ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

Similar documents
FIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF

MULTIFUNCTION ALARM SYSTEM TYPE ED510 FIRE LEVEL GAS ZONE 1 ZONE 2 ZONE 1 ZONE 2 SENSOR 1 SENSOR 2 ALARM FAULT TEST ON TEST OFF

Installation, Operating and Maintenance Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

OPERATION AND INSTALLATION MANUAL

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Conventional Fire Alarm System 2014 V1.2

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Intelligent Security & Fire Ltd

System 800 Addressable Fire Detection & Alarm System

Excel-EN Conventional Fire Control Panel

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

FR-4000 & FR-8000 Fire Alarm Monitor Installation Manual

Intelligent Security & Fire Ltd

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

USER MANUAL & MAINTENANCE GUIDE OG OO

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

Door Release Power Supply

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

FEC400 Series. Installation Manual

The EN54 Part 2 and 4 Fire System

Application, Installation, Operation & Maintenance Manual

The EN54 Part 2 & 4 Fire System

General Routing Interface

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Surveyor Envoy-MINI 4

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Interface Modules for SENTRI

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

DB5 Intrinsically Safe Sounder Type DB-5

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

DICTATOR Hold-Open Systems for Hazardous Areas

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

5000 INSTALLATION GUIDE

Control Panel User Guide

Reflective Optical Beam Smoke Detector User Guide

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

YO3 - YO4 / YL4 - YO5 / YL5

Commercial and Light Industrial Fire Alarm Control Panel

Analogue addressable devices

Precept Marine Control Panel Application Guide

GAS SUPRESSION CONTROL PANEL:

Power Supply Display Module PSDM. Installation and Operation Manual

Conventional Leaflets

2018 Johnson Controls. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland DUO-CEL

1) This manual covers 4400, 5400 and 6400 fire alarm systems. The differences are described in the appropriate sections.

AL600ULADA. NAC Power Extender. Installation Guide

2000 Series Sensors Installation Guide

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

Menvier Fire System MF9300

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

Fire Alarm Control Panel. System Maintenance and Log Book

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

RE 102 RE Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

Document No Issue 4 user manual

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

OSA 3. Level alarm for oil separator. Afriso Ema AB. Kilvägen 2 SE Arlöv Sweden T +46-(0) F +46-(0)

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

IFD-E Flame Detector User Manual

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

ORION Mini-Rep INSTALLATION MANUAL

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

Installation and Operating Instructions

Tel: +44(0) Fax: +44(0) /17 LGM Products Ltd. Web: ISO 9001:2015 certified

ZSC100 Gas Detection and Alarm System Controller

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

RP1r-Supra / VSN-RP1r+ / ESS-RP1r-Supra Extinguishing Control Panel User Manual. HLSI-MN-103I v.06 September 2017

SYSTEM 5000 USER MANUAL

MINERVA MX. 800 Series Ancillary Equipment

Addendum for STI-6406 with Dual Access Control

Conventional Fire Detection

4) Intrinsic Safety Certification

Orbis IS Product Guide MAN 3041

Conventional & Twin-wire Fire System

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections.

Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

Barrier. ED /07/09 Release to production R.P. A ECO N DATE DESCRIPTION OF CHANGE CHG By ISSUE TITLE TC842B1007 AE PRODUCT SPECIFICATION

End To End Optical Beam Smoke Detector. Additional Information

Flostop TS D7E and A8E. Operation Manual

IFD-E Flame Detector User Manual

Fire Alarm Control Panel Installation, Commissioning & Operation MAN

Transcription:

ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk Website: www.electronicdevices.co.uk

INDEX PAGE SPECIFICATION 3 INSTALLATION 4 OVERVIEW AND FEATURES 4 TYPICAL SYSTEM LAYOUT 4 CONTROL UNIT 5 DETECTORS 5 DETECTOR CONNECTIONS 6 CONTROL UNIT TERMINAL LIST 7 SOUNDER WIRING 8 OPERATION 9 FRONT PANEL KEY SWITCH 9 ZONE AND SOUNDER DISABLEMENT 9 EXTERNAL & INTERNAL SOUNDER SILENCE 9 RESET 9 INTRINSICALLY SAFE ZONES 9 in service testing 10 basic fault finding 10 BASIC PRINCIPLES 10 OPEN CIRCUIT ZONE FAULT 11 SHORT CIRCUIT ZONE FAULT 11 commissioning 11 ED820 FIRE DETECTOR ED820 IM REV 2 09.01.2017 2

SPECIFICATION 24V MODEL ONLY THE EQUIPMENT MUST NOT BE MODIFIED IN ANY WAY AND MUST BE INSTALLED AND SERVICED BY COMPETENT PERSONNEL ONLY. IF IN DOUBT CONSULT ELECTRONIC DEVICES LTD (01684) 891500 The ED820 is a four zone conventional fire detection control unit. It is capable of driving nominal 24Vdc detection heads and call points, such as the Apollo Orbis ranges of marine approved detectors. Power Supply Requirements Main Power Input: Emergency Power Input: Current Consumption Standby: Alarm: Enclosure Weight: Dimensions: 20.0 32.0 VDC @ 3A 20.0 32.0 VDC @ 3A 140mA 220mA Output devices (700mA All zones in alarm) 1.1Kg. See diagram below Approvals Type Approved by The American Bureau of Shipping (ABS) for Marine and Offshore applications. Tested to BS EN 542:1997A1:2006 Fuse Ratings There are five fuses inside the ED820 labelled F1 F5. To access the fuses remove the terminal cover, the fuses are all mounted in holders on the printed circuit board. F1 is located on the left hand side, through to F5 fitted on the right hand side. The values are as follows: F1 & F2 = 4A Quick Blow F3, F4 & F5 = 1A Quick Blow 137mm 185mm 198mm 38 27 29 29 29 29 120mm M10 M20 235mm ED820 FIRE DETECTOR ED820 IM REV 2 09.01.2017 3

INSTALLATION OVERVIEW AND FEATURES The ED820 fire alarm panel features include the following: 4 Zones (detector circuits). 2 Monitored sounder circuits. Key switch entry to access authorised user controls (access level two). Programmable sounder resound option silenced sounders to resound, or not resound, when new zone in alarm. Disablement per zone and per sounder circuit. Hazardous Area device compatibility, programmable per zone. Fault relay output. Fire Alarm relay output. IMPORTANT NOTE This equipment must only be installed and maintained by competent persons. Fire alarm system design is beyond the scope of this document. Understanding of fire alarm systems, components and their use is assumed. TYPICAL SYSTEM LAYOUT Sounder Circuit 1 EOL 4K7 Sounder Circuit 2 EOL 4K7 Conventional Zone 1 EOL 4K7 Conventional detectors Call points EOL 4K7 Power Supply Unit Conventional Zone 4 Fire Detector Main 24VDC or 12VDC dependant on model Emergency 24 VDC or 12VDC dependant on model Power supply fault signal Fault re lay contacts Alarm relay contacts Delayed relay contacts 110VAC / 230VA C ED820 FIRE DETECTOR ED820 IM REV 2 09.01.2017 4

INSTALLATION CONTROL UNIT The control unit should be mounted, in a convenient position for the operator, away from possible mechanical damage and allowing sufficient room for the front panel to swing open, and cables to enter without kinking etc. The location should be considered carefully to limit access to authorised personnel only. The enclosure is fixed to a bulkhead with four screws through holes in the rear of the enclosure. Cabling should follow Classification Society Regulations e.g. ABS, D.Tp., I.E.E. Regulations for electronic and electrical equipment in ships and be suitable for marine applications, fire detection systems and Hazardous Area applications, where necessary. INSTALLATION DETECTORS Avoid siting near to ventilation shafts etc. to minimise the possibility of false alarms. They should be mounted high on the deck head and not on the underside of beams etc. Exact fitting instructions are normally supplied with each detector but Figures 1, 2 and 3 detail the connections of some types approved for use with the ED820. It is good practice to always make the first device on a fire detection zone a call point, enabling manual operation of the alarms when early signs of fire are spotted before any detector has operated. Additionally making a call point the first item on a zone reduces the risk of it being out of circuit due to head removal or wiring faults. Suitable marine approved detectors include Apollo Orbis and manual call points type EDCP and EDCP/W. The types of detector required varies for each location. Guidance should be sought from classification societies and SOLAS regulations. For general use, two types of smoke detector are recognised by standards as good, general purpose fire detectors offering a high level of protection. 1. Ionisation smoke detectors have a high sensitivity to fires that produce small smoke particles ie fastburning, flame fires that can burn for some time without generating much smoke. 2. Optical smoke detectors are particularly well suited to detecting slowburning, smouldering fires which produce smoke with large particles. They are widely used for protection in areas such as accommodation, escape corridors and electrical rooms, as well as for general purposes. Heat detectors offer protection in areas such as galleys and engine rooms where the environment is dirty or smoky under normal conditions or where there is a high presence of airborne particles such as water vapour or exhaust fumes. However, it must be recognised that any heat detector will respond only when a fire is wellestablished and generating a high heat output. Therefore, especially for vessels with large engine rooms, flame or smoke detectors should be considered. Two types of heat detectors are available: * Rateofrise heat detectors are designed to sense a rapid increase in the temperature and are useful in environments where the ambient temperature is normal, such as small occasionally used galleys, workshops and stores. * Fixed temperature heat detectors will signal an alarm once the temperature exceeds a predefined level and are effective in environments with fluctuating temperatures (such as boiler rooms) or where the ambient temperature is unusually high (for example in an engine room). ED820 FIRE DETECTOR ED820 IM REV 2 09.01.2017 5

DETECTOR CONNECTIONS NOTES: 1. Connect detector earth connection to cable screen. 2. Always fit call points at the beginning of a zone or on a separate zone. If detectors are fitted between the control unit and call points removal of these detectors would disable the call points. 3. Never use looped wire for connection into and out from the same terminal, always break wire to enable fault monitoring. Zone VE 3 4 R L L1 L2 R L L1 L2 4K7 EOL Zone VE 1 2 FIG 1 EDCP Call point Tyco 600 series connections ve Control unit zone connections L E D COM IN APOLLO ORBIS 4 OUT L E D COM IN APOLLO ORBIS 4 OUT L E D COM IN APOLLO ORBIS 4 OUT 4K7 EOL ve FIG 2 ve Control unit zone connections ve 5 3 4 6 YBOR/6M 1 2 3 4 3 4 5 6 1 2 5 6 1 2 YBOR/6M YBOR/6M 4K7 EOL FIG 3 HOCHIKI DETECTORS ED820 FIRE DETECTOR ED820 IM REV 2 09.01.2017 6

ED820 TERMINAL CONNECTIONS MAIN DC INPUT EMERG DC INPUT ZONE 1 ZONE 2 ZONE 3 ZONE 4 PSU FAULT INPUT FUSED DC OUTPUT NOTE: The fault relay is wired active on. In the event of a complete power failure this could be used to activate an alarm. SOUNDER CIRCUIT 1 SOUNDER CIRCUIT 2 NC C NO NC C NO ALARM OUTPUT FAULT OUTPUT ED820 FIRE DETECTOR ED820 IM REV 2 09.01.2017 7

SOUNDER AND BEACON CONNECTION The fault monitored sounder circuits can be used to operate several sounders and beacons, up to a maximum load of 1A. A 4K7 Ohm end of line resistor should be fitted across the last device to facilitate fault monitoring. SOUNDER OUTPUT VE VE SND 1 SND 2 SND 1 SND 2 4K7 EOL ED6 SOUNDER ED6 SOUNDER / BEACON COMBINATION ED6 BEACON IMPORTANT Never use looped wire always use separate conductors for input and outputs thus enabling fault monitoring. If Sounders and Beacons are not supplied by EDL, ensure they have a series polarity protection diode fitted. If not an external diode suitably rated should be used. Please contact EDL for further information. See diagram below. SOUNDER OR BEACON WITHOUT INTERNAL SERIES DIODE. VE SOUNDER OUTPUT DIODE E.G. 1N4005 4K7 EOL OR NEXT SOUNDER VE JUNCTION BOX / TERMINAL BLOCK ED820 FIRE DETECTOR ED820 IM REV 2 09.01.2017 8

OPERATION In general an audio alarm attracts attention and panel lamps indicate the type of alarm. It is important that personnel recognise the audible alarms so that correct, and prompt, action can be taken. Fire alarm sounds the internal buzzer continuously and a fault condition sounds the internal buzzer intermittently. In normal operation (quiescent state) only the Power lamp should be illuminated. If either the Main or Emergency power supply fails, or a fault signal is received from the power supply, a general fault will occur and the Power Supply fault will be illuminated. Note: The fault relay is wired active on. This could be used to provide an alarm out in the event of a complete power supply failure. FRONT PANEL KEY SWITCH The ED820 is fitted with a key switch, as required by EN542, intended to limit access to the following specific functions: 1. Zone / Sounder Disable. 2. Silence internal or external alarms (mute). 3. Reset. 4. Sound alarms. It is very important that the key, if removed, can be located quickly. In particular the sound alarms function maybe required urgently. Locating a call point (MCP) next to the control panel and connecting to a spare zone, one that will never need to be isolated, is good practice as it will allow the operation of the alarms in an emergency even if the key cannot be located. In order to comply with EN542 the control panel door must not be locked. ZONE & SOUNDER DISABLEMENT With the key switch set to the Key Enable position, any zone or sounder circuit can be disabled by pressing the Disable ON button or returned to the normal state by pressing the Disable OFF button. When a zone is disabled both faults and alarms, from that zone only, are ignored. When a sounder circuit is disabled all sounders and beacons, connected to that circuit only, are disabled and will not operate in the event of an alarm. The sounder circuits remain fault monitored, any open or short circuit faults detected will operate the general fault condition. If any zone or sounder circuits are disabled the appropriate Disable lamp and the General Disablement lamp will be illuminated. EXTERNAL AND INTERNAL SILENCE SOUNDERS BUTTONS With the key switch set to Key Enable, pressing the Internal Silence sounders button will silence the internal alarm / fault buzzers. Pressing the External Silence Sounders button will silence any external sounders and turn off any beacons connected to sounder circuits 1 or 2. The Jumper JMP1, fitted as standard, is located on the base printed circuit board and controls retriggering of external sounders and beacons. When fitted, each new alarm will reactivate the sounder circuits if previously silenced. If removed, once silenced new alarms will not activate the external sounder circuits until the system has been reset to the quiescent non alarm state. RESET BUTTON Pressing the Reset Button will return the panel to the normal condition, if any faults or alarms remain these will reactivate the appropriate lamps and output functions. INTRINSICALLY SAFE ZONES For use with Intrinsically Safe detectors the following guidelines must be followed: 1. Never mix Ex and non Ex rated devices on the same zone. 2. A suitable Zener or Galvanic Barrier must be used, e.g. The EDL dual channel Zener Barrier type ZBD7 ATEx certified [EEx ia IIC]. 3. Wiring must be in accordance with Hazardous Area regulations. 4. To setup a zone suitable for Intrinsically Safe detectors the appropriate jumper, located on the ED820 Base printed circuit board, must be moved from the NO jumper to the YES jumper: STANDARD DEVICES NO YES J MP 3 J MP 4 ZONE 1 EX DEVICES ED820 FIRE DETECTOR ED820 IM REV 2 09.01.2017 9

in service TESTING Tests should be carried out periodically to ensure that both fault and alarm circuits are functioning correctly. Detectors should be operated individually to ensure correct detector and zone operation. Fault circuits may be tested by open circuiting and short circuiting, in turn, each zone pair at the final detector base. The control unit should be observed during testing to ensure that all panel indicators operate correctly. Aerosols of synthetic smoke which can be purchased from EDL provide a clean and simple way of testing both ionisation and optical smoke detectors. Professional kits are available for testing heat detectors, however a domestic hair drier can be used provided it is able to reach the necessary temperature and if a mains supply is available. For testing flame detectors an expensive infrared or ultraviolet source is required, therefore it is advisable to contact a fire detection Service engineer with the necessary equipment. BASIC FAULT FINDING 20VDC (for 24V ED820) 10VDC (for 12V ED820) 470 Ohms RESISTOR Vz SMOKE DETECTOR CALL POINT 470 Ohm 470 Ohm 470 Ohm 4K7 Ohm EOL 0V HEAT DETECTOR CONTROL UNIT CONVENTIONAL FIRE DETECTION BASIC PRINCIPLES All of Electronic Devices conventional fire detection systems are designed with the same simple and robust method of detection. The diagram below shows the essential principle of a conventional fire detection system. The zone line completes a potential divider chain across a stabilised 20VDC supply. The internal 470 Ohm resistor mounted in the control unit is the top half of the divider and in normal operation the end of line (EOL) resistor, 4K7 Ohms, completes the potential divider so that Vz is at 18.2V. Any detector placed across the zone line will be electrically equivalent to a normally open switch with a series 470 Ohm resistor. If any of the detecting elements operates, the voltage Vz will drop to just below half of the 20V supply which initiates an alarm via the voltage monitoring and logic circuit inside the control unit. If the zone line goes open circuit, Vz becomes 20V and an open circuit fault is given. If the zone line goes short circuit, Vz becomes 0V and a short circuit fault is given. In practice, the effects of line resistance cannot be completely discounted but since the volt drops incurred are normally small, do not present the designer with a problem. ED820 FIRE DETECTOR ED820 IM REV 2 09.01.2017 10

OPEN CIRCUIT ZONE FAULT The control unit indicates a open circuit fault by illumination of a yellow LED and sounding of the internal buzzer. The most likely cause will be loose or open circuit field wiring on the zone in question. Depending upon the devices fitted an open circuit fault can also be caused by removal of a detector from its wiring base. The Engineer should measure, using a digital volt meter, the voltage across the zone terminals. The voltage should normally be approximately 18VDC. If this has increased to 20VDC this indicates correct operation of the control unit and that the fault lies in the field wiring. To narrow down the search for an open circuit on zone wiring measure the zone voltage at the detector at roughly the midpoint of the zone. If there is no voltage measured the fault lies between the midpoint and the control unit. If the voltage measured is 20V then the fault lies between the midpoint and the EOL. SHORT CIRCUIT ZONE FAULT The control unit indicates a short circuit fault by illumination of a yellow LED and sounding of the internal buzzer. The Engineer should measure, using a digital volt meter, the voltage across the zone terminals. The voltage should normally be approximately 18VDC. If this has dropped close to 0VDC this indicates correct operation of the control unit and gives a short circuit fault indication. First disconnect the Zone wiring from the terminals if the terminal voltage now rises to 20VDC then the fault lies in the field wiring, If the voltage remains low then the fault is within the control unit. To narrow down the search for a short circuit on zone wiring disconnect the wiring at roughly the midpoint of the zone and check if the short circuit is replaced with an open circuit. If yes, this indicates the short circuit is between here and the EOL. If no, this indicates it is between here and the control unit. COMMISSIONING 1. All connections, power supplies and peripheral devices should be checked and must conform to the requirements of this manual and the appropriate standards. 2. Ensure there are no earth faults by using a Megger or similar Insulation / resistance tester. 3. Ensure End of Line resistors (4K7 Ohm) are fitted as the last device on all zones and both sounder circuits. 4. In the normal quiescent state only the green Power lamp is illuminated. 5. Remove each detector in turn and ensure the appropriate fault lamp illuminates and the fault buzzer and relay operate. 6. Repeat 5, above, for both sounder circuits. 7. Test each detector alarms and the appropriate alarm lamps and sounders operate. 8. Test all other features as detailed on pages 9 and 10. ED820 FIRE DETECTOR ED820 IM REV 2 09.01.2017 11