Model D12. Digital Gas Transmitter

Similar documents
Toxic Gas Detection. Model F12. Toxic Gas Detection

Model D12-IR. Digital Gas Transmitter...

GasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

SIL 2. Ultima X Series Gas Monitors CERTIFIED

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

UniSens 2-Wire Gas Transmitter

UniSens. 2-Wire Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

Sieger Apex. Flexibility that meets your requirements

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

FREEDOM SERIES 5000 AND 5600 GAS TRANSMITTERS

Series D12 Toxic Gas Transmitter

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

Xgard. Fixed detectors For flammable, toxic or oxygen gases

GAS DETECTOR ST400EC PART.NO

OLC(T) 100 FIXED GAS DETECTOR

Two-Channel Gas Controller

Improve Performance and Reduce Maintenance Costs. Model Q45D. Dissolved Oxygen Monitor...

3M Oldham OLCT 100. Description. Fixed Gas Detector

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Certifications. The Fixed Gas Detection People

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Aluminium or Stainless Steel version

Model Q45P/R. ph/orp Monitor...

Satellite XT. Analogue or digital Point-of-Use gas detection transmitter to detect toxic, corrosive and combustible gases

Model Q45P/R. ph/orp Monitor...

MultiRAE Lite. Wireless Portable Multi-Gas Monitor

Industrial Grade Gas Detection Detecting The Difference

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety

Series F12 Toxic Gas Transmitter

OLCT 100 DETECTION DE GAZ FIXE. Certifications. Better detection. Better protection. Detection of Combustible, Toxic or Oxygen gases

GasSens. Hydrogen Peroxide Monitor. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

3years. Detection of explosive gases, toxic gases and oxygen. Infrared XP IR version. SIL 2 high reliability IP 66.

Toxic Smarter Transmitter Instruction Manual

EAGLE 2. 6 Channel Capacity. Inlet fitting. Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility

Satellite XT. Analog or digital Point-of-Use gas detection transmitter to detect toxic, corrosive and combustible gases

GAS PLUS ALARM SYSTEM

Frequently Asked Questions

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

Series F12/D Toxic Gas Transmitter

Electrochemical DrägerSensor Sensors for Fixed Gas Detectors

ALTAIR 5X Multigas Detector Product Specification

compact detector Detection of more than 200 flammable and toxic gases iso 9001:2008

FX-SMT Series INSTRUCTION MANUAL P/N THERMO ELECTRON CORPORATION ENVIRONMENTAL INSTRUMENTS 27 FORGE PARKWAY FRANKLIN MASSACHUSETTS 02038

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.

Monitores Personales. Personal Monitor

VASTHI ENGINEERS. Vasthi Multi Gas Monitor/Analyzer. Sheet No. 1 of 4. Vasthi Multi Gas monitor/analyzer with alarm and Graphical Display.

OLCT 700 & 710. Certifications FIXED GAS DETECTION. Better detection. Better protection.

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

The Art of Gas Detection

Warranty Registration

SP-220. Features. Combustible handheld gas leakage detector

Fixed Gas & Flame Detection International Product Range Overview

Equipment. Model R002. Description. SF6 leak detector

Carbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Stand Alone DYNAGARD SP Operation Manual

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

ESD3000 ESD200 Combustible / Toxic Gas Detector

Dependable Solutions for Gas Detection

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

RIG RAT III. Wireless Multi-Point Gas Detection System. The Stand-Alone Solution

MODEL: Q8 SERIES NON-INTRUSIVE CALIBRATION GAS TRANSMITTER/SENSOR

Micro III (Models G203, G203S, and G213) Operation Manual

Instructions TXL Series Oxygen and Toxic Gas Detectors 4/

Murco Core Product Guide Gas Leak Detection Solutions for all your building needs

incontrol Systems Inc. Flame and Gas Detection

MDA Scientific Midas. Gas monitoring system for fast and reliable detection of flammable and toxic gases used in industrial manufacturing processes

S5000 Gas Monitor. GMS5000.com

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

ULTIMA XIR ULTIMA X 3 ULTIMA XE. ULTIMA X Series. [ State-of-the-Art Gas Monitoring]

M2A Transmitter Operator s Manual

Midas. Gas monitoring system for fast and reliable detection of flammable and toxic gases used in industrial manufacturing processes

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

Honeywell EC-P2 EC-P2. Gas Detector CHARGE BATTERY WHEN NOT IN USE. Instruction Manual

G-TECTA TM. Portable Gas Detection Instruments

Carbon Monoxide Transmitter

Oxygen (O2) Single-Point Gas Detection System

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Quality. Water. Water Quality. Testing. Testing. Toxic Gas Detection. Toxic Gas. Detection. Air Quality. Monitoring. Monitoring. Monitoring.

MERIDIAN UNIVERSAL GAS DETECTOR

Dräger Polytron 8310 IR Detection of flammable gases and vapour

Single Gas Detector. Long-term solution H 2 S O 2 SO 2 NH 3 PH 3. Cl 2. ClO 2 NO 2 HCN ETO O 3

Series 3000 XPIS. 2-wire loop powered toxic and Oxygen gas detector for use in potentially explosive atmospheres

ULTIMA X5000. MSAX5000.com

M2 Transmitter Operator s Manual

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

FIXED POINT SINGLE OR DUAL GAS MONITOR WITH DUAL ANALOG OUTPUTS

Combustible Gas Detection and Control System

Dräger Polytron 8200 CAT Detection of flammable gases and vapors

MODEL 4300-PG CENTRAL ACCESS PANEL FOR EC-GOLD TRANSMITTERS. User Manual

APPLICATION DATA SHEET

ESD500. ESD500 Combustible / Toxic Gas Detector

Sensepoint. Fit For Purpose Flammable, toxic and oxygen versions available High performance, low cost Suitable for new and retro fit applications

Dräger Polytron 5200 CAT Detection of flammable gases and vapours

Dräger Polytron 5700 IR Detection of flammable gases and vapours

Micro IV. Single Gas Detector. Operations Manual Oak Valley Dr, Ste 20, Ann Arbor MI USA (800) (734)

Transcription:

Model D12 Digital Gas Transmitter

Gas detection systems come in all shapes and sizes. Some require simple 4-20 ma transmission. Some are better suited to local alarm relay functions. Some really require both. And increasingly, digital communication directly to the transmitter is desirable. Not to mention the fact that selftesting sensor capability adds to the reliability of any system. We couldn t come up with a catchy name that would convey all the capabilities of the D12, so we ll just explain everything our transmitter can provide starting with our four different configurations. Loop Powered Transmitter For measurement and data transmission to remote display and alarm equipment, the D12 will operate in 2-wire mode (except for combustible gas). Integral LCD indicates gas concentration as well as alarm conditions. Loop Powered with HART For plants operating with Hart protocol communications systems, the D12 can be supplied with this option. Our HART output supports both 4-20 ma and constantcurrent mode of operation. Transmitter with Integral Relays For systems requiring local alarm functions, or systems where discrete outputs are desired, the D12 can provide 3 relay outputs. Relays are assignable to any alarm setpoint or fault condition and are fully programmable for setpoint, hysteresis, and time delay. Transmitter with Modbus When RS-485 communication is desirable, D12 transmitters with alarm relays can be supplied with a Modbus(tm) interface. Software supports up to 247 unique addresses for large system use. D12 with Combustible Gas Sensor Typical Applications Chemical Processing Pulp & Paper R&D Labs Semiconductor Plants Refineries Pharmaceuticals Food Processing Aluminum Refining Breweries Metals Processing Water Treatment Wastewater Treatment Electric Utilities Agricultural Chemicals Plastics Manufacturing

Features For Every Application D12 transmitters provide useful features that simplify installation, operation, and maintenance. From clear menu-driven setup pages to large numerical display of gas values, you simply can t find a more versatile transmitter. LCD Graphics Display: Gas concentrations are displayed in large, easy to read numbers. The display also provides alarm indication and complete menus for setting up operating parameters. A backlight is available when operating in 3-wire mode. Internal Data Logger: Measured gas values are stored at user definable intervals and can be recalled when needed on the LCD display. Data can be downloaded using the MODBUS interface. Non-Intrusive Operation: Operating functions such as calibration, alarm setup, alarm reset, data view, and setup options are all available using a magnetic tool. It is not necessary to open the enclosure when making adjustments. Password Protection: Program settings stored in the transmitter may be protected by a user selectable 4-digit password. Operators may still review all functions, but changes may only be made by authorized personnel. Modular Electronics: The D12 electronic assembly plugs easily into the power supply board in the base of the enclosure. Transmitters can be removed for wiring and quickly replaced in the event of a fault condition. Explosion Proof Enclosure: Transmitters are designed for operation in hazardous areas. The cast aluminum housing for the D12 transmitter is rated for Class 1, Division 1, Group B, C, D locations and is UL, FM, and CSA certified. Scalable 4-20 ma: The output range for a particular sensor is programmable within the range boundaries set in that sensor. Three Internal Alarm Relays: Optional relay outputs can be used for local alarm functions. All relays are programmable for setpoint, hysteresis, on-delay, off-delay, and other variables. Even a remote reset feature is provided for in the transmitter design. Analog Output Simulation: Transmitter analog output can be set to user definable values. This provides for complete loop testing without the need to apply gas to the sensor. Relay Output Simulation: Alarm relays may be activated on command to allow testing of local alarm devices. Any combination of relays may be activated based on operator selection. Output and alarms may also be inhibited for maintenance and calibration. Serial Communication Interface: The transmitter is available with either HART or MODBUS protocol. The HART protocol supports the HART Universal and Common Practice Commands at 1200 baud using the Bell 202 FSK modem standard. The MODBUS protocol supports 9600 baud access to concentration and status information, and supports alarm setup and many other functions on either RS485 or RS232 (software selectable). Comes with a register/tag database on a 3-1/2" diskette

Available Gas List Symbol Gas Min. Range Max. Range Symbol Gas Min. Range Max. Range C 2 H 2 Acetylene * 0-50 PPM 0-500 PPM HX Acid Gases * 0-10 PPM 0-200 PPM C 2 H 6 O Alcohol 0-50 PPM 0-2000 PPM NH 3 Ammonia * 0-50 PPM 0-2000 PPM AsH 3 Arsine 0-500 PPB 0-200 PPM Br 2 Bromine * 0-1 PPM 0-200 PPM CO Carbon Monoxide * 0-50 PPM 0-1000 PPM Cl 2 Chlorine * 0-1 PPM 0-200 PPM ClO 2 Chlorine Dioxide * 0-1 PPM 0-200 PPM CH 4 Combustible Gas * 0-50% LEL 0-100% LEL B 2 H 6 Diborane 0-500 PPB 0-200 PPM C 2 H 4 O Ethylene Oxide * 0-20 PPM 0-200 PPM F 2 Fluorine * 0-1 PPM 0-200 PPM HCHO Formaldehyde * 0-20 PPM 0-200 PPM GeH 4 Germane 0-500 PPB 0-200 PPM H 2 Hydrogen 0-500 PPM 0-10% HCl Hydrogen Chloride * 0-10 PPM 0-200 PPM HCN Hydrogen Cyanide * 0-10 PPM 0-200 PPM HF Hydrogen Fluoride * 0-10 PPM 0-200 PPM H 2 O 2 Hydrogen Peroxide * 0-10 PPM 0-1000 PPM H 2 Se Hydrogen Selenide 0-500 PPB 0-200 PPM H 2 S Hydrogen Sulfide * 0-10 PPM 0-200 PPM I 2 Iodine * 0-1 PPM 0-200 PPM NO Nitric Oxide 0-50 PPM 0-200 PPM NO 2 Nitrogen Dioxide * 0-10 PPM 0-200 PPM O 2 Oxygen 0-5% 0-25% O 3 Ozone * 0-1 PPM 0-200 PPM COCl 2 Phosgene 0-1 PPM 0-100 PPM PH 3 Phosphine 0-500 PPB 0-200 PPM SiH 4 Silane 0-10 PPM 0-200 PPM SO 2 Sulfur Dioxide * 0-10 PPM 0-200 PPM * Auto-Test gas generator available Specifications Gas Type: Sensor Type: Range: Response Time: Accuracy: Repeatability: Linearity: Zero Drift: Span Drift: Alarms: Customer selected from available sensor list. Electrochemical for toxic gases and oxygen. Catalytic bead for combustible gas User adjustable within limits of selected sensor. Sensor dependent Generally ±10% of value (limited by available calibration gas) ±1% (Electronic) ±0.5% (Electronic) Less than 2% full scale per month, non-cumulative Dependent on environment but generally less than 3% per month Three concentrations alarms (Caution, Warning, Alarm) programmable for setpoint, hysteresis, alarm delay, and manual or automatic reset. One fault alarm with programmable output and relay response. Analog Output: Loop-powered 4-20 ma, 675 ohms maximum at 24 VDC Serial Interface: HART (1200 baud modem interface ) MODBUS (1200-9600 RS232 or RS485, software selectable) Power: 12-30 VDC, 25 ma maximum in loop-powered mode 12 30 VDC, 200 ma maximum in 3-wire mode. Alarm Relays: Three SPDT, 5 A @ 230 VAC resistive Relay Coil: Programmable either normally energized or normally deenergized. Enclosure: Explosion-proof, Class 1, Div. 1, Groups B, C, & D. Sensor Auto-Test: Optional gas generator dependent on sensor. Controls: 4 magnetic switches on front of transmitter Operating Temp.: -30º to +60º C for toxics (-10º C minimum for O 2 sensor) -40º to +70º C for combustibles Weight: 4 Lbs (1.8 Kg.)

Sensor Flexibility No matter which style of transmitter you choose, your D12 transmitters come with features that enhance performance and provide operational flexibility, starting with our own advanced electrochemical sensors. Interchangeable Sensors: Every toxic gas transmitter will accept up to 46 different sensors, greatly reducing the need for multiple transmitter models. The self-aligning sensor holder simply plugs in, with automatic sensor recognition and verification when contact is made. Plug-In Sensor Smart Sensors: Plug-in sensors store calibration data, allowing sensors to be calibrated separately from the transmitter. This allows bench calibration (or factory calibration) of sensors to reduce the necessity for carrying calibration gas around the plant. Sensors are even interchangeable with ATI's C16 portable gas leak detector. Calibration History: Each time a sensor is zeroed or calibrated, the data is stored in sensor memory. Calibration history can be recalled and sensor condition reviewed by operating personnel whenever necessary. Sensor Response Verification Self-aligning Sensor/Generator Holder For many toxic and combustible gases, ATI offers a unique sensor response testing system unmatched by any competitive transmitter. Even outdoors in high wind conditions, the Auto-Test system provides reliable response checks to insure system integrity. Electrochemical Gas Generator: Sensor response is verified with an actual gas sample, generated on demand. Electronic sensor and circuit tests just can't provide the same level of confidence. Plug-in Smart Generator: Auto-Test gas generators are easily installed and removed when necessary. Generators store run time information accessible to operators, and are automatically tested for compatibility with the installed sensor. Auto-Test Log: Systems using Auto-Test generators store a testing log indicating the number of tests performed as well as test results. This data is stored in individual sensor memory for later review. Auto-Test Generator

Order Information: Model D12-E-F-G For transmitters to be used with electrochemical sensors, sensors must be selected separately from the list shown below. Note that the sensor part number will vary in some cases depending on the range of operation. If an Auto-Test generator is to be used, this item must also be specified separately. Combustible gas sensors are part of the sensor holder specified under Suffix F Suffix E Transmitter Type 1 Electrochemical without alarms 2 Electrochemical with alarms 3 Combustible gas without alarms 4 Combustible gas with alarms Suffix F Sensor Holder Style 1 Integral holder for sensor and generator 2 Remote Sensor System for toxic sensors 3 Integral combustible gas sensor 4 Integral combustible sensor with generator 5 Remote Sensor System for combustible gas sensor 6 Remote Sensor System for combustible sensor with generator Suffix G Digital Output 1 None 2 MODBUS interface (requires alarm option in Suffix E) 3 HART interface Accessories 00-1056 Calibration adapter 00-1251 Flowcell assembly 00-0981 Sensing module keeper for 4 sensors Auto-Test Generator 00-1239 C18-11 Chlorine gas generator 00-1240 C18-15 Ammonia gas generator 00-1241 C18-16 Carbon Monoxide gas generator 00-1243 C18-24 Hydrogen Sulfide gas generator 00-1244 C18-27 Sulfur Dioxide gas generator Toxic Gas Sensors Part No. Gas & Range 00-1000 Bromine, 0-1/5 PPM (2 PPM Standard) 00-1001 Bromine, 0-5/200 (20 PPM Standard) 00-1002 Chlorine, 0-1/5 PPM (2 PPM Standard) 00-1003 Chlorine, 0-5/200 (20 PPM Standard) 00-1004 Chlorine Dioxide, 0-1/5 PPM (2 PPM Standard) 00-1005 Chlorine Dioxide, 0-5/200 (20 PPM Standard) 00-1006 Fluorine, 0-1/5 PPM (2 PPM Standard) 00-1007 Fluorine, 0-5/200 (20 PPM Standard) 00-1008 Ozone, 0-1/5 PPM (2 PPM Standard) 00-1009 Ozone, 0-5/200 PPM (20 PPM Standard) 00-1010 Ammonia, 0-50/500 PPM (200 PPM Standard) 00-1011 Ammonia, 0-500/2000 PPM (1000 PPM Standard) 00-1012 Carbon Monoxide, 0-50/1000 PPM (200 PPM Standard) 00-1013 Hydrogen, 0-1/10% (4% Standard) 00-1014 Oxygen, 0-5/25% (25% Standard) 00-1015 Phosgene, 0-1/5 PPM (2 PPM Standard) 00-1016 Phosgene, 0-5/100 PPM (100 PPM Standard) 00-1017 Hydrogen Chloride, 0-10/200 PPM (20 PPM Standard) 00-1018 Hydrogen Cyanide, 0-10/200 PPM (20 PPM Standard) 00-1019 Hydrogen Fluoride, 0-10/200 PPM (20 PPM Standard) 00-1020 Hydrogen Sulfide, 0-10/200 PPM (50 PPM Standard) 00-1021 Nitric Oxide, 0-50/500 PPM (200 PPM Standard) 00-1022 Nitrogen Dioxide, 0-10/200 PPM (20 PPM Standard) 00-1023 Sulfur Dioxide, 0-10/500 PPM (20 PPM Standard) 00-1024 Arsine, 0-500/2000 PPB (1000 PPB Standard) 00-1025 Arsine, 0-10/200 PPM (10 PPM Standard) 00-1026 Diborane, 0-500/2000 PPB (1000 PPB Standard) 00-1027 Diborane, 0-10/200 PPM (10 PPM Standard) 00-1028 Germane, 0-500/2000 PPB (1000 PPB Standard) 00-1029 Germane, 0-10/200 PPM (10 PPM Standard) 00-1030 Hydrogen Selenide, 0-500/2000 PPB (1000 PPB Standard) 00-1031 Hydrogen Selenide, 0-10/200 PPM (10 PPM Standard) 00-1032 Phosphine, 0-500/2000 PPB (1000 PPB Standard) 00-1033 Phosphine, 0-10/200 PPM (10 PPM Standard) 00-1034 Phosphine, 0-200/2000 PPM (1000 PPM Standard) 00-1035 Silane, 0-10/200 PPM (10 PPM Standard) 00-1036 Iodine, 0-1/5 PPM (2 PPM Standard) 00-1037 Iodine, 0-5/200 PPM (20 PPM Standard) 00-1038 Acid Gases, 0-10/200 PPM (20 PPM Standard) 00-1039 Ethylene Oxide, 0-20/200 PPM (20 PPM Standard) 00-1040 Formaldehyde, 0-20/200 PPM (20 PPM Standard) 00-1041 Hydrogen, 0-500/2000 PPM (2000 PPM Standard) 00-1042 Hydrogen Peroxide, 0-10/100 PPM (20 PPM Standard) 00-1043 Alcohol, 0-50/500 PPM (200 PPM Standard) 00-1044 Alcohol, 0-500/2000 PPM (2000 PPM Standard) 00-1057 Acetylene, 0-500/2000 PPM (0-500 PPM Standard) Represented By: Analytical Technology, Inc. 6 Iron Bridge Drive Collegeville, PA 19426 Phone: 610/917-0991 Toll-Free: 800/959-0299 Fax: 610/917-0992 E-Mail: sales@analyticaltechnology.com Web: www.analyticaltechnology.com ATI (UK) Limited Bank Chambers, 33 Stamford Street Mossley, Aston-u-Lyne OL5 0LL Phone: +44 (0) 1457 832800 Fax: +44 (0) 1457 83950 E-Mail: sales@atiuk.com

Model D12 Toxic Gas Transmitter - Enclosure Dimensions ENCLOSURE DIMENSIONS D12 GAS TRANSMITTER NOTES: 1) Enclosure Matl: Sand Cast copper-free aluminum O-Brien yellow in color. Cover: Sand Cast copper-free aluminum O-Brien yellow in color, with 3-5/16" dia. tempered glass window. 2) Certifications: FM standard 3615 CSA standard C22.2 No.30 UL Standard 1203 KEMA CENELAC standard EN50014, 50018 3) Ratings: UL Class I, Groups B,C,D Class II, Groups E,F,G CENELAC: EExd IIC, IP66 Nema 4X, 78CD, 9EFG ATI-0532 SS-D12, RE (10/04) Page 1 of 9

Model D12 Toxic Gas Transmitter - Sensor Dimensions INSERTION SENSOR DIMENSIONS ATI-0669 PIPE ADAPTER DIMENSIONS ATI-0670 SS-D12, RE (10/04) Page 2 of 9

Model D12 Toxic Gas Transmitter - Wiring Diagrams POWER SUPPLY PCB GENERAL LAYOUT ATI-0526 2-WIRE LOOP POWER WIRING ATI-0527 SS-D12, RE (10/04) Page 3 of 9

Model D12 Toxic Gas Transmitter - Wiring Diagrams 3-WIRE WIRING DIAGRAM ATI-0528 SEPARATE POWER & ANALOG LOOP SUPPLIES ATI-0529 SS-D12, RE (10/04) Page 4 of 9

Model D12 Toxic Gas Transmitter - Wiring Diagrams POWER OPERATION w/o ANALOG OUTPUT ATI-0530 SS-D12, RE (10/04) Page 5 of 9

Model D12 Toxic Gas Transmitter - Enclosure Dimensions REMOTE SENSOR DIMENSIONAL DRAWING ENCLOSURE RATINGS: CLASS I, GROUPS B,C,D CLASS II, GROUPS E,F,G CLASS III Assembly is normally mounted directly to suitable explosion-proof conduit. To maintain the explosion-proof integrity of the transmitter, a suitable cable entry seal must be used in accordance with the applicable electrical code. SS-D12, RE (10/04) Page 6 of 9

Model D12 Toxic Gas Transmitter - Wiring Diagrams REMOTE SENSOR WIRING DIAGRAMS SS-D12, RE (10/04) Page 7 of 9

Model D12 Toxic Gas Transmitter - Dimensionals INSERTION PROBE - OPERATING MODE ATI-0663 INSERTION PROBE - CALIBRATING MODE ATI-0664 SS-D12, RE (10/04) Page 8 of 9

Model D12 Toxic Gas Transmitter - Wiring Diagrams INSERTION PROBE - WIRING DIAGRAM ATI-0665 SS-D12, RE (10/04) Page 9 of 9

Model D12-17 Combustible Gas Transmitter - System Dimensions SENSOR/TRANSMITTER D12 GAS TRANSMITTER Enclosure Matl: Sand Cast Copper-Free Aluminum O-Brien yellow in color. Cover: Sand Cast copper-free aluminum O-Brien yellow in color, with 3-5/16" dia. tempered glass window. Certifications: FM standard 3615 CSA standard C22.2 No.30 UL standard 1203 KEMA CENELAC standard EN50014, 50018 Ratings: UL Class I, Groups B,C,D Class II, Groups E,F,G CENELAC: EExd IIC, IP66 Nema 4X, 78CD, 9EFG SENSOR/TRANSMITTER WITH AUTO-TEST D12 GAS TRANSMITTER SS-D1217-RA.PMD, DATE: 2/3/06, DRAWN: KJN, APPD: Page 1 of 6

Model D12-17 Combustible Gas Transmitter - Typical System Diagram and Installation JUNCTION BOX NOTES 1) Enclosure Ratings: CLASS I, Groups B, C & D CLASS II, Groups E, F & G CLASS III 2) Assembly is normally mounted diectly to suitable explosion-proof conduit. 3) When transmitter is used in classified areas, an x-proof seal should be used as required by electrical code. Any connection made must be watertight. - WARNING- Failure to seal the conduit entries will result in water entering the enclosure causing damage or failure to the transmitter electronics. ATI-046 JUNCTION BOX w/ AUTO-TEST ATI-0396 SS-D1217-RA, (2/06) Page 2 of 6

Model D12-17 Combustible Gas Transmitter - Electrical Installation DUAL CONDULET INSTALLATION D12 GAS TRANSMITTER SS-D1217-RA, (2/06) Page 3 of 6

Model D12-17 Combustible Gas Transmitter - Electrical Installation without Auto-Test STANDARD SYSTEM D12 GAS TRANSMITTER ATI-0282 STANDARD SYSTEM WITH JUNCTION BOX D12 GAS TRANSMITTER ATI-0283 SS-D1217-RA, (2/06) Page 4 of 6

Model D12-17 Combustible Gas Transmitter - Electrical Installation with Auto-Test POWER SUPPLY PCB GENERAL LAYOUT ATI-0526 3-WIRE WIRING DIAGRAM ATI-0528 SS-D1217-RA, (2/06) Page 5 of 6

Model D12-17 Combustible Gas Transmitter - SEPARATE POWER & ANALOG LOOP SUPPLIES ATI-0529 POWER OPERATION w/o ANALOG OUTPUT ATI-0530 SS-D1217-RA, (2/06) Page 6 of 6