ELECTRICAL SAFETY Information Bulletin

Similar documents
ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin

Overview of Hazardous Locations as They Relate to Solenoid Valves

MODULAR INTEGRATION OF PROCESS EQUIPMENT PACKAGES FOR OIL AND GAS FACILITIES

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT

USER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

Ontario Fire Code SECTION 5.10 COMBUSTIBLE DUST PRODUCING PROCESSES. Illustrated Commentary. Office of the Ontario Fire Marshal

Electrical Area Classification 101 An Introduction to Area Classification the Basics IEEE Houston CED

Certificate of Compliance

Certificate of Compliance

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR PIPE THREAD IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

Portable Equipment. Equipment with electrical components suitable to be moved by a single person without mechanical aids.

Electrical Safety Requirements

GAS SAFETY Information Bulletin

SERIES & NO. SMI SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF SPECIAL ELECTRICAL SYSTEMS

Smoke detection in hazardous areas:

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

AM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74

Red Deer. AMA Regional Meeting. Electrical, Plumbing, Gas, Private Sewage, Building and Fire

ORDINANCE NO

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

GASEOUS HYDROGEN SYSTEMS

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Providing Solutions. Simplifying Regulation. IIAR Standards. Peter Thomas, P.E., CSP Resource Compliance, Inc.

Part I Extraction Process Equipment

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

PRIMATECH WHITE PAPER PROCEDURE FOR DUST HAZARD ANALYSIS (DHA)

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

Certificate of Compliance

Above Ground Fuel Tank Requirements

MODELS 304GC, 304GCX, 314GC, and 314GCX

PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

Survey of electrical equipment installed in hazardous areas on tankers

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

BUILDING CODE INTERPRETATION

[ TECHNOLOGY ] and does this definition affect a burner.

DIRECTIVE NO: D-B

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

1.1 SECTION INCLUDES.1 Materials and installation for aboveground oil storage tanks..2 Section Waste Management and Disposal.

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

Field Certification Certificate of Compliance

Copy Right By: Thomas T.S. Wan

Certification Supplement Manual

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

MODELS ASHP, ASHH, ASUP, and ASUH

Safe Operation Manual. Honeywell IQ Force Gas Detector

ICC CODE CORNER 2015 International Fire Code

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012

SEMICONDUCTOR FABRICATION FACILITIES

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.

INSTRUCTION & SERVICE MANUAL

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

FX5 Series Explosion-Proof Electric Air Heaters

Industrial furnaces and associated processing equipment Safety. Part 2: Combustion and fuel handling systems

DuPont Formacel Z-2. Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications FOAM EXPANSION AGENT TECHNICAL INFORMATION

Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Installation Instructions

INSTALLATION, OPERATION INSTRUCTIONS FOR FLOW SWITCHES 62-9FS & FS

1303 Trans Canada Way SE Medicine Hat, AB T1B 3Z9 Phone

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

2012 Annual Technical Conference FIRE CODE VARIANCE INTERCONNECTION OF SMOKE ALARMS IN EXISTING SECONDARY SUITES

SEMICONDUCTOR FABRICATION FACILITIES

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

LGB. Control Supplement. Gas fired boiler. Universal Control System. Series 2 Propane gas. Contents

User manual. Explosion-safe window air conditioning system Type series AR-054. II 3 G Ex ic nac h IIC T3 Gc

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version

OPTIBAR DP 7060 Supplementary Instructions

Process Control PIP PCEA001 Fixed Gas Detection Guidelines

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

rpsa FIRE PROTECTION ENGINEERS

ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

First Revision No. 20-NFPA [ Section No ]

Selection of Explosion Protected Equipment for Hazardous Locations. Compiled by: Pieter Coetzee ZONE 2 ZONE 1 ZONE 0.

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

Installation Instructions U-RAD-LT Electric Radiant Heaters

Portable Generator Safety Lloyd Shank, P.E. Director of Electric and Gas Utilities 4/12/2005

ULTRA-SAFE Explosion-proof Duct Heaters

Liquefied Petroleum Gas Facility Written Fire Safety Analysis

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

PORTABLE FIRE EXTINGUISHERS

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

1. PURPOSE This standard specifies safe design, construction, installation, and operation of refrigeration systems.

Fire Alarm System Accessories

GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS

Selecting a Safe Tank Gauging Product. Understanding Hazardous Area Definitions for Equipment Approvals

Guide to Explosion Protection and Plant Safety

SEMICONDUCTOR FABRICATION FACILITIES

GAS SAFETY Information Bulletin

Transcription:

ELECTRICAL SAFETY Information Bulletin October 2007 Page 1 of 11 CANADIAN ELECTRICAL CODE SUBJECT: Section 18 Hazardous Locations Rule 18-006 Division of Class I Locations General For classification requirements at oil and gas facilities please consult the Code for Electrical Installations at Oil and Gas Facilities published by the Safety Codes Council. For classification requirements at dispensing stations, garages, bulk storage plants, finishing processes, and aircraft hangars please consult Section 20 of the Canadian Electrical Code and STANDATA CEC-20. Anhydrous Ammonia (Liquid Fertilizer) The space within 3 m surrounding an anhydrous ammonia (NH 3 ) storage tank, pump, valve, meter, and similar equipment is considered a Class I, Zone 2 hazardous area. Area Classification Persons doing area classification should consider the following: a) Although the purpose of area classification, as outlined in the CEC, is to determine the proper equipment, materials, and wiring methods for electrical installations in the Hazardous Locations, it is important to recognize that other codes and regulations may reference the resulting area classification. In Alberta, the Occupational Health and Safety Code also references the electrical area classification requirements of the CEC. b) The area classification should address whether systems are in place to limit a location s exposure time to explosive concentrations of combustible gas to a short time as required by rule 18-006(c)(i). When abnormal releases or failure of ventilation result in flammable concentrations of gas or vapour, the hazard caused by the abnormal release or failure of ventilation should be mitigated in a short time. c) For remote unattended facilities, gas detection with remote notification should be considered to allow an effective response that limits the facility s exposure to an explosive gas atmosphere to a short time. Otherwise, the location should be classified as Zone 1 (or Division 1). Issue of this STANDATA is authorized by the Administrator Pierre McDonald Alberta Municipal Affairs and Housing Safety Services, 16 th floor, Commerce Place, 10155 102 Street, Edmonton, Alberta, Canada, T5J 4L4 Safety Codes Council, Suite 800, 10707 100 Avenue, Edmonton, Alberta, Canada, T5J 3M1

Page 2 of 11 For an indication on what constitutes a short time, the American Petroleum Institute API Recommended Practice 505 - Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Zone 0, Zone 1, and Zone 2 states the following: Although there is no firm rule relating the time that flammable mixtures occur in with Zone 0, Zone 1, Zone 2, and unclassified locations, many use the rule-ofthumb shown in Table 3. Table 3 Showing the Typical Relationship Between Zone Classification and the Presence of Flammable Mixtures Zone 0 1 2 unclassified Flammable Mixture Present 1000 or more hours / year (10%) >10 and <1000 hours/year (0.1% - 10%) >1 and <10 hours/year (0.01% - 0.1%) Less than 1 hour/year (0.01%) Rule 18-008 Division of Class II Locations Ammonium Nitrate Fertilizer Storage Areas where ammonium nitrate is stored in bulk, is being placed into bags or is otherwise being handled are not considered to be combustible or electrically conducting. Such areas are therefore, considered to be non-hazardous in so far as electrical requirements are concerned. Ammonium nitrate however, is an oxidizing agent, and for this reason, corrosion resistant wiring methods should be considered in designing or wiring such installations. Sulphur Handling Areas Indoor areas where sulphur dust is in suspension in the air in quantities sufficient to produce explosive or ignitable mixtures should be classified as Class II, Division I locations requiring equipment approved for Group G atmospheres. Indoor areas where sulphur dust is not normally in suspension in the air in quantities sufficient to produce explosive or ignitable mixtures may be classified as Class II, Division 2. Outdoor areas where sulphur is being ground, pulverized, or handled in a way that will produce fine dust may also be classified as Class II, Division 2.

Page 3 of 11 The Appendix B note in Rule 18-008 also references NFPA (National Fire Protection Association) Standard 655 for Prevention of Sulphur Fires and explosions which provides additional information on the safe handling of sulphur dusts. Sulphur, under some conditions, is very corrosive and this should be taken into consideration in the design, installation and maintenance of the electrical system for this type of facility. Area Classification for Dusty Locations Following is a guide for classifying grain elevators, feed mills and seed cleaning plants, where good housekeeping procedures are implemented and maintained (i.e., dust collection systems) to prevent dust accumulation. Grain Elevators The interior of a grain elevator is normally classified as Class II, Division 2. Historical precedent has established that dust conditions may permit alternate wiring methods and equipment installation as follows: Rule 18-252 Wiring Methods EMT with rain-tight couplings may be used where not subject to mechanical damage, excessive vibration or movement. Boxes and fittings enclosing taps, joints or terminal connections must meet the requirements of 18-252(2) to minimize the entrance of dust. Rule 18-256 Switches,... Lighting switches may be mounted in one piece cast metal boxes, such as type FS and FD, with gasketted covers. Rule 18-270 Receptacles and Attachment Plugs Standard receptacles mounted in one piece cast metal boxes such as FS and FD type boxes with spring loaded weatherproof gasketted covers may be used in the driveway on the outside wall. Receptacles installed elsewhere in the classified area must comply with rule 18-270.

Page 4 of 11 Feed Mill The interior of a feed mill is normally classified as Class II, Division 1 and the storage area Class II Division 2. Historical precedent has established that dust conditions may permit alternate wiring methods and equipment installation as follows: CLASS II DIVISION 1 Rule 18-202 Wiring Methods Standard gasketted conduit fittings, such as LB s, etc. may be used. One piece cast metal boxes threaded for connection to conduit may also be used. Rule 18-206 Switches,... Oil tight push buttons in dusttight enclosures threaded for connection to conduit are acceptable. CLASS II DIVISION 2 Rule 18-252 Wiring Methods EMT with rain-tight couplings and connectors may be used where not subject to mechanical damage, excessive vibration of movement. Rule 18-256 Switches, Controllers,... Lighting switches may be mounted in one piece cast metal enclosures, such as FS and FD type boxes with gasketted covers. Rule 18-270 Receptacles and Attachment Plugs Standard receptacles mounted in one piece cast metal boxes such as type FS and FD with springloaded weatherproof gasketted covers may be used where dust conditions are not too severe. Electrical rooms located in the hazardous location must be constructed in accordance with the requirements for Dust Free Rooms as indicated in Appendix E of the Canadian Electrical Code.

Page 5 of 11 Seed Cleaning Plant The interior of a seed cleaning plant is normally classified as Class II, Division 2. Historical precedent has established that dust conditions may permit alternate wiring methods and equipment installation as follows: Rule 18-252 Wiring Methods EMT with rain-tight couplings may be used where not subject to mechanical damage, excessive vibration or movement. Boxes and fittings enclosing taps, joints or terminal connections must meet the requirements of 18-252(2) to minimize the entrance of dust. Rule 18-256 Switches,... Lighting switches may be mounted in one piece cast metal boxes, such as type FS and FD, with gasketted covers. Rule 18-270 Receptacles and Attachment Plugs Standard receptacles mounted in one piece cast metal boxes such as FS and FD type boxes with spring loaded weather proof gasketted covers may be used in the driveway on the outside wall. Receptacles installed elsewhere in the classified area must comply with rule 18-270. Rule 18-050 Electrical Equipment Area Classification of Ammonia Machinery Rooms Ammonia is listed in Rule 18-050 as a Group IIA (Group D) hazardous gas. CSA Standard B52- Mechanical Refrigeration Code includes installation requirements for refrigerating systems that use ammonia. A refrigerating system that uses ammonia in a "Machinery Room", the room is normally considered a Class I, Zone 2, hazardous location. However, when a refrigerating system using ammonia is installed in a "Class T Machinery Room", the room shall not be considered a hazardous location. One of the requirements for a Class T machinery room is that where the independent mechanical ventilation system is not

Page 6 of 11 operated continuously, a gas monitoring system shall be installed that will automatically start up the ventilation system and actuate a remote alarm at the lowest practical instrument-detection level not exceeding 25 per cent of the lower explosive limit. To be acceptable as a non-hazardous location, it may be necessary to provide the electrical inspection department written confirmation that the refrigerating system is installed in a "Class T Machinery Room" in conformance with CSA Standard B52. Installation of Transducers and Similar Devices Transducers are devices used to convert one form of energy into another (such as pressure-to-current or vice versa). In a typical application the transducer converts an electrical output signal (usually 4-20mA) from a controller to a pneumatic signal necessary to operate a control valve actuator or pneumatic positioner (I/P). Another application may be to monitor the flow and/or pressure of process fluids with transducers that convert pressure to a 4-20mA signal (P/I). Careful consideration must be given to the selection of an appropriate transducer if a flammable gas or liquid (explosive fluid) is intended as the medium for operation. Using transducers designed only to be operated with normal air pose significant safety hazards when they are actually operated by an explosive fluid. In these situations, the device has not been designed or tested for use with an explosive fluid and is not suitable for the application thus voiding its certification and in non-compliance with the Canadian Electrical Code. When a normal air transducer is operated with an explosive fluid there is a significant risk that the explosive fluid will migrate into the wiring system with potentially increased pressures within the equipment and the wiring system further compounding the hazard. Even though the wiring system and equipment enclosure may be explosion proof, they may not have been designed for use where we have a combination of an explosive fluid at elevated pressures therefore the normal air transducer is not suitable for the application. CSA Standard C22.2 No. 30 M1986 (R2003) Explosion Proof Enclosures for Use in Class I Hazardous Locations has provisions for incorporating an explosive fluid seal where a transducer is operated by an explosive fluid. When selecting a transducer (or similar device) intended for operation with an explosive fluid be sure to specify to the supplier/manufacturer its intended application and that it requires an explosive fluid seal. At existing transducer installations, where an explosive fluid is the medium used to operate the device, you are encouraged to review documentation and consult with the manufacturer to determine whether the device incorporates an explosive fluid seal. Where it is identified that these installations have a transducer that is not suitable for the application, you are advised to take all necessary actions to resolve a potentially hazardous situation. Note: Although the installation of this type of equipment is prevalent in hazardous locations, there are certainly situations where a transducer operated by an explosive fluid is located in a non-hazardous location. In those cases, the above information is also equally applicable. Relocatable Structures (Skid Units) See STANDATA CEC-2, Item Rule 2-100 Marking of Equipment.

Page 7 of 11 Rule 18-052 Marking Rule 18-054 Temperature To comply with Rule 18-054, electrical equipment that does not bear the temperature mark indicated in Subrule 18-052(4) must not be used where there are vapours with an ignition temperature less than the values given in Subrule 18-052(5). Where it is intended to use non-explosion proof motors or generators in compliance with Rule 18-168, particular attention should be given to motors with a Class F or Class H insulation. The allowable operating temperature of these motors exceeds the minimum ignition temperature of some flammable vapours and the equipment motors must not be used where these vapours exist. Rule 18-064 Pressurized Equipment or Rooms CEC Rule 18-064 allows equipment pressurized with a protective gas to be located in a Class I Hazardous Location. The appendix B note to this Rule suggests two possible references that could be used to meet the requirements of this Rule. The NFPA standard 496 Standard for Purged and Pressurized Enclosures for Electrical Equipment is frequently used as a guide in designing systems to meet the requirements of Rule 18-064 in Class I Zone 2 or Division 2 Hazardous Locations. The purpose of this STANDATA item is to highlight a common error that is made in applying this Standard, as outlined in the following. The pressurization system used by the standard to pressurize enclosures in Class I Zone 2/Division 2 Hazardous Locations is a type Z purge. Three requirements of type Z pressurizing in the standard read as follows: 4.8* Type Z Purging 4.8.1 Detection shall be provided to indicate failure to maintain positive pressure within a protected enclosure. 4.8.1.1* Failure to maintain positive pressure within a protected enclosure shall be communicated by an alarm or an indicator. 4.8.1.2 It shall not be required to de-energize the protected equipment upon detection of the failure to maintain positive pressure within the protected enclosure. Note that when reading the standard an asterisk (*) at the beginning of a paragraph, indicates that explanatory material on the paragraph can be found in Appendix A of the standard. In some cases designers have interpreted paragraph 4.8.1.2 to mean that while loss of pressurization requires an alarm, it will not be necessary to de-energize the protected equipment. It should be noted that the wording in paragraph 4.8.1.2 should be understood to mean that while it may not be necessary to de-energize the protected equipment immediately upon loss of pressurization, if the pressurization cannot be restored within a short period, the protected equipment should be de-energized.

Page 8 of 11 This interpretation is confirmed by the Appendix A note to the definition for an alarm which reads as follows: A.3.3.1 Alarm. An alarm is intended to alert the user that the pressurizing system should be immediately repaired or that the electrical equipment protected by the failed pressurizing system should be removed from service. If the protected equipment is critical to the operation of a facility, installation of backup pressurization means should be considered as a part of the design. Rule 18-074 Bonding, in Hazardous Locations For sizing bonding conductors or bonding jumpers in hazardous locations, Rule 10-814 (Bonding Conductor Size) should be used. The use of table 41, as required by rule 10-614 is intended to apply only to service equipment. Previously, bonding requirements were such that cables be bonded in accordance with 10-606(1)(a), (c), and (d), essentially requiring grounding bushings to supplement bonding of the sheath. Currently, 18-074(2) recognizes that where cables and raceways incorporate a bonding conductor, the bonding of the sheath through standard locknuts is adequate and bonding bushings are not mandatory. Rules 18-092(1), 18-108(1), 18-158(1), J18-108(1) and J18-158(1) Secondary Seals Secondary Seals are intended to prevent the flow of flammable fluids (gases or liquids) from devices (such as pressure switches, flow and level devices, solenoid valves, etc.) connected directly to process containing flammable fluids in the event that the Primary Seal within the device fails. The installation requirement for secondary seals in the 2006 edition Canadian Electrical Code resulted from a worker sustaining serious injuries in December 2000, at a Natural Gas Compressor Station. The incident occurred when a primary seal failed and, due to the pressure of the process, natural gas was forced through the motor feeder cables into a non-hazardous area. Since this unfortunate incident there have been other cases documented where due to the failure of a single primary seal, process fluids were able to migrate through cable and conduit systems. As the rules imply, secondary seals must be installed if there is a possibility of flammable process fluids migrating through the conduit or cable system in the event of a primary seal failure. While the CEC rule provides for black and white situations, a reasonable approach to not justifying the requirements for secondary seals needs to be provided based on the circumstances of the installation. If the probability of the following three situations is remote: 1) a primary seal fails; and

Page 9 of 11 2) flammable fluids enters the conduit or cables system and flows into non-classified areas; and 3) an ignition source is present; then justification can be made by engineering professionals for the elimination of the secondary seal. Rules 18-092(2), 18-108(2), 18-158(2), J18-108(2) and J18-158(2) Verification of Primary Seal Failure Rules 18-092(2), 18-108(2), 18-158(2), J18-108(2) and J18-158(2) of the Canadian Electrical Code (CEC) all require that where field installed secondary seals are present, primary seal failure must be made obvious (enunciated). The intent of these rules is not made clear in either the CEC Handbook or the Appendix B notes to the rules. As the CEC is a Safety standard for the installation and maintenance of electrical equipment it can be assumed that the rational behind the above rules provides for both a safety requirement, warning personnel of pressures present within the device, and an operational requirement, identifying when a device has failed. Annunciation methods as described in the Instrumentation, Systems, and Automation Society ANSI/ISA-12.27.01-2003 document for devices incorporating a factory installed secondary seal include but are not limited to: Audible whistle (suitable breathers and drains, CAUTION: This method may not be suitable for toxic fluids, e.g. sour gas, acid gas ) Visible rupture or leakage (pressure relief valves, drains, some devices are engineered to rupture under certain pressures, CAUTION: This method may not be suitable for toxic fluids, e.g. sour gas, acid gas ) Electronic detections (gas detection relays, pressure switches all monitoring the space between primary and secondary seals remote indication could be possible) Rapid, predictable and detectable failure of the equipment to operate as intended (erroneous readings from measuring devices, complete catastrophic destruction of the device, failure of remote monitoring) Devices incorporating field installed secondary seals with one of the above annunciation features would also be an acceptable installation. The secondary seal would serve as the safety requirement, preventing flammable process fluids from passing under pressure through the electrical system, and the annunciation feature providing the operational requirement. Additional requirements, to ensure worker safety, are needed in situations where the annunciation feature of the instrument goes unnoticed. Situations where the primary seal failure was not substantial enough to provide an audible whistle or visible leakage or the remote

Page 10 of 11 detection went unnoticed by maintenance personnel. A cautionary label is considered as an effective method to alerting workers of potential hazards. Rules 18-108 Sealing, Class I, Zone 1 & 18-158 Sealing, Class I, Zone 2 Sealing of Control Cables with Bundled Sub-Assemblies CSA Standards C22.2 No.174 (Cables and Cable Glands for Use in Hazardous Locations) and C22.2 No.230 (Tray Cables) have provisions to test and mark cables with bundled subassemblies for extending through a sealing fitting or gland without removing the shield. Cables that meet the requirements of these standards will bear the mark "HL" (for cables approved for hazardous locations) or "TC" (for Tray Cable) followed by the group designation A, B, C, or D (eg. "HL D" or "TC D"). Only those cables tested and marked in accordance with the appropriate CSA Standards will be acceptable when extended through a seal without removing the shield and separating the individual conductors of the pairs, triads, etc. Sealing Underground Conduits and Cables Areas in earth below grade are normally considered non-hazardous, although the areas above grade have been classified as hazardous locations. In some cases however, spilled flammable liquids or heavier than air gases seeping through the earth and entering underground can enter conduits and cables. Examples of such locations may be service stations, bulk storage plants, refineries, tank farms and batteries. To prevent the transfer of ignitable vapours into non-hazardous areas, conduits and cables located in such areas should be sealed [per Rule 18-108(6)] at the point of emergence in the nonhazardous area. Cables may be sealed at the first point of termination in the non-hazardous area. The holes through which such conduits and cables enter the building should be made vapourtight to prevent ignitable vapours from entering the building around the outside of the conduits or cables. Rule 18-152 Process Instrumentation, Communication, and remote-control Equipment, Class I, Zone 2. Resistance Temperature Devices (RTDs) RTDs used to measure temperature do not operate above ambient temperature and are therefore considered part of the exception that exempts them from the requirements of Rule 18-150 Installation of Transducers and Similar Devices See Information item to Rule 18-050 above.

Page 11 of 11 Rule 18-156 Wiring Methods, Class I, Zone 2 Use of Non-metallic Liquid-tight Flexible Conduit in Class I Zone 2 Hazardous Locations Where corrosion problems exist in Class I Zone 2 hazardous locations, the use of Non-metallic liquid-tight flexible conduit is considered acceptable.