Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

Similar documents
Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified

Data Aire LCS TM (Large Ceiling System) R-407C. 6, 8, 10, and 13 ton. ISO 9001 Certified

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified

Data Aire Series Chilled Water 7 through 50 ton

Chilled Water 7 to 211 kw

Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities R-410A. ISO 9001 Certified

Chilled Water 7 to 211 kw

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits R-407C

Modular Data Temp Systems Air Cooled Water/Glycol Cooled R-407C. 8, 10 and 13 ton capacities. ISO 9001 Certified

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits

gforce - R-407C Air Cooled, Water/Glycol Cooled kw Dual Circuits

R-410A Air, Water/Glycol Cooled 21 through 106 kw - Dual Circuits

gforce GT R-407C Single Circuit Air Cooled, Water/Glycol Cooled 7-46 kw

C13-Series Engineering Guide

CeilMate TM Series 3 and 4 tons of cooling capacity. Ceiling Mounted Systems. Air Handler with Remote Condensing Unit Air Handler designed for R-410A

VertiCool Aurora Engineering Guide

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

SKY-COM HI-CAP SERIES. Precise Environmental Control SKY-COM 15 & 20 TON Series. Suited for Telecommunications, Laboratories and Computer Rooms

CoolSpot Engineering Guide

Series 6. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Contents. APC NetworkAIR CW. CW 020 C= Chilled Water BA= /3/60 D= Downflow. Capacity (kw) Configuration Voltage Air Pattern

Series 8. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

STULZ CyberAiR Floor Mounted Systems. Engineering Manual. Floor Mounted Air Conditioners

VERTICOOL TECHNICAL DATA MANUAL. Vertical Air/Water Cooled 3-25 Tons

VariCool VAV Engineering Guide

Computer Room Air-Conditioning 60 Hz. Technical Data

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

Precision Air-Conditioning Units 60 Hz. Technical Data

Liebert Mini-Mate2. 8-Ton (28kW) Capacity, Air, Water, Glycol, GLYCOOL, Chilled Water; 50 & 60 Hz. Technical Data Manual

ENGINEERING MANUAL 3, 5, & 7 TONS PRECISION ENVIRONMENTAL CONTROL

Precision Air-Conditioning Units 60 Hz. Technical Data

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

CeilMate. Ceiling Mounted Units. Series 1 to 3 tons of cooling capacity

Advance Release September 2009

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

RTU. Roof Top Units 8 30 Ton. Maxi-Kool.

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Mission Critical Air Conditioning Systems

FULLY SELF-CONTAINED AIR CONDITIONING WITH INDUSTRIAL DURABILITY

STULZ FLAiR Systems Floor Mounted Console Air Conditioners 5-17 kw / Single Circuit / DX Air / Water / Glycol. Engineering Manual

Mini-Space EC DX and CW 4 12 kw Systems Vertical Floor Mounted, 60 Hz Data

Computer Room Air-Conditioning 60 Hz. Technical Data

HEATING & COOLING SUBMITTAL The DuraPac Series Unit 559F/579F180, 216, 240, , 18, 20, and 25 NOMINAL TONS

Mission Critical. Series 6, 8 & 9. vertical floor mount Ton Units. Air Conditioning Systems

SC SpotCool. 1 to 3 Tons. R407c & R410a. 2 x 4 Packaged & Split. Spot-Cooler & Ducted. eair above-the-ceiling air conditioners (ASC-L22)

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

Contents. APC NetworkAIR AFX AFX

Series PS6, Vertical Floor-Mount Units

gforce Units Data Aire and Data Temp Series

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Liebert. Deluxe System/3 Chilled Water Systems ENVIRONMENTAL CONTROL TECHNICAL DATA MANUAL. 50 Hz and 60 Hz ISO 9000 CERTIFIED COMPANY

Water-Cooled Self-Contained Units

Guide Specifications for InRow Direct Expansion

Environmental Control

System 2100 & System 2100k

Split System Heat Pumps

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Contents. APC NetworkAIR AFX AFX

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

All side discharge units are having high pressure switch (LP switch- Optional) and time delay relay. Compressors are scroll type, Copeland make.

Liebert Mini-Mate2 1 To 8 Tons

technical guide Water-Cooled Self-Contained Units

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

GreenPac & GreenPac HGR Heat Pumps & Air Conditioners Models AVP

System Floor Mount Systems DX / Glycol / Chilled Water 6-12 Tons. High Density Presicion Cooling. Kompact.

Liebert. Mini-Mate2 1 To 8 Tons Overhead Precision Cooling And Humidity Control

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

STULZ Compact CWE. Engineering Manual. Computer Room Air Handlers kw Precision Air Handlers Utilizing EC Fan Technology (60 Hz Data)

Product Specifications. Vertical Floor Consoles By First Co.

Flexible & Innovative. Cooling Solutions

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

Liebert Mini-Mate2 1 To 8 Tons

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

Wall Mounted Air Conditioners with Gas Heat Models AVGA

-2x2. eair floor mounted precision air conditioners (MC22-L10) R407C & R410a Data. From 1 to 3 Tons. Engineering Manual

Service Step by Step Trouble-Shooting Check-List

9 EER 1-5 Ton Vertical Packaged Wall Mount Air Conditioners

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

The Premium Quality Fan Coil Units for Vertical, Horizontal (Left or Right) Application with Direct Expansion, Hydronic or Electric Heat

1 to 5 Ton Vertical Wall Mount Air Conditioners Models AVPA

50TM COMBINATION HEATING/COOLING UNITS

Commercial High-Efficiency Condensing Units

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

48TM GAS HEATING/ELECTRIC COOLING UNITS

Control Systems. Design & Manufacturing. Eco-Friendly. High Performance

PGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

Transcription:

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A ISO 9001 Certified

Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing engineers who sought optimum environmental conditions for early computers. It was clear that people comfort air conditioning system were unable to meet the environmental requirements of computers and data processing equipment. Precision environmental control equipment with high sensible cooling ratios was a necessity. Problems with paper sticking, head crash, and static electricity were eliminated. Humidity fluctuation were controlled saving possible electrical and mechanical failures and more importantly Downtime. Data Aire s innovative response to the challenge of eliminating problems within the computer room environment was the start of wide use precision cooling. As in the past, Data Aire is meeting today s challenge of not only the computer room but also the ever expanding telecommunications industry where precision cooling is vital to our everyday communications. Telecommunication equipment requires a controlled environment with clean and properly distributed air. As in the computer room, the environment must be precisely controlled 24 hour a day, 365 days a year. Data Aire produces solutions. We have offered environmental control solutions to meet specific needs in the smallest of places and in areas of thousands of square feet. We are prepared to assist you, your in-house engineering department, consulting engineer, or construction department in defining the proper solutions and bringing them to a predefined outcome. Data Aire is committed to being the supplier of choice for environmental process cooling with flexibility, reliability, and expertise required to meet our customer s needs. To be successful, it is essential to be creative and use our resources to their fullest capabilities. The Data Aire goal is to benefit the employees, partners, and most of all our customers with honesty and integrity. Data Aire Delivers! 3

Mini Ceiling System 1, 1.5, 2, and 2.5 ton Air and Water Cooled and Chilled Water R-410A TABLE OF CONTENTS Design Features...6 Options...8 Configuration Drawings Package Systems...9 Split Systems...11 Performance Data Air and Water Cooled...13 Electrical Data Air Cooled...16 Water Cooled...19 Performance Data Chilled Water...20 Electrical Data Chilled Water...21 Dimensional and Component Drawings...22 Guide Specifications...38 Weights...42 4

DATA AIRE, FOR ALL THE RIGHT REASONS! PRECISION COOLING Computers, batteries, electronic and telephone equipment have special comfort requirements. These spaces require air which is clean with precisely controlled temperature and humidity. Data Aire Mini Ceiling Systems TM are designed with this in mind. Building or people comfort systems simply are not designed to meet demands. PERFORMANCE, LOW COST Engineered and built by the people who introduced computer room air conditioning, the Mini Ceiling unit offers quality at a competitive price. Every Mini Ceiling System comes with Data Aire s commitment to excellence which began with our first air conditioner and has been tested and proven for more than forty years. PEOPLE COMFORT Although thru-the-wall systems may help cool your staff, they still fall short where precision cooling is needed. Data Aire s Mini Ceiling Systems are the practical answer. It will keep your equipment on-line and will add to your personnel s comfort as well. DATA AIRE DELIVERS Units shown with optional side drain connections. Data Aire s reputation for speedy delivery applies with special emphasis to the Mini Ceiling System. Units are shipped within a few days from receipt of order. Call your nearest Data Aire representative for details. 5

MINI CEILING SYSTEMS TM 1, 1.5, 2, and 2.5 ton capacities Air Cooled Water Cooled Chilled Water Data Aire s Mini Ceiling Series is the perfect environmental control system for small computer centers, electronic, telephone, and battery rooms, or wherever spot cooling may be necessary and space is a problem. While vertical supply/return air units are designed to fit in a 2 ft x 4 ft standard T-bar ceiling grid space, horizontal units hang in the ceiling space with duct work connected to supply and return connections. The system offers an unsurpassed combination of features and options along with a high standard of performance. Mini Ceiling Systems are available as air cooled, water cooled, or chilled water systems with a variety of return and supply air arrangements. Air cooled can be specified as packaged indoor units or split systems with either remote outdoor condensers or condensing units. CONTROLS Precise temperature regulation is provided by a built-in control system. All electrical components, including capacitors, contactors, relays, and control transformers are pre-wired and contained in an electrical box that is hinged and swings out for easy access and servicing. A factory installed microswitch will disable the unit prior to condensate pan overflow should the drain line become plugged with debris. Each unit is shipped with a thermostat and subbase as standard. A red indicator light is unit mounted to indicate a condensate problem. Units with the optional Mini Data Alarm Processor-II TM have a high condensate water level alarm standard. CABINET Units are designed with a supply and return air plenum that fits in a 2 ft x 4 ft opening of a standard dropped ceiling grid. The field installed supply and return air plenum is constructed of aluminum and finished with off-white textured paint. Both the supply and return air grilles are hinged for easy access when replacing filters. A 2 inch, 30% efficient filter (based on ASHRAE Std. 52.1-1992) is provided behind the return air grille. Mini Ceiling Systems are constructed with tubular steel frames for strength and service access. Removable panels of galvanized steel are lined with 1/2 inch thick, closed cell insulation for quiet and efficient operation. EVAPORATOR SECTION The evaporator coil contained in each unit is constructed with copper tubes and aluminum fins mounted in a stainless steel drain pan. The drain pan is made with a bottom drain connection and installed in a manner that provides a positive drain to prevent standing water in the condensate pan. The refrigeration circuit includes a scroll compressor with internal overload protection and crankcase heater. The circuit includes an expansion valve with an external equalizer, filter drier, sight-glass, and high and low pressure safety switches. The high and low pressure safety switches are connected to the refrigerant system with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. The blower assembly is a draw-through type with a centrifugal, forward curved, double width, double inlet blower configuration engineered for quiet, reliable operation. The belt driven variable pitch drive provides adjustable air flow capability to match the requirements of the controlled space. The draw-through design insures even distribution across the coil, low internal cabinet losses, and static sealing of the filter section. The motor has internal overload protection and is mounted on an adjustable slide base. SELF-CONTAINED UNITS Air Cooled - The cabinet houses the evaporator section, evaporator blower assembly, filter section (located in air distribution plenum), and the condenser coil. The condenser coil is constructed of copper tubes and aluminum fins. The condenser blower section is field installed. The condenser fan is double inlet, double width, with direct drive type two-speed motor that is controlled with a temperature operated switch. The condenser blower motor electrical connection is through a factory wired plug. Water Cooled - The cabinet houses the evaporator section, evaporator blower assembly, and filter section (located in air distribution plenum). In addition, a high efficiency plate fin condenser with head pressure activated 2-way water regulating valve is built into the refrigeration system and is contained in the evaporator section. The capillary tube connection from the water regulating valve to the refrigerant system is connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. Chilled Water - All components are housed within the cabinet. Chilled water units utilize an existing chilled water loop. Chilled water flow is controlled by a 2-way valve for accurate and economical temperature control and dehumidification. he maximum operating water pressure is 150 psi. 6

SPLIT SYSTEMS Air cooled systems are available with an outdoor condensing unit or remote air cooled condenser. Remote Outdoor Condensing Unit - The outdoor condensing unit contains the scroll compressor, sight-glass, filter drier, high and low pressure safety switches, and condenser coil. The high and low pressure safety switches are connected to the refrigerant system with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. The condenser coil is constructed with copper tubes and aluminum fins. Air discharge is vertical. The condenser fan is variable speed for head pressure control down to -20 F. The capillary tube connection from the fan speed control to the refrigerant system is connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. Field piping and wiring is required from the condensing unit to the indoor evaporator section. Remote Outdoor Air Cooled Condenser - Condensers are industrial duty design with galvanized corrosion resistant housing, aluminum finned/copper tube coils, coated fan guard, energy efficient, thermally protected motor, and variable fan speed control with an integral factory wired and tested control panel. The capillary tube connection from the fan speed control to the refrigerant system is connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. Air discharge is vertical. Field piping and wiring is required from the condenser to the indoor compressor/evaporator section. Mini Ceiling Systems - OPTIONS Mini Data Alarm Processor-II - The microprocessor based Mini Data Alarm Processor-II is wall mounted and has a single row, 16 character liquid crystal display (LCD) in clear vernacular format. The Mini Data Alarm Processor-II not only controls and monitors your room s temperature, humidity, air flow, and cleanliness, but also provides alarm history and an automatic self-test of the microprocessor system startup. Multiple messages will be displayed by automatically scrolling from each message to the next. Multiple alarms will be displayed sequentially in order of occurrence. Each Mini Data Alarm Processor-II is shipped with 25 feet of cable for field connection, (additional cable is available). Contact factory for cable lengths in excess of 75 feet. For full details on the Mini Data Alarm Processor-II, see product brochure. Operation - Unit on/off operation is controlled by a slide switch and push button control switches which allow menu selection for programming, operational information, diagnostics, and historical data. A password feature prevents unauthorized access. Menu programmed information for basic system operation and alarm parameters is nonvolatile. 7 Programmable Functions/Monitoring - The user friendly switch permits step-by-step programming and display of the following functions: Temperature setpoint (60-80 F, 15.6-26.7 C) Temperature sensitivity (+1 to + 5 F or.5 to 2.7 C, in 0.1 increments) Humidity setpoint (30-70% RH) Humidity sensitivity (+1 to +15% RH in 0.1% increments) Temperature alarm points (50-90 F, 10-32.2 C) Humidity alarm points (10-90% RH) Unit start time delay Interstage time delay Password 1 st level Password 2 nd level Audio alarm level Restart mode Firestat trip temperature Local alarm function Normal functions are monitored and displayed on the LCD and include, in addition to the above set points, the following: Current temperature ( F or C) Current humidity (% RH) Cooling Reheat Humidification Dehumidification Date and time Alarms - Alarm conditions are monitored on the LCD and are enunciated by an audible alarm. The alarm silence button will quiet the audible alarm but the display will continue to indicate the alarm condition until the problem is corrected. The following alarms are standard: High temperature High humidity Compressor high pressure High condensate water No air flow alarm Temperature sensor failure Low temperature Low humidity Compressor short cycle Firestat tripped Humidity sensor failure Historical Data - The current temperature and humidity, with minimum and maximum readings for the last 24 hours of operation can be recalled and displayed. Alarm history of the last five alarms is maintained in sequential order. Diagnostics - Automatic and manual diagnostics sequences simplify troubleshooting.

Site Monitoring DARA-4 (Data Aire Relay Autochangeover) Controls up to four Mini Ceiling units using a dry set of relay contracts. The DARA-4 provides unit rotation, backup capacity and the ability to interface with most BMS systems. Unit Options Remote Mounted Temperature and Humidity Sensors Temperature and humidity sensors are provided in a wall mounted plastic case for remote sensing of temperature and humidity. Standard unit sensors are removed. Requires field wiring of (field provided) shielded cable. Remote temperature and humidity sensors option only available when used with the Mini Data Alarm Processor-II. Steam Generator Humidifier The steam generator humidifier eliminates air contamination caused by mineral deposits. The totally self-contained system includes a quick change, disposable cartridge, and automatic flush cycle. When steam generator humidifier option is selected, a Mini Data Alarm Processor-II is required. Electric Reheat Low-watt density finned tubular sheathed coils are constructed of stainless steel and provide ample capacity to maintain room dry bulb conditions on a call for dehumidification. Low-watt density coils eliminate ionization associated with open wire electrical resistance heating. Electric reheat is available in 2, 4, or 5 kw capacities, shipped factory installed with high limit cutout. Condensate Pumps Condensate pumps can be provided for field mounting or factory installed and wired. The pump body can be placed within the unit coil pan. Pump capacity is 60 GPH at 8 feet of head. Field installed condensate pumps require either separate 110 or 230 volt power source. Horizontal, Front, or Side Supply Air Units may be ordered with optional horizontal supply air configurations of front or either side. Optional supply air converts unit for ducted supply air connection. Side Return Air Units may be ordered with optional side return consisting of a factory modified flanged for ducting return air. Optional side return air converts unit for ducted return air connection. An additional option provides ceiling mounted return air filter grille, ceiling mounted return air filter box with hinged grille, and filter for duct connection. Filter included with this option is a 20 x 20 x 2 deep, 30% efficient (based on ASHRAE Std. 52.1-1992) pleated filter. Extended Compressor Warranty Extended compressor warranties are available from Data Aire. Contact your local representative for one that best suites your needs. Low Ambient Control Damper A low ambient control damper is available for use with ducted outside condenser air. The low ambient control damper kit is field installed and consists of a 14 x 14 damper section and head pressure operator. The low ambient control damper allows unit to operate down to -30 F (-34.4 C). The capillary tube connection from the head pressure control to the refrigerant system is connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. 8

CONFIGURATION VERSATILITY Data Aire Mini Ceiling Systems allow for a wide variety of supply and return options capable of satisfying the most demanding installation requirements. PACKAGED SYSTEMS Standard Confi guration - is provided with one ducted attachment, the condenser air out from the end of the unit with flange. Condenser air intake is supplied from the side and top. Evaporator return air is supplied from below and the evaporator supply air is returned to the space below. Mini Ceiling Systems with non-ducted condenser supply air Ducted alternate end supply air Ducted alternate rear air supply Shown with option 260 Ducted alternate front air supply Shown with option 262 Ducted alternate return air and alternate end supply air Shown with option 261 Shown with options 260 and 263 9

PACKAGED SYSTEMS Mini Ceiling Systems with non-ducted condenser supply air Ducted alternate return air and alternate rear supply air Ducted alternate return air and alternate front supply air Shown with options 262 and 263 Shown with options 261 and 263 PACKAGED SYSTEMS Mini Ceiling Systems with flange for condenser supply air Standard Configuration - has flange for condenser air intake and condenser discharge air. Evaporator return and supply air are from the space below. Ducted condenser air intake Ducted alternate end supply air Ducted alternate return air and alternate front supply air Shown with option 260 Shown with options 261 and 263 10

CONFIGURATION VERSATILITY continued PACKAGED SYSTEMS - continued Ducted alternate return air and alternate rear supply air Ducted alternate return air and alternate end supply air Shown with options 262 and 263 Shown with options 260 and 263 SPLIT SYSTEMS Configuration of a split system is the same as the package system, except that you don t have to take into consideration the condenser supply and return air. Typical configuration is with the evaporator supply and return air from the space below, however all the following options are available to meet your requirements. Standard confi guration with standard supply air and standard return air Ducted alternate end supply air Ducted alternate front supply air Shown with option 260 Shown with option 261 11

SPLIT SYSTEMS - continued Ducted alternate rear supply air and alternate return air Ducted alternate end supply air and alternate return air Shown with option 262 and 263 Shown with option 260 and 263 Ducted alternate front supply air and alternate return air Ducted alternate end supply air and special return air Shown with options 261 and 263 Shown with options 260 and special Ducted alternate front supply air and alternate return air Shown with options 262 and special 12

AIR COOLED: Performance data - R-410A MODEL NUMBER DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5 CAPACITY in Btu/hr - Gross 80 DB/67 WB Total 19,700 21,000 27,000 32,700 50% RH Sensible 13,600 16,200 21,600 26,300 75 DB/62.5 WB Total 18,300 19,500 25,100 30,100 50% RH Sensible 13,200 15,600 20,800 25,200 75 DB/61 WB Total 17,500 18,900 24,000 29,000 45% RH Sensible 13,800 16,600 22,100 26,800 72 DB/60 WB Total 17,400 18,600 23,900 28,600 50% RH Sensible 12,900 15,300 20,300 24,600 72 DB/58.6 WB Total 16,700 18,100 22,900 27,600 45% RH Sensible 13,500 16,200 21,500 26,000 GLYCOL COOLED: Performance data - R-410A MODEL NUMBER DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5 CAPACITY in Btu/hr - Gross 80 DB/67 WB Total 18,700 20,200 25,900 31,100 50% RH Sensible 13,200 16,000 21,300 25,700 75 DB/62.5 WB Total 17,400 18,800 23,800 28,700 50% RH Sensible 12,800 15,400 20,300 24,600 75 DB/61 WB Total 16,900 18,200 23,200 27,700 45% RH Sensible 13,600 16,500 21,900 26,400 72 DB/60 WB Total 16,700 17,900 22,600 27,200 50% RH Sensible 12,600 15,000 19,800 24,000 72 DB/58.6 WB Total 16,300 17,400 22,100 26,500 45% RH Sensible 13,300 15,900 21,100 25,600 WATER COOLED: Performance data - R-410A MODEL NUMBER DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5 CAPACITY in Btu/hr - Gross 80 DB/67 WB Total 21,800 23,500 30,300 36,800 50% RH Sensible 14,500 17,200 22,900 27,900 75 DB/62.5 WB Total 20,100 22,000 28,100 34,000 50% RH Sensible 14,000 16,700 22,100 26,800 75 DB/61 WB Total 19,500 21,200 27,200 32,800 45% RH Sensible 14,800 17,700 23,600 28,600 72 DB/60 WB Total 19,100 21,100 26,800 32,300 50% RH Sensible 13,700 16,400 21,600 26,200 72 DB/58.6 WB Total 18,600 20,400 26,000 31,200 45% RH Sensible 14,400 17,300 22,800 27,700 13 R-410A

AIR, GLYCOL and WATER COOLED: Performance data MODEL NUMBER DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5 EVAPORATOR BLOWER Airflow - CFM 550 775 1000 1225 Standard motor - horsepower 1/2 1/2 3/4 3/4 External Static Pressure (E.S.P.) - inches of W.G. 0.5 0.5 0.5 0.5 EVAPORATOR COIL Face area - sq ft 2.4 2.4 2.4 2.4 Face velocity - fpm 229 323 417 510 Rows of coil 3 3 4 4 CONDENSER COIL Air cooled indoor packaged units Face area - sq ft 2.4 2.4 2.4 2.4 Face velocity - fpm 500 500 500 500 Rows of coil 4 4 6 6 CONDENSER BLOWER Air cooled indoor packaged units Standard airflow - CFM 1,200 1,200 1,200 1,200 Standard motor - horsepower 1/2 1/2 1/2 1/2 External Static Pressure (E.S.P.) - inches of W.G. 0.5 0.5 0.5 0.5 CONDENSER DATA Water cooled units Type Plate-fin Plate-fin Plate-fin Plate-fin Water regulating valve 2-way 2-way 2-way 2-way Size - inches 3/8 3/8 3/4 3/4 Maximum working pressure - PSI 150 150 150 150 ENTERING WATER Water cooled units Using 65 F EWT GPM 1.2 1.9 2.5 3.1 PD in PSI 1.3 2.9 2.1 3.0 Using 75 F EWT GPM 2.0 3.0 3.9 4.9 PD in PSI 2.0 4.3 3.1 4.5 Using 85 F EWT GPM 2.8 4.2 5.6 7.0 PD in PSI 3.0 6.7 4.8 6.9 With Fluid Cooler GPM 3.5 5.3 7.0 8.8 PD in PSI 5.8 12.4 9.2 13.3 COMPRESSOR DATA Type Scroll Scroll Scroll Scroll Quantity 1 1 1 1 Cooling stages 1 1 1 1 Refrigerant type R-410A R-410A R-410A R-410A Crankcase heater Standard Standard Standard Standard * Insert: A- Air cooled, F - Flycol cooled, or W - Water cooled R-410A 14

AIR, GLYCOL and WATER COOLED: Performance data MODEL NUMBER DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5 REHEAT SECTION Optional Type - Electric Capacity- kw 2 2 2 2 Btu/hr 6,830 6,830 6,830 6,830 Capacity - kw 4 4 4 4 Btu/hr 13,660 13,660 13,660 13,660 Capacity- kw N/A N/A 5 5 Btu/hr 17,075 17,075 HUMIDIFIER SECTION Optional Type - Steam Generator Capacity - lb/hr 5 5 5 5 kw 1.7 1.7 1.7 1.7 FILTER SECTION Type Pleated Pleated Pleated Pleated Quantity 1 1 1 1 Size - inches 20x20x2 20x20x2 20x20x2 20x20x2 Efficiency - percentage 30 30 30 30 CONNECTION SIZES Condensate drain - fpt 3/4 3/4 3/4 3/4 Humidifier 1/4 1/4 1/4 1/4 With condensing unit: Liquid line - O.D. Copper 1/2 1/2 1/2 1/2 Suction line - O.D. Copper 3/4 3/4 3/4 3/4 With condenser: Liquid line - O.D. Copper 1/2 1/2 1/2 1/2 Hot gas line - O.D. Copper 1/2 1/2 1/2 1/2 Water and glycol cooled: Condenser water - In/Out 3/4 3/4 3/4 3/4 15 R-410A

AIR COOLED: Electrical data ELECTRICAL SECTION AIR COOLED (Packaged Systems) MODEL NUMBER DAMA-01-P DAMA-1.5-P DAMA-02-P DAMA-2.5-P Electrical data based on: electric reheat - NO, steam generator humidifier - NO. 208-230 V FLA/MCA/MOP 19/23/35 19/23/35 23/26/40 23/27/40 277 V FLA/MCA/MOP 18/21/30 18/21/30 20/24/35 23/27/40 Electrical data based on: electric reheat - NO, steam generator humidifier - YES. 208-230 V FLA/MCA/MOP 28/33/40 28/23/40 31/37/45 32/37/50 277 V FLA/MCA/MOP 24/29/35 24/29/35 27/31/40 29/35/45 Electrical data based on: 2 kw electric reheat -YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MOP 29/35/45 29/35/45 32/38/50 33/39/50 277 V FLA/MCA/MOP 25/30/35 25/30/35 28/33/40 31/36/50 Electrical data based on: 4 kw electric reheat -YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MOP 39/47/50 39/47/50 42/50/60 43/51/60 277 V FLA/MCA/MOP 33/39/45 33/39/45 35/42/50 38/45/50 Electrical data based on: 2 kw electric reheat -YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MOP 29/35/45 29/35/45 32/38/50 33/39/50 277 V FLA/MCA/MOP 25/30/35 25/30/35 28/33/40 31/36/50 Electrical data based on: 4 kw electric reheat -YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MOP 39/47/50 39/47/50 42/50/60 43/51/60 277 V FLA/MCA/MOP 33/39/45 33/39/45 35/42/50 37/45/50 AIR COOLED (Split Systems with Outdoor Condensing Unit) MODEL NUMBER DAMA-01-AO DAMA-1.5-AO DAMA-02-AO DAMA-2.5-AO Electrical data based on: electric reheat - NO, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MOP 4.0/5.0/15 4.0/5.0/15 5.3/6.6/15 5.3/6.6/15 Outdoor FLA/MCA/MOP 13/15/20 17/21/30 19/23/35 20/24/35 277 V Indoor FLA/MCA/MOP 3.6/4.5/15 3.6/4.5/15 4.3/5.4/15 4.3/5.4/15 Electrical data based on: electric reheat - NO, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MOP 12/15/20 12/15/20 14/17/20 14/17/20 Outdoor FLA/MCA/MOP 17/21/30 17/21/30 19/23/35 20/24/35 277 V Indoor FLA/MCA/MOP 9.7/12/15 9.7/12/15 10/13/15 10/13/15 Note: Transformers are required to step from 277 volt to 208-230 volt on outdoor condensing units. 277 volt condensing units are not available. FLA - Full load amps MCA - Minimum circuit amps wire sizing amps MOP - Maximum rating of the Overcurrent Protective device R-410A 16

AIR COOLED: Electrical data AIR COOLED (Split Systems with Outdoor Condensing Unit) MODEL NUMBER DAMA-01-AO DAMA-1.5-AO DAMA-02-AO DAMA-2.5-AO Electrical data based on: 2 kw electric reheat - YES, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MOP 14/17/20 14/17/20 15/19/20 15/19/20 Outdoor FLA/MCA/MOP 17/21/30 17/21/30 19/23/35 20/24/35 277 V Indoor FLA/MCA/MOP 11/14/15 11/14/15 12/14/15 12/14/15 Electrical data based on: 4 kw electric reheat - YES, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MOP 23/29/30 23/29/30 25/31/35 25/31/35 Outdoor FLA/MCA/MOP 17/21/30 17/21/30 19/23/35 20/24/35 277 V Indoor FLA/MCA/MOP 18/23/25 18/23/25 19/23/25 19/23/25 Electrical data based on: 2 kw electric reheat - YES, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MOP 14/17/20 14/17/20 15/19/20 15/19/20 Outdoor FLA/MCA/MOP 17/21/30 17/21/30 19/23/35 20/24/35 277 V Indoor FLA/MCA/MOP 11/14/15 11/14/15 12/14/15 12/14/15 Electrical data based on: 4 kw electric reheat - YES, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MOP 23/29/30 23/29/30 25/31/35 25/31/35 Outdoor FLA/MCA/MOP 17/21/30 17/21/30 19/23/35 20/24/35 277 V Indoor FLA/MCA/MOP 18/23/25 18/23/25 19/23/25 19/23/25 Note: Transformers are required to step from 277 volt to 208-230 volt on outdoor condensing units. 277 volt condensing units are not available. FLA - Full load amps MCA - Minimum circuit amps wire sizing amps MOP - Maximum rating of the Overcurrent Protective devices 17 R-410A

AIR COOLED: Electrical data AIR COOLED (Split Systems with Remote Air Cooled Condenser) MODEL NUMBER DAMA-01-CO DAMA-1.5-CO DAMA-02-CO DAMA-2.5-CO Electrical data based on: electric reheat - NO, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MOP 17/20/30 17/20/30 20/24/35 21/25/40 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277 V Indoor FLA/MCA/MOP 15/17/25 15/17/25 17/20/30 20/24/35 Electrical data based on: electric reheat - NO, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MOP 25/30/40 25/30/40 28/34/45 29/35/45 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277 V Indoor FLA/MCA/MOP 21/25/30 21/25/30 23/28/35 26/31/45 Electrical data based on: 2 kw electric reheat - YES, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MOP 26/32/40 26/32/40 30/36/45 30/37/50 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277 V Indoor FLA/MCA/MOP 22/26/35 22/26/35 24/29/40 27/33/45 Electrical data based on: 4 kw electric reheat - YES, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MOP 36/44/50 36/44/50 39/48/50 40/49/50 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277V Indoor FLA/MCA/MOP 29/35/40 29/35/40 31/38/45 34/42/50 Electrical data based on: 2 kw electric reheat - YES, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MOP 26/32/40 26/32/40 30/36/45 30/37/50 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277 V Indoor FLA/MCA/MOP 22/26/35 22/26/35 24/29/40 27/33/45 Electrical data based on: 4 kw electric reheat - YES, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MOP 36/44/50 36/44/50 39/48/50 40/49/50 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277 V Indoor FLA/MCA/MOP 29/35/40 29/35/40 31/38/45 34/42/50 FLA - Full load amps MCA - Minimum circuit amps wire sizing amps MOP - Maximum rating of the Overcurrent Protective device R-410A 18

WATER COOLED (Packaged Systems) WATER or GLYCOL COOLED: Electrical data MODEL NUMBER DAMW-01 DAMW-1.5 DAMW-02 DAMW-2.5 Electrical data based on: electric reheat - NO, steam generator humidifier - NO. 208-230 V FLA/MCA/MOP 17/20/30 17/20/30 20/24/35 21/25/40 277 V FLA/MCA/MOP 15/17/25 15/17/25 17/20/30 20/24/35 Electrical data based on: electric reheat - NO, steam generator humidifier - YES. 208-230 V FLA/MCA/MOP 25/30/40 25/30/40 28/34/45 29/35/45 277 V FLA/MCA/MOP 21/25/30 21/25/30 23/28/35 26/31/45 Electrical data based on: 2 kw electric reheat - YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MOP 26/32/40 26/32/40 30/36/45 30/37/50 277 V FLA/MCA/MOP 22/26/35 22/26/35 24/29/40 27/33/45 Electrical data based on: 4 kw electric reheat - YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MOP 36/44/50 36/44/50 39/48/50 40/49/50 277 V FLA/MCA/MOP 29/35/40 29/35/40 31/38/45 34/42/50 Electrical data based on: 2 kw electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MOP 26/32/40 26/32/40 30/36/45 30/37/50 277 V FLA/MCA/MOP 22/26/35 22/26/35 24/29/40 27/33/45 Electrical data based on: 4 kw electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MOP 36/44/50 36/44/50 39/48/50 40/49/50 277 V FLA/MCA/MOP 29/35/40 29/35/40 31/38/45 34/42/50 COMPRESSORS and MOTORS (DX Units, Air Cooled, and Water Cooled) COMPRESSORS and MOTORS (DX Units, Air Colled, and Water Cooled) MODEL NUMBER DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5 EVAPORATOR FAN MOTOR Standard motor - horsepower 1/2 1/2 3/4 3/4 FLA at 208-230 V 4.0 4.0 5.3 5.3 FLA at 277 V 3.6 3.6 4.3 4.3 CONDENSER FAN MOTOR (Air Cooled Indoor Packaged Units) Standard motor - horsepower 1/2 1/2 1/2 1/2 FLA at 208-230 V 3.4 3.4 3.4 3.4 FLA at 277 V 3.6 3.6 3.6 3.6 CONDENSER FAN MOTOR (Air Cooled Split Systems - Condensing Units or Air Cooled Condensers) Standard motor - horsepower 3/4 3/4 3/4 3/4 Motor FLA at 208-230 V 1.5 1.5 1.5 1.5 COMPRESSOR Standard motor - horsepower 1.5 1.5 2.0 2.5 FLA at 208-230 V 12.8 12.8 14.7 15.4 FLA at 277 V 10.9 10.9 12.5 15.4 FLA - Full load amps MCA - Minimum circuit amps wire sizing amps MOP - Maximum rating of the Overcurrent Protective device 19 R-410A

CHILLED WATER: Performance data MODEL NUMBER DAMC-01 DAMC-1.5 DAMC-02 DAMC-2.5 CAPACITY in Btu/hr - Gross 80 DB/67 WB Total 15,800 21,300 28,700 33,900 50% RH Sensible 12,200 16,500 22,400 26,600 75 DB/62.5 WB Total 12,500 16,800 22,800 26,900 50% RH Sensible 11,000 14,900 20,200 24,000 75 DB/61 WB Total 11,900 16,000 21,700 25,600 45% RH Sensible 11,400 15,400 21,000 24,900 72 DB/60 WB Total 10,800 14,600 19,800 23,300 50% RH Sensible 10,200 13,700 18,700 22,200 72 DB/58.6 WB Total 10,500 14,100 19,200 22,700 45% RH Sensible 10,400 14,000 19,200 22,700 Note: Chilled Water capacity based on 45 F entering chilled water temperature. CHILLED WATER COIL Face are - sq ft 2.4 2.4 2.4 2.4 Rows of coil 3 3 4 4 Face velocity - fpm 229 323 417 510 BLOWER SECTION Airflow - cfm 550 775 1000 1225 Standard fan motor - hp 1/2 1/2 3/4 3/4 External Static Pressure (E.S.P.) - inches of W.G. 0.5 0.5 0.5 0.5 Number of fans 1 1 1 1 CHILLED WATER REQUIRED (Maximum 150 PSI) Using 45 F EWT GPM 3.0 4.5 6.0 7.5 PSI 2.4 5.3 7.7 10.5 CHILLED WATER VALVE Valve body 2-WAY 2-WAY 2-WAY 2-WAY Valve size - inches 3/4 3/4 3/4 3/4 REHEAT SECTION (Optional) Electric kw 2 2 2 2 Btu/hr 6,825 6,825 6,825 6,825 kw 4 4 4 4 Btu/hr 13,650 13,650 13,650 13,650 kw N/A N/A 5 5 Btu/hr N/A N/A 17,075 17,075 HUMIDIFIER SECTION (Optional) Steam generator Capacity - lbs/hr 5 5 5 5 kw 1.7 1.7 1.7 1.7 20

CHILLED WATER: Performance data MODEL NUMBER DAMC-01 DAMC-1.5 DAMC-02 DAMC-2.5 FILTER SECTION Type Pleated Pleated Pleated Pleated Quantity 1 1 1 1 Size - inches 20x20x2 20x20x2 20x20x2 20x20x2 Efficiency - percentage 30 30 30 30 CONNECTION SIZES Chilled water in/out O.D. copper 3/4 3/4 3/4 3/4 Condensate drain - FPT 3/4 3/4 3/4 3/4 Humidifier 1/4 1/4 1/4 1/4 ELECTRICAL SECTION Electrical data based on: electric reheat - NO, steam generator humidifier - NO. 208-230 V FLA/MCA/MOP 4.0/5.0/15 4.0/5.0/15 5.3/6.6/15 5.3/6.6/15 277 V FLA/MCA/MOP 3.6/4.5/15 3.6/4.5/15 4.3/5.4/15 4.3/5.4/15 Electrical data based on: electric reheat - NO, steam generator humidifier - YES. 208-230 V FLA/MCA/MOP 12/15/20 12/15/20 14/17/20 14/17/20 277 V FLA/MCA/MOP 9.7/12/15 9.7/12/15 10/13/15 10/13/15 Electrical data based on: 2 kw electric reheat - YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MOP 14/17/20 14/17/20 15/19/20 15/19/20 277 V FLA/MCA/MOP 11/14/15 11/14/15 12/14/15 12/14/15 Electrical data based on: 4 kw electric reheat - YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MOP 23/29/30 23/29/30 25/31/35 25/31/35 277 V FLA/MCA/MOP 18/23/25 18/23/25 19/23/25 19/23/25 Electrical data based on: 2 kw electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MOP 14/17/20 14/17/20 15/19/20 15/19/20 277V FLA/MCA/MOP 11/14/15 11/14/15 12/14/15 12/14/15 Electrical data based on: 4 kw electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MOP 23/29/30 23/29/30 25/31/35 25/31/35 277 V FLA/MCA/MOP 18/23/25 18/23/25 19/23/25 19/23/25 BLOWER SECTION Standard motor - hp 1/2 1/2 3/4 3/4 FLA at 208-230 V 4.0 4.0 5.3 5.3 FLA at 277 V 3.6 3.6 4.3 4.3 FLA - Full load amps MCA - Minimum circuit amps wire sizing amps MOP - Maximum rating of the Overcurrent Protective device 21

Air Cooled Split with DARC Outdoor Condenser DAMA-XXXX-CO 22

Air Cooled Split with DARC Outdoor Condenser DAMA-XXXX-CO 23

Air Cooled Split with DRCU Outdoor Condensing Unit DAMA-XXXX-AO 24

Air Cooled Split with DRCU Outdoor Condensing Unit DAMA-XXXX-AO 25

Air Cooled Packaged DAMA-XXXX-P 26

Air Cooled Packaged DAMA-XXXX-P 27

Air Cooled Split with Indoor Condenser DAMA-XXXX-CI 28

Air Cooled Split with Indoor Condenser DAMA-XXXX-CI 29

Air Cooled Split with Indoor Condensing Unit DAMA-XXXX-AI 30

Air Cooled Split with Indoor Condensing Unit DAMA-XXXX-AI 31

Water/Glycol Cooled DAMW-XXXX 32

Water/Glycol Cooled DAMW-XXXX 33

Chilled Water DAMC-XXXX 34

Chilled Water DAMC-XXXX 35

Condenser and Condensing Unit Dimensional Drawings Condenser Unit Condensing Unit 36

Return Air Filter Box Typical Hanging Installation Detail MINI CEILING SYSTEM TYPICAL HANGING INSTALLATION DETAIL 5/8" Threaded Rod (4) Required 5/8" Flat Washer See Mounting Detail 5/8" Nut MINI CEILING SYSTEM LOW AMBIENT DAMPER CONTROL PACKAGE (Optional) 5/8" Jam Nut All Mounting Hardware Field Provided Connect to Schrader Valve Fitting on Discharge Line See Damper Detail Duct Work Supplied and Installed by Others 5 1/2" 16" x 16" Ambient Controlled Damper Supplied by Data Aire (Shipped Loose) 37

Provide and install an air conditioning system designed specifically for use in small computer/data processing areas, or controlled office environments, and shall be capable of cooling, humidifying, dehumidifying, and filtering air. Units shall be ETL or UL listed. The frame shall be constructed of 14 gauge welded tubular steel and be coated with a heavy corrosion inhibiting finish for long life. The side panels shall be of galvanized steel. The cabinet shall be insulated with one-half inch (1/2 ) thick, closed cell insulation. The plenum shall be of cold rolled steel and painted in a cloud white finish. The plenum (vertical unit only) shall be field mounted. The unit shall be serviceable through the removable side panels. The vertical air flow unit is to be ceiling mounted and sized to fit a standard 2 ft x 4 ft T-bar ceiling grid opening. The horizontal supply/return air unit is to be ceiling hung with duct work attached to supply and return openings. The total cooling capacity shall be Btu/hr at degree F DB and degree F WB entering air temperature. The voltage shall be, 1 ph, 60 hz. Electrical - All electrical components including contactors, relays, control transformers, and capacitors shall be pre-wired. The control circuit voltage shall be 24 volts. A micro-switch shall disable the unit operation prior to condensate pan overflow should the drain line become plugged with debris. Filter - Provide a two (2 ) inch, 30% efficient (based on ASHRAE Std. 52.1-1992) disposable filter of twenty inches square (20 x 20 ). The filter shall be located behind and accessible through the hinged return air grille. Air Cooled Self-Contained - The refrigeration system shall be self-contained, factory assembled, charged, and tested. No refrigerant piping shall be required. The unit shall contain an evaporator and condenser section. The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The single refrigeration circuit shall include the expansion valve with external equalizer, filter drier, high and low pressure safety switches. The scroll type compressor shall have internal overload protection. Units with capillary tube metering devices shall not be acceptable. Mini Ceiling Systems Guide Specifications General 38 The evaporator blower assembly shall be draw-through configuration consisting of a double inlet, double width, direct drive centrifugal fan with belt drive and variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be horsepower. Air delivery shall be a minimum of cfm. The condensate drain pan shall be constructed of stainless steel and provide a positive drain to prevent standing water in the condensate pan. The field attached condenser section shall have a condenser coil constructed with copper tubes and aluminum fins and built into the refrigeration system. The condenser fan shall be double inlet, double width, direct drive type. The condenser blower motor electrical connection shall be through a factory wired plug. Air Cooled Split System (with outdoor condensing unit) - The refrigeration system shall be split consisting of an evaporator section and remote outdoor condensing unit. The evaporator and condensing unit shall be factory assembled and tested. The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The single refrigeration circuit shall include the expansion valve with external equalizer, filter drier, and high and low pressure safety switches. The high and low pressure safety switches are connected to the refrigerant system with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. The scroll type compressor shall have internal overload protection. Units with capillary tube metering devices shall not be acceptable. The evaporator blower assembly shall be draw-through type consisting of a double inlet, double width, centrifugal fan with belt drive and variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be horsepower. Air delivery shall be a minimum of cfm. The condensate drain pan shall be constructed of stainless steel. The condensing unit shall be constructed of heavy duty gauge corrosion resistant steel with a powder coated finish and contain a scroll type compressor with crankcase heater, filter drier, sightglass, and condenser coil. The coil shall be constructed with copper tubes and aluminum fins. The condenser fan motor shall be variable speed for head pressure control down to -20 degrees F. The capillary tube connection from the fan speed con-

GUIDE SPECIFICATIONS continued trol to the refrigerant system shall be connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. The condenser motor shall be direct drive with a propeller type fan. Air Cooled Split System (with outdoor condenser) - The refrigeration system shall be split consisting of an evaporator section and remote outdoor condenser. The evaporator and condenser shall be factory assembled and tested. The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The single refrigeration circuit shall include the expansion valve with external equalizer, filter drier, and high and low pressure safety switches. The scroll type compressor shall have internal overload protection. Units with capillary tube metering devices shall not be acceptable. The evaporator blower assembly shall be draw-through configuration consisting of a double inlet, double width, centrifugal fan with belt drive, variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be horsepower. Air delivery shall be a minimum of cfm. The condensate drain pan shall be constructed of stainless steel. The condenser section shall be a low profile, slow speed, direct drive propeller fan type. The condenser shall be constructed of heavy duty gauge corrosion resistant steel with a powder coated finish and contain a copper tube aluminum fin coil with vertical air discharge. The condenser shall have fan speed control with transducers to modulate the speed of the condenser fan and provide positive start-up and operation at ambient temperatures to -20 F. All controls including the fan speed control, shall be factory mounted in the air cooled condenser. Water Cooled Self-Contained - The refrigeration system shall be self-contained, factory assembled, charged and tested. No refrigerant piping connections shall be required. The unit shall contain an evaporator and condenser section. The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The single refrigeration circuit shall include the expansion valve with external equalizer, filter drier, and high and low pressure safety switches. The scroll type compressor shall have internal overload protection. Units with capillary tube metering devices shall not be acceptable. The evaporator blower assembly shall be draw-through configuration consisting of a double inlet, double width, centrifugal fan with belt drive, variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be horsepower. Air delivery shall be a minimum of cfm. The condensate drain pan shall be constructed of stainless steel and provide a positive drain to prevent standing water in the condensate pan. A high efficiency plate-fin water cooled condenser with head pressure activated water regulating valve built into the refrigeration system shall be provided. The capillary tube connection from the water regulating valve to the refrigerant system shall be connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. Maximum operating water pressure shall be 150 psi. Chilled Water - Provide a packaged system designed to utilize an existing chilled water loop. The unit shall be factory assembled, piped, wired, and tested. A chilled water coil consisting of copper tubes and aluminum fins shall be provided. The chilled water flow shall be controlled by a two-way valve for accurate and economical temperature control and dehumidification. The blower assembly shall be drawn through a configuration consisting of a double inlet, double width, direct drive centrifugal fan with belt drive, variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be horsepower. Air delivery shall be a minimum of cfm. The condensate drain pan shall be constructed of stainless steel and provide a positive drain to prevent standing water in the condensate pan. All components shall be housed within the same cabinet. Controls -The control system shall be electromechanical type, utilizing a 24 volt thermostat. A sub-base shall be provided for remote wall mounting of thermostat. The controls shall be accessible through the side panel of the unit and contained in a hinged electrical box that shall swing out for easy access and servicing. Removal of the unit from the ceiling space shall not be required for access. 39

CONTROLS Unit Control Mini Data Alarm Processor-II - The control system shall be furnished with the microprocessor based Mini Data Alarm Processor-II. The panel shall include unit switching functions and display normal functions, malfunctions, and service diagnostics on a one row, 16 character liquid crystal display (LCD) in clear vernacular format. The panel shall automatically display temperature and humidity along with all operational and alarm messages. The panel shall recall and display the high and low temperature and the high and low humidity for the last 24 hours, date and time, reheat, humidification, dehumidification, and chilled water operation (as applicable). Programming shall have a two level password security to prevent unauthorized access. Programming shall be accomplished entirely from the microprocessor. Programmable functions shall be entered on nonvolatile EEPROM to insure program retention should power fail. Multiple messages shall be displayed by automatically scrolling from each message to the next. Alarm conditions, in addition to being displayed, shall enunciate an audible alarm with variable output. Additional test or service terminals shall not be required for any functions. An alarm condition shall continue to be displayed until the malfunction is corrected. Multiple alarms shall be displayed sequentially in order of occurrence and only those alarms which have not been acknowledged shall continue to sound an audible alarm. The Mini Data Alarm Processor-II shall perform an automatic self-test on system start-up. A user accessible diagnostic program shall aid in system component trouble shooting by displaying on the unit LCD screen output relay number, terminal plug and pin number for each controlled item. The following functions shall be programmable: Temperature setpoint (60-80 F, 15.6-26.7 C), Temperature sensitivity (1-5 F,.5-2.7 C in 0.1 increments), Humidity setpoint (30-70% RH), Humidity sensitivity (1-15% RH in 0.1% increments), Temperature alarm points, Humidity alarm points, Unit start time delay, 40 Interstage time relay, Password 1 st level, Password 2 nd level, Audio alarm level, Restart mode, Firestat trip temperature, Local alarm function The following normal functions shall be monitored and displayed: Current temperature ( F or C), Current humidity (Percentage RH), Cooling, Reheat, Humidification, Dehumidification, Date and time The following alarm functions shall be monitored and displayed when they occur, in addition to enunciating an audible alarm: High temperature, Low temperature, High humidity, Low humidity, Compressor high pressure, High condensate water, Firestat tripped, No air flow, Compressor short cycle, Temperature sensor error, Humidity Sensor error The following switching and control functions shall be included: System On/Off switch, Menu selection button for: Programming operational information, Diagnostics, Historical data, and Alarm silence/program set button Site Monitoring DARA-4 (Data Aire Relay Autochangeover) Controls up to four Mini Ceiling units using a dry set of relay contracts. The DARA-4 provides unit rotation, backup capacity and the ability to interface with most BMS systems.

OPTIONS Unit Options HORIZONTAL SUPPLY AND RETURN AIR HUMIDIFIER Provide a steam generator type humidifier. The steam humidifier shall be of the self-contained cylinder type with electronic controls. The humidifier shall discharge pure steam with no material dust carry-over, and shall have self-regulating flush cycle. Cylinders shall be disposable not requiring cleaning or maintenance. Humidifier rate shall automatically adapt, both in frequency and duration, to variations in the incoming water. The humidifier capacity shall be 5 pounds per hour with power consumption of 1.7 kw. (Note: When specifying the steam generator type humidifier, a Mini Data Alarm Processor-II is required.) REHEAT Provide electric reheat. The electrical heating element shall be of the finned tube resistant type and constructed of stainless steel with high limit cutout. The capacity shall be kw, Btu/hr. CONDENSATE PUMP A condensate pump shall be provided with the unit and shall have a capacity of 60 GPH at 8 feet of head. The pump shall be shipped loose for field mounting and installation. It is also available installed and wired from the factory. The pump voltage shall be. Supply and return air shall be horizontal for ducted connection. Refer to the project drawings. FRONT SUPPLY AIR Supply air shall be through the front of the unit for ducted connection. The unit shall be provided with a flange connection. Refer to the project drawings. SIDE SUPPLY AIR Supply air shall be through the side of the unit for ducted connection. The unit shall be provided with a flange connection. Refer to the project drawings. SIDE RETURN AIR Return air shall be through the side of the unit for ducted connection. The return air shall be through a factory provided ceiling mounted return air grille. The ceiling mounted return air grille shall be hinged for easy access and shall contain a 30% efficient (based on ASHRAE Std. 52.1-1992) 20 x 20 x 2 pleated filter. Refer to the project drawings. EXTENDED COMPRESSOR WARRANTY Extended compressor warranties are available from Data Aire. Contact your local representative for one that best suites your needs. LOW AMBIENT CONTROL DAMPER Provide a low ambient control damper for ducting of outside condenser air. The low ambient control damper shall consist of a 14 x 14 damper section with headpressure operator. The control shall enable the unit to operate down to -30 F ambient. The capillary tube connection from the head pressure control to the refrigerant system shall be connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. 41

Weights - lbs Operational Shipping 1.0 1.5 2.0 2.5 1.0 1.5 2.0 2.5 Packaged Systems Air Cooled 425 425 425 425 450 450 450 450 Water Cooled 350 350 350 350 375 375 375 375 Chilled Water 300 300 300 300 325 325 325 325 Split Systems* Air Cooled - AO 280/300 280/300 280/300 280/300 305/340 305/340 305/340 305/340 Air Cooled - CO 325/260 325/260 325/260 325/260 350/300 350/300 350/300 350/300 * Weights provided are for the evaporator section (inside-first number) and condensing or condenser section (outside-second number). Each section shipped separately. Weights shown are for standard units. 42

230 W. BlueRidge Avenue Orange CA 92865 800-347-2473 www.dataaire.com e-mail: sales@dataaire.com A Member of the CS Group of Companies 2010 Data Aire Inc. Data Aire, Inc. reserves the right to make design changes for the purposes of product improvement, or to withdraw any design without notice. DAMCS-R-410A - 0810