USE OF DOE-2 TO EVALUATE EVAPORATIVE COOLING IN TEXAS CORRECTIONAL FACILITIES

Similar documents
ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Two Stage Indirect/Direct Evaporative Cooling

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

Modified Air Cooler with Split Cooling Unit

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

Optimizing Electric Humidifier Operation with an Air Side Economizer

Thermodynamics II Chapter 6 Mixtures & Psychrometry

Redesign of Bennett Hall HVAC System

Investigation of an evaporative air cooler using solar energy under Algerian climate

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Design and Development of Combined Direct and Indirect Evaporative Cooling System

Achieving Dry Outside Air in an Energy-Efficient Manner

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Cold Storage Warehouse Dock Parametric Study

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Analysis and Evaluation of a Passive Evaporative Cool Tower in conjunction with a Solar Chimney

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

ω = (1) Kirby S. Chapman Ph.D.

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Psychrometric Engineering Applications

A review on Efficient Technique of Air-Conditioning Rajesh Kumar, Pravesh Mishra, Ram Raja

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

TECHNICAL NOTE ON EVAPORATIVE COOLING. Renato Lazzarin, President of the IIR s Commission E1

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Performance Rating of Computer and Data Processing Room Air Conditioners

Humidity Control & Psychrometrics

Chapter 8 Balances on Nonreactive Processes PSYCHROMETRIC CHART

Optimisation of cooling coil performance during operation stage for improved humidity control

Do All DOAS Configurations Provide the Same Benefits?

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Oxyvap Evaporative Cooling Applications

Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Comfort and health-indoor air quality

CE311 Fall 2016 Mid-Term Exam 1

Air Conditioning Clinic

Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates

Project Report 6 REFRIGERATION ENERGY USE IN THE FOOD CHAIN PROJECT REFERENCE (TBA) CONTRACT REFERENCE (TBA)

GRAPSI_DRAW DIGITAL PSYCHROMETRIC CHART

ANALYSIS OF DESICCANT COOLING SYSTEM

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Evaporative Cooling Applicability in the Middle East

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Scholars Research Library


Performance of an Improved Household Refrigerator/Freezer

CE311 Fall 2016 Mid-Term Exam 1

Recent Advances in Energy, Environment and Economic Development

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

Scientific Journal Impact Factor: (ISRA), Impact Factor: Methodology. [Yadav, 3(9): September, 2014] ISSN:

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Dynamic performance of a novel dew point air conditioning for the UK buildings

R07. Answer any FIVE Questions All Questions carry equal marks *****

Chapter 14, Problem 27.

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Mechanical Engineering Laboratory

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

Performance Optimization of the Evaporative Condenser Design

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Basic Principals of Air conditioning By Dr. Esam Mejbil Abed

Mathematical Simulation of Longan Fruit Drying

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

Variable Air Volume with Indoor Air Quality

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, August 2015

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

announcements 4/10/08

Transcription:

USE OF DOE-2 TO EVALUATE EVAPORATIVE COOLING IN TEXAS CORRECTIONAL FACILITIES Namir Saman, Ph.D., P.E. Tarek Bou-Saada Tia Heneghan Visiting Assistant Professor Research Associate Energy Manager Energy Systems Laboratory Energy Systems Laboratory Texas Department of Criminal Justice College Station, Texas College Station, Texas Hantsville. Texas ABSTRACT This study investigates the feasibility of using direct and indirect evaporative cooling systems for correctional facilities in two different Texas climatic regions with the DOE-2.1E hourly energy simulation program. The analysis is based on adding user defined functions to the DOE-2 SYSTEMS subprogram to simulate direct and indirect evaporative cooling configurations. The DOE-2 program was run with two weather tapes, one for Kingsville, Texas and one for Abilene, Texas during April, July, and October to resemble neutral, summer and winter weather conditions. The results showed that direct evaporative cooling is applicable in April for Abilene and October for fingsville. The indirect evaporative cooling is feasible in July for Abilene and April for Kingsville. INTRODUCTION Evaporative cooling provides an energy efficient, environmentally safe, and cost effective alternative to traditional space conditioning methods for residential homes, industrial facilities, and commercial and institutional buildings. Evaporative cooling may also be used to control dry-bulb temperature andfor humidity levels. Furthermore, it can be combined with mechanical refrigeration to enhance space comfort conditions, or simply as a mechanical refrigeration back-up system. Today's increased attention to rising energy costs, energy conservation issues, indoor air quality questions, and environmental CFC concerns has led engineers to focus on direct and indirect evaporative cooling systems. The humidification and cooling energy savings of evaporative cooling as compared to conventional economizer cycles were studied by Brown (1989). It was found that when evaporative coolers are employed in conjunction with economizer cycle operation, humidification by evaporation can be achieved for most of the operating hours without expenditure of energy (Brown, 1989). In addition, the use of evaporative cooling is not solely restricted to arid climates. Evaporative cooling can be used over a broad geographical region to provide a quality indoor environment at a reduced annual energy consumption (Brown, 1990). The use of evaporative cooling in the summer to reduce peak cooling loads and cooling ton-hours as well as in the winter to increase building humidification leads to a short payback period (Scofield and Sterling, 1992). Accordingly, evaporative cooling can be considered as an energy conservation approach that can be used individually or in combination with other cooling systems to save energy and improve the environment. It is not the purpose of this study to consider all evaporative cooling applications for the correctional facilities in Texas. Rather, the purpose is to investigate the feasibility of using DOE-2 as a tool to investigate the possibility of using evaporative cooling to produce a comfortable indoor environment for correctional facilities. Modeling evaporative cooling systems using hourly energy simulation programs makes it possible to analyze a variety of direct, indirect, and multiple-stage evaporative cooling systems (McDonald et al. 1990). The technique described here will enable the user to modify, enhance, or replace the DOE-2 calculations without having to recompile the program. The procedure includes using direct and indirect userdefined functions in the DOE-2 SYSTEMS subprogram together with two different weather conditions in Texas (Kingsville and Abilene). BACKGROUND This section introduces direct and indirect evaporative cooling concepts and how they can be used for cooling and humidification processes. Evaporative coolers exchange sensible heat for latent heat (ASHRAE, 1992). In the direct evaporative cooler, water is evaporated into an airstream, and the continuously recirculated water will reach an

equilibrium temperature that approaches the entering air wet-bulb temperature. For direct evaporative cooling as shown in Fig. 1, the process of cooling and humidifying the air takes place at constant total heat (i.e. adiabatic process), which nearly coincide with the wet-bulb temperature lines on the psychrometric chart (ASHRAE-Applications, 1995). The effectiveness of an evaporative cooler is defined as the depression in dry-bulb temperature of the air leaving the evaporative cooler divided by the difference between the dry bulb and wet bulb temperatures of the incoming air (ASHRAE, 1995). Evaporative cooling effectiveness can range between 80% to 90%. The indirect evaporative cooling process is also shown in Fig. 1. The cooling process is sensible since there is no direct contact between the supply air and the water. In this study the direct evaporative cooling is used to cool the incoming outside air as demonstrated in Fig. 2. For the indirect evaporative cooling used in this analysis, and shown in Fig. 3, the evaporative cooler is used to cool the mixed air temperature using outside air. A combination of indirect and direct evaporator cooling can be used in a system or any of the direct or indirect modes can be used with mechanical refrigeration. In addition, more than one stage evaporative cooling can also be used (ASHRAE, 1995). EXISTING HEATINGNENTILATING SYSTEMS AT TDCJ The existing heating and ventilating system at the Texas Department of Criminal Justice (TDCJ) prison facilities consists of a system that is similar to the DOE-2 HVSYS system in the cell buildings. The existing heatinghentilating system pulls outside air directly into the building. There is no means of conditioning the air with respect to cooling the air and controlling humidity. During the heating season. the outside air is pulled and heated using natural gas as the heating medium. In the summer, especially in hot or hot and humid climates, indoor conditions are outside ASHRAE recommended comfort zones. Two locations in Texas were chosen for this study, namely Abilene and Kingsville. Abilene is located in the upper middle part of Texas with cold and dry weather in the fall, hot and humid weather in the summer and moderate temperature and humidity in the spring. Kingsville is located in the south part of Texas. The weather is hot and humid during the summer and the spring, and with moderate temperature but humid in the winter. DOE-2 MODELS The Functional Value features in the DOE-2 LOADS and SYSTEMS sub-programs allow the user to modify the calculations without recompiling the program (DOE-2 manual, 1992). The FORTRANlike language models employ modifications to the direct and indirect evaporative cooling models developed by McDonald et al. (1 990). The evaporative cooling models are implemented at the air economizer subroutine within the DOE-2 program labeled ECONO-2. The modified ECONO- 2 INDIRECT subroutine includes algorithms to calculate the drop in supply air dry-bulb temperature as a result of using indirect evaporative cooling (McDonald et a]., 1990). The DOE-2 simulation produced hourly zone temperature for Abilene and Kingsville using weather conditions for April 30, July 3 1, and October 3 1. The analysis was carried out with and without the use of evaporative cooling. The format of the model for the indirect evaporative cooling is shown in the Appendix. The modified ECONO-2 DIRECT subroutine includes an algorithm that calculates the temperature drop and humidity change as a result of using the direct evaporative cooling in the outside air intake (see Appendix). A fixed value for evaporative cooling effectiveness is used. The psychrometric equations used are based on ASHRAE humidity calculation algorithms (ASHRAE 1993) and McDonald et al. (1990). Two TMY weather tapes were used for the DOE- 2 simulation (Kingsville and Abilene). The DOE-2 input file of a typical TDCJ 2,250-bed cell building was run with evaporative cooling and with existing heating and ventilating systems simulated with HVSYS in DOE-2. The direct and indirect evaporative cooling models were run together with the no evaporative cooling model. The hourly room temperature and relative humidity for April 30, July 31, and October 31 were determined and plotted on the ASHRAE comfort region psychrometric chart (similar to Fig. 11) to determine the comfort level of using evaporative cooling for both locations.

RESULTS Figures 4 through 14 summarize the results of this work. Figures 4 and 5 show the variation of the difference between the dry-bulb and wet-bulb temperatures for Kingsville and Abilene for April 30, July 3 1 and October 31, respectively. It was expected that the higher temperature difference would produce the best performance with direct evaporative cooling. However, the high outside dry-bulb temperature and relative humidity during July and April for Kingsville left only October as the suitable direct evaporative cooling month of the three. In Abilene, the high temperature and humidity in July, and the low temperature in October made April to be the suitable direct evaporative cooling month. Figures 6 and 7 show the variation in the supply air temperatures for Kingsville and Abilene, respectively. Use of the evaporative cooling lowered the supply air temperatures in both locations. Supply air temperatures of less than 68" F was considered for the analysis (McDonald et al., 1990). For hngsville, shown in Fig. 6, both April and July supply air temperature values were above the 68" F level. October conditions produced supply air temperatures below 68" F. For Abilene, shown in Fig. 7, April proved to be the month with the most suitable supply air temperatures. July supply air temperatures were higher than 68" F and October supply air temperatures were too low for comfort cooling. Figures 8 and 9 show the variation in room air temperature and humidity ratio, respectively, for Kingsville and Abilene, with October shown in Fig. 8 and April shown in Fig. 9. Both direct evaporative cooling and no evaporative cooling were considered. The combination of temperature and humidity ratio was plotted on the psychrometric chart to compare with ASHRAE's comfort conditions as shown in Fig. 10. The combination of room dry-bulb temperature and humidity ratio fell outside the standard ASHRAE comfort zones. However, the combination fell inside the ASHRAE comfort zones with higher air velocities accompanying evaporative coolers, as demonstrated in Fig. 11. For the indirect evaporative cooling mode, the supply and room air temperatures for Abilene and Kingsville are shown in Figs. 12 and 13, respectively. The same discussions mentioned above concerning ASHRAE comfort zones applies to indirect evaporative cooling room dry-bulbhumidity ratio combination. In the indirect evaporative cooling mode, no humidification of the supply air takes place. The humidity of the outside air or the mixture of outside and return air will be the humidity of the supply air. For both Abilene and Kingsville, the indirect evaporative cooling reduced room air temperature by 5 to 10' F. DISCUSSION The use of direct and indirect evaporative cooling was investigated for three days in three different months for two locations in Texas (Abilene located in upper central Texas, and Kingsville located in southern Texas). The results showed that indirect evaporative cooling is feasible in July for Abilene and in April for Kingsville with room temperatures of 5 to 10' F lower than the case of no evaporative cooling. Direct evaporative cooling is feasible in April for Abilene, and October for Kingsville. The high drybulb temperature and relative humidity in Kingsville made October suitable for direct evaporative cooling. The humid weather in April and July led to an inappropriate humidityldry-bulb temperature combination that was rendered ineffective by the humidification effect of the direct evaporative cooling process. For Abilene, October temperatures are too low and thus not suitable for direct evaporative cooling. On the other hand, July temperatures were high enough to result in supply air temperatures of greater than 68" F. Since there is no direct contact between the supply air and the water for the indirect evaporative cooling, there will be no humidification of the supply air. For Abilene, July was the month with moderate outside temperature that resulted in suitable supply air temperatures. For Kingsville, April was the suitable month. The performance of the direct and indirect evaporative cooling process can be modified by using chilled water in an evaporative cooling/chiller system that will supply better indoor conditions. This issue will be addressed in a future study. Figure 14 shows the regions on the psychrometric chart where evaporative cooling and evaporative cooling plus mechanical refrigeration systems can be used (reference 9). CONCLUSIONS DOE-2 is a useful tool to study the feasibility of using a evaporative cooling process in different regions of the country once weather conditions and building construction information are available. The subroutines in DOE-2 may be modified to accommodate the use of special routines that model the performance of direct and indirect evaporative

cooling processes. The use of evaporative cooling during certain times of the year will lead to improved indoor comfort conditions in correctional facilities in Texas. This study is preliminary and will be expanded in a future study to include more regions in Texas as well as yearly simulation with the DOE-2 program. The following is a summary of the conclusions of this work. 1- Although large differences between the dry-bulb and wet-bulb temperatures existed for both locations, the high dry-bulb temperature values led to unsuitably high supply air temperatures. This was especially noticeable for Kingsville in July. 2- For cold weather, using an evaporative cooling process is not appropriate (October in Abilene). 3- The ASHRAE comfort zones are affected by supply air velocity. Therefore, the combination of humidity ratio and dry-bulb temperature resulting from using the direct and indirect evaporative cooling processes fell inside the "moved" comfort zone. This was the case of the indirect evaporative cooling in July for Abilene and April Kingsville. The same was true for the direct evaporative cooling in April for Abilene and October for Kingsville. 4- The regions appropriate for using evaporative cooling are shown in Fig. 14 (Reference 9). ACKNOWLEDGMENTS The authors would like to acknowledge Mr. Bryce Munger for preparing some of the figures used in this study. Professor Jeff Haberl also provided helpful review and suggestions. REFERENCES 1. Brown, W.K., "Humidification by Evaporation for Control Simplicity and Energy Savings," ASHRAE TRANSACTIONS, V. 95, Pt. 1, 1989. 2. Brown, W.K., "Fundamental Concepts Integrating Evaporative Techniques in HVAC Systems," ASHRAE TRANSACTIONS, V. 96, Pt. 1, 1990. 3. McDonald, G.W., M.H. Turietta and R.E. Foster, "Modeling Evaporative Cooling Systems with DOE- 2. ID," ASHRAE TRANSACTIONS, V. 96, Pt. 1, 1990. 4. Scofield, C.M. and E. Sterling, "Dry Climate Evaporative Cooling with Refrigeration Backup," ASHRAE Journal, June 1992. 5. DOE-2.1 D users Manual, 1992. 6. ASHRAE Handbook-WAC Systems and Equipment, 1992. 7. ASHRAE Handbook-Fundamentals, 1993. 8. ASHRAE Handbook-WAC Applications, 1995. 9. Private communications with Mr. Mehrad Sadrisabet, President, Professional Engineering & Technology Engineering Firm, Tucson, Arizona, 1992. APPENDIX Direct Evap-Cooling Routine (ECONO-2 DIRECT, based on ref. 3) FUNCTION NAME=DIRECT.. ASSIGN DBT=DBT WBT=WBT TM=TM PO=PO TR=TR PATM=PATM HUMRAT=HUMRAT WM=WM WR=WR.. CALCULATE.. C EVAP-COOLER CONTROL, PERFORMANCE, AND MIXED AIR C TEMP CALCULATION IF(DBT.LT.55) GO TO 80 Po=l.O EFF=0.85 C CALCULATE EVAP COOLER EXIT DBT DBT2=DBT-EFF*(DBT-WBT) IF (DBT2.GT.68) GO TO 80 IF (DBT.LT.68) GO TO 60 60 TM2=(PO*DBT2)+(1.O-PO)*DBT C PSYCHROMETRIC CALCULATION FOR PRE-COOLED AND MIXED AIR C HUMIDITY RATIO C CALCULATE PARTIAL PRESSURE OF WATER VAPOR IN MOISTURE C SATURATED AIR A 1=-7.90298 A2=5.02808 A3=-O.OOOOOOl38 16 A4=ll.344 A5=0.008 1328 A6=-3.49149 TW=(WBT+459.688)/1.8

2-373.16fW PI=AI*(Z-1) P2=A2*ALOG 1 O(Z) DUMMY I=A4*(I -( IIZ)) P3=A3*((lO**DUMMY 1)-1) DUMMY2=A6*(Z- I) P4=A5*((1 O**DUMMY2)- I) DUMMY3=P 1 +P2+P3+P4 PVP=29.921* 10**DUMMY3 GO TO 85 80 TM2=DBT 85 CONTINUE C CALCULATE HUMIDITY RATIO OF PRE- COOLED AIRSTREAM HUMRATS=0.622*PVP/(PATM-PVP) HUMRAT2=HUMRAT+EFF*(HUMRATS- HUMRAT) C CALCULATE HUMIDITY RATIO OF MIXED AIR AFTER EVAP COOLER WM I =(PO*HUMRAT2)+(1.O-PO)*WR C CALCULATE ROOM HUMIDITY RATIO WROOM=WM 1 +(WR-WM) C CALCULATE HUMIDITY RATIO OF AIR AFTER COOLER HL=l093.049+0.44 1 *TM2-WBT CH=0.24+0.44 1 *HUMRATS WH=HUMRATS-CH*(TMZWBT)/'L PV=PVP-(5.704E-04*PATM*(TM2-WBT)/I.8) WEVAP=0.662*(PV/(PATM-PV)) TROOM=TM2+(TR-DBT) C CALCULATE THE RELATIVE HUMIDITY OF ROOM AIR RH=RHFUNC(dbt,humrat,press) PRINT 1,TM2,DBT,TR,TROOM,WROOM,WEVAP 1 FORMAT( I X,'TM2=',F4.O,'OAT=',F4.0,'TR=',F4.0, 1 'TROOM='F4.O,'WROOM=',F7.6,'WEVAP=',F7.6) END END-FUNCTION. Indirect Evap-Cooling Routine (ECONO-2 INDIRECT, based on ref.3) $ INDIRECT EVAP-COOLER MODEL SUBR-FUNCTIONS ECONO-2=*INDIRECT*.. $HOURLY REPORTS RP- 1 = SCHEDULE THRU DEC 3 1 (ALL) (1,241 (1).. BLOCK- I = REPORT-BLOCK VARIABLE-TYPE = SYST- 1 VARIABLE-LIST = (3.4,8,35,36).. BLOCK-2 = REPORT-BLOCK VARIABLE-TYPE = ZONE-J3-1 VARIABLE-LIST= (6).. HR- 1 = HOURLY-REPORT REPORT-SCHEDULE = RP- I REPORT-BLOCK=(BLOCK- I,BLOCK-2).. END.. FUNCTION NAMEINDIRECT.. ASSIGN DBT=DBT WBT=WBT TM=TM PO=PO TR=TR PATM=PATM HUMRAT=HUMRAT WM=WM WR=WR.. CALCULATE.. C EVAP-COOLER CONTROL, PERFORMANCE, AND MMED AIR C TEMP CALCULATION IF(DBT.LT.55) GO TO 80 TM=(PO*DBT)+(( 1.-PO)*TR) EFF=0.65 TM2zTM-EFF*(TM-WBT) IF(TM2.LT.55) GO TO 60 TM=TM2 GO TO 80 60 TM=55 80 CONTINUE TROOM=TM+(T'R-DBT) PRINT 1,TM,DBT,TR,TROOM,PO 1 FORMAT(F4.O,F4.0,2F4.O,F4.2) END END-FUNCTION..

Figure 2 Schematic of direct evaporative cooling. Figure 3 Schematic of indirect evaporative cooling. Dry Bulb Temperature (F) Figure 1 Psychrometrics of direct and indirect evaporative cooling. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time (hr) Figure 4 Variation of the difference between outside DBT and WBT with time for April 30, July 31, and October 31 for Kingsville, Texas.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time (hr) Figure 5 Variation of the difference between outside DBT and WBT with time for April 30, July 31, and October 31 for Abilene, Texas. Time (hr) Figure 6 Variation of supply air temperature with and without direct evaporative cooling for Kingsville, Texas.

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time (hr) Figure 7 Variation of supply air temperature with and without direct evaporative cooling for Abilene, Texas. Figure 8 Variation of room air temperature in October with and without direct evaporative cooling for Kingsville and Abilene, Texas 366

Time (hr) Figure 9 Variation of room humidity ratio in April with and without direct evaporative cooling for Kingsville and Abilene, Texas Dry Bulb Temperature (F) Figure 10 Standard ASHRAE comfort zones. 10 20 30 4b 5b 6b 7b sb 901d01io1io Dry Bulb Temperature (F) Figure 11 Change of human comfort zone due to higher air velocities.

Figure 12 Variation Figure 13 Variatior

Figure 14 Regions of using evap-cooling or evap-cooling/chiuer combination.