENTRAL UNIT HOME 5 USER S MANUAL

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

NEO XL NEO XL NEO XL POWER SUPPLIES - MADE IN SWEDEN ENGLISH

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

EAE/EAES «HEPHEA 248» Product Technical Instructions

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Addressable NAC Output Module D327A

Gas Central with built-in Gas Detector for Nitrogen Dioxide (NO 2

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

User Manual. Security Systems Security System L208

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

Installation Guide for models:

OPERATION AND INSTALLATION MANUAL

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Fire Control Panel FS4000

EXTINGUISHING AGENT RELEASE MODULE

General Routing Interface

FX FIRE DETECTION SYSTEM

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

VSN-RP1r Extinguishing Control Panel. User Manual (Software version 3.x) by Honeywell. doc. MIE-MN-570I rev.008

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

System 800 Addressable Fire Detection & Alarm System

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

EVO192 v3.0 Fire and Burglary What s New

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

INSTALLATION MANUAL PC56O. Version 1.OA

Installation Guide for models:

RMS/RPX Reader. User Manual

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

RE 102 RE Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

Chlorine gas leak detector

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

CA60Plus. Installation manual

TECHNICAL DATA OBSOLETE

Carbon Monoxide Transmitter

Transcription:

1) DESCRIPTION IFP-2.2 Manual IFP-2.8 and IFP-2.2 is a microprocessor controlled Fire Panel with 2 loops intended either for privat Homes & Apartments or larger installations. The two loops are balanced by 2k7 Ohm resistor mounted at the last detector in each loop. The device is named as IFP-Y.X, where Y describes number of loops and X number of detectors in the loop. IFP-2.8 can handle 8 detectors of standard 12V Icas detectors type 500-IDx or Icas type CHOR-E (9V) in each loop. IFP-2.2 can handle 2 detectors of standard 12V Icas detectors type 500-IDx or Icas type CHOR-E (9V) in each loop. This could be useful for larger installations. Connection of Detectors: - 500-IDx detectors do not have sound in the detector which trigger Alarm unless a 4 wire solution is used otherwise uses external siren. The siren is controlled by the IFP-2.2 Fire Panel. The alarm relay of IFP-2.2 can be used for external siren control. - CHOR-E detectors (9V detector) can be connected only Alarm in one Alarm in all function. The different functions are chosen by use of jumper. The IFP-2.2 is supplied by 20V AC and the internal backup 12V/0,8Ah. The IFP-2.2 is equipped with one internal siren, fault relay, alarm relay and 2 open collectors, each for one loop. The IFP-2.2 is controlled by 4 underlighted pushbuttons. In the IFP-2.2 is possible to control each loop separately by the functions for Switch OFF/ON loops, also Switch OFF/ON the Test of loops, remove Alarm and Fault in loops. The IFP-2.2 includes also complete functions for battery testing and firmware testing. When the Alarm is triggered, the internal siren of IFP-2.2 and siren of detectors shall be silenced with pushbutton SIREN. This will stop the sirens of detectors. Removing of Alarm and other control functions are described in chapter Button Functions. 1

2) INSTALATION IFP-2.2 AND SMOKE DETECTORS Place the Fire Panel in vertical position near a power outlet. Use minimally 2 screws in upper part of the Fire Panel box for fixing to the wall. Install the Fire Panel at least 0.5m from fuse box or other electrical appliances. Be aware that EMC can harm the Fire Panel. Recomended place for Fire Panel fixing 20V Terminal Low power terminals side Battery Switch jumper Connect the 20V into the terminal on the left side of the IFP-2.2. Connect the Detectors and siren. Follow pictures on the page 2 and page. The recommended detector cable type is AF CEI 20-22 IEC 2 or VD-04 shielded cable, or equivalent type. Shield of the cable has to be terminated in the 0V in all the Detectors and to Shield terminal in the Fire Panel. Set all jumpers in correct position. Switch the Jumper for backup battery (Battery Switch) and it shall always be on! IFP-2.2 shall be powered from a separate circuit protected by overvoltage protection level II and by an automatic Fuse. This fuse shall be tripped to disconnect the Fire Panel when work is to be done. IFP-2.2 is equipped with automatic 0.125A overcurrent protection. 2

CONNECTION 500-IDX SMOKE DETECTORS CONNECTION CHOR-E SMOKE DETECTORS (Connection meets EN52-2 with only the exception of clause 8.2.4. - Removal of a point)

JUMPERFIX: 500-IDX SWITCH BATTERY SWITCH Shorted 12V loop output voltage Open 9V loop output voltage Shorted Backup battery connected (Normal operation). Open Backup battery is not connected (The Detectors do not work after power cut). FUNCTION: If IFP-2.2 main power on and battery switch is open, the power supply fault occurs. IFP-2.2 is started right when battery switch is shorted and main power on. The IFP-2.2 waits for establish of the current in the loops min (Establishing signalization). Then the current loop is detected. The right loop current (EOL has right value, any shorts and any opens) is signalized by the 2 flashes of the blue LED and by 2 short beeps (LOOPS GUARD MODE). The IFP- 2.2 is in guard mode from this moment. Fire alarm is detected in the loop when current is higher than 12 ma. Fault alarm is detected when the loop is open or when the loop is shorted. If the battery is very low and starts to be undercharged and main power is off, the IFP-2.2 is switched off. ) LED SIGNALIZATION Dark, No light, power is OFF; blinking powered from Battery; Power Lights main power is ON Level 2 Lights for button functions in level 2 System Fault Software error, memory error Alarm Main Alarm Fault Main Fault Off Main Off Test Main Testing Power supply fault If lights, the charger does not work, the battery is not connected, or the battery is low Loop A Red = Alarm, Yellow blinking = Fault, Yellow and Off lights = Loop is off, Yellow and Test lights = Loop in Test Loop B Red = Alarm, Yellow = Fault, Yellow blinking and Off lights = Loop is off, Yellow blinking and Test lights = Loop in Test ALARM: one of the loops is in alarm state, < 12mA 160mA > current detected can be switched off only in level 2 sound signalization can be suppressed in level 1 4

FAULT: Loop open or short Loop A or Loop B When the fault is removed The signalization can be switched off manually only in level 2 or automatically in 1 min. sound can be suppressed in level 1 SYSTEM FAULT: undefined runs in program or reset of the unit, or flash memory error could be switched off only by switching off the unit POWER SUPPLY FAULT: the battery charger does not work, battery is disconnected or the battery is low POWER SUPPLY FAULT led signalization is dark (reset) after the battery is fully charged it can not be reset in another way OFF: The loop is switched off/on only in level 2 The actual Loop & LED is lightning TEST: At least one loop is in test mode Can be switched off / on in level 2 Actual Loop & LED is flashing OK SIGNALIZATION: POWER LED 2x flashes and 2x short beeps Used for signalizing that the button command was received Occurs after each complete right button command LOOPS GUARD MODE: 2x blue LED flashes and 2x short beeps occurs after min, when the loop is established and there is any loop fault ESTABLISHING SIGNALISATION: 1x blue flash and the loop which is establishing is signalized by 1x yellow flash flashing occurs after some fault or reset of the loop, where the loop needs to be established it continues min, and is followed by LOOPS GUARD MODE signalization 5

4) BUTTON FUNCTIONS There are two levels of the manual control. Following tables can be used for simple guide to control IFP-2.2 unit. Button Function 1-Level 1 Control : Button function 1 - LEVEL 1 Control Button LEVEL 1 A - B - AB at the Enter into LEVEL 2 same time Siren Silent of sounds Lamp All LEDs light control In the level 1 buttons A and B have any function. The user can press also AB at the same time and enter into level 2. Buttons Lamp and Siren has only one function. Siren is for silent of the sound and Lamp is for test LEDs lights. Button Function 2-Level 2 Control : The table Button function 2 ALARM RESET can be used step by step to Reset the alarm in loops. NOTE! The detectors in the loop is not in alarm (the current in the loop is lesser than 12 ma). 1. First step is entering into LEVEL 2 Press AB at the same time If received OK Signalization occurs (step 1). 2. Press and hold A (B) (step 2).. Then hold A(B) and press 1x B (A) for Alarm Reset Choice in the loop. The control choice can be checked by ALARM blinking LED. Do not release the button A(B). The control choice is confirmed by A(B)Lamp button If received OK Signalization occurs (step ). 4. Release All buttons (step 4). Button function 2 - ALARM RESET LOOP A 2 Press and hold A LOOP A Choice Hold A 1x B ALARM LOOP A Reset Choice 6

Button function 2 - ALARM RESET LOOP B 2 Press and hold B LOOP B Choice Hold B 1x A ALARM LOOP B Reset Choice The table Button function FAULT RESET can be used step by step to delete fault manually in loops. Important! The fault of the loop has been fixed. In case that the Loop-fault has been removed, the Fault-Alarm is Reset automatically, or manually. 1. First step for manual removing The Fault-Alarm is entering into LEVEL 2. Press AB at the same time If received OK Signalization occurs (step 1). 2. Press and hold A (B) (step 2). Then hold A(B) and press 2x B(A) for Fault Reset Choice in the loop. The control choice can be checked by FAULT blinking LED. Do not release the button A(B). The control choice is confirmed by A(B)Lamp button If received OK Signalization occurs (step ). 4. Release All buttons (step 4). Button function - FAULT Reset LOOP A 2 Press and hold A LOOP A Choice Hold A 2x B FAULT LOOP A Reset Choice 7

Button function - FAULT Reset LOOP B 2 Press and hold B LOOP B Choice Hold B 2x A FAULT LOOP B Reset Choice The table Button function 4 LOOP ON/OFF can be used step by step for switch on or switch off the loop. 1. First step is entering into LEVEL 2. Press AB at the same time If received OK Signalization occurs (step 1). 2. Press and hold A (B) (step 2). Then hold A(B) and press x B (A) for Switch Off/On Choice in the loop. The control choice can be checked by OFF blinking LED. Do not release the button A(B). The control choice is confirmed by A(B)Lamp button If received OK Signalization occurs (step ). 4. Release All buttons (step 4). 5. Press LampSiren at the same time for LEVEL 2 switching off. LEVEL 2 can be switched off also automatically by waiting 0s (step 5). Button function 4 LOOP A OFF/ON 2 Press and hold A LOOP A Choice Hold A x B LOOP A is in Off / On Choice 5 LAMPSIREN at the same time, or wait 0 s Exit LEVEL 2 and return into LEVEL 1 8

Button function 4 LOOP B OFF/ON 2 Press and hold B LOOP B Choice Hold B x A LOOP B is in Off / On Choice 5 LAMPSIREN at the same time, or wait 0 s Exit LEVEL 2 and return into LEVEL 1 The table Button function 5 LOOP TEST ON/OFF can be used step by step for switch on or switch off the test of the loop. 1. First step is entering into LEVEL 2. Press AB at the same time If received OK Signalization occurs (step 1). 2. Press and hold A (B) (step 2). Then hold A(B) and press 4x B (A) for Switch Off/On Test Choice of the loop. The control choice can be checked by TEST blinking LED. Do not release the button A(B). The control choice is confirmed by A(B)Lamp button If received OK Signalization occurs (step ). 4. Release All buttons (step 4). 5. Press LampSiren at the same time for LEVEL 2 switching off. LEVEL 2 can be switched off also automatically by waiting 0s (step 5). Button function 5 - LOOP A TEST OFF/ON 2 Press and hold A LOOP A Choice Hold A 4x B LOOP A is in Test Off / On Choice 5 LAMPSIREN at the same time, or wait 0 s Exit LEVEL 2 and return into LEVEL 1 Button function 5 - LOOP B TEST OFF/ON 9

2 Press and hold B LOOP B Choice Hold B 4x A LOOP B is in Test Off / On Choice 5 LAMPSIREN at the same time, or wait 0 s Exit LEVEL 2 and return into LEVEL 1 1

Simple Map of Button functions : A1x pressed B for ALARM Reset A2x presed B for FAULT Reset A (press not release) Applied for LOOP A Ax pressed B for Switch Off/On A4x pressed B for Switch Test Off/On LAMP Test of Signalization LAMP Test of Signalization ALAMP for confirmation previous choices LEVEL1 control AB Enter LEVEL2 menu SIREN Silent of sounds A1x pressed B for ALARM Reset SIREN Silent of sounds B (press not release) Applied for LOOP B A2x presed B for FAULT Reset Ax pressed B for Switch Off/On A4x pressed B for Switch Test Off/On ALAMP for confirmation previous choices LAMPSIREN Return into LEVEL1 11

5) PARAMETERS POWER SUPPLY Power supply: Operating voltage: Power consumption normal: Minimal load ( Imin ) Maximal load (Imax a) Maximal load without charging (Imax b) BATTERY SUPPLY Backup batteries: Backup time: Charger current: Power consumption normal: Battery cut-off voltage: 10.5V /- 0.2V Fault battery internal resistor: >1Ω DETECTION LOOPS Number of loops: 2 20V ( 10% / - 15% ) ~ 50Hz 14 V <60 ma 2 ma 480 ma 600 ma Pb, 12V / min. 0,8 Ah 24 h / 15 min in alarm <0.2 A <20 ma Max. number of detector in loop: 2 (max. 0.64 ma) Max. possible number of detector: 64 Max. possible number of sirens: 2 detectors 500-IDX type End of line resistor: 2k7 Ohm / (CHOR-E 2k Ohm) Current in loop for alarm detection: min. 12mA - max. 160mA (max. 8 detectors 500-IDX) Output loop voltage: 12 V (/ 20%) / (for CHOR-E 9.5V (/ 5%)) OUTPUTS Fault relay: 1x 125VAC / 0.5A, 24VDC / 1A Alarm relay: 1x 125VAC / 0.5A, 24VDC / 1A Transistor outputs (OC): 2x 14V / 0.1A Power output for external device: 12 V (/ 20%) / 5mA 9.5V (/ 5%)) / 5mA CHOR-E SET-UP FUSES Fuses for the loops: 2x Resettable fuse PFRA.00 ( 0.6A ) Fuse for the power output: Resettable fuse PFRA.00 ( 0.A ) MECHANICAL SPECIFICATION Plastic box material: UL 94 V-0 Colour: RAL9002 Size: 200mm x 210mm x 48mm Weight: 1.25 kg IP-Class: IP40 Temperature: -10 to 50 C Humidity: 95% RH Cable terminals: 2.5 mm2 REQUIRED TIMES FOR SIGNALIZATION Operation Time Loops start up time of the IFP-2.2 and switching into Guard Mode Automatical Fault Alarm reset Fire Alarm detection Fault Alarm detection Battery test Test of program memory min < 20 s < 10 s < 100 s < 15 min < 7 min SPECIFICATION Certified according to standard: EN54-2 & EN 54-4 1

129 ICAS AS, Grini Naeringspark 15 161 Oesteraas, Norway 1 129-CPD-072 EN54-2:1999, EN54-2:2007/A1 EN54-4:1999, EN54-4:200/A1, EN54-4:2007/A2 Control Unit for electrical fire alarm systems for buildings Power Supply for electrical fire alarm systems for buildings IFP-2.2 Optional requirements: State Test Documentation: IFP-2_2-Manual_EN.pdf ver.04/201 IFP-2_2-Manual_EN.doc ver.04/201 1

6) MAINTENANCE WARNING!!! SERVICING INSTRUCTIONS ARE FOR THE USE OF SERVICE TRAINED PERSONNEL ONLY. TO AVOID DANGEROUS ELECTRIC SHOCK, DO NOT PERFORM ANY SERVICING UNLESS QUALIFIED TO DO SO. BATTERY VOLTAGE AND CHARGER CHECKS Open the right side of the IFP-2.2. Warning! High Voltage of 20V is connected to P1 20V terminal. Measure the voltage at P10 terminal (EXT BAT 12V). This should be 1.5V /- 0.2V. Switch off the primary power supply and check that the battery voltage at P10 terminal does not drop significantly. Close the right side of IFP-2.2 and lock. BATTERY CHANGE Open the right and left side of the IFP-2.2. Warning! Remove the Power before battery change. Remove the top cover of the IFP-2.2. Switch off the battery switch jumper on the right side. Remove the battery out of the box and plug it out. Plug in the new battery with right polarization and place it in the box. Switch on the battery switch jumper. Close the top cover of the IFP-2.2. Close the right and left side of the IFP-2.2 with locks. Switch on the mains. NOTE: BATTERIES MUST BE REPLACED PERIODICALLY IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATION. ALWAYS USE SEALED LEAD ACID BATTERIES (YUASA NP0.8-12 12V 0.8Ah). LOOPS CHECKS Set the TEST function in IFP-2.2 for LOOP A and B. For further instruction see section 5 in chapter 4. Activate the alarm of the detector in the loop. The Fire Panel shall detect alarm in the correspondent loop. Repeat the previous action for the other loop as well. Now test open loop fault. Remove the detector in alarm from the socket. The Fire Panel shall detect fault alarm in the correspondent loop. Repeat the previous action for the other loop as well. Place the detector back into the socket in accordance with point of the 500-IDx installation manual. Switch off the fire alarm and fault alarm of the IFP-2.2 in both loops. See section 2 and of chapter 4. Wait until loops are in LOOPS GUARD MODE. Switch off the TEST function in loop A and B. Follow section 5 in chapter 4. SIGNALISATION CHECK Press the LAMP button (the section 1 in chapter 4). All LED signalizations and buzzer shall go on for approximately 2s. POWER OUTPUT VOLTAGE CHECK Open the left side of the IFP-2.2. Measure the voltage at P5 terminal (12V-). The value should be 12 V (/ 20%). Close the left side of the IFP-2.2. 1