AIR CONDITIONING SYSTEMS MODEL CMH-WM-V-A

Similar documents
PURY-M YNW-A (-BS) PURY-EM YNW-A (-BS)

AIR CONDITIONERS MODELS PQHY-P650YSHM-A PQHY-P700YSHM-A PQHY-P750YSHM-A PQHY-P800YSHM-A PQHY-P850YSHM-A PQHY-P900YSHM-A DATA BOOK

Mitsubishi Electric's

PMFY-P-VBM-E. Ceiling cassette (1-way flow type) R410A Data G8 1. SPECIFICATIONS EXTERNAL DIMENSIONS CENTER OF GRAVITY 1-100

PUHY-P-Y(S)JM-A PFAV-P-VM-E(-F)

Digital Inverter 4 series 8 & 10HP

AIR CONDITIONERS DATA BOOK. Model PUHY-P250YHM-A PFD-P250VM-E PFD-P500VM-E

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

PUHY-P250YJM-A PUHY-P500YSJM-A PQHY-P250YHM-A PFD-P250VM-E PFD-P500VM-E

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.

PUHY-P250YHM-A PUHY-P500YSHM-A PQHY-P250YHM-A PFD-P250VM-E PFD-P500VM-E

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2

Series PEAD SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS R32/R410A PEAD-SM100JA(L) PEAD-SM125JA(L) PEAD-SM140JA(L) Models PEAD-SM71JA(L)

SUBMITTAL DATA: PEAD-A42AA7 & PUZ-A42NKA7(-BS) 42,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A42NKA7

SUBMITTAL DATA: PVA-A36AA7 & PUZ-HA36NHA5 36,000 BTU/H AIR HANDLER HEAT PUMP SYSTEM. Job Name: System Reference:

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

1. INDOOR UNITS... MSZ-FH-3 2. OUTDOOR UNITS... MSZ-FH-4 3. SYSTEM... MSZ-FH-5

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

Engineering Data Book

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SUBMITTAL DATA: PVA-A42AA7 & PUZ-A42NKA7(-BS) 42,000 BTU/H AIR HANDLER HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A42NKA7

Air to Air Heat Exchanger

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

Engineering Data Book

TECHNICAL & SERVICE MANUAL

4-Way Cassette type. Contents MMU-AP 2H2UL

Installation Manual PMV Kit RBM-PMV0363E RBM-PMV0903E

Engineering Data Book

SUBMITTAL DATA: PVA-A36AA7 & PUY-A36NKA7(-BS) 36,000 BTU/H AIR HANDLER AIR-CONDITIONING SYSTEM. Job Name: System Reference: Outdoor Unit: PUY-A36NKA7

PUHZ-SHW140YHA PUHZ-SHW230YKA

SUBMITTAL DATA: PEAD-A30AA7 & PUZ-A30NHA7(-BS) 30,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A30NHA7

SUBMITTAL DATA: PEAD-A24AA7 & PUY-A24NHA7(-BS) 24,000 BTU/H HORIZONTAL-DUCTED AIR-CONDITIONING SYSTEM. Job Name: System Reference:

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

SUBMITTAL DATA: PEAD-A12AA7 & PUZ-A12NKA7(-BS) 12,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A12NKA7

TABLE OF CONTENTS RMXS-E8V1B

DESIGN & TECHNICAL MANUAL

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

Ceiling type. Contents MMC-AP 1H2UL MMC-AP0181H2UL MMC-AP0361H2UL MMC-AP0421H2UL

DESIGN & TECHNICAL MANUAL

250mm dia straight pipe length SP4 SP3. Air volume

Engineering Data Book

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

Compact 4-way Cassette ( ) Type

TECHNICAL MANUAL. PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) MULTI-TYPE (V-MULTI) PACKAGED AIR-CONDITIONER

MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service manual MSZ-EF VE Series (OBH589)

TECHNICAL & SERVICE MANUAL

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

technical data air conditioning systems Indoor Units FCQ-C8VEB

PURY-P200YMF-C, PURY-P250YMF-C CONTENTS

Installation Instructions

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

EHS. EHS (Mono, LT, 50Hz)

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

Engineering Data Book

Alpha Aire. Dedicated Outdoor Air System, VAV, Air-Source Heat Pump with Energy Recovery. Engineering Guide Effective February 2018

SUBMITTAL DATA: PCA-A24KA7 & PUZ-A24NHA7(-BS) 24,000 BTU/H CEILING-SUSPENDED HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A24NHA7

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

DESIGN & TECHNICAL MANUAL

SEZ-KD25VAQ.TH SEZ-KD35VAQ.TH SEZ-KD50VAQ.TH SEZ-KD60VAQ.TH SEZ-KD71VAQ.TH

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

Installation Instructions

OA Processing unit GUF-RD4, GUF-RDH4

GHP OUTDOOR UNIT INSTALLATION INSTRUCTIONS E1 Combination Multi Type

SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE

Ventilation. Technical Data. Outdoor air processing unit, ventilation and air processing EEDEN FXMQ-MF

PEFY-P20VMS-E, PEFY-P40VMS-E PEFY-P25VMS-E, PEFY-P50VMS-E PEFY-P32VMS-E, PEFY-P63VMS-E

INSTALLATION INSTRUCTIONS

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-SP100JA(L) PEAD-SP125JA(L) PEAD-SP140JA(L) Models PEAD-SP71JA(L) <indoor unit>

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

technical data air conditioning systems Indoor Units FBQ-C7VEB

11. WALL MOUNTED TYPE PACKAGED AIR CONDITIONER Split system, Air cooled cooling only type

Concealed ceiling unit with medium ESP

EHH SERIES DRAW THROUGH FAN COILS CFM

GUG-01SL-E GUG-02SL-E GUG-03SL-E

SERVICE MANUAL AIR CONDITIONER SPLIT TYPE

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit

Air Conditioners. Technical Data FBQ-C

TECHNICAL & SERVICE MANUAL

PACKAGE AIR CONDITIONER

M-SERIES SUBMITTAL DATA: SEZ-KD15NA4** & SUZ-KA15NA. Job Name: Location: Date: Submitted to: For Reference Approval Construction

TECHNICAL & SERVICE MANUAL

INSTALLATION MANUAL. BP (Branch Provider) Unit. Models BPMKS967A2B BPMKS967A3B BPMKS967B2B BPMKS967B3B. Installation manual BP (Branch Provider) Unit

AIR CONDITIONER (MULTI TYPE) Installation Manual. Indoor Unit. Model name:

GUF-100RDH3. Model name The picture is shown GUF-50RDH3. Notice: The term of validity is for a year from the issued date.

FULL AUTOMATIC EXTINGUISHING SYSTEM FOR INDUSTRIAL MACHINERY YAC-3A. Table of Contents

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

Air Conditioner CONTENTS

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

technical data air conditioning systems FDKS-CVMB Concealed ceiling, Inverter Controlled Unit Split Sky Air

DESIGN & TECHNICAL MANUAL

TECHNICAL & SERVICE MANUAL

SERVICE MANUAL R410A PUHZ-SP100VHA.UK PUHZ-SP125VHA.UK PUHZ-SP125VHA PUHZ-SP140VHA.UK PUHZ-SP140VHA PUHZ-SP100YHA.UK PUHZ-SP100YHA PUHZ-SP125YHA.

SERVICE MANUAL MXZ-2A40VA - MXZ-2A52VA - MXZ-3A54VA - MXZ-3A54VA - MXZ-4A71VA - MXZ-4A71VA - MXZ-4A80VA - E1 OUTDOOR UNIT. No. OB377 REVISED EDITION-A

Transcription:

AIR CONDITIONING SYSTEMS MODEL CMH-WM-V-A

CONTENTS CMH-WM-V-A 1. SPECIFICATIONS... 2 2. EXTERNAL DIMENSIONS... 5 3. CENTER OF GRAVITY... 7 4. ELECTRICAL WIRING DIAGRAMS... 8 5. SOUND LEVELS... 9 5-1. Sound levels... 9 5-2. NC curves... 9 6. ELECTRICAL CHARACTERISTICS... 10 7. INSTALLATION... 11 7-1. Lifting method... 11 8. OPTIONAL PARTS... 12 8-1. Drain pan... 12 I. 1

1. SPECIFICATIONS I.Hydro 1. SPECIFICATIONS unit Model name Power source CMH-WM250V-A 1-phase 220-230-240 V 50 Hz 60 Hz Power input Cooling kw 0.74/0.74/0.74 0.74/0.74/0.74 (220/230/240) Heating kw 0.74/0.74/0.74 0.74/0.74/0.74 Current input Cooling A 3.84/3.67/3.52 3.84/3.67/3.52 (220/230/240) Heating A 3.84/3.67/3.52 3.84/3.67/3.52 Sound pressure level (measu in anechoice room) db <A> 60 Applicable temperature range of installation site C (D.B.) -5~52 External finish Pre-coated galvanized steel sheets (Lower part drain pan: Pre-coated galvanized sheets + powder coating) Connectable outdoor/heat source unit capacity (E)M200~250 External dimension H x W x D mm 660 x 920 x 740 in. 25-63/64 x 36-7/32 x 29-9/64 Refrigerant piping diameter To outdoor/heat source unit Connectable outdoor/heat source unit capacity M200 M250 EM200 EM250 Water piping diameter Liquid pipe mm (in.) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) O.D. Brazed Brazed Brazed Brazed Gas pipe mm (in.) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8) O.D. Brazed Brazed Brazed Brazed To Indoor unit Inlet Pipe mm (in.) I.D. 40 (1-1/2) housing joint Outlet Pipe mm (in.) I.D. 40 (1-1/2) housing joint Net weight kg (lbs) 112 (247) [119 (263) with water] Standard Document attachment Accessories Y-type strainer, Auto air vent valve, Joint, Elbow, Pipe Optional parts Note Drain pan (PAC-SH01DP-E) 1.Works not included: Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications. 2.The equipment is for R32 refrigerant. 3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background noise, position the at least 5 m away from any indoor units.) 4.Please install the in a place where noise will not be an issue. 5.Please attach an expansion vessel (field supply). 6.Use copper, plastic, steel, or stainless steel pipes for the water circuit. Furthermore, when using copper pipe-work use a non-oxidative brazing method. Oxidation of the pipe-work will uce the pump life. 7.When brazing the pipes, be sure to braze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat. 8.Please install an air purge valve where air will gather in the water circuit. 9.Please install a pressure ucing valve and a strainer on the water supply to the. 10.Please refer to the databook or the installation manual for the specified water quality. 11.Please always make water circulate or pull out the circulation water completely when not using it. *Please do not use it as a drinking water. 12.Please do not use ground water and well water. 13.When installing the in an environment which may drop below 0 C, please add antifreeze to the circulating water. (Refer to the data-book and the installation manual). 14.R32 is flammable, and certain restrictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions. 15.Drain or condensation water will be discharged from hydro units during test run. If this will be a problem, install a separately sold drain pan. 16.Do not install the unit where it could be salt-damaged. 2

1. SPECIFICATIONS Model name Power source CMH-WM350V-A 1-phase 220-230-240 V 50 Hz 60 Hz Power input Cooling kw 0.90/0.90/0.90 0.90/0.90/0.90 (220/230/240) Heating kw 0.90/0.90/0.90 0.90/0.90/0.90 Current input Cooling A 4.69/4.48/4.30 4.69/4.48/4.30 (220/230/240) Heating A 4.69/4.48/4.30 4.69/4.48/4.30 Sound pressure level (measu in anechoice room) db <A> 60 Applicable temperature range of installation site C (D.B.) -5~52 External finish Pre-coated galvanized steel sheets (Lower part drain pan: Pre-coated galvanized sheets + powder coating) Connectable outdoor/heat source unit capacity (E)M300~350 External dimension H x W x D mm 660 x 920 x 740 in. 25-63/64 x 36-7/32 x 29-9/64 Refrigerant piping diameter To outdoor/heat source unit Connectable outdoor/heat source unit capacity M300 M350 EM300 EM350 Water piping diameter Liquid pipe mm (in.) 9.52 (3/8) 12.7 (1/2) 9.52 (3/8) 12.7 (1/2) O.D. Brazed Brazed Brazed Brazed Gas pipe mm (in.) 22.2 (7/8) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8) O.D. Brazed Brazed Brazed Brazed To Indoor unit Inlet Pipe mm (in.) I.D. 40 (1-1/2) housing joint Outlet Pipe mm (in.) I.D. 40 (1-1/2) housing joint Net weight kg (lbs) 122 (269) [126 (278) with water] Standard Document attachment Accessories Y-type strainer, Auto air vent valve, Joint, Elbow, Pipe Optional parts Note Drain pan (PAC-SH01DP-E) 1.Works not included: Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications. 2.The equipment is for R32 refrigerant. 3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background noise, position the at least 5 m away from any indoor units.) 4.Please install the in a place where noise will not be an issue. 5.Please attach an expansion vessel (field supply). 6.Use copper, plastic, steel, or stainless steel pipes for the water circuit. Furthermore, when using copper pipe-work use a non-oxidative brazing method. Oxidation of the pipe-work will uce the pump life. 7.When brazing the pipes, be sure to braze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat. 8.Please install an air purge valve where air will gather in the water circuit. 9.Please install a pressure ucing valve and a strainer on the water supply to the. 10.Please refer to the databook or the installation manual for the specified water quality. 11.Please always make water circulate or pull out the circulation water completely when not using it. *Please do not use it as a drinking water. 12.Please do not use ground water and well water. 13.When installing the in an environment which may drop below 0 C, please add antifreeze to the circulating water. (Refer to the data-book and the installation manual). 14.R32 is flammable, and certain restrictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions. 15.Drain or condensation water will be discharged from hydro units during test run. If this will be a problem, install a separately sold drain pan. 16.Do not install the unit where it could be salt-damaged. 3

1. SPECIFICATIONS Model name Power source CMH-WM500V-A 1-phase 220-230-240 V 50 Hz 60 Hz Power input Cooling kw 1.06/1.06/1.06 1.06/1.06/1.06 (220/230/240) Heating kw 1.06/1.06/1.06 1.06/1.06/1.06 Current input Cooling A 5.47/5.23/5.02 5.47/5.23/5.02 (220/230/240) Heating A 5.47/5.23/5.02 5.47/5.23/5.02 Sound pressure level (measu in anechoice room) db <A> 60 Applicable temperature range of installation site C (D.B.) -5~52 External finish Pre-coated galvanized steel sheets (Lower part drain pan: Pre-coated galvanized sheets + powder coating) Connectable outdoor/heat source unit capacity (E)M400~500 External dimension H x W x D mm 660 x 920 x 740 in. 25-63/64 x 36-7/32 x 29-9/64 Refrigerant piping diameter To outdoor/heat source unit Connectable outdoor/heat source unit capacity M400 M450/500 EM400 EM450/500 Water piping diameter Liquid pipe mm (in.) 12.7 (1/2) 15.88 (5/8) 12.7 (1/2) 15.88 (5/8) O.D. Brazed Brazed Brazed Brazed Gas pipe mm (in.) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8) O.D. Brazed Brazed Brazed Brazed To Indoor unit Inlet Pipe mm (in.) I.D. 50 (2) housing joint Outlet Pipe mm (in.) I.D. 50 (2) housing joint Net weight kg (lbs) 143 (316) [157 (347) with water] Standard Document attachment Accessories Y-type strainer, Auto air vent valve, Joint, Elbow, Pipe Optional parts Note Drain pan (PAC-SH01DP-E) 1.Works not included: Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications. 2.The equipment is for R32 refrigerant. 3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background noise, position the at least 5 m away from any indoor units.) 4.Please install the in a place where noise will not be an issue. 5.Please attach an expansion vessel (field supply). 6.Use copper, plastic, steel, or stainless steel pipes for the water circuit. Furthermore, when using copper pipe-work use a non-oxidative brazing method. Oxidation of the pipe-work will uce the pump life. 7.When brazing the pipes, be sure to braze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat. 8.Please install an air purge valve where air will gather in the water circuit. 9.Please install a pressure ucing valve and a strainer on the water supply to the. 10.Please refer to the databook or the installation manual for the specified water quality. 11.Please always make water circulate or pull out the circulation water completely when not using it. *Please do not use it as a drinking water. 12.Please do not use ground water and well water. 13.When installing the in an environment which may drop below 0 C, please add antifreeze to the circulating water. (Refer to the data-book and the installation manual). 14.R32 is flammable, and certain restrictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions. 15.Drain or condensation water will be discharged from hydro units during test run. If this will be a problem, install a separately sold drain pan. 16.Do not install the unit where it could be salt-damaged. 4

2. EXTERNAL DIMENSIONS 2. EXTERNAL DIMENSIONS CMH-WM250, 350, 500V-A Unit: mm <Accessories> Y-type strainer(rc1-1/4) WM250,350 1pc. Y-type strainer(rc1-1/2) WM500 1pc. Joint(From Rc1-1/4 to 1-1/2inch housing joint) WM250,350 1pc. Joint(From Rc1-1/2 to 2inch housing joint) WM500 1pc. Elbow(IDø25.4 ODø25.4) WM350,500 1pc. Pipe (IDø25.4 ODø28.6) WM350,500 1pc. Auto air vent valve(g3/8) 1pc. Note 1.Please refer to the next page for information regarding necessary foundation work. 2.Take notice of service space as follows. (Please give attention not to occupy service space by letting ducts and pipes through.) 3.At brazing of pipes, wrap the pipe with wet cloth and keep the temperature of pipe under 120 C. 4.If dew condensation water dropping from holes on the unit base is concerned, please install the drain pan. 5.Install this product in a location where noise emitted by the unit will not disturb the neighbors. 155 192 230 102 148 290 105 150 83 92 NO. 94 100 120 175 681(678~684) 29.5 (Mounting pitch) (740) 215 50 96 84 345 150 300 1 2 3 4 5 6 7 8 29.5 160 170 223 190 400 310 518 740 135 217 920 A 35 Detail of X section 450 450 660 2 4 3 1 Refrigerant pipe <Liquid> 7 8 Top view Front view 5 6 Control box Refrigerant pipe <Gas> Refrigerant pipe <Liquid> Refrigerant pipe <Gas> Sling hole Y-type strainer(accessory) Service panel Joint(Accessory) 2 2-14 20 Oval hole Water pipe(exp.vessel) ø22.0(use attachment pipe) [field supply] Water pipe(inlet) ø22.0(use attachment pipe) [field supply] X Right Side view Rear view Model WM250 WM350 WM500 A 256 281 Water outlet WM250,350:1-1/2inch housing joint WM500:2inch housing joint Service panel Water inlet WM250,350:1-1/2inch housing joint WM500:2inch housing joint Connecting pipe specifications Diameter Model Refrigerant pipe Liquid Gas WM250 ø9.52 Brazed ø22.2 Brazed WM350 ø12.7 Brazed ø25.4 Brazed WM500 ø15.88 Brazed (ø28.6 Brazed) *1 *1 Using difference diameter pipe joint. *2 Connect the refrigerant pipe according to the Installation Manual. *3 Indicates dimensions and connection specifications in the case the unit is used in combination with other outdoor units. For pipes For wires For transmission cables Service space Service space Usage Specifications Front through hole 148 84 Knockout hole Bottom through hole 150 94 Knockout hole Front through hole Front through hole Bottom through hole Bottom through hole Front through hole Bottom through hole Cutting point ø28 Knockout hole ø28 Knockout hole ø28 Knockout hole ø28 Knockout hole ø35 Knockout hole ø35 Knockout hole 80 760 80 (Mounting pitch) Bottom view THE SPECIFICATION OF THE PRODUCT IS FOR THE IMPROVEMENT A PREVIOUS NOTICE AND MIGHT CHANGE. 5

2. EXTERNAL DIMENSIONS CMH-WM250, 350, 500V-A Unit: mm 1. Foundation work 1 Take into consideration the surface strength, water drainage route, piping route, and wiring route when preparing the installation site. <Note that the drain water comes out of the unit during operation.> 2 Build the foundation in such way that the corner of the installation leg is securely supported as shown in the right figure.(fig.a) When using a rubber isolating cushion, please ensure it is large enough to cover the entire width of each of the unit's legs. 3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A) 4 Use four fixing plates as shown in the right figure <field supply requi> when using post-installed anchor bolts.(fig.b) 5 To prevent small animals and water and snow from entering the unit and damaging its parts, close the gap around the edges of through holes for pipes and wires with filler plates <field supply requi>. 6 When the pipes or cables are routed at the bottom of the unit, make sure that the through hole at the base of the unit does not get blocked with the installation base. 7 Refer to the Installation Manual when installing units on an installation base. 30mm max Fig.A M10 anchor bolt <field supply requi> Fixing plate <field supply requi> Fig.B 6

3. CENTER OF GRAVITY 3. CENTER OF GRAVITY CMH-WM250, 350, 500V-A Y 660 X Z 740 90 Unit: mm Model X Y Z CMH-WM250V-A 443 256 398 CMH-WM350V-A 433 256 394 CMH-WM500V-A 392 260 406 7

4. ELECTRICAL WIRING DIAGRAMS 4. ELECTRICAL WIRING DIAGRAMS CMH-WM250, 350, 500V-A 1 2 3 4 5 12 3 12 3 12 12 CNVDC CNDC CN17V CN4 CN2 INV-BOARD pink black MAIN-BOARD yellow green PS-BOARD CN4 yellow SC-S SC-T black SC-R 1 2 3 4 5 CN2 FT002 FT001 CNRST blue CN301 CN001 SC-P2 CN110 CN002 blue SC-P1 CT2 CN401 CN101 CN102 X01 CNFG yellow X02 black green 12 3 12 3 12 U DSA U CNAC CN413 12 3 CN402 CN412 black CN401 CN411 t t t t TH32 TH35 TH11 TH13 PSR PSLW PSHW 123 123 123 CN601 CN801 CN802 green CN303 green CN305 blue CN301 green CN701 2 3 4 5 M LEV 5 4 3 2 1 2 1 3 2 1 1 2 3 4 56 12 12 1 2 3 4 5 1 2 1 2 1 2 3 4 1 2 3 4 56 1 2 ACL SW1 ON 123456 LED4:CPU in operation LED1:Normal operation(lit) /Error(blink) LED01:CPU in operation LED02:Normal operation(lit) /Error(blink) LD001 CN306 green 1 2 3 4 1 1 23 6 5 4 3 21 1 2 3 4 1 2 SW1 ON UP SWP01 SWP02 DOWN SWP03 SWU02 SWU01 TB-P TB-N SC-U CT1 SC-W SC-V black PTC X52 Primary current detection circuit CT F 3.15A F 6.3A F15A 1 2 3 4 1 23 ON 987654321 ON SW011 10 87654321 ON 10 987654321 1234 SW002 SW001 TB3 M1 M2 LD601:power supply CN403 yellow 1 2 1 2 3 4 5 RYPN V U MS 3~ WP W H SV green Indoor/outdoor Transmission Line Z1 N L TB01 (Symbol explanation) Symbol Name ACL AC reactor F Fuse H Electric heater (Antifreeze) LEV Expansion valve PSHW,PSLW Pressure sensor(water) PSR Pressure sensor (refrigerant) SV Solenoid valve Symbol Name TB01 Terminal block (for power source) TB3 Terminal block (for Transmission) TH11,TH12, TH32,TH35 Thermister sensor WP Pump Z1 Function setting connector power supply ~220V-240V 50Hz/60Hz Note:1.The broken lines indicate the field-supplied parts,and field work. 2.TB3 is transmission terminal block. Never connect power line to it. 3.Control box houses high-voltage parts. Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage of the connector RYPN on INV-BOARD has dropped to DC20V or less. 4.The initial set values of switch on MAIN BOARD are as follows. SWU01:0 SWU02:0 8

5. SOUND LEVELS 5. SOUND LEVELS 5-1. Sound levels (Measu point) 1m Measurement location *Measu in anechoic room. 5-2. NC curves CMH-WM250, 350, 500V-A Power Source: 220-240V (50/60Hz) 90 80 Octave band sound level (db) 70 60 50 40 30 NC-70 NC-60 NC-50 NC-40 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1k 2k 4k 8k Octave band central frequency (Hz) 9

6. ELECTRICAL CHARACTERISTICS 6. ELECTRICAL CHARACTERISTICS Symbols: MCA: Max. Circuit Amps, MFA: Max. Fuse Amps, RLA: Rated Load Amps Power supply Hz Volts Range+-10% MCA(A) MFA(A) RLA(A) CMH-WM250V-A 50/60 220 3.84 Max.: 264V 230 4.40 15 3.67 Min.: 198V 240 3.52 CMH-WM350V-A 50/60 220 4.69 Max.: 264V 230 5.38 15 4.48 Min.: 198V 240 4.30 CMH-WM500V-A 50/60 220 5.47 Max.: 264V 230 6.28 15 5.23 Min.: 198V 240 5.02 10

7. INSTALLATION 7. INSTALLATION 7-1. Lifting method When hanging the unit for transportation Use hanging holes to hang the unit. Keep the ropes from coming into contact with the water supply and expansion vessel pipes while the unit is being hung. 40 Protective pad Protective pad Unit Water-supply pipes Expansion vessel pipes Out of contact with rope Protective pad Hanging holes 11

8. OPTIONAL PARTS 8. OPTIONAL PARTS 8-1. Drain pan CMH-WM250, 350, 500V-A Drain pan PAC-SH01DP-E CMH-WM-A base Drain pan PAC-SH01DP-E PAC-SH01DP-E Item Drain pan Additional panel Nut M10 Quantity 1 2 10 (Spare included) Shape Item Quantity Washer M10 Screw 5 10 KNURLED 5 (Spare included) 12 (Spare included) Shape Detailed installation information should be refer to its Installation Manual. 12

Warning Do not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate. - Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, repair, or at the time of disposal of the unit. - It may also be in violation of applicable laws. - MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant. Our air conditioning equipment and heat pumps contain a fluorinated greenhouse gas, R32. New publication effective Nov. 2018 Specifications subject to change without notice