for CLIMATRON GROWTH CABINET MODEL CLIMATRON 520 & 1100-DL/SL-H-CO 2 With Humidity, CO 2 & Touch screen Control REVISION

Similar documents
OPERATING INSTRUCTIONS FOR:

for LABORATORY REFRIGERATOR MODEL TELR-145/ L/200L CAPACITY REVISION

OPERATING INSTRUCTIONS FOR: MODEL: TGO-80W, 150W, 240W GLASSWARE DRYING OVEN

Plant Growth Cabinets

for LABORATORY STORAGE FREEZERS MODELS TUF GD/SD, TUF GD/SD, & TUF GD/SD 520, 740, & 950 Litre CAPACITY REVISION

for PHARMACY REFRIGERATOR MODEL TPR SD/GD TPR-750/950 2 SD/GD TPR SD/GD 520, 750, 950, 1150 Ltr CAPACITY REVISION

WITH OMRON E5CC CONTROL

REFRIGERATED RECIRCULATORY COOLER

Plant Growth Cabinets

LABORATORY ILLUMINATED FLOTATION BATH

PHARMACY REFRIGERATOR INSTRUCTION MANUAL

CLIMATRON GROWTH CABINETS

Plant Growth Cabinets

Operating Manual Refrigerated Display Cabinet

Operation Manual Portable Room Air Conditioner Models: RPC26WA / RPC35WA / RPC41WA

LABORATORY OVENS MODELS INCLUDE: TO-152G & TOH-152G TO-152F & TO-235F DEHYDRATING OVENS MODELS INCLUDE: TD-150F TD-330F TD-500F

InstructIon Manual KrEs EQuIPMEnt stands

Plant Growth Cabinets

20L Electronic Dehumidifier

12L DEHUMIDIFIER OPERATING INSTRUCTIONS

General Care and Safety Guide

CUBE ICEMAKER MODELS SCU25, SCU35, SCU45, SCU75, SCU95, SCU120 INSTALLATION AND SERVICE MANUAL VERSION 2

8L DEHUMIDIFIER OPERATING INSTRUCTIONS

ICS PACIFIC. Installation Instructions & User Manual. G135L Medical Refrigerator

Model pictured: ST6001

OWNER S MANUAL. Convair Tower Heater CTH09. (English) (CTH09)

Table of Contents. Features Quality Policy Section A - Unit Operation Section B Unit Maintenance Trouble Shooting Guide...

Operating Instructions

Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC iers.com

PRACTICAL USER S GUIDE FOR THE DIMPLEX PURIFIRE ELECTRIC STOVE

Instruction Manual. Please read this manual and the Safety Instructions carefully before using your refrigerator.

Blade Series Heat Exchanger Operation and Installation

THERMOFILM CONVECTIVE PANEL HEATER INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Models: CP 2400 CP 2000 CP 1500 CP 1000 TABLE OF CONTENTS

Ui REFRIGERATOR SPEC SHEET

PRODUCT MANUAL OPERATION, INSTALLATION AND MAINTENANCE MANUAL. Indoor Convective Panel Heater

RSA2CL6SS model pictured

User and Installation Instructions. Wall Mounted Water Boiler WMB3F/B and WMB3F/W IS435 ECN3461

Operator s Manual. Histology Bath

2.9kW Portable Air Conditioner

PRACTICAL USER S GUIDE FOR THE ELECTRIC STOVE

INSTALLATION, OPERATION & MAINTENANCE AVANTCO SERIES 177AG OWNER S MANUAL

Platinum Series Electronic Panel Heaters

General Care and Safety Guide

USER MANUAL. Adventure Kings WiFi Refrigerator

Operating Instructions. Oil Column Heater. Models: GOC155, GOC157, GOC1511

VF X Series. User Manual. SKOPE Vertical Freezer. MAN11137 Rev. 1.1 Sep VF650X

i.c³ User Guide For Helmer i.series Ultra-Low Freezers A/A

ETLW7. Product: 7kg Top Load Washing Machine. User Manual

REFRIGERATED DROP-INS (2-6)FT-DI Installation and Operating Manual

Model No.: VUM33AS20G

IMPORTANT SAFETY INFORMATION:

INSTRUCTION MANUAL TS21. 2 Heating and 1 Cooling

MariGlo LED. Inspiring Excellence in Fish Keeping! 45 / 60 / 90 / 120.

User and Installation Instructions C6R/75, C6R/100, C6R/105, C6R/125, C6R/130, D6R/100, D6R/125, D5R/100, D5R/125, D3R/100

Table of Contents. Forward Quality Policy Design Parameters Section A Unit Operation Section B Unit Maintenance...

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

Cool Mist Ultrasonic Humidifier

USER MANUAL PLEASE READ AND UNDERSTAND THIS MANUAL COMPLETELY BEFORE USE.

General Care and Safety Guide

Product Manual. Argon (AMC 1020)

INSTRUCTION MANUAL P Heating and 1 Cooling

TBR 40 1 GD Blood Refrigerator Instruction Manual. for BLOOD STORAGE REFRIGERATORS MODEL TBR 40 1 GD. (40 x 500ml Blood Bag Capacity)

T-Series Air Conditioner T15 Model

Superdryer Dehumidifiers

Installation, Operating and Servicing Instructions

Zip Chilltap Extra. Affix Model Number Label Here UK. Installation and Operating Instructions

G-10s. Instruction Manual. G-Series Cooler UPRIGHT COOLER. Part No.11IPA

R A D I A N T O U T D O O R H E A T E R S OPERATION, INSTALLATION AND MAINTENANCE MANUAL. TT-MTM Wall Controller

Table of Contents. Forward Quality Policy Design Parameters Section A Unit Operation Setting the Timer...

Installation and Operating Instructions for Microlene Underbench System

Outdoor Refrigerator USER S MANUAL

Model pictured: RCB2AH6WH/SS

Operating instructions Page 12

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

WatchDog NXT60. Installation and Operations Manual. Seaira Global, LLC NC Highway 50 Surf City, NC (910)

PRACTICAL USER S GUIDE FOR THE DIMPLEX ELECTRIC FIREPLACE WITH REMOTE CONTROL

Zip Domestic Chill Tap

Model pictured: ST7001SLIM/ST7001SLIMA

OPERATING INSTRUCTIONS

STEAM WALLPAPER STRIPPER MODEL HTW5

B 353 COFFEE BREWING MACHINES MACHINES A CAFE KAFFEEBRUEHMASCHINEN KOFFIEZETAPPARATEN

User and Installation Instructions. Electric Auto-Fill Water Boilers EB3F, EB4F, EB6F, EB6TF IS339 ECN3539

Cooled Incubators Series 1, 3 & 4. Instruction Manual

6.5L SLOW COOKER INSTRUCTION MANUAL

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

Instruction Manual. By Evakool. Please read these instructions and the Safety section carefully before using your refrigerator.

OWNER S MANUAL IMPORTANT - INSTALLER MUST COMPLETE FOR WARRANTY PURPOSES. Made in Western Australia by:

Electronic Ceramic Tower Heater

TRAVELMATE. Instruction Manual

PRODUCT MANUAL. TT-MTM2 Hard-Wired Controller with Remote

BRITA. Water Filter & Chiller II. Chilled water filter. Instruction Booklet WF6100

Outdoor/Commercial Refrigerator USER S MANUAL

Mira Vision Wireless Controller

Wax Base Heater & Dispenser

2.9kW Portable Air Conditioner

BEFORE USE, PLEASE READ AND FOLLOW ALL SAFETY RULES AND OPERATING INSTRUCTIONS.

OPERATION & MAINTENANCE MANUAL RHS680

YORK KETTLE INSTRUCTIONS & WARRANTY 2 YEAR WARRANTY 20431AU 20431AU_IB_FA_190314

The Classeq under counter range

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model ABM - 715

Transcription:

for CLIMATRON GROWTH CABINET MODEL CLIMATRON 520 & 1100-DL/SL-H-CO 2 With Humidity, CO 2 & Touch screen Control REVISION 26-01-16 Thermoline Scientific Equipment Pty. Ltd. T/AThermoline ScientificABN 80 000 859 129 10-12 Ross Place, Wetherill Park. N.S.W. 2164. Australia. P.O. Box 6862, WetherillPark Delivery Centre, N.S.W. 1851. Australia. Phone: (02) 9604 3911. International: 61 2 9604 3911. Fax: (02) 9725 1706. International: 61 2 9725 1706. Email:sales@thermoline.com.auWeb:www.thermoline.com.au

Introduction: Thank you for selecting this equipment from the large range of products manufactured in Australia by Thermoline Scientific. The materials incorporated in this design have been carefully selected for their durability, technical performance and practicability, the resultant product is one we are proud of. Please take the time to read this manual. It contains information that will allow the operator to understand how the equipment operates, what it can and cannot do, how to operate the controls, and how to ensure reliable operation. Please take note of the maintenance section to ensure trouble free operation and keep this manual in a safe place for future reference. LIST OF CONTENTS: INTRODUCTION: 2 LIST OF CONTENTS: 2 UNPACKING: 3 USE AND FUNCTION: 3 LOCATION, INSTALLATION & SERVICES REQUIRED General: 4 Location 4 Level: 5 Castors: 5 Mains Power: 5 Water 5 Co2 Supply (Optional) 6 Drain 6 Assembly, Shelves, Shelf Lighting & Dimming Option 6 Ultrasonic Humidifier 7 & 8 Installation 8 & 9 Loading of Product into Cabinet 9 CLEANING & MAINTENACE General Cleaning 10 Maintenance Requirements 10 Cleaning Condenser 10 & 11 Ultrasonic Humidifier 11 Floor Drain 11 STAR-700 TOUCHSCREEN OPERATING GUIDELINES Safe Operating Value (SOV) 12 & 13 Program/Diurnal Set-Up 14 to 20 Trend Menu 21 Data Menu 22 Security Screensaver, Passcodes & Blank Screen 23 to 25 Calibration Screen & Passcodes 26 & 27 Contact Screen 27 Service Screen 27 TEMPERATURE & HUMIDITY PERFORMANCE Temperature & Humidity Performance charts 28 to 31 Warranty 32 & 33 26-1-16 2

UNPACKING: Remove the equipment from the packing material and check for damage. Notify the detail of any damage to your supplier or to Thermoline Scientific without delay. Retain the packing materials until the equipment has been thoroughly checked. Inventory Shelf Light Model (SL): Shelf Lighting Trays as per quantities ordered. 1 x Shelf per Light Tray (520 litre model), 2 x shelves per tray (1100 model). Shelf Clips: 8 per Light Tray/shelf (520 litre model), 12 per light tray/shelf (1100 litre model). Inventory Door Light Model (DL): 4 x Shelves (520 litre model), 8 x shelves (1100 litre model). 4 x Shelf Clips per Shelf (520 litre model), 8 x shelf clips per shelf (1100 litre model) Inventory Humidity Model (H) Water supply bottle, fittings and hose. Ultrasonic humidifier, hoses, and filters. Humidifier mounting bracket. USE & FUNCTION: The Thermoline range of Climatron cabinets has been designed to maintain environmental conditions critical for general research, and/or growth of flora and/or fauna. The cabinets are available as Temperature only control, with the option of Humidity control, Lighting control, and CO2 control. Two sizes are available (520 & 1100litres), with door or shelf lighting options. Temperatures can be controlled accurately from -5ºC to +45ºC without the lighting option, and +5ºC to +45ºC with lights. Diurnal (day/night) control of Temperature, Humidity (optional) Co2 (optional) and Lighting is provided by the easy to use touch screen. Electronic control of heating elements and refrigeration valves for optimum temperature control. Fan forced air circulation allows even air flow across each shelf level. Adjustable open wire shelves. Shelf Lighting Lamps are covered with a polycarbonate sheath for safety, and are switched by electronic ballasts for higher efficiency. Castors fitted to each cabinet for easy movement, with the front castors being lockable. 26-1-16 3

LOCATION, INSTALLATION& SERVICES REQUIRED: This section deals with the provision and connection of services that will be required for your cabinet to function correctly and advice on where to locate the cabinet. General: The equipment is designed to operate under the following ambient conditions: Suitable for indoor use only. Ambient temperature range: 10ºC to 32ºC. Ambient humidity range: Maximum relative humidity of 85% for ambient temperatures up to 25ºC. Note: Optimum performance of the cabinet is achieved when the ambient temperature is within a 20 to 25ºC range. Location: All refrigerated equipment generates heat as part of the normal operation. It is vital for correct performance and reliability that adequate ventilation is provided to allow this heat to dissipate. Any refrigerated equipment that is operated in a small unventilated area, especially in warm weather, can cause the compressor to overheat and may result in premature failure. NOTE: Failure to observe ventilation guidelines will void the manufacturer s warranty! A minimum of 300mm above the cabinet and 300mm at the back and sides must be maintained at all times to ensure adequate air flow to dissipate heat generated by the refrigeration unit. Do not store items on top of the cabinet as this will also affect ventilation! Note: On cabinets with the humidity option the water supply bottle is mounted on the top right side. CAUTION: When installing more than one cabinet in the same location ensure that they are positioned in such a way that warm air exhausted from one cabinet, is not drawn directly into the other cabinet. 26-1-16 4

Level: The cabinet should be standing on level ground to ensure correct operation of the self-closing door, and proper draining of condensate from the evaporator. Castors: The cabinet is fitted with castors for ease of movement to allow for cleaning under the cabinet. Where lockable castors are fitted they must be locked to prevent accidental cabinet movement. This can be achieved by pressing the lock-down tab with your foot. These castors are usually at the front of the cabinet; ensure that both castors are locked. Mains Power: This cabinet is suitable for connection to a standard 240 volt, 50Hz, supply. A dedicated outlet should be used for the supply, do not use power boards or the like. Confirm that the power supply is suitable for this equipment; refer to the equipment rating plate for details. Water: A water supply is required if the cabinet is fitted with optional Humidity control. The water supply can come from either town water or from gravity fed water reservoir placed on top of the cabinet. If using a mains water connection, a pressure regulator must be fitted to reduce water pressure below 100kpa. If the pressure regulator is not fitted the fittings and hoses to the ultrasonic humidifier filters will be damaged! Thermoline supply a 30litre water tank complete with hose, drain tap, and connection fittings. This tank should be elevated above the ultrasonic humidifier by at least 200mm and filled with water; the tank would normally sit on the top right side of the cabinet. The gravity fed water supply has a number of advantages over a town water supply: Firstly, the water in the tank can be treated water : such as distilled water. This will increase the maintenance period of the water filters as the water will already be quite clean. Secondly, if the automatic water level controls were to fail or if there was a water leak, the worst spillage would be 30litres instead of a potential flood. 26-1-16 5

Co2 Supply (Optional). At the rear of the chamber is a ¼ barbed fitting labeled Co2 inlet. This is the inlet for the Co2. Connect a regulated Co2 supply to this point with set to a maximum pressure of 125kpa. (+/-25kpa). Make sure that when connecting the Co2 supply that is connected in a manner that will not leak. Use a hose clamp if necessary. See STAR-700 operating Guidelines on how to control the Co2. Drain: Because we are controlling humidity levels inside the cabinet, there will be water coming out of the drain located on the side of the cabinet. There is also a drain valve and an overflow pipe in case of a malfunction. Therefore it is essential that the location for the cabinet has a floor drain for the water to flow into. Water from the cabinet will exit through a drain pipe on the right hand side of the cabinet, you will need to connect this drain pipe to the floor drain (see note below). It is important that the cabinet drain pipe is connected to a suitable waste outlet (drain) at all times. Make sure that there are no restrictions in the drain pipe; it will need to cope with an overflow of 3litres per minute in the case of a fault. Assembly: Shelves: 4 stainless steel clips are supplied per shelf. Determine the space required between each shelf level, and simply hook the clips into the slotted strip attached to the walls. Place the shelves on top of the clips. Door lighting: For cabinets with door lighting the lights are permanently mounted in the door enclosure. Shelf lighting: For cabinets with shelf lighting there are 4 x shelf clips to support each shelf. As with the wire shelves, simply hook the clips into the slotted strip attached to the walls. Place the shelves on top of the clips. Feed the cables for the light trays through the cable ports in the side of the cabinet. The cables for the light trays plug into sockets on the bracket at the rear of the cabinet. The plugs push into the sockets and you turn the outer ring clockwise to lock them in place. If the dimming option is fitted a White knob is located above the connectors. Simply turn this to dim the lights. 26-1-16 6

Cabinet with door open showing 3 x shelves and lighting trays. Ultrasonic Humidifier: Humidity Model (H) Cabinets may be supplied with the ultrasonic humidifier separately, and may require assembly. Mount the humidifier onto the side of the cabinet by sliding it into the bracket. Connect the 2 x vapor hoses between the fittings on top of the humidifier and those on the side of the cabinet. Make sure to use the hose clamps to hold the hoses securely in place. Connect the overflow and drain pipes on the humidifier to the black drain hose on the side of the cabinet. Connect the wiring plugs from the humidifier to the sockets at the rear of the cabinet. Note the humidifier control plug is female and the humidifier power supply plug is male so they cannot be mixed up. As with the plugs for the light trays turn the outer ring clockwise to lock them in place. If using the gravity feed water supply mount the tank on top of the cabinet and connect the 6mm tube to the water inlet on the filters. If mains water supply is used a pressure regulator should be used to keep the pressure below 100kpa! Make sure the drain valve on the black drain pipe is closed. 26-1-16 7

Installation: Locate the cabinet in a well-ventilated area on a firm level surface as described earlier. The cabinet is fitted with castor wheels so that it can easily be moved during installation. Leave sufficient room at the rear and sides for air flow around the cabinet as previously described (30cm each side 30cm at the rear). Leave enough room in front of the door/s to allow them to open fully when loading the cabinet. Connect the drain pipe at the right side of the cabinet; to a suitable floor drain with flexible hose (drain pipe is 19mm diameter). 26-1-16 8

If you are using the gravity feed water bottle the top of the cabinet is strong enough to take the weight of a 30litre water bottle. Place the empty container onto the top of the cabinet prior to filling with water. Then carefully fill the water container with water. Do not attempt to fill the container then lift it on to the top of the cabinet. This could cause serious damage or injury to persons. Extreme caution should be taken as not to spill or splash water onto the cabinet surface when filling the Water Container. Spillage of water onto the cabinet may result in equipment damage, personal injury or death. Note: When filling the bottle make sure that the small valve is closed until you connect the water supply to the filters. After filling the bottle the valve can then be opened. Valve closed Valve open Loading Of Product into Cabinet: All forced draught enclosures such as this one require constant air flow throughout the cabinet to maintain the desired temperature. Correct loading of the shelves must be considered for efficient refrigeration performance. Never block off air vents. Allow sufficient space around the product on each shelf for air flow. Distribute the load evenly over all of the shelves rather than stacking everything on one shelf. 26-1-16 9

General cleaning: CLEANING & MAINTENANCE: The interior, exterior, and door gasket can be cleaned as often as required using a soft cloth and soapy water. Never use abrasive cleaners or scouring pads as these will scratch the surface and may result in corrosion. Never use caustic type cleaning agents. All cabinets have electrical components such as the temperature control, internal light, refrigeration condensing unit. These items should not be subjected to any levels of moisture. For example do not use a hose to wash down the incubator. Evidence of moisture entry into any electrical device will void the manufacturer s warranty! Maintenance: Apart from normal levels of cleanliness, it is important that the refrigeration condenser is kept clean, the Ultrasonic Humidifier is maintained and the Floor Drain is checked for blockages. Failure to keep the condenser clean could lead to higher temperatures inside the cabinet, higher running costs, and often a failure of the compressor. A clean condenser is a critical factor in keeping the refrigerator operating correctly. The condenser should be cleaned at least 3 monthly, in some dusty locations this may need to be more frequent. By monitoring the amount clogging due to dust, the frequency of cleaning can be adjusted to keep it clean. Manufacturer s warranty does not cover the failure of the compressor due to a blocked condenser. Cleaning the Condenser: The condenser is located at the top of the cabinet and requires the front panel to be removed to gain access. It looks like an assembly of aluminium fins with a fan arranged to blow air through it. Turn off the power at the power point before cleaning the condenser! Using a stiff paint brush, carefully remove dust and dirt build-up from the condenser, ensuring that dust is not pushed back into the condenser fins. The use of a vacuum cleaner will help in cleaning up the dislodged material. 26-1-16 10

The condenser fins may be sharp, take care to avoid personal injury by not directly contacting them with your hands! The fin material is thin and can be easily bent, take care not to flatten the fins as this may affect the efficiency of the condenser. Ultrasonic Humidifier. The Ultrasonic Humidifier tank is constantly evaporating water. To maintain a long service life of the Ultrasonic Oscillator it is important that the tank has very clean filtered water. Failure to replace the Water filters on a regular basis will drastically reduce the life of the Oscillators. The Oscillators themselves are a consumable item with an expected life cycle of 5000hrs (Approximately 6 months). However due to the output of the controller the duty cycle of the oscillators would be approximately 50% which with regular maintenance and replacement of the filter regularly should last longer than 6 months. Thermoline recommend that the Water filters should be replaced every 3 to 6months depending on the water quality being used. Failure to replace these filters on a regular basis will void the warranty applicable to the Ultrasonic Humidifier. Contact Thermoline for replacement Water Filters. Do not rinse out the old Water Filters and re-use. Floor Drain. Due to the nature of products (Plant Material) that will be present inside the cabinet, it will be necessary to check the drains for blockages. Depending on the nature of a blockage due care will need to be taken. Do not try to force any blocked large particles through the drain. This will simply cause them to get blocked further down the drain. If necessary force water back into the outlet of the drain. Please note that the drain is manufactured from Irrigation tubing. It cannot cope with a lot of internal pressure. Be very careful when back flushing the drain. This will force any blocked particles back into the cabinet. Simply collect the debris and throw into a waste bin. If this does not clear the blockage then the services of a qualified technician maybe require. 26-1-16 11

STAR-700 TOUCHSCREEN OPERATING GUIDELINES. Safe Operating Value (SOV). On initial Power up the STAR-700 Touchscreen shows the Screen Saver page. See Below Image. On Initial power up cabinet controls the Safe Operating Value only. The Touchscreen is fitted with a Security Screensaver to stop unauthorised access to the controlling parameters. This Security Screensaver becomes active if the Touchscreen has not been touched for more than 5minutes or if power is cycled. To exit out of the Security Screensaver simply press the Press to Log In & Exit Screensaver Button. The User Access window will appear. To exit out of the Security Screensaver and enter into the Main Menu Screen use the following passcodes: User Number: 1 Passcodes: 1111 These passcode should only be given to Authorised Personnel. To enter the User Number and/or the Passcode simply press the Numeric Window and the Numeric Keyboard will be displayed. Simply enter the User Number and/or the Password and press enter. Once you have pressed enter press the screen anywhere above the Login Button and the Main Menu screen will appear. When in the Main Menu Screen you will notice that the indicator in the top right corner states that the Diurnal/Program Cycle is Off. The Values below the heading Safe Operating Value are the current set values and the controller will start to control these values. During Safe Operating Value control, the Lights can only be manually operated by using the drop down menu underneath the heading Lights (SOV). The Lights SOV is a manual operation of the Lights, in the ON mode they are continually on and in the OFF mode they are continually off. To operate the Lights on a Diurnal/Program Cycle the operator will need set up the Diurnal/Program Cycle. To change the Safe Operating Value simply touch the Operating Value box. A popup numeric keypad is displayed. Type in the new value and press enter. The cabinet will automatically control the new Safe Operating Value. The Safe Operating Value has been designed to be set by the operator to a safe condition that will not cause damage to any of the Research, Experimental and/or Plant Material within the cabinet, in the event of a power failure. If the controller is operating in Diurnal/Program Cycle mode and there is a power failure, on resumption of power the Diurnal/Program Cycle mode will stop and the cabinet will be controlled at the Safe Operating Value. Security Screensaver (SOV Mode) 26-1-16 12

Security Screensaver with User Access Window. Main Menu Screen (SOV Mode) Main Menu Screen with Pop-Up Numeric Keypad. 26-1-16 13

Program/Diurnal Set-Up. The STAR 700 has a 250 segment Programmer. The 250 segments are split between 25 Programs (10 Segments per program). The Program Set-Up is securely protected by means of a user name and password. By pressing the Thermoline Logo the Login Screen appears. The Username is 02 and the Password is 2222. Once the Password is entered the next touch of the screen needs to be the Program Set-Up button. If the screen is touch anywhere but the Program Set-Up button the password will be reset and will need to be re-entered. Once the Program Set-Up button has been pressed then the Program Set-Up screen is displayed. Main Screen with Login Screen showing Login Screen Diurnal/Program Set Up Screen. The above screen shows the Program set-up page. This consists of 25 programs having a total of 250segments (10segments per program). Program 1: Segments 1-10 Program 2: Segments 11-20 Program 3: Segments 21-30 Program 4: Segments 31-40 (etc) Program 25: Segments 241-250. 26-1-16 14

Each program can be set as an independent program or can be linked to create one large or multiple large programs. This is achieved by not using an End segment in a particular program. For example if your program requires the use of 15 segments we can use the 10 segments of Program 1 and the first 5 segments of Program 2 making Segment 15 (5 th Segment of Program 2) an End Segment type. We would then start program 1 and as the program runs through the first 10 segments of program 1 and because there is no end segment in Program 1 it continues to run program 2 until it find the end segment at segment 15. When linking multiple Programs, to use more than 10 segments, the programs need to be sequential. By pressing on Program 1 the following screen is displayed. The below example is a Diurnal cycle of 40degC and 40% day and 10degC and 80% Night. Assuming that 40degC is at midday this program has been written to start at 25degC and 60%RH assuming that the day condition of 40degC and 40%RH is Midday then this program would need to be started by the operator at 6am. Program 1 Segment 1-5 Program 1 Segment 6-10 26-1-16 15

The following is a description of what each of the items in the Program are and what function they perform. Segment Type: Jump To: Jump Cycle: Temperature: Humidity: Co2: Hours: Minutes: Seconds: End Action The segment type can either be a Time, Jump To, or End type. Time: This determines that the segment is a period of time. The time is set in Hours, Minutes and Seconds. Jump To: This allows the program to repeat a predetermined set of segments. By selecting the Jump To parameter in segment type and then entering a segment value at the Jump To parameter, will tell the program were to jump back to. At Jump Cycle enter how many times it jumps back to or repeats the predetermined set of segments. See Example on next page. End: This tells the program when to end. There has to be an end segment. Failure to enter an end segment will cause the controller to indefinitely dwell at the last segment. The operator would enter the segment number that the program will jump back to. This value is ignored if the segment is set to either a Time or End Segment. The operator would enter a value here as to how many times the Jump To repeats itself. A value of 0 will continually repeat the Jump To segments until the operator ends the Program Cycle manually. This value is ignored if the Segment Type is set to either a Time or End Segment. The operator would enter the Temperature they require the cabinet to achieve. This value is ignored if the segment s Step Type is Jump To. The operator would enter the Humidity they require the cabinet to achieve. This value is ignored if the segment s Step Type is Jump To. The operator would enter the Co2 they require the cabinet to achieve. This value is ignored if the segment s Step Type is Jump To. The operator would enter the required length of time for the segment in Hours. This value is ignored if the segment Step Type is set to either Jump To or End. The operator would enter the required length of time for the segment in Minutes. This value is ignored if the segment Step Type is set to either Jump To or End. The operator would enter the required length of time for the segment in Seconds. This value is ignored if the segment Step Type is set to either Jump To or End. This value determines what will happen when the program ends. It can be set to SOV, which stops the program from operating and controls the Safe Operating Values. Or it can be set to dwell, in which case it will continue to control the Temperature, Humidity and Co2 of the last Time segment. 26-1-16 16

G Soak Temp This is the Guaranteed Soak Parameter and is only visible if the Guaranteed Soak is enabled. This parameter is generally not used on the Climatron range of Plant Growth Cabinets as it can extend the time of a Diurnal Program effectively making the Diurnal Cycle longer than 24hours. The Guaranteed Soak allows the Program to maintain its Programmed Temperature Value for the duration of the Segment Time by automatically placing the Program into a holding pattern and not allowing the program to proceed if the Actual Temperature Value deviates the Programmed Temperature Value by a predetermined value. Once the Actual Temperature Value is within the predetermine range then the Program will automatically continue. G Soak Humidity This is the Guaranteed Soak Parameter and is only visible if the Guaranteed Soak is enabled. This parameter is generally not used on the Climatron range of Plant Growth Cabinets as it can extend the time of a Diurnal Program effectively making the Diurnal Cycle longer than 24hours. The Guaranteed Soak allows the Program to maintain its Programmed Humidity Value for the duration of the Segment Time by automatically placing the Program into a holding pattern and not allowing the program to proceed if the Actual Humidity Value deviates the Programmed Humidity Value by a predetermined value. Once the Actual Humidity Value is within the predetermine range then the Program will automatically continue. G Soak CO 2 This is the Guaranteed Soak Parameter and is only visible if the Guaranteed Soak is enabled. This parameter is generally not used on the Climatron range of Plant Growth Cabinets as it can extend the time of a Diurnal Program effectively making the Diurnal Cycle longer than 24hours. The Guaranteed Soak allows the Program to maintain its Programmed CO 2 Value for the duration of the Segment Time by automatically placing the Program into a holding pattern and not allowing the program to proceed if the Actual CO 2 Value deviates the Programmed CO 2 Value by a predetermined value. Once the Actual CO 2 Value is within the predetermine range then the Program will automatically continue. Lighting/Event Outputs. At each segment page there is a Lighting/Events button. By pressing this button the display shows Eight events that can be turned ON and OFF for each segment. The First Event which is generally labelled Lights is what turns the lights ON and/or Off. A total number of Eight Lighting/Event Outputs are available, however only the required hardware is fitted per cabinet. 26-1-16 17

Program 1 Lighting/Event Segment 1-5 Program 1 Lighting/Event Segment 6-10 Program Features. There are a few other features of the program that cannot be changed but are described below. Guaranteed Soak: This is a tolerance value, set at +/-2.0degC, and guarantees that the Program Set Values for Temperature only are reached. If during a program cycle the Actual Temperature deviates the Program Set Value (PSV) by more than +/-2.0degC the program will be put into a hold mode until the Actual Temperature is within the PSV. There is no Guaranteed Soak on the Humidity Value or the Co2 value. These values can deviate without the program going into a hold mode. Program Start Value: The Program starts at whatever the Actual Temperature, Humidity and Co2 are. If when starting the program the Actual Temperature is more than +/-2.0degC from Segment 1 s PSV the Guaranteed Soak value will hold the program until it reaches Segment 1 s target temperature. 26-1-16 18

Power Failure: In the event of a power failure the Program Cycle will end. On resumption of power the cabinet will control the Safe Operating Values. Starting the Diurnal/Program. The following screen shows the Diurnal/Program Set-Up screen. Once the desired program has been set up then the operator will need to enter the desired program number value into Start Program Number. Once the desire value has been entered the operator can then start the program by using the drop down menu. The following describes the item and the function of the parameters in the drop down menu. End The end parameter is what stops a current running program from operating Start The Start parameter is what starts the program that is entered into the Start Program Number. Pause The Pause Parameter will simply pause the program at its present point. It will hold this point until the resume parameters is selected. If the Start parameter is selected while a program is in pause it can restart the program from the beginning. Resume The Resume parameter will resume a program after it has been paused. Diurnal/Program Set Up Screen. Note: The Program can be Started, Stopped, Paused and Resumed in the Main Menu Screen. However you cannot select the Program Number in the Main Menu Screen. When the program is operating the Start Program Number value disappears and the Program Number Running value appears. The Program Running Number is a read only value just to give the operator and understanding of which program is operating. To change the Program that is running the operator will need to End the program to change the Start Program Number. This can only be performed in the Program Set-Up page. 26-1-16 19

Main Screen (SOV) Showing Diurnal Drop Down Menu. Main Screen (DSV Mode) 26-1-16 20

Trend Menu The images below are the Trend and the Co2 Trend Screen. They show a live trend of the performance of the cabinet. The screen shows the last 12hr period. By pressing the left pointing arrows the screen scrolls back to view a graphical depiction of the previous period from power up. A total of approximately 800days of logging can be viewed. After approximately 800 days the data is lost. The Trend Screen is refresh s every time power to the instrument is cycled at power up. Trend Screen Co2 Trend Screen 26-1-16 21

Data Menu By pressing the Data Menu Button the image below is displayed. On this screen Data can be retrieved for archiving purposes. Insert a USB Memory Card into the USB port at the front of cabinet. Keep watching the screen for the following message USB Disk/SDMMC Card Plugin Once this message has been viewed the operator can press the Download Data to USB button. The Red Indicator will flash whilst data is being downloaded to the USB Memory Card. When the Red Indicator stops flashing it is safe to remove the USB Memory Card. The length of time it takes to download the data will depend on how much data is being downloaded. If the memory is full, then the download period could be quite long. Data is downloaded as a Comma Delimited File. This data can be imported into Microsoft Excel. When importing data make sure that the date format is set for YMD (Year- Month-Day). Every 24hrs the Data Log Menu screen is refreshed. The Data that is downloaded to the USB Memory Card is downloaded in files that represent every 24hrs. The data in the table is refreshed every 24hrs. However the data in the memory that can be downloaded will store approximately 800 days. Data Menu Screen. 26-1-16 22

Security Screensaver. The Touchscreen is fitted with a Security Screensaver to stop unauthorised access to the controlling parameters. This Security Screensaver becomes active if the Touchscreen has not been touched for more than 5minutes or if power is cycled. If the Touchscreen has not been touched for more than 10minutes the Backlight switches off and the screen goes blank. (This is designed to lengthen the life of the Touchscreen). To re-illuminate the Touchscreen simply touch the screen and the Security Screensaver will be shown as below. This Security Screensaver allows the operator to check the conditions without the need to enter the security code to access the Control Pages of the Touchscreen. Security Screensaver (SOV Mode) Security Screensaver (DSV Mode) If the Security Screensaver is active and the screen is touched a Pop-Up window appears as shown in the next image. 26-1-16 23

Security Screensaver with Pop-Up Login Message To exit out of the Security Screensaver simply press the close button. Then press the Press to Log In & Exit Screensaver Button. The User Access window will appear. Security Screensaver with User Access Window. To exit out of the Security Screensaver and enter into the Main Menu Screen use the following passcodes: User Number: 1 Passcodes: 1111 These passcode should only be given to Authorised Personnel. To enter the User Number and/or the Passcode simply press the Numeric Window and the Numeric Keyboard will be displayed. Simply enter the User Number or the Password and press enter. 26-1-16 24

Security Screensaver with Pop-Up Numeric Keypad. As soon as you have pressed enter simply touch the screen anywhere within the Black rectangle. The Touchscreen will then show the Main Screen as shown below. Main Menu Screen (SOV Mode) 26-1-16 25

Calibration Screen. The Thermoline Touchscreen has been fitted with a simple one point calibration adjustment. Access to the Calibration is password protected. To access simply touch the Thermoline Logo and the User Access window will appear. Main Menu Screen with User Access Window To access the Calibration Screen use the following passcodes: User Number: 2 Passcodes: 2222 These passcode should only be given to Authorised Personnel. Calibration Screen. To adjust the calibration simply press the Offset window you require to adjust and enter the difference between the PV and you calibrated device. For example if the PV is showing 10.0degC and you calibrated device indicates the cabinet is at 9.0dgC then the Calibration Offset that needs to be entered is -1.0degC 26-1-16 26

System Screen & Passcodes. By pressing the System Button on the Calibration Page the above screen is displayed. This is the System Settings Screen. It shows the Network Communication parameters, (These will only be displayed if connected to a network) The Time & Date settings, Passcodes and Memory information. To change the Time and date simply touch the parameter that needs to be changed and enter the current or required Time and Date. Please note that the Time does not automatically adjust for Daylight Savings. This needs to be manually adjusted. Passcodes can be changed if needed. Passcode Number 1 is the passcode for User 1. This is the passcode required to exit the screen saver mode. Passcode number 2 is the passcode for user 2 and allows access to the Calibration, System Settings page and the Program Screen. It advised that passcodes are only given to authorised personnel. Thermoline takes no responsibility for lost/forgotten passcodes. Please remember new passcodes. If Passcodes are forgotten they can be retrieved however it will incur the cost of a service technician to come to site. Memory information shows the amount of memory left on the Touchscreen before old data is lost. The number of data files indicates the number of days of data that is stored; this can be as high as 800days. The size of the raw data files is indicative of the amount of memory being used. It does not indicate the size of the data files that are downloaded to the Flash Memory USB port. When the files are downloaded to the Flash Memory USB port they are converted from a file specific with the touchscreen to a Comma Separated File (CSV). (See Data Menu). System Screen Service Screen. This screen is for the sole purpose of our service technicians or service contractors. This is a password protected screen and is only accessible by authorised Thermoline Technicians or Authorised Thermoline Contract Technicians. 26-1-16 27

Diagnostics Screen. The Diagnostics screen is simply a screen to help the operator when problems may occur. For example if the STAR-700 is operating a Program Cycle and there is a cycle of Power, the STAR-700 usually reverts back to SOV mode. However as power loss may occur due to storms and lighting strike and possibly construction work, the disruptive power supply may cause interference with the communication cable and cause the STAR- 700 Controller to turn the control actions for Temperature, Humidity and CO 2 Off. The Diagnostic screen allows the Authorised operator to turn the Temperature, Humidity and CO 2 functions back on again. It also shows the percentage output of each control function. This is a good diagnostic tool if the cabinet is not operating correctly. Diagnostic Screen. Contact Screen The Image Below is the Thermoline Contact Page. Contact Screen. 26-1-16 28

% RH % RH TEMPERATURE & HUMIDITY PERFORMANCE CLIMATRON 520DL With 6 x 54 Watt-DL 100 90 80 70 60 50 40 30 20 10 0 Temperature/Humidity Limits (Lights Off) Min RH Max RH 5ºC. 10ºC 15C. 20ºC 25ºC. 30ºC. 35ºC. 40ºC. 45ºC. Temperature 100 Temperature/Humidity Limits (Lights On) 90 80 70 60 50 Min RH Max RH 40 30 20 10 0 5ºC. 10ºC 15C. 20ºC 25ºC. 30ºC. 35ºC. 40ºC. 45ºC. Temperature Operations at 5.0degC or lower for an extended period of time will eventually result in the refrigeration cooling coil becoming a block of ice. It is a requirement that if operating a Night Temperature of 5.0degC or lower than the Day Temperature needs be at least 10.0degC or higher to allow for any ice formation to melt and drain away. 26-1-16 29

Lights Off. 100 90 80 70 60 Temperature Performance of Thermoline Climatron-520-SL. With 3 Shelf Light Trays (4x24WATT-SLT). 50 40 Min RH Max RH 30 20 10 0 5ºC. 10ºC 15C. 20ºC 25ºC. 30ºC. 35ºC. 40ºC. 45ºC. Lights On. 90 80 70 60 50 40 30 Min RH Max RHx3SLT Max RHx2SLT Max RHx1SLT 20 10 0 5ºC. 10ºC 15C. 20ºC 25ºC. 30ºC. 35ºC. 40ºC. 45ºC. Relative Humidity is based on an empty cabinet and an ambient condition of 25degC and 35%RH. 26-1-16 30

Temperature Performance of Thermoline Climatron-1100-DL. With 12 x 54WATT-DL. Lights Off 90 80 70 60 50 40 Min RH Max RH 30 20 10 0 5ºC. 10ºC 15C. 20ºC 25ºC. 30ºC. 35ºC. 40ºC. 45ºC. Lights On 90 80 70 60 50 40 Min RH Max RH 30 20 10 0 5ºC. 10ºC 15C. 20ºC 25ºC. 30ºC. 35ºC. 40ºC. 45ºC. Relative Humidity is based on an empty cabinet and an ambient condition of 25degC and 35%RH. 26-1-16 31

Lights Off 90 80 70 60 Temperature Performance of Thermoline Climatron-1100-SL. With 3 Shelf Light Trays (4x54WATT-SLT) 50 40 Min RH Max RH 30 20 10 0 5ºC. 10ºC 15C. 20ºC 25ºC. 30ºC. 35ºC. 40ºC. 45ºC. Lights On 90 80 70 60 50 40 30 Min RH Max RHx3SLT Max RHx2SLT Max RHx1SLT 20 10 0 5ºC. 10ºC 15C. 20ºC 25ºC. 30ºC. 35ºC. 40ºC. 45ºC. Minimum Humidity is based on an empty cabinet and an ambient condition of 25degC and 35%RH. 26-1-16 32

WARRANTY: Have the following information available when you contact the service department: Model number and serial number. This is generally found on the exterior of the cabinet in the form of a stick-on label. The company name, address, contact name, contact phone number. A brief description of the problem. All warranty claims must be reported to, and agreed to by a Thermoline representative prior to any work being carried out. 26-1-16 33

Standard 12 month Warranty Thermoline Scientific Equipment Pty Ltd ABN 80 000 859 129 ( Thermoline ) Thermoline warrants to the original purchaser that this product will perform to its product specification for a period of 12 months from date of purchase, provided that the installation of the product has been carried out in accordance with the latest version of the manufacturer's instructions and further provided that the use of the product complies with that specified in the relevant specification. Thermoline is not responsible for any loss or damage arising from incorrect usage, usage outside the suitability of the product as stipulated in the manufacturer's instruction, damage caused by accident, fire, flood, act of God or failure to properly install, operate or maintain the goods in accordance with the printed instructions provided. The following statement applies only to product sales that fall within the definition of a Consumer Sale set out in the Australian Consumer Law contained within the Competition and Consumer Act (Cth) 2012: Our goods come with guarantees that cannot be excluded under the Australian Consumer Law. You are entitled to a replacement or refund for a major failure and for compensation for any other reasonably foreseeable loss or damage. You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure. Notwithstanding the preceding clause and to the extent permissible by law, the liability of Thermoline is limited, in relation to the warranted product and at the option of Thermoline to: replacing the product or the supply of equivalent product; the repair of the product; the payment of the cost of replacing the product or of acquiring equivalent product; or the payment of the cost of having the product repaired. To the extent permitted by law, all other warranties whether implied or otherwise, not set out in this Warranty are excluded and Thermoline is not liable in contract, tort (including, without limitation, negligence or breach of statutory duty) or otherwise to compensate the Purchaser for: any increased costs or expenses; calibration/certification services; any loss of profit, revenue, business, contracts or anticipated savings; any loss or expense resulting from a claim by a third party; or any special, indirect or consequential loss or damage of any nature whatsoever caused by Thermoline s failure in complying with its obligations or the purchaser s failure due to accident damage, impact, misuse or negligence. The benefits given to the purchaser in this Warranty are in addition to other rights and remedies under a law in relation to the products or services to which this warranty applies. This warranty applies only to products purchased and installed in Australia and does not cover any consumable items e.g. filters, light globes, ultrasonic nebulizers. The warranty does not extend to labour and freight costs where the warranted product is located outside Australia. To make a warranty claim, contact Thermoline on 02 9604 3911 or service@thermoline.com.au. 26-1-16 34