Linear Heat Detection Cable - Monitor

Similar documents
LDM-519-DIM LHDC MONITOR Digital Line Heat Detector Interface

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

ALARMLINE ANALOGUE Linear Heat Detection System

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

Installation, Operating and Maintenance Manual

Interface Modules for SENTRI

Software Version 2.01 LEVEL MONITOR MODEL 220

Intelligent Security & Fire Ltd

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

Intelligent Security & Fire Ltd

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

General Routing Interface

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Model 5610 Infra-red Transit Heat Sensor

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

An introduction to... Sigma

FIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

CU-02 with Senaco Plus

Instruction Manual August sitrans CU 02

IFD-E Flame Detector User Manual

Excel-EN Conventional Fire Control Panel

Instruction Manual December 2001 ENACOCU02

IFD-E Flame Detector User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Fireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds

Application, Installation, Operation & Maintenance Manual

SET Installation and Operating Instructions. Level switch for one sensor

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

INSTRUCTION MANUAL. DECKMA HAMBURG GmbH. Type OMD-12. Oil-in-Water Monitor

The EN54 Part 2 and 4 Fire System

EXTINGUISHING AGENT RELEASE MODULE

System 800 Addressable Fire Detection & Alarm System

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Reflective Optical Beam Smoke Detector User Guide

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

SOUNDER CONTROL MODULE SCM-AS4

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

DICTATOR Hold-Open Systems for Hazardous Areas

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

DCS-100. intelligent damper control & monitoring system

Tel: +44(0) Fax: +44(0) /17 LGM Products Ltd. Web: ISO 9001:2015 certified

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504

Door Release Power Supply

Fire and Smoke Control Systems

ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL

LC2200 Level Controller Installation and Maintenance Instructions

PTE0705 Electric Fence Monitor

Public Safety DAS Annunciator Panel

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

C-Bus Four Channel General Input Unit Installation Instructions

SET-2000 Hi Level/Oil

STOCKIST OF LINEAR HEAT SESNING CABLE in INDIA

The EN54 Part 2 & 4 Fire System

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

OPERATION AND INSTALLATION MANUAL

FEC400 Series. Installation Manual

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Conventional & Twin-wire Fire System

MINERVA MX. 800 Series Ancillary Equipment

PHOTOELECTRIC REFLECTIVE BEAM DETECTOR MODEL SRA-ET. Mounting Guidelines

Data Sheet 220 LEVEL MONITOR. Supplied by. .com. Call us on +44 (0)

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

IGD.CO.UK

Gasmonitor+ Installation, Operation and Maintenance Manual

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 Rev.

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

Using Non-Twisted Flat Cable in Analogue Addressable Retrofits

Smoke Vent Control Panel PCB4 V4 Installation Manual

System 57. An advanced World of intelligent gas detection system management

Input/Output Modules Data Sheet

Crowcon Gasmaster. 1 to 4 channel gas detection control panel. Installation, Operation and Maintenance Manual

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

APPLICATION DATA SHEET

Addressable Loop Modules

Vigilant MX4428 Fire Alarm System

MSP1000 Motor Protection Relay

DiMM Unit. LST Digital Interface Monitor Module (LST-DiMM) MAN3109

Solution F2. Fire Alarm Control Panels one step ahead.

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

INPUT / OUTPUT MINI MODULES

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

Transcription:

/-Z/-G Digital Interface with Distance Display The module is designed to monitor a length of Digital (Non-resettable) Linear Heat Detecting Cable () for both Fire condition, and Fault status (open circuit). The unit has a 3½ digit LCD which activates on fire condition and displays the distance into the zone that the alarm has occurred. Digital may be employed in lengths up to 2Km (1999m) with an adjustment to accommodate interposing cables. The unit is designed such that it may be configured to operate in a two wire mode that emulates the operation of conventional smoke & heat detectors. The unit may therefore be directly interfaced with fire control panels by connection to fire zone trigger circuits or addressable interface modules. If a separate power supply is employed, signalling of the fire and fault status, by means of volt free relay contacts and a 4 to 20m output are also available. The DIN rail modular form of the unit enables it to be installed in a variety of housings and readily integrated into multi zone control panels. The primary features of the control unit are:- Operable from two wire fire panel Trigger Circuits. Line / Low Power. nalogue address loop interface-able - Powered. Display of larm Location - Distance in metres. 4m to 20m instrumentation current loop output. Versions of this unit are available for use with Intrinsically Safe Zener arriers (-Z) and Galvanic Isolators (-G) for connecting to within Hazardous reas. - ll are SIL 2 Certified. Fault monitoring of for open circuit conditions. LED indication of Fire, Fault & status. Test & push-buttons. Volt free contact outputs for Fire & Fault conditions - when connected to a separate power supply. DIN ail mounting. ODEL SHOWN 1 D1137-13

Principles The unit is operated in conjunction with a length of Digital (Non-resettable) Linear Heat Detection Cable () and an end of line () terminator. The Digital is a twisted pair twin core cable. When the trigger temperature of the is reached the heat reactive polymer causes the cores to connect and a Fire alarm is registered. The units automatically determine the distance to the point of operation and displays this by means of the LCD. The current loop output provides an analogue value of the distance. This o/p is 0m when normal, and scaled 4m = 0m to 20m = 2000m on operation. eference should be made to the (separate) Sales Information Sheet D1179 on the Linear Heat Detection Cable for the specification of their performance. There are three principle modes of supply & signalling operation :- Figure 1 shows a typical minimum system where a separate 24Vdc supply is employed. The repeat contacts may be employed to signal an alarm panel and/or initiate control systems. Figure 1 4 to 20m CUENT LOOP LINE HET DETECTO TEINTO J INTEPOSING CLE L EPET CONTCTS (2 SET) EPET CONTCTS (2 SET) 24Vdc PSU Figure 2 shows a simple configuration with the unit directly connected to a fire panel trigger circuit. Note: Values of trigger and resistors may vary depending on the Fire Panel. Figure 2 CONVENTIONL CICUIT CONTOL PNEL LINE HET DETECTO TEINTO J INTEPOSING CLE L TIGGE CICUIT & L ESISTOS Figure 3 shows the configuration when an DDESS LOOP interface / zone monitor unit (ZU) module is fitted. Connection between the and the addressable loop module is as the trigger circuit connection of Figure 2. Note: Values of trigger and resistors may vary depending on the Fire Panel loop interface/zone onitor Unit. Figure 3 LINE HET DETECTO TEINTO J INTEPOSING CLE L DDITIONL LOOP INTEFCE CICUIT 2 WIE DDESS LOOP NLOGUE DDESSLE L CONTOL PNEL 2 D1137-13

20 20 190 odule rrangement 105 58 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 LED's LINE HET DETECTION CLE LCD 3½ DIGIT 90 TEST DISTNCE (m) TEST ESET PUSH UTTONS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 DIN IL - 35mm SYETICL Enclosures The onitor can be mounted in a variety of enclosures. For the example shown :- ating :- IP 65 Cover :- Dark Grey 746 Key-lockable hinged window aterial :- Shock esistant Polystyrene ase :- Light Grey L750 aterial :- Shock esistant Polystyrene HEIGHT INCLUDING LID 115.6 82 164 LINE HET DETECTION CLE Part Numbers Standard 700-451 For use with Zener arrier 700-451(Z) For use with Galvanic Isolator 700-451(G) Enclosure 700-801 TEST DISTNCE (m) e-mail: info@patol.co.uk Tel: 44 (0) 1189 701701 TEST ESET Operational Specification Two Wire ode elay ode Voltage: 14-30Vdc 20-30Vdc Current - Normal: Current - Fire: Current - Fault: <1.7m Plus user defined monitoring () current <12m Plus user defined Fire (Trigger) load <700µ <11.5m - (with Fault elay) <29m - (with oth elays) Plus 4 to 20m loop current if used Display: 3½ Digit LCD : 0 to 1999 - Character Height : 8.5mm Unit ccuracy : /- 1% Tolerance : /- 3% Hold Time : 3 sec elay Contacts: Environment: Fire - changeover - 2 sets Fault - changeover - 2 sets 0-60 C @ 95% max Humidity 1 @ 24Vdc / 120Vac esistance: Nominal 0.18 Ω /m 3 D1137-13

470 Direct Powered Configuration - elay ode In this mode both fire & fault relays are enabled by links at 7/8 & 9/10. The fault relay is energised in normal condition. 24Vdc power supply is required as the fault relay coil current requirement is greater than can be obtained from most trigger circuits whist maintaining the required voltage. oth fire & fault relays have twin contacts enabling both local control and repeat signalling. The 4 to 20m analogue current loop output may be employed to signal to PLC s etc. Figure 4 shows in more detail a typical minimum system where a 24Vdc supply is employed. The repeat contacts may be employed to signal an alarm panel and/or initiate control systems. OX INTEPOSING CLE LL CONTCTS ENLED 4-20m Site Zero Fire elay -Norm. De-energised Fault elay -Norm. Energised djust Figure 4 elay elay larm /on. Test Test Zero Enable Enable esistor esistor esistor djust - - - s c c s s s EOTE DISPLY ELY ENLED djustment section of this manual Figures 5 shows in more detail a typical connection to a conventional panel or One Input Zone onitor similar to Hochiki CHQ-SZ, CHQ-SI, CHQ-PO; pollo 55000-812, 55000-845, 55000-833. Other zone monitor manufacturers may also work. 1 INPUT ZONE ONITO TYPICL VLUES OX INTEPOSING CLE 4-20m Site Zero Fire elay -Norm. De-energised Fault elay -Norm. Energised djust Figure 5 elay elay larm /on. Test Test Enable Enable esistor esistor esistor Not Used - - - s c c s s s EOTE DISPLY ELY ENLED djustment section of this manual 4 D1137-13

470 470 Figures 6 shows in more detail a typical connection to a Two Input Zone onitor similar to Hochiki CHQ -DZ, CHQ-DI, CHQ-PO Other zone monitor manufacturers may also work. 2 INPUT ZONE ONITO TYPICL VLUES INPUT 1 INPUT 2 OX INTEPOSING CLE 4-20m Site Zero Fire elay -Norm. De-energised Fault elay -Norm. Energised djust Figure 6 elay elay larm /on. Test Test Enable Enable esistor esistor esistor Not Used - - - s c c s s s EOTE DISPLY ELY ENLED djustment section of this manual Figure 7 shows in detail a typical Zener arrier system where the is located in a Hazardous rea. Hazardous rea principles used in the installation of Zener arriers need to be closely adhered to. Those principles will vary depending on the Hazardous rea, equipment, type of installation and site. s in the examples above the repeat contacts may be employed to signal an alarm panel and or initiate control systems. INTEPOSING CLE Figure 7 OX ZENE IE 700-702 E E I.S. ETH LL CONTCTS ENLED 4-20m Site Zero djust Fire elay -Norm. De-energised Fault elay -Norm. Energised elay elay larm /on. Test Test Zero 0V - - 24V - s Enable c Enable c esistor s esistor s esistor s djust ELY ENLED EOTE DISPLY djustment section of this manual 5 D1137-13

1K 10K Figure 8 shows in detail a typical Galvanic Isolator system where a length of is located in a Hazardous rea. Hazardous rea principles used in the installation of Galvanic Isolator need to be closely adhered to. Those principles will vary depending on the Hazardous rea, equipment, type of installation and site. The main advantage in using a Galvanic Isolator over a Zener arrier is that a special IS Earth is not required. OX INTEPOSING CLE GLVNIC ISOLTO 700-705 700-706 470 SEE NOTE LL CONTCTS ENLED 4-20m Site Zero Fire elay -Norm. De-energised Fault elay -Norm. Energised djust Figure 8. Note: For the Galvanic Isolator to work correctly with the -G, a 470Ω, 250mW resistor is required in series with the positive terminal on the hazardous side of the Isolator and the connection in the Junction ox. elay elay larm /on. Test Test Zero Enable Enable esistor esistor esistor djust - - - s c c s s s ELY ENLED EOTE DISPLY djustment section of this manual s in the examples above the repeat contacts may be employed to signal an alarm panel and or initiate control systems. Line Powered Configuration - 2 Wire ode This 2 wire mode can be used with any of the previous Hazardous rea circuits. In this mode the relays are disabled and the unit s quiescent current is very low. y connection of appropriate value resistors at terminals 11/12 and 13/14, the unit replicates the characteristics of smoke and heat detectors and may be directly connected to, and powered from, most conventional fire system trigger circuits. The resistor at terminals 13/14 is connected to the trigger circuit when the unit is in normal condition. Should a open circuit fault or low voltage condition occur the resistor is switched out and the unit draws less than 700µ from the trigger circuit. Systems employing an end of line Zener diode should operate satisfactorily with the Zener connected at 13/14 instead of a resistor. It may be necessary to use a lower value device than normal as there is a 0.7-1.0V loss through the unit. The alarm resistor at terminals 11/12 is connected to the trigger circuit on fire detection. The alarm resistor value should be compatible with the conventional panel/zone monitor trigger circuit. The value of resistor may be less than the 1KΩ shown below. Figures 9 shows a typical connection to a conventional panel or Two Wire ode Zone onitor similar to Hochiki CHQ-SZ, CHQ-PO; pollo 55000-812, 55000-845, 55000-833 Other zone monitor manufacturers may also work. CONTCTS ND LOOP O/P NOT EPLOYED EFE TO FIGUES 4, 5, 6, 7 ND 8 FO CONNCTIONS 4-20m Site Zero Fire elay -Norm. De-energised Fault elay -Norm. Energised djust elay elay larm /on. Test Test Zero Enable Enable esistor esistor esistor djust - - - s c c s s s Figure 9. CONTOL PNEL TIGGE CICUIT INPUT O DDESSLE LOOP INTEFCE ODULE INPUT TYPICL VLUES djustment section of this manual 6 D1137-13

Operation It should be noted that in order for the unit to operate at very low supply currents, as is necessary for connection to Fire System trigger circuits, the & Fault LEDs illuminate in a flashing mode. The flash cycle is approximately 2s (0.5Hz) with an ON : OFF ratio of approximately 1:5. The relay & resistor o/p conditions described in the following are appropriate to the configured mode detailed in the previous section. NOL OK & Voltage Present Green LED - Flashing Liquid Crystal Display - Off / lank 4-20m output - 0 m Fire & Fault LEDs - Off Fire relay & Trigger circuit larm resistor o/p (terminals 11/12) - De-energised Fault relay & Trigger circuit resistor o/p (terminals 13/14) - Energised Open Circuit or Voltage Low Yellow Fault LED - Flashing Fault relay & Trigger circuit resistor o/p (terminals 13/14) - De-energised current - < 700 µ The unit will automatically return to Normal on rectification of the Fault condition ctivated ed Fire LEDs - On LCD - ctivated - Displaying distance to larm Point in metres. 4-20m output - Current gives distance to larm Point - Scaled 4m=0m 20m=2km Fire relay & Trigger circuit larm resistor o/p (terminals 11/12) - Energised TEST odule Fire Test push-button operated Indications, Fire relay and alarm resistor output operate as for Fire above. Please note terminals 15/16 must be linked by wire or a resistor of less than 320Ω or this function is disabled or may display beyond range (1---). LCD - Display distance as defined by calibrate resistor (terminals 15/16). Details below Note : The Test push-button must be depressed until the LC Display stabilises (3s). On P release the unit will remain latched to Fire but the LCD will go beyond range (1---). Note : The output is only valid during push-button operation. On push-button release before module reset the 4 to 20m output will drive over scale - 40m. TEST odule Fault Test & push-button operated Fault condition is simulated during push-button operation ESET odule Fault Test & push-button operated The unit is normalised after a Fire Test push-button operation On activation push-button operation causes refresh of the LCD indication. after a true Fire can only occur after replacement of the operated 7 D1137-13

Site djustments - Interposing Cable When a fire condition is detected the distance in metres from the start of the zone to the hot spot is displayed by the LCD. The mechanism employed is the resistance characteristic of the. In some circumstances the may be connected to the monitoring unit by interposing cables and Hazardous rea intrinsic safety barriers. re-zero adjustment control (V2) located at terminal positions 35/36 is provided to negate the resistance of the interposing cable and where used, barriers. The procedure is as follows:- a) With the unit connected to a power source, place a short circuit (s/c) at the start of the at the Junction ox terminals. This will place the unit into a Fire mode. b) The LCD will show a figure which will stabilise after a few seconds. The decimal points between digits will appear if the reading is negative. c) The resistance of the Interposing Cable and if used, IS arriers can be cancelled out by adjusting V2 until Zeros (000) are shown on the display. If the is directly connected at the controller, i.e. no interposing cable or barrier. Place the temporary s/c at terminals 19/20 and adjust V2 to Zeros (000) in the display. d) When a zero reading is achieved, the short circuit should be removed from the signal and the Controller using the TEST / ESET green push-button (P) on the right of the display. e) The red TEST push-button is a configured option as part of the aintenance Test programme and is referred to in the Operation Section of this anual. It is important to understand that its use will place the controller into larm. Ensure the connected Fire Panel / Zone is isolated before operating the Fire Test. To enable this function install a shorting link across terminals 15/16. Keep the button pressed down and adjust the Variable esistor (V3) at terminals 17/18 until zeros (000) are displayed. On release of the Fire Test push-button the LCD will display (1---) until the reset button is operated. (Note that in this condition the unit may provide more than 40m current at the 4 to 20m output terminals 33/34). f) If a different reading in the display is required, for example 1000 metres, replace the Shorting Link with a 160Ω resistor (>250mW). Disclaimer :- The information contained in this document (D1137) is intended as guidance notes only, and do not take precedence over any applicable on site policies or Hazardous rea regulations. We recommend that you always closely follow the manufacture s own applicable datasheets when installing any Hazardous rea Technology. Notes. Contact Details: Patol Limited rchway House ath oad Padworth, eading, erkshire. G7 5H Tel: 44 (0)1189 701 701 Fax: 44 (0)1189 701 700 Email: info@patol.co.uk Web: www.patol.co.uk 8 D1137-13