Installation and user manual for the BiWire / Conventional Repeater Panel

Similar documents
BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

Installation, Operating and Maintenance Manual

EFBW series - BiWire Ultra control panel

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

5000 INSTALLATION GUIDE

10yr O2NE & Safe-Ox. User Manual

Distributed Amplifier Unit (DAU) (EESDAU100) Emergency Microphone All Call (EMA) (EESEMA) User Operational & Maintenance Manual

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Operation and Maintenance Manual

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

X10 Mini, Midi & Maxi

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Control Panel Engineering and Commissioning Instructions

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

New Silent Alert Fire Safe System

Silent Alert Fire Safe System

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Door Release Power Supply

USER MANUAL & MAINTENANCE GUIDE OG OO

Excel-EN Conventional Fire Control Panel

Unity DAU Voice Alarm System

Product Data Sheet. Remote Terminals. Features:

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

ANALOX 3000 Carbon Monoxide Monitor

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014

FIRE ALARM CONTROL PANEL FVC01-08

CFDAU30 Voice Alarm System

CW9000 Wireless Fire System. Installation Manual

KFP-CF Series Operation Manual

Menvier Fire System MF9300

Smoke Vent Control Panel PCB4 V4 Installation Manual

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

General Routing Interface

DCS-100. intelligent damper control & monitoring system

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Premier Hazard STC Instructions

USER MANUAL. Pharmacy Refrigerator Range. Applicable models: PSR353/PGR353 PSR273/PGR273 PSR151/PGR151

Installation and Operating Instructions

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards.

Networked Access Control Panel. Installation Guide

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

Public Safety DAS Annunciator Panel

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Industries. As a premier global manufacturing company, we believe that great brands are

Intelligent Security & Fire Ltd

USER MANUAL. Laboratory Refrigerator Range. Applicable models: LSR151 LSR288

Intelligent Security & Fire Ltd

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

M2500 Engine Controller Installation Manual

Conventional Leaflets

SECURIT 703 USER MANUAL

OPERATION AND INSTALLATION MANUAL

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL

1X-F Series Installation Manual

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

FEC400 Series. Installation Manual

Application, Installation, Operation & Maintenance Manual

Remote NAC Power Supply D7038

LEAKSTOPPER 1 Single zone water leak detection system

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax:

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

The Remote alarm Panel, TYPE RAPv2

Model 17A00 Expansion Enclosure

PROFYRE C8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FIRE ALARM CONTROL PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

Racal-Guardall. Countess. User Instructions. Countess

FSTP2-2-wire 2 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS2 Issue 01 April 2012

PAC1500Xi PORTABLE APPLIANCE CHECKER

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

SECURIT 700L PLUS ENGINEERING MANUAL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

FSTP4-2-wire 4 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS4 Issue 01 April 2012

Temporary wireless battery operated fire system from Channel Safety Systems

Conventional Fire Control Panel

IFP-2.32 Manual 1) DESCRIPTION ICAS FIRE PANEL IFP 2.32

OPERATION / INSTALLATION

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

USER MANUAL FOR OPERATING SYSTEM

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Transcription:

Panel EFBWCV-REPEATER

Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O.... 7 Installation Instructions.... 8 Before you begin.... 8 Panel Installation... 9 Installation Testing.... 14 Operating Instructions.... 15 Multi-Function Buttons.... 15 Mute Buzzer.... 15 Lamp Test.... 15 Technical Specification.... 16 Panel Specification.... 16 PSE Specification.... 16 Manufacturers Contact Details.... 17 2

Introduction Purpose This manual is intended as a guide for the installation and commissioning of the panel. The content of this guide is intended to assist the user to install a fire alarm system and does not specify the detailed design of the product. The guide assumes a reasonable level of competency with this type of system. The installation of this system can only be carried out by a competent person with relevant current training and experience, with access to requisite tools, equipment and information (as stipulated by BS5839). The design has been carried out in accordance with a quality management system, which incorporates a set of rules for the design of all elements of the Indication Equipment (IE) and Power Supply Equipment (PSE). The components of the IE and PSE have been selected for the intended purpose, and are expected to operate within their specification when the environmental conditions outside the cabinet of the IE / PSE comply with class 3k5 of EN 60721-3-3:1995. The BiWire/Conventional Repeater Panel The BiWire/Conventional Repeater Panel mimics the visual and audible indications of the Fire panel it is connected to. This is a purely passive repeater panel so it is not possible to send instructions to the Fire panel to perform actions such as Sound Alarms, Silence Alarms, or Reset. Each repeater panel comes with an integral power supply and battery backup so there is no power requirements from the main Fire panel. Indication Equipment (IE) The panel enclosure is constructed from PC ABS components. The front cover is hinged at the bottom and is secured at the top of the panel by two retaining screws. On the in-side of the panel a sliding PCB tray makes it easy to remove the tray without touching the PCB. The back box houses the PSE, the stand-by batteries and has 29 x 20mm cable access points. Terminal blocks are positioned to enable ease of connection. Figure 1 shows the dimensions of the panel. Figure 1. BiWire/Coventional Repeater Panel Dimensions 3

Power Supply Equipment (PSE) The PSE has been specifically designed to operate the panel and may not be substituted for any other power source. The PSE is a Switch Mode Power Supply located within the cabinet as shown below. A dedicated 230V AC mains supply is required as the primary source; the supply is fused on the PCB by a 10 amp antisurge fuse. In the event of mains failure the PSE will automatically switched over to the standby battery power source until the main power source is restored. The PSE maintains the charge for the two 12V 5Ah sealed lead acid batteries in a fully charged state. On initial power up the batteries will charge over a 24 hour period. Dependent on the charge of the installed battery the system may initially show a charger or battery fault. The supply should be clearly labelled FIRE ALARM: DO NOT SWITCH OFF at all isolation points. PSE faults originating from the following are indicated by the panel using a dedicated repeater power fault indicator: The loss of either power source Failure of the charger circuit High internal resistance of the battery Figure 2 shows the location of the power supply. PSE Specification on page 16 provides a full technical specification for the power supply. Note that the charging circuit will be in its high impedance state (approximately 3V DC) if no batteries, faulty batteries, or only one battery is connected. The full 27V DC (nominal) charging voltage should be present if the correct batteries are connected. In order to test for correct operation of the batteries, remove the mains 230V AC fuse and allow the batteries to settle from their charging voltage for approximately 5 minutes. The battery voltage should then be measured using an electronic test meter and a voltage greater than 24V DC should be present. Figure 2. Power Supply Equipment BATTERY DISPOSAL INSTRUCTIONS WARNING RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE This product contains batteries and they must be disposed of in accordance with current waste disposal and pollution legislation and in particular The Environmental Protection Act 1990, Special Waste Regulation 1996. It is recommended that the following authorities are contacted before any attempt is made to dispose of batteries; Environment Agency Local office, Local Authority Environmental Health or Waste Handling department. The batteries and fire panel comply with WEEE disposal regulations. Do not dispose in general industrial or household waste. Return unwanted products to a designated collection point for waste electrical and electronic equipment recycling. 4

System Wiring As the repeater panel have integral power supplies the only wiring that is required is the mains input to the power supply unit and the data cable between the Fire Panel and each repeater panel as illustrated in Figure 3. CIE REPEATER REPEATER REPEATER RS485 RS485 RS485 RS485 Figure 3. System Wiring Diagram Status Indications Figure 4. Front Panel Status Indications 5

KEY ON (---------) OFF SLOW ( - - - - ) FAST ( - - - - - ) SILENT CONT Indicator lit Indicator unlit Indicator slow flashing, buzzer slow pulsing Indicator fast flashing, buzzer fast pulsing Sounders off, buzzer off Sounders on, buzzers continuous Any condition could be indicated Visual indications Audible Indications Condition Power ON General Fault General Disablement Repeater Fault/ System Fault Battery Fault/ Mains Fault Battery Failure/ Charger Fault Sounder Fault/ Sounder Disablement Self Test On /Test Repeater Power Fault FRE On FRE Fault/ FRE Disablement FPE Fault/ FPE Disablement General Fire Zone Fire (1-8) Detector Removed /Zone Fault/ Zone Disablement Panel Buzzer Comments Fire Panel Indications (These mirror the current Fire Panel state) Normal Condition Access Level 2 or 3 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Normal condition and at access level 1 FAST Access level 2 or 3 pass code accepted Fire Condition ON ON ON CONT Only the zone in fire will have its zone fire indicator lit System Fault ON ON SLOW Severe fault condition with the Fire Panel Repeater Fault ON SLOW SLOW Communication problem between Fire panel and repeater(s) Battery Fault ON SLOW SLOW No battery voltage or battery voltage too low Mains Fault ON ON SLOW Mains voltage has been lost Battery Failure ON SLOW SLOW Battery impedance fault Charger Fault ON ON SLOW Charger voltage fault Sounder Fault ON SLOW SLOW Short or open circuit condition on the sounder circuit FRE Fault ON SLOW SLOW Short or open circuit condition on the FRE output FPE Fault ON SLOW SLOW Short or open circuit condition on the FPE output Zone Fault ON SLOW SLOW Only the zone that has a short or open circuit fault will have its zone fault indicator slow flashing Sounder disabled ON ON All fire alarm devices are disabled FRE disabled ON ON FRE ouput disabled FPE disabled ON ON FPE output disabled Zone disabled ON ON Only the zone that is disabled will have its zone fault indicator lit Repeater Panel Indications (Local to the repeater) Normal Condition ON Normal condition and at access level 1 Battery Fault ON ON No battery voltage or battery voltage too low Mains Fault ON ON Mains voltage has been lost Battery Failure ON ON Battery impedance fault Charger Fault ON ON Charger voltage fault Communication Fault ON Communication lost with the Fire Panel 6

Repeater I/O The Fire Panel provides a monitored RS485 bus that allows for up to 3 passive repeater panels to be connected to it. The repeater panels have their own power supplies so no power connection is required from the Fire Panel. Each repeater panel must be assigned a unique address using the DIP switches provided on the repeaters. When the Fire Panel is first powered up or after a hard reset it will scan the RS485 bus for any repeaters connected. The panel will briefly flash the Zone Fault indicators to show the number of repeaters it has found. Below is a table of what these indications mean. 1 2 1 2 1 2 1 2 = 0 repeaters found = 1 repeater found = 2 repeaters found = 3 repeaters found It is important to note this during installation to ensure that the panel has found the correct number of repeaters. Once the repeaters have been found the Fire Panel will broadcast all status information to them so that they will mirror the indicator and buzzer states of the Fire Panel. The Fire Panel expects to receive a response from each repeater, if at any time a repeater stops responding for more than 60 seconds then the Fire Panel will start to flash the Repeater Fault indicator. Figure 5. Repeater Panel Connection 7

Installation Instructions This section of this guide explains in detail how the panel should be installed and configured to function properly. Please ensure you have fully understood the components of the system and how they operate before proceeding with this section. Take notice of the warnings and cautions as they are displayed for your own safety and to prevent damage to your equipment. Before you begin WARNING WHEN INSTALLING THE REPEATER PANELS CARE SHOULD BE TAKEN TO ENSURE THAT THE INSTALLATION LOCATION DOES NOT SUBJECT THE PANEL TO ENVIRONMENTAL FACTORS IN EXCESS OF THE LIMITS OUTLINED IN THE TECHNICAL SPECIFICATION CONTAINED WITHIN THIS GUIDE. NOTE WHEN INSTALLED THIS EQUIPMENT IS SUBJECT TO THE EMC DIRECTIVE 2004/108/EC. TO MAINTAIN EMC COMPLIANCE THE FIRE ALARM SYSTEM MUST BE INSTALLED AS INSTRUCTED. THE INSTALLER WILL BE RESPONSIBLE FOR ANY EMC PROBLEMS THAT MAY OCCUR EITHER TO THE FIRE ALARM SYSTEM OR TO ANY OTHER EQUIPMENT AFFECTED BY THE INSTALLATION IF THERE IS ANY DEVIATION FROM THIS GUIDE. NOTE DIP SWITCH SETTINGS ONLY TAKE EFFECT ONCE THE PANEL HAS BEEN POWER CYCLED OR THE HARD RESET BUTTON IS PRESSED. CAUTION ENSURE ANTI-STATIC PRECAUTIONS ARE TAKEN WHEN HANDLING ELECTRONIC COMPONENTS OF THE SYSTEM. DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE TERMINAL BLOCKS. NOTE INSTALLATION & MAINTENANCE MUST BE PERFORMED BY AN APPROPRIATELY QUALIFIED PERSON. THE EQUIPMENT CARRIES NO WARRANTY UNLESS THE SYSTEM HAS BEEN INSTALLED AND COMMISSIONED AND SUBSEQUENTLY MAINTAINED BY APPROPRIATELY QUALIFIED PERSONS OR ORGANISATIONS. DO NOT ATTEMPT TO INSTALL THIS EQUIPMENT UNTIL YOU HAVE FULLY READ AND UNDERSTOOD THE OPERATION AS DESCRIBED WITHIN THIS MANUAL, FAILURE TO DO SO MAY RESULT IN DAMAGE TO THE EQUIPMENT AND COULD INVALIDATE YOUR WARRANTY. 8

Panel Installation NOTE THE FOLLOWING INSTRUCTIONS MUST BE FOLLOWED WITH MAINS AND BATTERY SUPPLIES DISCONNECTED UNLESS OTHERWISE STATED. NOTE THE PANEL SHOULD BE INSTALLED IN A CLEAN, DRY, REASONABLY WELL VENTILATED PLACE, AND NOT IN DIRECT SUNLIGHT. TEMPERATURES IN EXCESS OF 40 C AND BELOW 5 C MAY CAUSE MALFUNCTIONS, IF IN DOUBT CONSULT EATON ELECTRICAL SYSTEMS. THE PANEL SHOULD BE LOCATED AWAY FROM ANY POTENTIAL HAZARD, IN A POSITION WHERE IT IS READILY ACCESSIBLE TO AUTHORISED STAFF, AND THE FIRE SERVICES, IDEALLY ON THE PERIMETER OF A BUILDING NEAR A PERMANENT ENTRANCE. Mounting the Panel To prepare the panel for mounting, you need to remove the front cover of the panel, and the PCB shelf and the PSE from the back box. To remove the front cover of the panel, unscrew the two retaining screws located at the top corners of the panel, see Figure 15. It is recommended to remove the PCB shelf and the PSE from the back box before drilling the holes. To remove the PCB shelf push the clips down 1, then push the shelf towards the top of the back box and then lift forwards 2, see Figure 17. To remove the PSE PCB from the back box unplug the cables from the main board as shown in Figure 17, then simply remove the screw and push the PCB up, to the right and forwards as shown in Figure 18. Figure 6. Remove Panel front cover Figure 7. Remove the PSE Shelf Figure 8. Disconnect the PSE Figure 9. Remove the PSE 9

Once the cable entry holes have been cut then fit the cable glands to the back box. If the panel is being flush mounted, then insert the panel into the recess feeding the cables through the rear cable entry points. If the panel is being wall mounted then cut out the required number of cable entry holes in the back using a 20mm hole saw with pilot drill bit as shown in Figure 19. Fit the glands to the back box and pull through the required cables. Figure 10. Cut cable entry holes Using the mounting holes in the back box, drill holes into the wall and insert wall plugs and secure the panel to the wall as shown in Figure 20. Ensure any dust is cleaned from the back box. Secure the PSE PCB back into the back box by following the reverse instructions in Figure 18. Fit the PCB shelf and cables by following the reverse instructions in Figure 16 and Figure 17 on page 9. If the panel is wall mounted, pull the cabling through the glands ready for wiring. Fit the door back onto the back box by following the reverse instructions in Figure 15. Figure 11. Secure the panel to the wall 10

Connecting the Mains Supply The mains supply should be exclusive to the fire alarm as detailed in BS5839. A plug and socket is not satisfactory. We recommend that a switched double pole fused spur unit is used for the sole use of the fire alarm system and should be clearly marked with: FIRE ALARM DO NOT SWITCH OFF Before connecting the fused spur to the PSE, slide the ferrite core (supplied with the panel) over the cable as shown in Figure 21. Connect the fused spur to the input marked MAINS on the PSE, observing correct wiring regulations. Connecting the Battery Supply A Battery cover is supplied to prevent accidental contact with the battery terminals and gives additional useful information. The battery cover can be moved out of the way as indicated in Figure 22. Connect the spade connectors of the two wire battery cable and the single wire battery cable as illustrated in Figure 21 Do not connect the plastic socket end of the battery cable to the PSE until all installation actions in this guide have been completed and the system is ready for testing. NOTES OBEY VOLT DROP LIMITATION WHEN SIZING CABLES. USE ONLY APPROVED CABLE TYPES. DO NOT TIGHTEN TERMINAL CONNECTOR SCREWS TOO TIGHT. KEEP POLARITY THROUGHOUT. NON COLOURED CONDUCTORS SHOULD BE PERMANENTLY MARKED. Figure 13. Battery cover removal Figure 12. Mains Supply connection to PSE 11

Battery Connections 1. Connect the BLACK battery wire to the BLACK (-) battery terminal of Battery B (Figure 23) 2. Connect the RED battery wire to the RED (+) battery terminal of Battery A (shown as grey) 3. Connect the link cable between the two remaining terminals CAUTION DO NOT USE A HIGH VOLTAGE TESTER WHEN WIRING IS CONNECTED TO ANY ELECTRONIC EQUIPMENT. NOTE IT IS IMPORTANT THAT ZONE CABLING IS CONNECTED TO THE CORRECT ZONE INPUT OTHERWISE ANY FIRE OR FAULT INDICATION ON THE PANEL WILL NOT MATCH THE ZONE MAP OF THE SITE, AND WILL NOT BE COMPLIANT WITH BS5839 Figure 14. Battery Connection Figure 15. Repeater Panel Wiring Diagram 12

Connecting a Repeater Panel If a single Repeater panel is being connected to the Fire Panel then simply connect one end of the twisted pair cable to the Repeater I/O terminals on the Fire Panel and the other end of the cable to the Repeater I/O terminals on the Repeater Panel (see Figure 15), observing correct polarity (+ to +., - to -). When daisy chaining repeater panels together simply connect another twisted pair cable between each Repeater I/O terminals. This will mean that some of the terminals will have 2 cables connected to it. Once all the repeaters are wired together each repeater panel needs to be assigned a unique address from 1 to 3 DIP switch 12 as shown below. Figure 16. Interlink wiring diagram 13

Installation Testing Initial Power-up Check Power up the panel by engaging the fuse spur to supply mains, then connect the white socket of the battery cable to the power supply (see Figure 24 on page 16). Check that all indicators turn on in turn momentarily and turn off again. Only the power on indicator should be lit afterwards. Any fault indications should be investigated and corrective actions taken before continuing with the installation tests. Status Indications on page 8 provides a comprehensive guide to the fault indications. Power off the panel before commencing any corrective action on the panel. Battery Fault Detection Check Disconnect the battery of the repeater panel. After about 20 seconds check the Repeater Power Fault indicator is on. Re-connect the battery of the repeater panel. After about 4 seconds check the Repeater Power Fault indicator is off. WARNING DO NOT FIX ANY FAULT CONDITIONS WITH THE SYSTEM STILL POWERED UP. THIS IS PARTICULARLY IMPORTANT WITH SHORT CIRCUIT FAULTS ON ZONES AS THE PTC FUSE NEEDS TIME TO RECOVER IF IT HAS TRIPPED. Repeater Check Place an individual zone into Zone Test Mode on the Fire Panel (see Fire Panel manual for further instructions on how to put it into Zone Test mode). Check the following on the repeater panel: Self-Test On indicator is slow flashing Buzzer is slow beeping Activate a call point that in the zone in test mode and then check the following on the repeater panel: Self-test On indicator is slow flashing General Fire indicator is on Correct zone fire indicator is on Buzzer is continuous Take the Zone out of Test Mode at the Fire Panel and reset the system. All indications on the repeater should mirror those on the Fire Panel. 14

Operating Instructions Multi-Function Buttons The numerical value in the centre of the button is used to enter access codes for level 2. Mute Buzzer This function is available at access level 1 and 2. To silence the panel s internal buzzer at access level 1 just press the Mute Buzzer button. To silence the panel s internal buzzer at access level 2 enter the code 3112 and then press the Mute Buzzer button. This will only silence the buzzer of the repeater and not the Fire Panel This function will immediately exit back to Access Level 1. Lamp Test This function is available at access level 2. Enter the access code 3112. Press Indicator Test button 3. Each indicator on the front of the panel will turn on in turn and then turn off in turn (excluding the Power On indicator). This function will immediately exit back to Access Level 1. 15

Technical Specification Panel Specification EFBWCV-REPEATER Power Specification Input Voltage Range 18.75-30.7V DC Maximum current drawn from battery 2.7A Communication Ports Repeater Port Type RS485 Nodes Up to 3 repeaters and a fire panel Environmental Note: The use of this port is outside the scope of EN54 certification Operating Temperature C -5 C to +40 C Relative Humidity % 93% +/3% non-condensing IP Rating IP30 Mechanical Dimensions mm 375 (W) x 366 (H) x 134 (D) Weight kg 2.25 Material PC ABS Front and Rear Cabling Cable Access Cable Type Compliance Compliance to Standards 29 x 20mm drill positions - Slots for rear cable entry Cable type 2 core 1.5mm, 2 screened fire rated cable (twisted pair) 500m (max) BS5839, part1 PSE Specification EFBWCV-REPEATER Power Specification Mains Voltage Mains Fuse Battery Details 230V AC -10% / +15%, 50Hz 1 Amp Anti-Surge Number of Batteries 2 Capacity Recommended Battery Battery Fuse Battery voltage (Charging value) Recommended period for battery replacement PSE Ratings 12V, 5Ah Yucell Y5-12 (Yuasa) 6.3A Anti-Surge 27.3V DC @20% 5 years Ouptut voltage Maximum ripple voltage Imin Ri max PSE Fault Options Mains OK (J4 pin 4) Fault_Charger (J4 pin 1) Fault_Battery (J4 pin 3) 0V (J4 pins 2 and 10) 18.75-30.7V DC 425mV rms (1.2Vp-p) 39mA 1Ω >=3V Mains present, <=3V Mains fault >=3V for 1s pulsed at 0.2Hz Charger OK >=3V for 1s pulsed at 1Hz Charger fault Steady high/low (no pulsing) PSE Micro fault =0.17* (Vbat-0.6) Volts reference 16

Manufacturers Contact Details Eaton Industries Manufacturing GMBH Electrical Sector EMEA Route de la Longeraie 7 1110 Morges Switzerland Technical Support Tel: +44 (0)1302 303 350 FireTechSupport@Eaton.com Eaton Electrical Systems Ltd. Wheatley Hall Road Doncaster South Yorkshire DN2 4NB http://www.cooperfire.com Sales: Tel: +44 (0)1302 303 303 FireSales@Eaton.com 17

Manufactured by Eaton Electrical Systems Limited. Wheatley Hall Rd Doncaster South Yorkshire DN2 4NB Eaton.uk.com Tel. +44 (0) 1302 303 350 www.cooperfire.com www.eaton.com Made in the UK Eaton Industries Manufacturing GmbH Electrical Sector EMEA Route de la Longeraie 7 1110 Morges, Switzerland Eaton.eu 2017 Eaton All Rights Reserved March 2017 Publication No. PR216-219-508-01 Eaton is a registered trademark. All other trademarks are property of their respective owners.