IN STAL LA TION IN STRUC TION

Similar documents
MODELS B1PA024, 030 AND 036

Supersedes: N2W (398) N2Z (1298) MODELS BCCB 090 & 120, MODELS BECB090 & 120 (9 EER) 208/230/460 VOLT MODELS ONLY

MODELS B3CH 048 AND 060 (WORLD 50 HZ)

MODELS B3CH 090 & 120A25, A46 MODELS B4CH090 & 120A58 (9 EER) 208/230/575 VOLT MODELS ONLY 208/230/460 VOLT MODELS ONLY

SUNLINE 2000 ELECTRIC / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N7Y (993) 530.

IN STAL LA TION IN STRUC TION

INSTALLATION INSTRUCTION

Supersedes: N2Y (498) N2Y (799) MODELS B1HH018 THRU THRU 5 TON (12 SEER)

INSTALLATION INSTRUCTIONS

Supersedes: N1Y (1099) N1Y (0500) MODELS B1HA018 THRU THRU 5 TON (10 SEER)

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED. MODELS: D1EB036 thru Thru 5 Ton (10 SEER)

Supersedes: A-0202 MODELS B1HA018 THRU THRU 5 TON (10 SEER)

R-410A AFFINITY SERIES DEX DEY Ton

INSTALLATION MANUAL SUNLINE 2000 SINGLE PACKAGE HEAT PUMP BCH 036, 048 & 060

INSTALLATION INSTRUCTIONS

MODELS D1EH018 THRU 060, 1-1/2 THRU 5 TON (12 SEER) AND MODELS D1EM036 THRU 060, 3 THRU 5 TON (13 SEER)

INSTALLATION IN STRUC TION

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL SUNLINE 2000 SINGLE PACKAGE HEAT PUMP BP

INSTALLATION INSTRUCTIONS

R-410A AFFINITY SERIES

INSTALLATION INSTRUCTIONS

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL

Installation Instructions

MODELS E1FB180 & E1FB240

SUNLINE PLUS GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: A A-0204

INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

SUNLINE 2000 GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N6Y (593) 530.

ELECTRIC / ELECTRIC & GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTRUCTION. Supersedes: N11W (1095) N11W(399)

SUNLINE 2000 SINGLE PACKAGE AIR-COOLED AIR CONDITIONERS DESCRIPTION FEATURES

INSTALLATION INSTRUCTION

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL SINGLE PACKAGE HEAT PUMP. MODELS: BA-15 and BA-20. ASHRAE 90.1 Compliant. Model BA-15. Model BA-20

Your safety and the safety of others are very important.

INSTALLATION INSTRUCTION Supersedes: N11Y (195) N11Y (399)

INSTALLATION INSTRUCTION

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

INSTALLATION INSTRUCTIONS

SUNLINE 2000 GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N2YI (1096)/ A-0204

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

USER'S MANUAL/INSTALLATION INSTRUCTIONS

Condensing Unit Installation and Operating Instructions

Q6SE Series 14 SEER. Single Package Heat Pump - Single Phase - R410A

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

MODELS W1LC220, 260 AND 320 STYLE B

INSTALLATION MANUAL WARNING WARNING MODULAR NON-VARIABLE SPEED AIR HANDLERS MODELS: MA LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES

L SERIES UNITS 504,520M. 10/2001 Supersedes 504,413M

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

MODELS K2EU060A, K4EU090A, & K3EU120A

SUNLINE SERIES SINGLE PACKAGE AIR CONDITIONERS. INSTALLATION INSTRUCTION Supersedes: Nothing N3Y (394) MODELS D*SC360 & 480 INSPECTION

INSTALLATION INSTRUCTIONS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

R-410A ZS SERIES. 3-6 Ton 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

USER'S MANUAL/INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS

INSTALLATION MANUAL (AIR COOLED) SPLIT-SYSTEM AIR CONDITIONER MODEL: LA120 NOTES, CAUTIONS AND WARNINGS SAVE THIS MANUAL B-0203

INSTALLATION INSTRUCTION

Model 655A Sizes

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL

Installation Instructions

INSTALLATION INSTRUCTION

Weathermaster Series 48HJ004, 005, 006, 007, 008, 009, 012 & 014 COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

INSTALLATION INSTRUCTIONS

48PGD/E/F/L/M/N PG20-28

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM HEAT PUMPS 60 HZ MODELS: EF-10 & FF-10

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Installer's Guide. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 18-BB35-D1-14 4WCZ6-IG-14

STELLAR 2000 SINGLE PACKAGE AIR CONDITIONERS GAS/ELECTRIC, AIR-COOLED INSTALLATION INSTRUCTION

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

INSTALLATION INSTRUCTIONS

VTC / VTH PRODUCT SPECIFICATIONS. ¾ Ton through 2 Tons VERTICAL TERMINAL AIR CONDITIONER AND HEAT PUMP

INSTALLATION INSTRUCTIONS HIGH EFFICIENCY PACKAGED AIR CONDITIONER

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS W12A2-A W12A1-K

Installer's Guide. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 18-EB25D1-15 TCC-IG-15

*P * INSTALLATION AND MAINTENANCE INSTRUCTIONS TGRG SERIES UNITS. RESIDENTIAL PACKAGED UNITS Gas/Electric /2016.

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

Transcription:

IN STAL LA TION IN STRUC TION SINGLE PACKAGE HEAT PUMPS Su per sedes: 511.06- N5W (1298) (900) MODELS B*CB036 AND 048 (STYLE B) AND MOD ELS B*CB060 (STYLE A ) (10 SEER w/belt-drive Option) (* = C or E) 035-16600 GEN ERAL 530.18-N7.2V -Fuse Block Accessory Model BCB units are single package heat pumps designed for outdoor installation on a rooftop or a slab. Supplemental electric heaters are available as field-installed accessories. The units are completely assembled on rigid, permanently attached base rails. All piping, refrigerant charge, and electrical wiring is factory installed and tested. The units require only electric power and duct connections at the point of installation. The supplemental electric heaters have nickel-chrome elements and utilize single point power connection. IN SPEC TION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. REF ER ENCE Additional information on the design, installation, operation and service of this equipment is available in the following reference forms: Re newal Parts: Refer to Parts Manual for complete listing of replacement parts on this equipment. All forms referenced in this instruction may be ordered from: AP PROV ALS Standard Register Norman, Oklahoma Toll Free Tel: : (877) 318-9675 Toll Free Fax: (877) 379-7920 Design certified by U.L. and C.G.A. as follows: 1. For use as a heat pump only unit or a heat pump unit with supplemental electric heat. 530.18-N1.2V -Economizer Accessory 530.18-N1.13V -Man. Outdoor Air Damper Accy 0-35% 530.18-N1.14V -Man. Outdoor Air Damper Accy 0-100% 530.18-N1.12V -Motorized Outdoor Air Damper Accy. 530.18-N7.1V -Electric Heater Accessory Installer should pay par ticu lar at ten tion to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation eas ier. Cau tions are given to pre vent equip ment dam age. Warn ings are given to alert in staller that per sonal in jury and/or equip ment damage may result if installation procedure is not handled properly.

2. For outdoor installation only. 3. For in stal la tion on combustible material. LIMI TA TIONS These units must be installed in accordance with the current edition of the following national and local safety codes: In U.S.A.: 1. National Elec tri cal Code ANSI/NFPA No. 70. 2. Lo cal electric utility requirements. In Canada: 1. Canadian Electrical Code C22.1 2. Canadian Installation Codes CAN/CGA-B149.1 and.2. Refer to Table 1 for Unit Application Data. If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and / or the customer's expense. Size of unit for proposed installation should be based on heat loss / heat gain calculation made according to the methods of Air Conditioning Contractors of America (ACCA). LO CA TION Use the following guidelines to select a suitable location for these units. 1. Unit is designed for outdoor installation only. 2. Out door coil must have an un lim ited supply of air. 3. For ground level in stal la tion, a level pad or slab should be used. The thick ness and size of the pad or slab used should meet lo cal codes and unit weight. Do not tie the slab to the build ing foundation. 4. Roof structures must be able to support the weight of the unit and its options and / or accessories. Unit must be installed on a solid level roof curb or appropriate angle iron frame. CAU TION: If a unit is to be installed on a roof curb or special frame other than a CES roof curb, gasketing must be applied to all surfaces that come in contact with the unit underside. 5. Maintain level tolerance to 1/2" maxi mum across the en tire length or width of the unit. 6. Ele vate the unit sufficiently to pre vent any blockage of the air en trances by snow in ar eas where there will be snow ac - cumulation. Check the local weather bureau for the ex - pected snow ac cu mu la tion in your area. OUTDOOR COIL CONDENSATE DRAINAGE PRECAUTION Condensate will drain from the outdoor coil during the heating and defrost cycles. Normally this condensate may be allowed to drain directly onto the ground/roof. A gravel bed is recommended to prevent mud splashing. WARNING:The unit should not be installed in an area where mud or ice could cause per sonal injury. Re mem ber that con den sate will drip from the out door coil dur - ing heat and de frost cy cles and that this conden - sate will freeze when the tem pera ture of the outdoor air is be low 32 F. RIG GING AND HAN DLING Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails. Spreaders, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit. BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY. Units may also be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose. LENGTH OF FORKS MUST BE A MINIMUM OF 42". Remove the nesting brackets from the four corners on top of the unit. All screws that are removed when taking these brackets off must be replaced on the unit. Refer to Table 5 for unit weights and to Figure 1 for approximate center of gravity. CLEAR ANCES All units require certain clearances for proper operation and service. Refer to Figure 4 for the clearances required for combustible construction, servicing, and proper unit operation. WARNING:Do not permit overhanging struc tures or shrubs to ob struct outdoor air discharge outlet. DUCT WORK Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA). A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be made with flexible joints to minimize the transmission of noise. The supply and return air duct systems should be designed for the CFM and static requirements of the job. They should NOT be sized to match the dimensions of the duct connections on the unit. CAU TION: When fas ten ing ductwork to the side duct flanges on the unit, insert the screws through the duct flanges only. DO NOT insert the screws through the casing. Out door ductwork must be insulated and wa ter - proofed. Refer to Figure 4 for information concerning side and bottom supply and return air duct openings. FIL TERS 1" filters are supplied with each unit. 2" replacement filters may be used with no modification to the filter racks. Filters must always be installed ahead of the evaporator coil and must be kept clean or replaced with same size and type. Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in Table 5. CON DEN SATE DRAIN Plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install a condensate drain line from the 3/4" PVC female connection on the unit to spill into an open drain. 2 Unitary Products Group

NOTE: The con den sate drain line MUST be trapped to provide proper drain age. See Figure 2. SERV ICE AC CESS Access to all serviceable components is provided by the following removable panels: Compressor compartment Heater compartment Blower compartment Main control box Filter compartment Motor Access (on units w/belt-drive option) Refer to Figure 4 for location of these access panels. COM PRES SORS On some units the compressor is mounted on springs which have been tightened down for shipment only. After this unit is installed, back out the compressor bolts until the sleeve clears the top grommet. CAU TION: Do Not loosen com pres sor mounting bolts. THER MO STAT The room thermostat should be located on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with thermostat for general installation procedure. Color coded insulated wires (#18 AWG) should be used to connect thermostat to unit. See Figure 3 for wiring details. NOTE: On units with econo mizer, re move jumper J1" from terminals 8 and 10 on plug connector J3/P7 on the re - lay board in the unit control box. Ref er to the unit wiring la bels lo cated on the inside of the con trol box access panel. An Emergency Heat position is provided with the thermostat. In the Emergency Heat position, the thermostat will allow electric resistance heat only. The compressor will be locked out. A pilot light on the thermostat will indicate that the switch is on EM HT. POWER AND CON TROL WIR ING Field wiring to the unit must conform to provisions of the National Electrical Code (NEC) ANSI/NFPA No. 70 (in U.S.A.), current Canadian Electrical Code (CEC) C22.1 (in Canada) and/or local ordinances. The unit must be electrically grounded in accordance with the NEC and CEC (as specified above) and/or local codes. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1. The wiring harness furnished with this unit is an integral part of a UL and C.G.A. design certified unit. Field alteration to comply with electrical codes should not be required. A disconnect switch should be field provided for the unit. The switch must be separate from all other circuits. Refer to Figure 4 for installation location. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram. Electrical lines must be sized properly to carry the load. USE COPPER CONDUCTORS ONLY. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly protected. CAU TION: When con nect ing electrical power and control wir - ing to the unit, wa ter proof type con nec tors MUST BE USED so that water or moisture cannot be drawn into the unit during nor mal operation. The above wa ter proof ing con di tions will also apply when in stall ing a field-supplied dis con nect switch. Refer to Figure 3 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information. Refer to Tables 3 and 4 for electrical data. ELEC TRIC HEATERS Supplemental electric heaters may be ordered as a fieldinstalled accessory. Refer to Form 530.18-N7.1V for installation instruction. These UL and C.G.A. approved heaters are located within the central compartment of the unit (see Figure 4 for access panel) with the heating elements extending into the supply air chamber. Fuses are supplied, where required, by the factory. Some KW sizes require fuses and others do not. Refer to the electric heater accessory installation instruction for the heater electrical data. The minimum air flow limitations across these heaters are listed in Table 2. BLOWER SPEED SE LEC TION Three blower motor speeds are available on the direct-drive units. The speed selection for the direct-drive units is determined by the CFM and ESP requirements of the applications. All units with belt-drive option have an adjustable motor pulley to achieve the above conditions. All direct-drive units are shipped with the black wire (labeled #8) connected to the high speed tap on the blower motor. If a lower blower motor speed is desired, this wire should be moved to the medium or low speed tap on the motor. DIS CON NECT SWITCH BRACKET FOR UNITS WITH OP TIONAL BELT- DRIVE BRACKET A special bracket for mounting a field-supplied disconnect switch is provided in each unit ordered with an optional beltdrive blower. The bracket is shipped inside the blower compartment taped to the top of the blower housing. Install the bracket on the left hand side of the unit as shown in Figure 4. Several existing screws at the top of the unit and one approximately midway down form the top will be used for mounting the bracket. Screws should be loosened only - NOT REMOVED. Mounting holes in the bracket have elongated keyways allowing easy installation. Re-tighten screws after the bracket is in place to ensure panel will remain leak tight. COOL ING SYS TEM The unit has an air-cooled condenser and is factory-charged with Refrigerant-22. The compressor is hermetically sealed, internally sprung, mounted on spring isolators and inherently (internally) protected. If there is an abnormal temperature rise in the compressor, the protector will open to shut down the compressor. PRE LIMI NARY OP ERA TION COOL ING After the installation has been completed, the crankcase heater of the compressor must be energized for at least 4 hours Unitary Products Group 3

before starting the unit. After this initial warm-up, the compressor should be given three false starts (energized just long enough to make a few revolutions) with a 5 minute delay between each start before being put into full time service. NOTE: Prior to each cooling sea son, the crank case heater must be en er gized at least 10 hours before the sys tem is put into op era tion. COOL ING SE QUENCE OF OP ERA TION When the thermostat calls for cooling, the compressor and the outdoor fan motor will be energized through terminal Y1" and the supply air blower motor will be energized through terminal G" (if the fan switch on the subbase is set in the AUTO position). The supply air blower motor will run continuously if the fan switch is set in the ON position. The reversing valve is energized thru the O circuit when the subbase is in the cooling mode. HEAT ING SE QUENCE OF OP ERA TION The following sequence of operation is based on using a standard CES heat pump thermostat with two heating stages. FIRST STAGE HEAT When the thermostat calls for heating, the compressor and the outdoor fan motor will be energized through terminal Y1" and the supply air blower motor will be energized through terminal G" (if the fan switch on the subbase is set in the AUTO position). The supply air blower motor will run continuously if the fan switch is set in the ON position. SECOND STAGE HEAT If compressor operation can not satisfy the heating requirements, second stage heat will energize supplemental electric heat (if supplied) thru the W1" circuit. DE FROST SE QUENCE OF OP ERA TION The BCB has a unique ambient modified time-temperature defrost control that automatically adjusts to changes in the outdoor temperature. The defrost control will shorten the defrost initiation time periods above 35 F and will extend the defrost initiation time periods below 35 F. The control is factory set to defrost at 110 minutes (T3), but it can be field adjusted to defrost at 80 minutes (T2) or 50 minutes (T1) in areas with high humidity. The curve in Figure 5 shows how defrost initiation times are automatically compensated for changes in outdoor temperature. EXAMPLE: If the time is factory set on pin T-3 (110 minutes at 35 F outdoor) and the outdoor temperature climbs to 45 F, the time initiation cycle will decrease to every 100 minutes. If the outdoor temperature drops to 10 F where ice is less likely to form, the 110 minute interval will extend to every 150 minutes. Two requirements must be met before a defrost cycle can be initiated. 1. The defrost time cycle must be complete. 2. The liquid line temperature must be less than 28 F. Defrost will terminate when the liquid line sensor reaches 55 F or after 10 minutes. The defrost time cycle will restart 10 minutes after the start of the defrost cycle even though the liquid sensor terminated defrost after 3 minutes. During troubleshooting, the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module. The pegs are 1/2" long, 3/16" apart and are mounted on a white base. See Figure 6. LOCK OUT CON TROL Any one of four conditions will put the system into a lock-out condition during the heating or cooling mode: 1. The discharge line temperature reaches 255 F (215 F reset) or, 2. The discharge pressure reaches 398 PSIG (310 PSIG reset) or, 3. The suction line freezestat equals 26 F (38 F reset) or, 4. The low- pressure cut-out equals 7 PSIG (22 PSIG re set). A lock-out will energize the emergency heat light on the thermostat and the red LED light on the unit relay board. Turning the thermostat switch to Off then back to On, will reset the system. NOTICE TO OWNER: If a lockout occurs, check for the following problems before calling a serviceman: 1. Dirty filters. 2. Snow accumulation. 3. Leaf or debris block age. After eliminating the problem, attempt to restart the system as follows: turn the system switch on the thermostat to its OFF position for 10 seconds. turn it back to its original position. If the unit doesn't start, call a serviceman. NOTE: Models with an anti- recycle accessory will have a 5- minute delay bef ore starting. CHECK ING SUP PLY AIR CFM The speed of the supply air blower will depend on the required CFM, the unit accessories and the static resistances of both the supply and the return air duct systems. With this information, the speed for the supply air blower can be determined from the blower performance and static resistance data on Tables 7, 8 and 9. Knowing the required blower RPM and the blower motor HP, the speed setting for the supply air motor can be determined. The setting (turns open) for the optional belt-drive supply air pulley can be determined from Table 11. OPTIONAL BELT-DRIVE BLOWER All units with belt-drive blowers have single speed motors. The variable pitch pulley on the blower motor can be adjusted to obtain the desired supply air CFM. Refer to Table 6 for blower 4 Unitary Products Group

motor drive data. The tension on the belts should be adjusted as shown in Figure 7. Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other than the equipment installer. To check the supply air CFM after the initial balancing has been completed: 1. Remove the (two) 5 16" dot plugs from the holes located on the fil ter access panel side of the unit. 2. In sert at least 8" of 1/4 inch tubing into each of these holes for sufficient pene tra tion into the air flow on both sides of the in door coil. NOTE: The tubes must be inserted and held in a position per - pen dicu lar to the air flow so that ve loc ity pres sure will not af fect the static pres sure readings. 3. Using an in clined ma nome ter, determine the pres sure drop across a dry indoor coil. Since the mois ture on an indoor coil may vary greatly, measuring the pres sure drop across a wet coil under field con di tions would be inaccurate. To en - sure a dry coil, the com pres sors should be de-energized while the test is being run. 4. Knowing the pres sure drop across a dry coil, the actual CFM through the unit can be determined from the curve in Figure 8. WARNING:Failure to properly adjust the total system air quan - tity can result in poor system performance. After readings have been obtained, remove the tubes and seal the drilled holes in the side panels. 5/16" dot plugs (P/N 029-13880) are available through normal parts ordering procedures. NOTE: DE- ENERGIZE THE COM PRES SORS BEF ORE TAKING ANY TEST MEAS URE MENTS TO ENSURE A DRY INDOOR COIL. Unitary Products Group 5