SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS

Similar documents
FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

SCROLL COMPRESSORS TYPE AIR COOLED PACKAGE CHILLERS

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Advance Release September 2009

R22 AIR COOLED HIGH STATIC DUCTED SPLIT SYSTEM. Single & Double Skin Evaporator Units. Cooling Capacity : 80 to 750 MBH

Split System Heat Pumps

TABLE OF CONTENTS INTRODUCTION NOMENCLATURE AC P S J 035 C CO AR Q - 2 -

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

Your Climate. We're There. TM: MDB B 2140B. Ducted Split Systems. Models: MDB 075B - MDB750B MDB 075B/B - MDB500BR. Air Conditioning REGISTERED

C13-Series Engineering Guide

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Concealed Ducted Split Series R-407C MBH

VertiCool Aurora Engineering Guide

Commercial High-Efficiency Condensing Units

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

DUCTED SPLIT AIR CONDITIONERS GCUN-A/GDS-A SERIES

Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz Technical Manual

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

DUCTED SPLIT AIR CONDITIONERS 50Hz GCUN/GDS SERIES R 407C

PACKAGE AIR CONDITIONER

VERTICOOL TECHNICAL DATA MANUAL. Vertical Air/Water Cooled 3-25 Tons

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

PAR5. Product Specifications

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

Commercial High-Efficiency Condensing Units

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

High Heat COP. High/Low Stage

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

48GS HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS

technical guide Water-Cooled Self-Contained Units

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

50TM TFF COMBINATION HEATING/COOLING UNITS

Technical Data OPA 101, 150, 180. Ducted Three Phase Packaged Air Conditioner kw 18.5 kw. Extra Long Life Epoxy Coated Outdoor Coil

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CATALOGUES SUMMARY - WCHBZ Pages WCHZ Pages 19-42

YAH SERIES FAN COIL UNITS

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MACH N-407 Heat Pump Air-Cooled Chiller

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

Water-Cooled Self-Contained Units

ROOFTOP PACKAGED AIR CONDITIONERS

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

SKYPAK II, 3 Ton Series, gives you a

PAJ3. Product Specifications

MAC N-407 Air-Cooled Chiller

WALL-MOUNT HEAT PUMPS - (60HZ)

JCseries EVAPORATIVE CONDENSER. engineering data

50TM COMBINATION HEATING/COOLING UNITS

SKYPAK II, 3 Ton Series, gives you a

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

48GS(N) STANDARD EFFICIENCY 48GX(N) HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING ELECTRIC COOLING UNITS

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

SELF CONTAINED HORIZONTAL AIR CONDITIONERS WATER COOLED CONDENSER (COAXIAL REFRIGERANT-WATER HEAT EXCHANGER)

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

MAC-120HE-03 Air-Cooled Chiller

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Condensing Units CUS 15-60

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

FF1DNA, FF1DNE FAN COIL UNITS. Sizes 018, 024, 030. Form No. PDS FF1D.18.3 FEATURES FF1D

SUBMITTAL DATA - OUTDOOR UNIT VEP075N432G VRF HEAT PUMP

Models: ACC 75D/DR ACC 100D/DR. ACC - D (Draft) Ceiling Concealed Split Systems

PRODUCT SPECIFICATIONS 2YCC3048A1120A /1/ /

VariCool VAV Engineering Guide

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

ELECTRICAL QUANTITY WEIGHT (LB)

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Weathermaster Series 48HJ004, 005, 006, 007, 008, 009, 012 & 014 COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

48TF GAS HEATING/ ELECTRIC COOLING UNITS

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

2YCC3060A1120A /1/ / YCC3060A1096A /1/ /

50TJM Nominal Cooling Capacity Tons HFC R - 410A Refrigerant

HEAT EXCHANGER Aluminized serpentine clamshell heat exchanger provides corrosion resistance for longer life and efficient heat transfer.

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

CFFWA4P-16-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 48,000 BTUH

CFFWA4P-12-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 36,000 BTUH

4YCC3048A3096A /3/ /

Product Catalog. Packaged Rooftop Air Conditioners Foundation Electric/Electric 3 to 5 Tons, 50Hz RT-PRC079B-EN. June 2017

CENTRAL SPLIT UNIT UNIC

CFFWA4P-08-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 24,000 BTUH

48TM GAS HEATING/ELECTRIC COOLING UNITS

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

Transcription:

SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS Cooling Capacity from 115,000 to 670,000 Btu/hr Btu/hr Smartwise Innovations... Towards Green, Quality & Reliability Solutions SERIES

INTRODUCTION GENERAL DESCRIPTION The Series of self-contained Air-Cooled Vertical Package air-conditioners are designed to provide quick, efficient and reliable air-conditioning to buildings with ease of installations, in any freely ventilated outdoor and indoor locations. The unit can either be located in a freely ventilated indoor plantroom or mounted on side walls or mounted around the perimeter, ground level of any buildings which requires quick supply of air-conditioning to the conditioned space. The unit is completely factory wired and packaged with starters and safety controls, pre-charged with full refrigerant charged; and ready for installations. There is no need to run refrigerant pipings and wirings between separate Evaporator-Blower section and air-cooled condensing section. As a self-contained air-cooled packaged air conditioner, there is no need to install cooling tower, condenser water pump, condenser water pipings and fittings etc., to contend with. By just bringing electrical power to the unit, connecting the supply air duct and return air duct from the unit to the conditioned space; it is ready to provide efficient air-conditioning to any conditioned space. Nomenclature 170 Series Self-Contained Vertical Air Cooled Package Air Conditioners Model Code Nominal Capacity, MBH 1

AIR-COOLED CONDENSING SECTION The air-cooled condensing section is designed and manufactured, with quality materials and components for efficient performance and high reliability, even in high ambient temperature conditions. The condensing section consists of a heavy gauge, galvanised sheet metal casing which is coated with oven-baked polyester paint, one or multiple hermetic scroll compressors, one or multiple axial condenser fans with direct drive 3 phase induction motor, a large surface area condenser coil, high-low pressure cut-out switch, suction and liquid access valves. With large surface area condenser coil and low noise and highly efficient axial propeller fans, the scroll compressor(s) operates efficiently with overall low noise level FEATURES Casing Constructed of heavy gauge galvanised steel sheet to ensure unit casing rigidity and eliminate casing drumming and vibration Oven-baked epoxy polyester paint finished Excellent finish, weatherability and high corrosion resistance against rust Compressor Hermetic Scroll Compressor(s) type operating at 2950 rpm. Proven high efficiency, low noise and high reliability of compressor(s) design. No-contact scroll design and 100% suction gas cooled motor ensure long operating life. With internal line break or solid state motor protectors. Single and multiple compressors each with independent refrigerant circuits. High low pressure cut-outs are provided for each compressor. Suction and liquid access valves are provided for each compressor. Multiple compressors increase system efficiency by sequential stagging of multiple compressor to match building load. High Efficiency Condenser Coils Staggered 3/8 inner groove tubes with 25-30% increased surface area Mechanically expanded into die-formed corrugated aluminum fins to ensure positive bonding Integral subcooling circuit to maximise system efficiency and reduce flash gas formation in the liquid line Access ports provided on discharge, liquid and suction lines for pressure measurements and charging in of refrigerant Coated condenser coil fins to improve corrosion resistance. Coils can withstand salt-spray test up to minimum 500 hours Condenser Axial Propellers High static axial propellers are suitable for short ducted, horizontal, condenser air discharge. Fan motors of IP55, maximum 960 rpm, 3-phase induction type, with high starting torque and low noise fan operation. 2

EVAPORATOR-BLOWER SECTION GENERAL DESCRIPTION The weather-proof evaporator-blower section is designed and manufactured with quality material and components to match the corresponding outdoor condensing section, to provide efficient performance and reliable operation. The Evaporator-blower section consists of a double-wall casing cabinetry, either single blower or twin fans, an evaporator cooling coil, motor and drive package resiliently mounted and isolated from unit casing with vibration isolators, thermal expansion valve(s), flexible canvas connector and heavy duty ball bearings. The Blower fan(s) are supplied with top supply air discharge connections. FEATURES Casing All casing cabinetry are of Double-walled construction with 1 inch. thick polyurethane insulation sandwiched between heavy gauge steel sheets Casing panels are coated with oven-baked polyester paint Removable side panels for easy access to internal components and filters Blower All standard fans are of forward curved Centrifugal double-width, double inlet type, belt driven and suitable for ducted supply air operation. Non-overloading type, backward curved fans are available as option All fan motor and drive assembly are internally isolated from unit casing by either rubber grommets or spring vibration isolators. Coil All evaporator coils are constructed from pre-coated, hydrophilic aluminium fins; with low-surface tension, to prevent moisture carry over; to ensure dry and clean aluminium fins surface during off cycle to prevent mould formation and dirt accumulation; and to improve corrosion resistance. Condensate water is allowed to drain over the condenser coil to improve system efficiency. Filters All standard filters are of 1 inch. thick, washable type Optional bag filter section, angle-filter sections and mixing box section can be provided when specified at time of order Optional Accessories Wired IEC-CE Direct Online Starters Suction, Discharge & Liquid Stop Valves Hot gas bypass Low Ambient Kit (fan cycling) up to 7 C Reverse cycle heat pump Thermostat 3

PERFORMANCE TABLE MODEL 115 130 150 170 200 230 260 300 340 390 440 500 580 630 670 STD. CAP. MBH STD. Sens. MBH STD. kw Input 112.0 81.2 8.8 129.3 93.0 10.0 4000 145.2 104.5 11.2 166.2 120.4 12.8 5200 198.2 143.3 16.0 224.0 162.4 17.6 6800 258.6 186.7 20.0 290.4 209.0 22.4 9000 332.4 240.8 25.6 387.9 279.3 30.0 11600 435.0 313.5 33.6 498.3 360.8 38.4 15200 580.4 417.8 44.8 622.8 449.0 48.0 18500 665.2 480.9 51.2 AIR ON EVAP. AIR TEMPERATURE ON COIL F CFM 75 95 115 WB TOTAL SENS TOTAL SENS TOTAL SENS TEMP F kw* kw* kw* MBH MBH MBH MBH MBH MBH 72 128.2 68.6 8.4 119.8 64.1 9.1 112.6 60.3 8.5 3500 67 119.8 86.9 8.2 112.0 81.2 8.8 105.3 76.3 8.3 62 111.5 104.3 8.0 104.2 97.4 8.6 97.9 91.6 8.1 57 100.7 100.7 7.9 94.1 94.1 8.5 88.4 88.4 8.0 72 148.0 78.6 9.6 138.4 73.5 10.3 130.0 69.1 9.7 67 138.4 99.5 9.3 129.3 93.0 10.0 121.5 87.4 9.4 62 128.7 119.4 9.1 120.2 111.6 9.8 113.0 104.9 9.2 57 116.2 116.2 9.0 108.6 108.6 9.7 102.1 102.1 9.1 72 166.2 88.3 10.7 155.4 82.6 11.5 146.0 77.6 10.8 4500 67 155.4 111.8 10.4 145.2 104.5 11.2 136.5 98.2 10.5 62 144.5 134.2 10.2 135.0 125.4 11.0 126.9 117.9 10.3 57 130.5 130.5 10.1 122.0 122.0 10.9 114.6 114.6 10.2 72 190.3 101.8 12.3 177.8 95.1 13.2 167.2 89.4 12.4 67 177.8 128.8 11.9 166.2 120.4 12.8 156.2 113.2 12.0 62 165.4 154.6 11.7 154.6 144.5 12.5 145.3 135.8 11.8 57 149.4 149.4 11.5 139.6 139.6 12.4 131.2 131.2 11.7 72 226.9 121.1 15.3 212.1 113.2 16.5 199.3 106.4 15.5 6000 67 212.1 153.3 14.9 198.2 143.3 16.0 186.3 134.7 15.0 62 197.2 184.0 14.6 184.3 172.0 15.7 173.3 161.6 14.7 57 178.1 178.1 14.4 166.5 166.5 15.5 156.5 156.5 14.6 72 256.5 137.3 16.9 239.7 128.3 18.1 225.3 120.6 17.0 67 239.7 173.8 16.4 224.0 162.4 17.6 210.6 152.7 16.5 62 222.9 208.5 16.0 208.3 194.9 17.2 195.8 183.2 16.2 57 201.3 201.3 15.9 188.2 188.2 17.1 176.9 176.9 16.0 72 296.1 157.8 19.2 276.7 147.5 20.6 260.1 138.6 19.4 8000 67 276.7 199.8 18.6 258.6 186.7 20.0 243.1 175.5 18.8 62 257.3 239.7 18.2 240.5 224.0 19.6 226.1 210.6 18.4 57 232.4 232.4 18.0 217.2 217.2 19.4 204.2 204.2 18.2 72 332.5 176.7 21.5 310.7 165.1 23.1 292.1 155.2 21.7 67 310.7 223.6 20.8 290.4 209.0 22.4 273.0 196.5 21.1 62 289.0 268.4 20.4 270.1 250.8 22.0 253.9 235.8 20.6 57 261.0 261.0 20.2 243.9 243.9 21.7 229.3 229.3 20.4 72 380.6 203.5 24.5 355.7 190.2 26.4 334.3 178.8 24.8 10400 67 355.7 257.7 23.8 332.4 240.8 25.6 312.5 226.4 24.1 62 330.8 309.2 23.3 309.1 289.0 25.1 290.6 271.6 23.6 57 298.8 298.8 23.1 279.2 279.2 24.8 262.5 262.5 23.3 72 444.1 236.1 28.7 415.1 220.6 30.9 390.1 207.4 29.0 67 415.1 298.9 27.9 387.9 279.3 30.0 364.6 262.5 28.2 62 386.0 358.6 27.3 360.7 335.2 29.4 339.1 315.1 27.6 57 348.6 348.6 27.1 325.8 325.8 29.1 306.3 306.3 27.4 72 498.0 265.0 32.2 465.5 247.7 34.6 437.5 232.8 32.5 13500 67 465.5 335.4 31.2 435.0 313.5 33.6 408.9 294.7 31.6 62 432.9 402.5 30.6 404.6 376.2 32.9 380.3 353.6 31.0 57 391.0 391.0 30.3 365.4 365.4 32.6 343.5 343.5 30.6 72 570.5 305.0 36.8 533.2 285.0 39.6 501.2 267.9 37.2 67 533.2 386.1 35.7 498.3 360.8 38.4 468.4 339.2 36.1 62 495.9 463.3 35.0 463.4 433.0 37.6 435.6 407.0 35.4 57 447.9 447.9 34.6 418.6 418.6 37.2 393.5 393.5 35.0 72 664.5 353.2 42.9 621.0 330.1 46.1 583.8 310.3 43.4 17000 67 621.0 447.0 41.7 580.4 417.8 44.8 545.6 392.7 42.1 62 577.6 536.5 40.8 539.8 501.4 43.9 507.4 471.3 41.3 57 521.7 521.7 40.4 487.5 487.5 43.5 458.3 458.3 40.8 72 713.0 379.5 46.0 666.4 354.7 49.4 626.4 333.4 46.5 67 666.4 480.4 44.6 622.8 449.0 48.0 585.4 422.1 45.1 62 619.7 576.5 43.7 579.2 538.8 47.0 544.5 506.5 44.2 57 559.8 559.8 43.3 523.2 523.2 46.6 491.8 491.8 43.8 72 761.6 406.5 49.0 711.8 379.9 52.7 669.1 357.1 49.6 19400 67 711.8 514.6 47.6 665.2 480.9 51.2 625.3 452.0 48.1 62 661.9 617.5 46.7 618.6 577.1 50.2 581.5 542.5 47.2 57 597.9 597.9 46.2 558.8 558.8 49.7 525.2 525.2 46.7 Notes 1) Total MBH - Rating are gross capacities, for net capacities, deduct evaporator blower motor heat. 2) Sensible MBH - Capacities are based on at 80 F (26.6 C) air on evaporator. 3) *kw - Compressor kw input. 4

PERFORMANCE TABLE Correction Factors For Performance A) Variation of Air on coil Dry Bulb Tempreture F on Sensible Cooling Capacity Dry Bulb Temp F 75 F 80 F 85 F Air on coil wet bulb temperature F 57 F 62 F 67 F 72 F 0.84 0.81 0.78 0.74 1.00 1.00 1.00 1.00 1.16 1.18 1.21 1.23 B) Variation in Airflow Rates % of Nominal Airflow Rates Total Cooling Capacity Sensible Cooling Capacity Compressor kw Input 80% 0.97 0.90 0.99 90% 0.98 0.95 1.00 100% 1.00 1.00 1.00 110% 1.02 1.05 1.00 120% 1.03 1.09 1.01 Notes: If the calculated sensible capacity is higher than the total capacity, then the correct sensible capacity is equal to the total cooling capacity. NOMINAL AIRFLOW RATES VERSUS EXTERNAL AVAILABLE STATIC PRESSURE (allowance included for 1 Thick Filters) Model 0.5" WG 1.0" WG 1.5" WG rpm BHP rpm BHP rpm BHP 115 3500 890 1.49 1042 1.90 1175 2.33 130 4000 905 1.86 1051 2.32 1182 2.80 150 4500 749 1.93 873 2.40 978 2.89 170 5200 773 2.21 905 2.77 1022 3.34 200 6000 799 2.89 913 3.50 1027 4.15 230 6800 991 3.77 1112 4.48 1232 5.25 Model rpm BHP rpm BHP rpm BHP 260 8000 898 4.31 1014 5.25 1124 6.24 300 9000 908 5.16 1017 6.22 1121 7.26 340 10400 941 5.96 1062 7.17 1174 8.62 390 11600 947 7.10 1065 8.46 1174 9.80 440 13500 992 9.41 1095 10.92 1191 12.44 Model Nominal CFM Nominal CFM Nominal CFM External Available Static Pressures External Available Static Pressures 1.0" WG 1.5" WG 2.0" WG External Available Static Pressures 1.5" WG 2.0" WG 2.5" WG rpm BHP rpm BHP rpm BHP 500 15200 1008 11.81 1099 13.67 1193 15.84 580 17000 1025 14.16 1111 16.11 1192 18.14 630 18500 1044 16.43 1125 18.49 1203 20.61 670 19400 1057 17.97 1135 20.06 1211 22.26 Notes: For other airflow rates, to consult nearest SMARTech Sales office for fan selection details. 5

PHYSICAL DATA DESCRIPTION Unit Electrical Supply Nominal Cooling Capacity(MBH) Nominal Airflow Rates, CFMs MODEL 115 130 150 170 200 230 260 300 380/415-3 - 50Hz Total 112.0 129.3 145.2 166.2 198.2 224.0 258.6 290.4 Sensible 81.2 93.0 104.5 120.4 143.3 162.4 186.7 209.0 3500 4000 4500 5200 6000 6800 8000 9000 Quantity 1 1 1 1 2 2 2 2 Nominal Running Amperes 16.1 18.2 19.4 22.2 15.0 x 2 16.1 x 2 18.2 x 2 19.4 x 2 Compressors Maximum Trip Amperes 24.0 28.0 31.0 34.0 22.0 x 2 24.0 x 2 28.0 x 2 31.0 x 2 Lock Rotor Amperes 142.0 147.0 158.0 170.0 142.0 x 2 142.0 x 2 147.0 x 2 158.0 x 2 Nominal Input Power (kw) 8.8 10.0 11.2 12.8 8.0 x 2 8.8 x 2 10.0 x 2 11.2 x 2 Evaporator Blower Section Air-Cooled Condenser Section Blower Model KAT 12/12 KAT 12/12 KAT 15/11 KAT 15/15 KAT 12/9C2 KAT 12/9C2 KAT 15/11C2 KAT 15/11C2 Motor HP / Ext S.P. inch WG 3.0/1.8" WG 3.0/1.8" WG 3.0/2.0" WG 4.0/2.0" WG 5.0/2.3" WG 7.5/2.8" WG 7.5/2.8" WG 7.5/2.5" WG Evaporator Coil - Rows Deep 4 4 4 4 4 4 4 4 Evaporator Coil - Face Area ft² 7.0 8.3 9.2 10.4 12.5 13.8 15.4 17.8 Cond. Fan/Motor Qty 1 1 1 1 2 2 2 2 Fan Diameter (Inch) 30 30 33½ 33½ 30 30 33½ 33½ Fan Motor Input kw, ea 0.75 1.25 1.8 1.8 0.75 x 2 0.75 x 2 1.8 x 2 1.8 x 2 Motor RPM 960 960 960 960 960 960 960 960 Motor N.R.A each 2.3 2.9 3.8 3.8 2.3 2.3 3.8 x 2 3.8 x 2 Cond. Coil, Rows/fpi 3/14 3/14 3/14 3/14 3/14 3/14 3/14 3/14 Cond. Coil, Face Area ft² 14.4 16.6 18.8 21.7 26.4 28.8 31.1 34.2 Cond. Airflow, cfms 8500 9000 11800 12000 15500 15600 22000 22500 Filters 1" Thick Size (Inch) - Quantity 16 x 20-4 16 x 25-4 16 x 25-4 16 x 20-6 16 x 20-4 16 x 20-4 16 x 20-6 16 x 20-8 16 x 25-4 16 x 25-4 16 x 25-2 Length x Width x Height (inches) Approximate Operating Weight (lbs) 48 x 40 x 96 54x 40 x 96 60 x 44 x 96 68 x 44 x 96 83x 44 x 94 83x 44 x 94 98 x 48 x 97 98 x 48 x 97 1400 1600 1850 2050 2400 2600 2900 3200 DESCRIPTION Unit Electrical Supply Nominal Cooling Capacity(MBH) Nominal Airflow Rates, CFMs Compressors Evaporator Blower Section Air-Cooled Condenser Section MODEL Total 332.4 387.9 435.0 498.3 580.4 622.8 665.2 Sensible 240.8 279.3 313.5 360.8 417.8 449.0 480.9 10400 11600 13500 15200 17000 18500 19400 Quantity 2 3 3 3 4 4 4 Nominal Running Amperes 22.2 x 2 18.2 x 3 19.4 x 3 22.2 x 3 19.4 x 4 Maximum Trip Amperes 34.0 x 2 28.0 x 3 31.0 x 3 34.0 x 3 31.0 x 4 Lock Rotor Amperes 170.0 x 2 147.0 x 3 158.0 x 3 170.0 x 3 158.0 x 4 Nominal Input Power (kw) 12.8 x 2 10.0 x 3 11.2 x 3 12.8 x 3 11.2 x 4 19.4 x 2, 22.2 x 2 31.4 x 2, 34.0 x 2 158.0 x 2, 170.0 x 2 11.2 x 2, 12.8 x 2 NOTE: Nominal cooling capacities rated at air on evaporator coil of 80 F DB/ 67 F WB and ambient air on condenser coil of 95 F 22.2 x 4 34.0 x 4 31.0 x 2, 34.0 x 2 12.8 x 4 Blower Model KAT 15/15C2 KAT 15/15C2 FDA355T2 FDA400T2 FDA 400 T2 FDA 400 T2 FDA 400 T2 Motor HP / Ext S.P. inch WG 10.0/2.8" WG 15.0/2.8" WG 15.0/3.0" WG 15.0/3.0" WG 20.0/3.2" WG 25.0/3.3" WG 25.0/3.3" WG Evaporator Coil - Rows Deep 4 4 4 4 4 4 4 Evaporator Coil - Face Area ft² 21.0 23.3 26.3 28.6 33.3 35.6 37.5 Cond. Fan/Motor Qty 2 2 2 2 2 3 3 Fan Diameter (Inch) 33½ 31½ 31½ 35 35 31½ 31½ Fan Motor Input kw, ea 1.8 x 2 2.8 x 2 2.8 x 2 3.5 x 2 3.5 x 2 2.8 x 3 2.8 x 3 Motor RPM 960 960 960 960 960 960 960 Motor N.R.A each 3.8 x 2 5.8 x 2 6.0 x 2 7.2 x 2 7.2 x 2 5.8 x 3 5.8 x 3 Cond. Coil, Rows/fpi 3/14 3/14 4/14 4/14 4/14 4/14 4/14 Cond. Coil, Face Area ft² 41.2 45.5 47.9 52.7 70.0 72.8 77.9 Filters 1" Thick Size (Inch) - Quantity Length x Width x Height (inches) Approximate Operating Weight (lbs) 340 Cond. Airflow, cfms 27500 26000 30500 23600 34000 40000 41000 16 x 20-2 16 x 25-2 20 x 20-2 20 x 25-2 390 440 500 580 630 670 16 x 20-5 18 x 20-5 18 x 20-6 380/415-3-50Hz 18 x 18-7 20 x 20-6 20 x 20-6 20 x 20-5 20 x 20-5 20 x 20-6 20 x 18-7 25 x 20-6 25 x 20-6 118 x 48 x 97 102 x 60 x 97 102 x 60 x 97 112 x 60 x 97 102 x 60 x 97 102 x 60 x 97 112 x 60 x 97 3700 4300 4900 5700 4300 4900 5700 6

DIMENSIONAL DATA 115-200 Note: All dimensions are in inches. 7

DIMENSIONAL DATA 230-340 Note: All dimensions are in inches. 8

DIMENSIONAL DATA 390-670 Note: All dimensions are in inches. 9

DIMENSIONAL DATA - TYPICAL OUTDOOR INSTALLATION - TYPICAL INDOOR INSTALLATION Note: All dimensions are in inches. 10

Smartech Sales & Services Sdn. Bhd. (829707-K) No.15, Jalan PJS 1/27, (Jalan Petaling Utama 6), Petaling Utama, Batu 7, Off Jalan Klang Lama, 46000 Petaling Jaya, Selangor. T: 603-7783 7288 / 7782 2788 F: 603-7782 3788 W: www.smart-hvac.com.my Specifications in this catalogue are subject to change without notice in order for SMARTECH to bring the latest innovations to their customers. -1501