Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation.

Similar documents
Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Installation Instructions Model DLC

AND ARCHITECT SPECIFICATIONS

Installation Instructions Model HZM

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

ANNUNCIATOR FIXED MODULE

Operating Instructions MXL Multi-Line Keyboard/Display Panel

Advanced Protection System

Addressable NAC Output Module D327A

4100U City and Relay Cards Installation Instructions

FireNET Plus Wiring Instructions

Marine Fire Detection System Manual MXL Control Panel

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

PSN-1000 & PSN 1000(E) Installation Manual

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

Fire Safety. Installation Instructions Model PSR-1 Remote Power Supply INTRODUCTION. Figure 1 PSR-1 Remote Power Supply

Installation Instructions Model SSD-C-REM

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview

Conventional Fire Alarm Systems

Installation, Operating and Maintenance Manual

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

Booster Power Supply Manual

MXL-IQ CONTROL PANEL. Operation, Installation, and Maintenance Manual. Siemens Industry, Inc. Building Technologies Division Florham Park, NJ

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Remote NAC Power Supply D7038

TECHNICAL DATA OBSOLETE

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

30.45 Electric Release PDRP-2001

Fire Safety. Installation Instructions Model CSM-4 Controllable Signal Module OPERATION INSTALLATION

Installation Instructions Model CDC-4

June 10, 2002 DF C S2424

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

MR-2602 Two Zone Fire Alarm Control Panel

IDP-Zone-6 Six Zone Interface Module

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

FX Intelligent Analog Fire Alarm Control Panel. Installation and Operation Manual

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

I NSTALLATION M ANUAL

Multiplex Eight Input Remote Modules

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EMC COMPATIBILITY UNPACKING...

General Routing Interface

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TotalPac 3 Deluge, Electric release Self-contained system

NETWORK FIRE ALARM CONTROL PANEL. Features

Notification Appliance Circuit Module

AND ARCHITECT SPECIFICATIONS

These instructions detail procedures to follow in order to avoid damage to equipment.

The ACM-8R Annunciator Control Module

Series. Access Power Controllers. Installation Guide

Installation Instructions Model ABHW-4S

Public Safety DAS Annunciator Panel

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

PS914 Power Supply. 900-KL Keylock (optional) Page BB Battery Backup (optional) Page 3

MPC-6000 / MPC-7000 / RND-2

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

Conventional Releasing Control Panel

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

/5121/5122 TrueAlert Power Supply Installation Instructions

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

MXL/MXLV Enclosuress & Equipment Models: MME-3, MBR-MP, MLE-6, MBR-3MP, MDL-1, MDB-1, MDG-1, MHD-1, MHD-2, MHD-3, MHD-4

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

LifeAlarm Fire Alarm Controls

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

July 14, 1999 DF C-100.

ACCURATE ELECTRONICS INC

AL600ULADA. NAC Power Extender. Installation Guide

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AND ARCHITECT SPECIFICATIONS

Desigo TM Fire Safety System A comprehensive fire-protection system

XR10/XR20 Command Processor Panels Installation Guide

Model 17A00 Expansion Enclosure

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Addressable Fire Alarm Control Panel

Installation Guide. XR5FC and XR5SL

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL

Transcription:

Fire Safety nstallation nstructions Model MMB- Main ontrol Board OPERATON The SEMENS Model MMB- board in each MXL System controls operations and monitors input device identity, network communication, and operator commands that are entered through the MKB-/ Annunciator/ Keyboard. The MMB- also provides two analog loop driver circuits. Each ALD loop can be used as lass B or lass A and can monitor and control up to 60 intelligent devices as well as programmable device relays. The MMB- module is field programmable. t is equipped with two programmable lass B (Style Y) or lass A (Style Z) notification appliance circuits. Each circuit can activate up to. amps of audible or visual notification appliances. The module also has auxiliary relays for the external monitoring of ommon System Alarm, ommon System Trouble, and ommon Supervisory conditions. The ommon Supervisory relay is user programmable. The MMB- includes a built-in battery charger and transfer circuit. The charger is microprocessor controlled and incorporates a brownout circuit that switches the System to standby batteries during the loss or reduction of the primary source A. The System can display the real time battery voltage, the A voltage, and the charger current on the MKB-/ alphanumeric display. t also has a amp, VD output that powers ZM- modules. NSTALLATON Always remove power before installation. nstalling the MMB- Board Unpack the MMB-. nspect the module, looking for such things as integrated circuits (s) not firmly seated in their sockets, bent pins, connectors not properly installed, dirt, packing material on the board, etc. The installation kit consists of the following: Four #0 nuts Two resistors Battery cable with wire To install the MMB-:. Place the MMB- with the mounting bracket over the four standoffs on the MBR-MP mounting plate in the upper left portion of the backbox (See Figure ).. Secure in place using the hardware provided. Be sure the screws and nuts are tight, as they provide the earth ground connection for the MMB-. Siemens Building Technologies, nc. 8 Fernwood Road Florham Park, New Jersey 079 Siemens Building Technologies, Ltd. Kenview Boulevard Brampton, Ontario L6T E N P/N -09097-8

Figure nstalling the MMB- F BATTERY P P B NA 0A MPS-6 MPS- B NA P P0 S7 S D00P TB P BATTERY P POWER TO MOM- AMP MAX. TB LOOP TB LOOP P A TO MOM- DO NOT USE MNET PRNTER PROGRAMMER P P6 F MOM- AMP 0 MOM- 0 F MPS-6 8 AMP MMB- (MXL Rev. 9 and higher) 6 K K P GND FAULT DSONNET P6 (MXL Rev. 8 and lower) 0 Figure MMB- Main Board P7 EXPANSON P8 TO ANN- OFF P7 F TAMPER SWTH ON AMP ZM- POWER NA NA SPV TRBL ALR ZM- POWER 0 9 8 7 6 9 8 7 6

ONFGURATON The MMB- has two jumpers jumper P for MNET and jumper P7 for Real Time clock which must be set for proper operation. Refer to Figure for the location of the jumpers. MNET To configure the MNET for either Style or Style 7 operation, set jumper P on the MMB-. f the MMB- has no remote PSR-s or is connected to remote PSR-s with a Style MNET, set the jumper to position S. f the MMB- is connected to remote PSR-s with a Style 7 MNET, set the jumper to S7 and install a NET-7 (Refer to the NET-7 nstallation nstructions, P/N -099). Real Time lock The second jumper on the MMB- is P7 which must be set for the real time clock to operate properly. Move the jumper to the on position to provide backup battery power to the real time clock. Note: The real time clock requires MXL/MXLV firmware Revision 9.0 or higher to operate. nternal Wiring To complete the MMB- internal wiring connections, follow the steps below, skipping those that do not apply to your particular MXL System.. Main Power onnections Primary power for the MMB- is provided by the MPS-6/-6W or MPS-/-W. Both of these mount in the lower right-hand corner of the MXL enclosure. Follow the instructions below for the appropriate power supply. MPS-6/-6W nstall the MPS-6/-6W (See MPS-6/-6W nstructions, P/N -090/W). With the A mains disconnected, connect the MPS-6/-6W power cable to P of the MMB-. Be sure that the jumper assembly is installed in P of the MMB-. f this jumper is not installed, the MMB- will detect a permanent A fail or indicate auxiliary power voltage is low. MPS-/-W nstall the MPS-/-W (See MPS-/-W nstructions, P/N - 0900/W). Remove and discard the jumper assembly installed in P of the MMB-. Disconnect the A mains. onnect the MPS-/-W power cable to P of MMB-.. Battery Power onnection The MMB- kit includes a battery cable (wiring harness). Use the harness to connect the V backup batteries to P of MMB-.. MOM- Optional Module ard age There are two connections between the MMB- and the MOM- board. a. The first is the V power connection. P provides backward compatibility with the MMB- and should only be used when replacing an MMB-. P is limited to amps. The MMB- allows the use of either an MPS-6/-6W or an MPS-/-W. TB terminals and supply V to the MOM- with a maximum of 6 amps (MPS-6/-6W) or amps (MPS-/-W) available. This output must be derated by the total current drawn from NA (.A max), NA (.A max) and the ZM-, power (A max) on the MMB-. onnect TB, and on the MMB- to TB6, and on the MOM. Refer to Figure for the wiring diagram. MOM- TB6 _ P7 _ TB AWG MN 6A MAX (MPS-6) A MAX (MPS-) 8- VD NOT POWER LMTED MMB- Figure MOM- V onnection P6 ABLE P/N -90967 SUPPLED WTH MOM-

Figure ZM- Supervised Auxiliary Power lass B Wiring Figure ZM- Supervised Auxiliary Power lass A Wiring Refer to Wiring Specification for MXL, MXL-Q and MXLV Systems, P/N -0977 revision 6 or higher, for additional wiring information. b. The second provides V power and the communication interface. onnect the 8-wire ribbon cable from P7 on the MOM- to P6 on the MMB-. Field Wiring (Refer to Figure ) The screw terminals for the field wiring circuits are located on the left and right sides of the MMB-. They are labeled TB through TB. The field wiring circuits available are: ZM- power Analog device loop Analog device loop Notification appliance circuit (Styles Y and Z) Notification appliance circuit (Styles Y and Z) ommon alarm relay ommon supervisory relay ommon trouble relay Style RS-8 Network (MNET) The following sections describe each circuit type and give the related instructions. Refer also to the wiring diagrams. Auxiliary lass A V Power Auxiliary power is available on TB, terminals 9 through. The circuit is power limited per NE Article 760 and is rated at amp, 8- VD. This power supply is for use with the ZM- Remote onventional Zone module. Figure shows lass B wiring; Figure shows lass A wiring. lass B wiring can be used to obtain the maximum of 0 ZM-s. Each lass B wire run can support a maximum of 0 ZM-s, ohms max. Multiple lass B power connections can be used provided you do not exced the rating above (0 ZM-s max and ohms per run max). For example, you could have four individual lass B power runs, for a total of 0 devices (6,,, and 7 ZM-s), each of the four runs not exceeding ohms resistance. Analog Device Loops and (TB and TB) These two loops each support up to 60 analog type devices. To install a device for lass B, refer to Figure 6 and the electrical specifications. To install a device for lass A, refer to Figure 6 and the electrical specifications. Electrical Specifications for the Analog Device Loops. Electrical ratings: SUPERVSORY: 0 VD peak, 0mA max ALARM: 0 VD peak, 0mA max (60 devices in alarm). All wiring must be in accordance with Article 760 of NE or the local building codes. Refer to Figure 6.

. Only the list of devices in Table may be used. A maximum of 60 devices may be connected to a single loop.. No end of line device is required.. Both circuits are power limited per NFPA 70, NE. Each detector, or group of detectors, requires a twowire circuit of 8 AWG minimum thermoplastic fixture wire, enclosed in a conduit, or 8 AWG limited-energy shielded cable without conduit, if permitted by local building codes. 6. Total circuit resistance must not exceed 00 ohms. Maximum capacitance: 0.µF between loop and loop 0.8µF between loop and chassis 0.8µF between loop and chassis 7. T-tapping is NOT allowed on lass A loops. ompatible Devices TABLE OMPATBLE DEVES Base nstallation nstructions ZM- P/N -0907-8 ZM-B6 P/N -09- FP-/FPT-* D-60/60H D-60A/60AH D-60B/60BH L-/H L-A/AH L-B/BH LP-/LPT- LP-(d) LP-** LP-**(d) LT- DB-S with DB-ADPT DB- P/N -099-6 P/N -099-6 DB-S, DB-XRS P/N -09087- DB-S, DB-XRS P/N -09087- AD- AD-XR P/N -09-6 P/N -09- DB-S, DB-XRS P/N -0987- DB-S, DB-XRS P/N -0987- AD- AD-XR P/N -09-6 P/N -09- DB-S, DB-XRS P/N -099- AD-LP AD-XRLP P/N -09- P/N -09- DB-S, DB-XRS P/N -0908- AD-LP AD-XRLP P/N -09-6 P/N -09- DB-S P/N -096- M S-0/0 P/N -09090- M S-0B/0B P/N -099- M S-MB6 P/N -096- T R-B6/B6D/B6R P/N -09- T R-B6M P/N -097- * The FP/FPT- is only compatible with MXL/MXLV Rev. 0.0 or greater firmware. **The LP- is only compatible with MXL/MXLV Rev. 8.0 or greater firmware. When the SG-M is configured, the DUT application must be selected when the device is used in an air duct housing or in a spot duct application. Refer to Wiring Specification for MXL, MXL-Q and MXLV Systems, P/N -0977 revision 6 or higher, for additional wiring information. Figure 6 Wiring the Analog Loops

Notification Appliance ircuits (TB, - and TB, -8) (Refer to Figure 7). These circuits are for notification appliances only, NFPA 7 Local. For NFPA 7 Municipal Tie or NFPA 7 Leased Line, use the Model SM-.. All wiring must be in accordance with Article 760 of NE or local building codes.. Both notification appliance circuits are power limited to NFPA 70 and NE.. Electrical ratings: Supervisory: 8 to VD, ma max Alarm: 8 to VD,.A max. End of line device: P/N 0-8080 6. Line Resistance: Must not exceed ohms max 7. For a list of ompatible Notification Appliances, refer to P/N -0966. TB Refer to Wiring Specification for MXL, MXL-Q and MXLV Systems, P/N -0977 revision 6 or higher, for additional wiring information. LASS B WRNG (STYLE Y) SUPERVSED POWER LMTED 8, 7, 6, _ NOTFATON APPLANES EOL*.K /W, *EOL DEVE P/N 0-8080 LASS A WRNG (STYLE Z) SUPERVSED POWER LMTED 8, 7, 6, TB _ EOL*.K /W NOTFATON APPLANES, _ *EOL DEVE P/N 0-8080 Figure 7 Wiring Notification Appliance ircuits (Polarity Shown n Supervisory) 6

ommon Alarm Relay The common alarm relay changes state whenever a fire alarm is detected. The relay is rated A, 0 VD/0 VA resistive. See Figure 8 for the wiring connections. Use only with power limited/lass circuits. ommon Supervisory Relay The supervisory relay changes state whenever a supervisory trouble is detected. t may be used for alternate functions if programmed by SG-M for them. The relay is rated A, 0 VD/0 VA resistive. Refer to Figure 8 for wiring connections. Use only with power limited/lass circuits. ommon Trouble Relay The trouble relay changes state whenever a System trouble is detected. The relay is rated for A, 0 VD/0 VA resistive. Refer to Figure 8 for the wiring connections. Use only with power limited/lass circuits. Refer to Wiring Specification for MXL, MXL-Q and MXLV Systems, P/N -0977 revision 6 or higher, for additional wiring information. RATNGS A, 0 VD/0 VA RESSTVE OLS ARE SUPERVSED WHEN DE-ENERGZED ONTATS ARE SHOWN N NORMAL STATE Figure 8 MMB- Relay onnections 7

Style Network (MNET) The MMB- provides a Style MNET network for connection to remote power supplies (PSR-) and annunciators (MO-/7, R-/F). See Figure 9 for wiring instructions. f a Style 7 network is required, a NET-7 must be used. Refer to the NET-7 nstallation nstructions, P/N -099, for wiring diagrams. FUSE REPLAEMENT N THE MXL SYSTEM F F F F MPS-6 nput Battery Reversal ZM- Power FUSE RATNGS V Output (TB, terminals and ) 8A, AG, Normal Blow 0A, AG, Normal Blow A, AG, Normal Blow A, AG, Normal Blow NOTE: The fuses are located on the upper left and right corners of the MMB- board. Refer to Wiring Specification for MXL, MXL-Q and MXLV Systems, P/N -0977 revision 6 or higher, for additional wiring information. Figure 9 Style Network (MNET) P/N -09097-8