TITLE SLIDE. FIRERAY2000 EExd OPTICAL BEAM SMOKE DETECTOR. Doc. No: Copyright Fire Fighting Enterprises Ltd.

Similar documents
TITLE SLIDE FIRERAY50/100R OPTICAL BEAM SMOKE DETECTOR. Doc. No: Copyright Fire Fighting Enterprises Ltd.

FIRERAY 2000 EExd Hazardous Area Smoke Detector Installation Guide

Reflective Optical Beam Smoke Detector User Guide

Fireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

FIRERAY 5000 range USER GUIDE

This training course discusses the correct use of Infrared (IR) Optical Beam Smoke Detectors for the protection of lives, equipment and property.

Why choose Fireray? Why use a Beam Smoke Detector? Product Range.

Motorised Infrared Optical Beam Smoke Detector. User Guide

Motorised Infrared Optical Beam Smoke Detector. User Guide

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

Apollo Intelligent Auto Aligning Beam Detector. User Guide

Table of Contents. 1. Mounting Tips... 2

Open-area Smoke Imaging Detector. Engineering Specification

Range brochure. Beam detection. others look up to.

Installation and Operation Manual

TX7130. Conventional Reflective Beam Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

Fireray 2000 Linear Smoke Detector

this is by far the best beam money can buy

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500 AND 6500S REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR

End To End Optical Beam Smoke Detector. Additional Information

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS NFXI-BEAM AND NFXI-BEAM-T REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR

Reflective Beam Smoke Detector

English. Series. Installation and Use Manual

INSTRUCTION MANUAL (ATEX / IECEx)

Snifter ATEX22 VERSION. User Manual. Distributor

Line Smoke Detector LRMX

4) Intrinsic Safety Certification

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

PTE0705 Electric Fence Monitor

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504

Installation Instructions

1 PRODUCT COMPONENTS This section describes the contents of the product package and the names and functions of

RK CO 2 Transmitter Operator s Manual

RK-05 Combustible Gas Transmitter Operator s Manual

RS Pro Infrared Temperature Sensor

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT FLR TYPE FLAMEPROOF RADIATORS

Passive Infrared Motion Detector 5420/90P. Installation Instructions

CONFIGURATION OF THE OPTICALS

IRIS IP65 IRIS UNISCAN APPLICATION MANUAL

AX-100TFR/AX-200 TFR INTRODUCTION 1-1 BEFORE YOUR OPERATION BATTERY OPERATED PHOTOELECTRIC DETECTOR. Warning FEATURES. Caution. Warning.

RED1. Technical Support And Installation Manual. Models ST, E1, E2, E3, E4, and 420. Approved

INSTRUCTION MANUAL (ATEX / IECEx)

Smoke Vent Control Panel PCB4 V4 Installation Manual

INSTRUCTION MANUAL (ATEX)

Optical Beam Smoke Detector RK90R - RK90RS

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

HART TOCSIN 903 SINGLE CHANNEL GAS DETECTOR USER INSTRUCTIONS. Oliver IGD Limited NEW WITH OPTIONAL. 4a Pepper Road Stockport SK7 5BW England

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

Hazardous Area Zirconia Oxygen Systems

MODEL 6200 ANALOGUE ADDRESSABLE OPTICAL BEAM SMOKE DETECTOR

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

Photobeam 5000 ISC-FPB1-W60QF, ISC-FPB1-W120QF, ISC-FPB1-W200QF. en Installation and Operation Guide

TECHNICAL MANUAL EDITION 1.0 VANDAL RESISTANT AUDIO AND VIDEO DOOR ENTRY SYSTEMS

IFD-E Flame Detector User Manual

INSTRUCTION MANUAL (ATEX / IECEx)

Flame Monitor for Multiple Burner Furnaces D-LE 603 D-UG 660

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FAW, FAW-C & FAW-C-T TYPE AIR WARMERS FCR & FCR-A TYPE CONVECTORS

Open-area Smoke Imaging Detection (OSID)

SIMRAD GD10 IR GAS DETECTOR

Air Sampling Smoke Detection

Photobeam 5000 ISC-FPB1-W60QS, ISC-FPB1-W120QS, ISC-FPB1-W200QS. en Installation and Operation Guide

RK Carbon Monoxide Transmitter Operator s Manual

Dräger Flame 3000 Visual Flame Detector Instructions for Use

HART XL High Sensitivity Smoke Detection

PHOTOELECTRIC AMPLIFIER SERIES

HART XL High Sensitivity Smoke Detection

Description. Optex Incorporated

GS100M Gas Detection Controller

INDEX. Installation recommendation

RMS-I-DE-01 Smoke Detector

IFD-E Flame Detector User Manual

5000 INSTALLATION GUIDE

Model 3300 Technical Support and Installation Manual

Movement Detector GJD 300

Carbon Monoxide Transmitter

GL-CO-RFG Channel Gas Leak Alarm System

LABORATORY OVENS MODELS INCLUDE: TO-152G & TOH-152G TO-152F & TO-235F DEHYDRATING OVENS MODELS INCLUDE: TD-150F TD-330F TD-500F

SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT INDUSTRIAL FLR & FLRA TYPE FLAMEPROOF RADIATORS

T3/E3 Fiber Optic Line Drivers

INSTRUCTION MANUAL (ATEX/IECEx/SIL2)

2G & 3G GSM Wireless Beam Alarm

Public Safety DAS Annunciator Panel

360º Surface Mount Ceiling PIR Light Controller

RK Hydrogen Sulfide Transmitter Operator s Manual

DUAL OPTIC. Installation manual

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

PHOTOELECTRIC BEAM SENSOR PR-11BE : OUTDOOR 3.3 to 36ft. (1 to 11m) : INDOOR 3.3 to 49ft. (1 to 15m)

For assistance with the product please contact: HELPLINE. For a product brochure please contact:

UBS1RF OPTICAL SMOKE ALARM EN 14604:2005/AC:2008 DOP:UBS1RF-001-V1

DESIGN MANUAL. The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0)

Transcription:

TITLE SLIDE FIRERAY2000 EExd OPTICAL BEAM SMOKE DETECTOR Doc. No: 32-0009-01

OPTICAL BEAM SMOKE DETECTORS This training material provides information to assist the Fire System Designer and Installer in achieving a successful Optical Beam Smoke Detector installation. The appropriate local installation standards and legislation in effect at the time of installation must be adhered to and take precedence over any statements made or implied by this training material. Fire Fighting Enterprises cannot take responsibility for the installation (beam positioning and mounting), commissioning or maintenance of products.

AGENDA AGENDA IS FIRERAY2000 EExd? ING FIRERAY2000 EExd ING FIRERAY2000 EExd USING FIRERAY2000 EExd ING FIRERAY2000 EExd NICAL SPECIFICATIONS OF FIRERAY2000 EExd

HAZARDOUS AREA Earth RX EEXD GLAND NON- HAZARDOUS AREA OVERVIEW Control Unit PSU PSU Earth The FIRERAY2000 EExd is comprised of a Transmitter Unit, a Receiver Unit and a Controller. The Transmitter projects light across the area to be protected. The Receiver collects a portion of this light and converts it into an electronic signal. Controller analyses this signal to determine if smoke is present based on the amount of obscuration. Earth TX EEXD GLAND The Transmitter transmits a diverging beam of infrared light The Receiver focuses the portion of light falling onto its lens, which then forwards a signal to the Control Unit for analysis When smoke is present in the beam path, the signal received by the Receiver is reduced relative to the smoke density If the density of smoke reduces the signal below the preset threshold for a period of 10 seconds, the alarm relay is activated A Control Unit is located within 100 metres cable run of the Receiver Unit, enabling low-level installation and diagnostic capability.

BENEFITS IN COMPARISON TO REFLECTIVE SYSTEMS Not susceptible to stray reflective light from reflective surfaces Can be aligned and operated through small spaces The FIRERAY2000 EExd is not susceptible to stray reflective light from reflective surfaces. It can be aligned and operated through small spaces and the Transmitter and Receiver heads are small in comparison to the reflective systems. FIRERAY2000 EExd comes with a three year warranty.

APPROVALS Approvals: ATEX (Certified by Sira) EN54:12 / CPD (Europe) VdS (Germany) The FIRERAY2000 EExd has these main approvals, which make it popular in many markets.

OUT OF THE BOX PARTS Transmitter (plus bracketry & fixings) Receiver 5mm & 10mm Allen keys Control Unit (plus access key) Test Filter Installation Guide ATEX Addendum

TRANSMITTER PARTS Vertical Adjustment Horizontal Adjustment Power is set via dip switches on the PCB within the sealed housing Lens behind window housing The Transmitter part can be identified by its clear lens. The supplied mounting bracket allows horizontal and vertical adjustment of the Transmitter. Range switches on the inside of the product set the operating range. These are selectable by the user by removing the window housing. (Range selection is covered later).

RECEIVER PARTS Mounting Holes (x4) Lens behind window housing The Receiver part can be identified by its dark lens. The Receiver is not sold with an adjustment bracket as standard. If the walls are not deemed to be parallel (within 20 degrees of each other) then an additional adjustment bracket must be purchased for the Receiver.

CONTROL UNIT PARTS Signal High LED Signal Level Knob Test/Reset ON/OFF switch Control Unit Door Signal Low LED Receiver Terminals Alarm Relay Terminals Test Meter Terminals External Reset Terminal Fault Relay Terminals Power Supply Terminals Supplied Key (Shown Right) Opens Door Latch Settable Pins - Alarm Latch, Compensation and 25%, 35%, 50% Sensitivity Fault LED The Control Unit board includes a number of terminals, controls and indications for the FIRERAY 2000 EExd system. The Control Unit board is housed within a white electrical enclosure accessed with the supplied key.

VARIANTS FIRERAY EExd 2000 (Designed specifically for potentially explosive atmospheres) FIRERAY 2000 MULTIWAY (Houses multiple FIRERAY2000 boards in a discreet cabinet with door)

FIRERAY Eexd 2000 Here is the equipment mark of the flameproof FIRERAY 2000 EExd (with explanation): II 2 G EEx d IIB T6 Tamb= -20 C to +55 C Specific marking of explosive protection Equipment group and category G denotes gases, vapours or mists d denotes Flameproof Protection Concept Gas Group and T Class Ambient Temperature FIRERAY 2000 EExd is our ATEX beam approved for Category 2 (old zone 1) It is EExd is safe for use in flammable liquid and gas stores. Note Optical Beam Smoke Detectors may not be the optimum detector if the combustibles generate colourless smoke.

OBSCURATION DEVICE After successful installation and alignment, it is important that the transmitted beam has a clear line of sight to the Receiver A fundamental part of testing the obscuration thresholds requires the use of the supplied Test Filter obscuration device. (Its use is described later on in this presentation)

ZONE WIRING

SYSTEM CONNECTIONS

KNOCKOUTS There are 2 off 20mm knockout holes on each side face of the Control Unit. (the photo below shows the 2 knockouts (1 in use) on the top face of the unit.) 20mm knockouts

SELECT REQUIRED ALARM THRESHOLDS Settable Pins - Thresholds 3 settable pins are provided for each alarm threshold i.e. 25%, 35% & 50% Only set ONE of these pins to the CLOSED position to select it (the remaining threshold pins should then be set OPEN)

SELECT EXTERNAL RESET OR AUTO RESET A settable pin is provided which can be set to either latching or non-latching External Reset Terminal Settable Pin - Alarm Latch A settable pin is provided which can be set to either latching or non-latching With non-latching selected, the alarm relay will reset 5 seconds after the smoke has cleared With latching selected, the alarm relay will remain set until either power down or the LLC receives an external reset (connected terminal shown to test meter negative for 1s).

CONTROL UNIT ATION The Controller MUST be mounted outside of the explosive atmosphere. Mount the Control Unit at ground level to a flat surface (preferably a wall) using the fixing holes provided Terminate the field wiring as required for zone or loop wiring accordingly

ING RECEIVER HEAD Receiver must be mounted onto a stable, solid surface Mount the Receiver such that it faces towards the proposed mounting position of the Transmitter Ensure that the line of sight is clear from obstructions Remove the window housing using the 5mm Allen key provided Wire the Receiver to the controller using suitable cable and glands Replace the window housing ensuring that it is fitted correctly Mount the Receiver first, such that it faces, and has un-obstructed line of sight with the expected final Transmitter position. Remove the Receiver Window housing (using 5mm Allen key provided). Connect the system cabling to the 3 way terminal block on the internal pcb. It is recommended that the External Earth point be used on the Tx and Rx housings, to minimise wiring lengths. This must be taken to the nearest suitable building Earth point. Alternatively, the housing s Internal Earth stud may be connected, via an additional cable core and connected back at the Control Unit Earth. Check the connections and tighten the cable glands, Refit the Window housing, taking care to position the O ring seal correctly, just below the flange. Tighten the 4 securing screws firmly. For safety reasons, and to give the best EMI rejection, do not omit any of the Earth connections.

ING TRANSMITTER HEAD Transmitter must be mounted onto a stable, solid surface Mount the Transmitter using the adjustment bracket provided such that it aligns as closely as possible to the Receiver Ensure that the line of sight is clear from obstructions Remove the window housing using the 5mm Allen key provided Wire the Transmitter using suitable cable and glands Set the Range Switch to the correct range or next higher setting Replace the window housing ensuring that it is fitted correctly Fit the Transmitter head in a position which aligns as closely as possible with the Receiver line of sight, making use of the adjustment bracket provided. Remove the Transmitter Window housing top (using 5mm Allen key provided) and set the Range Switch to the correct or next higher setting, to match the expected operating range. Connect the system cabling to the 3 way terminal block on the internal pcb. Earth the unit housing. Check the connections and tighten the cable glands. Refit the Window housing top, taking care to position the O ring seal correctly, just below the flange. Tighten the 4 securing screws firmly. For safety reasons, and to give the best EMI rejection, do not omit any of the Earth connections.

PRE-ALIGNMENT Apply power to the Control Unit and check voltage is within 11.5 to 28V Apply power to the Transmitter (if not connected to the same power supply) and check voltage is within 11.5 to 28V

METER ALIGNMENT (2 PERSONS REQUIRED) Connect a voltmeter to the test meter terminal and ground on the Control Unit PCB Set the RESET/TEST switch to ON Adjust signal level pot to 12 o clock position While 1 person observes the voltmeter reading the other person should orient the transmitter head Connect a voltmeter to the test meter terminal and ground on the Control Unit PCB Set the RESET/TEST switch to ON at the Control Unit Adjust signal level pot to 12 o clock position at the Control Unit While 1 person observes the voltmeter reading the other person should orient the Transmitter head If moving the Transmitter head causes the voltage to increase continue in that direction to attain the highest voltage possible A voltage of at least 4.1v is required for correct function. If the voltage on the meter reads 2.6v +/-0.1 then the Receiver is not seeing the Transmitter Secure the Transmitter by tightening all bolts on the bracket. Recheck the voltage. Go to the Final Settings Slide

FINAL SETTINGS AFTER ALIGNMENT At the Control Unit adjust the signal level pot slowly anticlockwise until the signal high LED just extinguishes Confirm that the output at the test meter is 4.2V +/-0.1V Disconnect the voltmeter and/or the Alignment Tool wires from the test meter terminals Confirm that both signal high and low LED s are both OFF Move the RESET/TEST switch to the OFF position and confirm that the fault LED extinguishes Wait 45 seconds and confirm that the fault LED is still extinguished

FIRE TESTING Take note of selected threshold setting (default 35%) Find the mark on the supplied Test Filter that corresponds with the threshold value Place the Test Filter over the receiver just past the correct threshold value mark The Control Unit will indicate a fire within 10 seconds by activating the RED LED on the Control Unit door and operating the fire relay

RESET AFTER FIRE TEST Once the Test Filter has been moved away from the front of the Receiver the Control Unit will reset after approx. 4 seconds (if the alarm latch is configured to the autoreset setting) If the latching alarm option is configured the Control Unit can be reset. Once the Test Filter has been moved away from the front of the Receiver the Control Unit will reset after approx. 4 seconds (if the alarm latch is configured to the auto-reset setting) If the latching alarm option is configured the Control Unit can be reset by either: Switching the TEST/RESET switch to ON, then OFF Disconnecting the power to the Control Unit for more than 1 second. Shorting the external reset terminal on the Control Unit PCB to the negative terminal for more than 1 second

FAULT TESTING The fault relay and the fault LED operate if the beam is totally blocked for approximately 10 seconds. The voltage on the meter should read 2.6v +/-0.1 Removing the obstruction will automatically reset the beam after approximately 4 seconds.

AGC - HOW IT WORKS AGC Automatic Gain Control is used to combat the effects of dirt / dust build-up on the lenses, small changes in the atmospheric conditions and building movement. However, it must be remembered that AGC can only compensate for slow changes in the previously listed conditions for a finite amount of steps i.e. AGC must not compensate out of a slow burning fire!

WITHOUT AGC Signal 100% 100% Fire Threshold 65% OK OK System Without Without AGC AGC Fire 10% 0% 0% Fig. 1 Time Time Fig. 1 shows what would happen to the signal level without AGC. Initially when the beam is setup and commissioned the signal level should be sitting at 100% (approx. 4.2V). Over time, external influences such as dirt, dust &/or building movement will start to degrade the signal level. Without AGC, as there is no means of combating this, the signal level will start to drop as the received signal is reducing. If the external influences persist, the signal level will eventually drop below the fire threshold (sensitivity), thus initiating an alarm. A system without AGC would therefore require a high level of maintenance as the transmitter and receiver would need to be accessed regularly to keep the surfaces clean and the system perfectly aligned.

WITH AGC Signal 100% 100% OK OK AGC System With AGC Slow Burning Fire 8.79% / Hour Slow Burning Fire Fire Threshold 65% AGC Fire Fire 10% 0% 0% Fig. 2 Time Fig. 2 shows a system with AGC. As the external influences build-up, the system will compensate for them by increasing the AGC potentiometer. As mentioned earlier the AGC does not compensate out of a slow burning fire. It should also be noted that the AGC would stop when the system is in either a fire or fault condition, so as not to compensate out of that condition. If the AGC limit is reached the beam will need to be cleaned and realigned.

LED INDICATORS GREEN SIGNAL HIGH LED indicates that the signal being received is too HIGH GREEN SIGNAL LOW LED indicates that the signal being received is too LOW AMBER FAULT LED indicates a FAULT condition will operate if the beam is totally blocked for 10 seconds RED LED (mounted on Control Unit door) indicates a FIRE condition when the obscuration is sufficient according to the threshold % value set in the Control Unit. GREEN SIGNAL HIGH LED indicates that the signal being received is too HIGH GREEN SIGNAL LOW LED indicates that the signal being received is too LOW AMBER FAULT LED indicates a FAULT condition will operate if the beam is totally blocked for 10 seconds RED LED (mounted on Control Unit door) indicates a FIRE condition when the obscuration is sufficient according to the threshold % value set in the Control Unit.

ING AN OPTICAL BEAM SMOKE ING DETECTOR To ensure the system continues to operate correctly: Routinely check for visual damage Check installation remains mechanically and electrically sound Check there have been no major changes to the environment such as line of sight, obstructions, reflections, strong light sources etc. Clean the system Confirm system operation with Trouble (Fault) and Fire tests Optical Beams are relatively maintenance-free after successful commissioning, however routine checks and cleaning are recommended to ensure satisfactory functioning of the system. Before maintenance, notify the relevant authorities that Optical Beams will be temporarily out of service and disable the zone or system to ensure fire services are not inadvertently dispatched. The system should be cleaned during regular maintenance. Refer to the particular product s installation guide for more detailed information. In general, use a lint-free cloth or lint-free feather duster to gently wipe lenses (and reflectors) taking care not to disturb alignment. Confirm alignment remains satisfactory after cleaning with Trouble (Fault) and Fire tests. Special servicing will be required: After a fire If an unacceptable rate of false alarms is experienced When a new maintenance organisation is contracted Following long periods of disconnection

CLEANING Clean during regular maintenance Clean carefully with lint free cloth/feather duster After cleaning follow simple re-alignment procedure Fault LED may indicate an AGC fault therefore clean & align

OPERATING VOLTAGES/CURRENT Operating Voltage Range: 11.5 to 28V DC Transmitter Current: <1.6 to 5.6mA Quiescent Current (Control Unit includes receiver): <8mA @24V DC

OPERATING RANGE Operating Distance: 10 to 100 Metres

MAX. TRANSMITTER AND RECEIVER MISALIGNMENT Maximum Transmitter Misalignment at 35%: ±1 Maximum Receiver Misalignment at 35%: ±4 These are the amounts the transmitter or receiver can be moved off axis and still be operational (and still able to detect a fire and fault correctly).

FIRE ALARM THRESHOLDS Fire Alarm Thresholds: 1.25dB (25%), 1.87dB (35%), 3dB (50%)

TIME TO FIRE / FAULT Between 2 to 12 seconds

OPTICAL WAVELENGTH Optical Wavelength: 880nm

FAULT/ALARM CURRENT Alarm Current (Control Unit includes Receiver): <16.5mA @24V DC Fault Current (Control Unit includes Receiver): <16.5mA @24V DC

RELAY SPECIFICATIONS Fire Relay Contacts: Normally Open, VFCO 2A @ 30V DC, resistive. Fault Relay Contacts: Normally Closed, VFCO 2A @ 30V DC, resistive. VFCO = volt-free changeover

GOLDEN RULES Install Transmitter and Receiver onto solid structures Always perform Fire and Fault Tests Ensure that the beam path is clear of any obstructions Ensure that the area to be protected is a non-condensing environment

OUR SUPPORT Website www.ffeuk.com Technical Support (outside US) Email: technical@ffeuk.com Telephone: 01462 444783 Sales Administration Support Email: sales@ffeuk.com Telephone: 01462 444740 Technical Support (inside US) Email: technical@ffeuk.com Telephone: 866-FIRERAY (= 1-866-347-3729) FFE Technical Support covers: helping you select the right type of Optical Beam and advising you of good installation practice providing telephone support throughout your installation troubleshooting if any issues arise after installation We first work with you by phone and email, discussing your data, photos etc. then we can arrange a site visit if necessary Call or email us to speak with one of our eight Engineers or with our Sales Managers (UK, USA and India) We offer flexible, modular training courses on Beams in general and our wide range of beam products in particular Courses can be arranged with the appropriate Sales Managers with an Agenda to suit your requirements In the UK, courses are usually delivered in our Hitchin office utilising the training room and 27m demonstration area

CONCLUSION CONCLUSION FIRERAY2000 could be the detector of choice for protecting lives, equipment and properties where: Areas are wide Ceilings are high Cost of installation and servicing need to be low Architecture cosmetics / aesthetics are important Ceilings are ornate There is potential for building movement

FIRERAY THANKYOU THANK YOU