Carbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output

Similar documents
Carbon Monoxide CO Transmitter ADT-X3-1110

Gas Central with built-in Gas Detector for Nitrogen Dioxide (NO 2

CMF, CMX & CMA series

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

Carbon Monoxide (CO) Gas Detector, 4-20mA GCO. Automatikprodukter. Oct. 15. Features. Technical Data. Design Features. Application.

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Two-Channel Gas Controller

Carbon Monoxide (CO) Gas Detector, 4-20mA or 2-10Vdc

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases

Nitrogen Dioxide Stand-Alone Detector - Analog, ModBus

Multi-Gas-Controller MGC2

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

PolyGard 2-channel Gas Controller MGC-03

Danfoss gas detection units

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features.

Danfoss gas detection units

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Toxic Gas Detection. Model F12. Toxic Gas Detection

User Manual. PolyGard Single Point Controller SPC3-11XX. Single Point Gas Controller Serial Number _E_1007. May 2009

IGD.CO.UK

Gas Controller Module GC-06

User Manual. PolyGard AT-3300 V3. Transmitter for Combustible Gases. Serial No. ET April 2009

APPLICATION DATA SHEET

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

Sensor unit MC2 with analog output for Freon gases and refrigerants

Danfoss gas detection unit Type GD Heavy Duty

Warranty Registration

SIL 2. Ultima X Series Gas Monitors CERTIFIED

INSTALLATION AND OPERATING INSTRUCTIONS

User Manual. PolyGard Gas Controller MGC3. Two-Channel Analog Gas Controller Serial Number _E _0907. September 2007

Oxygen (O2) Single-Point Gas Detection System

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

Carbon Monoxide Transmitter

PolyGard Digital Gas Controller DGC-05 RS-485 Bus

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

Model D12. Digital Gas Transmitter

O3TH. Ozone Detector c/w Indicator for Temperature/Humidity. Automatikprodukter. Features. Technical Data. Description. Ordering Codes. Dec.

CH 4 C 2 H 2 C 3 H 8 CO 2 H 2 H 2 S HFC NH 3 NO 2 O 2 O 3 SO 2

GAS DETECTOR ST400EC PART.NO

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

GAS DETECTION SYSTEMS

Danfoss gas detection Controller unit

Sensepoint. Fit For Purpose Flammable, toxic and Oxygen versions available High performance, low cost Suitable for new and retro fit applications

GasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability

Accuracy by Design Products for the HVAC Professional

ULTIMA XIR ULTIMA X 3 ULTIMA XE. ULTIMA X Series. [ State-of-the-Art Gas Monitoring]

VASTHI ENGINEERS. Vasthi Multi Gas Monitor/Analyzer. Sheet No. 1 of 4. Vasthi Multi Gas monitor/analyzer with alarm and Graphical Display.

Murco Core Product Guide Gas Leak Detection Solutions for all your building needs

Inc Series Digital Gas Detector/Controller. Operation Manual

Model D12-IR. Digital Gas Transmitter...

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

TOXIC GAS AND OXYGEN DETECTOR DTX 420 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS DTX420_MAN01_EN_V1R2

ESD3000 ESD200 Combustible / Toxic Gas Detector

ALTAIR 5X Multigas Detector Product Specification

GAS DETECTION SYSTEMS

portable gas analyser

THE BELGIAN PIONEER IN GAS DETECTION

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Electrochemical DrägerSensor Sensors for Fixed Gas Detectors

Sensepoint. Fit For Purpose Flammable, toxic and oxygen versions available High performance, low cost Suitable for new and retro fit applications

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety

Macurco DVP-120 / DVP-120M Detection and Ventilation Control Panel User Instructions

User Manual. PolyGard SPC Carbon monoxide (CO) gas detection and control system serial no. SPC April 01, 2004

TOCSIN 750 SERIES SAFE AREA GAS DETECTORS. 2-Wire Addressable Systems. 2 Core Cable Unscreened. 6 Standard 20mm Gland Entry Knockouts

Frequently Asked Questions

P R O D U C T D ATA S H E E T

Recalibrate the way you look at gas detection

Sieger Apex. Flexibility that meets your requirements

EXAMPLES OF HOW TO ORDER

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

EXAMPLES OF HOW TO ORDER

Stand Alone DYNAGARD SP Operation Manual

Warranty Registration

Warranty Registration

GAS DETECTION MANUFACTURED BY. Aerionics, Inc. Sioux Falls, SD Phone:

S5000 Gas Monitor. GMS5000.com

Xgard. Fixed detectors For flammable, toxic or oxygen gases

Version Inc Series Digital Gas Detector/Controller. Operation Manual

Zareba Metro Gas Detector

BST-MG01 Single Gas Detecting Alarm Manual Instruction

Quality. Water. Water Quality. Testing. Testing. Toxic Gas Detection. Toxic Gas. Detection. Air Quality. Monitoring. Monitoring. Monitoring.

Duct and Rough Service Carbon Monoxide Sensor

User Manual. PolyGard Single Point Controller SPC-43-20XX. Single Point Gas Controller for Refrigerant Gases Serial Number _E_.

Ammonia Leak Detector Manual

ESD500. ESD500 Combustible / Toxic Gas Detector

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Certifications. The Fixed Gas Detection People

ULTIMA X5000. MSAX5000.com

3years. Detection of explosive gases, toxic gases and oxygen. Infrared XP IR version. SIL 2 high reliability IP 66.

compact detector Detection of more than 200 flammable and toxic gases iso 9001:2008

OLC(T) 100 FIXED GAS DETECTOR

GLD-30 Gas Leak Detector

Macurco DVP-120 Detection and Ventilation Control Panel

GAS DETECTION International Gas Detectors CH4 NO

CO2 transmitters TRANSMITTERS TO DETECT CARBON DIOXIDE (CO 2 )

Combustible Gas Detection and Control System

Transcription:

Features Electrochemical sensor element (0)2-10 Vdc or (0)4-20 ma output, jumper selectable Standard IP65 plastic enclosure Measuring ranges 0-50 ppm 0-100 ppm 0-150 ppm 0-200 ppm 0-250 ppm 0-300 ppm 0-500 ppm 0-1000 ppm 0-2000 ppm Wide supply voltage range (18-28 Vac/dc) with LCD display to show actual ppm-range with LED indicators Power supply = Green Low-Alarm = Yellow High-Alarm = Red Overload protected Reverse polarity protected Continuous monitoring Low zero point drift Positoning stable Long life sensor Modular plug-in technology Applications IP55 stainless steel enclosure TL1 SSE To avoid unauthorized opening, the stainless steel enclosure can only be opened by the opening tool TL1 SSE with duct mounting set Options Relay Pack (2 alarm relays) *LCD display *LED indicator Buzzer (Siren) Heater RS-485 Modbus *Not for vehicle exhaust in parking structures (e.g. underground garages) engine repair shops engine test benches go-kart race cources loading bays tunnels shelters equipment rooms ventilation systems etc. Description CO detectors, and -series including digital measurement value processing and temperature compensation for the continuous monitoring of the ambient air to detect carbon monoxide concentrations (CO). Comfortable calibration routine with selective access release is integrated in the transmitter. The CO detector, and -series possesses a standard analog output (0)2-10 Vdc or (0)4-20 ma. As option RS-485 interface and 2 relays with adjustable switching thresholds are available. Due to the standard analog signal the CO detector is compatible to DDC and PLC.

Ordering Type no. ppm range Enclosure 050VC 0-50 ppm IP65 100VC 0-100 ppm IP65 150VC 0-150 ppm IP65 200VC 0-200 ppm IP65 300VC 0-300 ppm IP65 400VC 0-400 ppm IP65 500VC 0-500 ppm IP65 1000VC 0-1000 ppm IP65 2000VC 0-2000 ppm IP65 050VC 0-50 ppm IP65, duct 100VC 0-100 ppm IP65, duct 150VC 0-150 ppm IP65, duct 200VC 0-200 ppm IP65, duct 300VC 0-300 ppm IP65, duct 400VC 0-400 ppm IP65, duct 500VC 0-500 ppm IP65, duct 1000VC 0-1000 ppm IP65, duct 2000VC 0-2000 ppm IP65, duct 050VC 0-50 ppm IP55, s/s 100VC 0-100 ppm IP55, s/s 150VC 0-150 ppm IP55, s/s 200VC 0-200 ppm IP55, s/s 300VC 0-300 ppm IP55, s/s 400VC 0-400 ppm IP55, s/s 500VC 0-500 ppm IP55, s/s 1000VC 0-1000 ppm IP55, s/s 2000VC 0-2000 ppm IP55, s/s TL1 SSE Tool for opening stainless steel enclosure Options: Type no. Descriptions RP2 Relay pack (2 alarm relays) BZI Buzzer LCD LCD display LED LED indicator HEA Heater MOD RS-485 protocol Modbus CUS RS-485 protocol customer-specification SER TL2 Service tool Notes: Options LCD and LED not possible with stainless steel (s/s IP55) enclosure. For warning buzzer BZI, additional relay pack RP2 is needed. 300VC RP2 LCD (with Relay Pack and LCD display) Order example: 300VC RP2 LCD CO detector, (0)2-10 Vdc or (0)4-20 ma, 0-300 ppm Relay pack (2 alarm relays) Alarm relay 1: (advise threshold) Alarm relay 2: (advise threshold) LCD display 300VC RP2 LED (with Relay Pack and LED indicator) For LED indicator, additional relay pack RP2 is needed. Advise the thresholds for Low-and-High alarm when ordering relay pack RP2. LCD Display (LCD) in comination with Relay pack (RP2) and Buzzer (BZI) not available. LCD Display (LCD) in comination with Relay pack (RP2) available. LCD Display (LCD) in comination with Buzzer (BZI) available. Important notes before ordering: The recommended storage life is up to 6 months unpowered, Carbon Monoxide (CO) detectors are manufactured on request. As the storage life for Carbon Monoxide (CO) detectors is up to 6 months unpowered we want pre-payment before process the order to production department, this to avoid any cancellation of order. Delivery time is normally 4 weeks after receipt

Technical data Sensor element Output Power supply Electrochemical, diffusion (0)2-10 Vdc, load < 50 Kohm, (0)4-20 ma, load < 500 ohm, overload and short circuit proof 18-28 Vac/dc, (reverse polarity protected) 22 ma, max. (0.6 VA) and wall types: Sensor coverage 400 m2 to 500 m2 (recommended) Mounting height 1.5 to 1.8 m above floor Accuracy Repeatability +/- 3 ppm +/- 3% of reading Long term output drift < 5% signal loss/year Response time Sensor life expectancy Humidity range Continuous: Short time: Temperature range Continuous: Short time: Storage temperature t90 < 50 seconds 5 years, normal operation enviroment 15 to 90% non-condensing 0 to 95% non-condensing -10 to +50 C -20 to +50 C +5 to +50 C Pressure range Atmospheric ± 10% Cable entry Enlcosure/Protection Dimensions M20 Plastic IP65 Plastic IP65 for duct Stainless steel IP55 H130 x W94 x D57 mm H130 x W94 x D57 mm H113 x W135 x D45 mm excluding cable entry duct type Gas inlet Flow speed Duct diameter (ca.) Length of sampling pipe Tube length Mounting Via a sampling pipe/ connection tube Min. 5000 m/h, Max. 20,000 m/h Min. 0.1 m, max. 1.0 m 250 mm, adaptable to the duct diameter by cutting to lengths: 192, 133 or 77 mm 2 x 1000 mm Arrow at the sampling set in flow direction. Always mount in the middle of the duct. Keep a minimum distance of 1000 mm to duct bends etc. Weight Guidlines 300 g 350 g 500 g EMC_ Directive 2004/108/EC EN 61010-1:2010 ANSI/UL 61010-1 CAN/CSA-C22.2 No. 61010-1 CE

Built-in options Relay output Alarm relay 1 30 Vac/dc 0.5 A, potential-free, SPDT Alarm relay 2 30 Vac/dc 0.5 A, potential-free, SPNO/SPNC 30 ma, max. 0.8 VA Warning buzzer Acoustic pressure Frequency 85 db (distance 300 mm) 3.5 khz 30 ma, max. 0.8 VA. LCD Display LCD Two lines, 16 characters each 10 ma, max. 0.3 VA LED indicator Green-Yellow-Red Supply, low alarm, high alarm 10 ma, max. 0.3 VA Heater Temperature controlled +3 C +/-2 C Ambient temperature -40 C 0.3A; 7.5 VA Side Warning Devices / External Devices See separate datasheet Side Warning Devices / External Devices External flash light External buzzer External flash light and buzzer

Terminal Block Wiring 7 6 5 4 3 2 1 Bus_B Bus_A 4-20 ma input 0-10 Vdc or 4-20 ma output 24 Vdc out Ground 24 Vac/dc PCB Output 0-10 Vdc or 4-20 ma is jumper selectable on pcb. Power supply can be 24 Vac or 24 Vdc for both 0-10 Vdc output and 4-20 ma output. 4-20 ma output is 2-wire (loop) connection on terminals 1 and 4. 0-10 Vdc is 3-wire connection on terminals 1, 2 and 4. Relay outputs are options. Wire connection on screw terminal min 0.25 mm2 and max 2.5 mm2 Wire distance: 500m for 4-20 ma output and 200 m for 0-10 Vdc output. Cross sensitivity* Concentration Reaction (ppm) (ppm) Acetone, C 3 H 2 6O 1000 0 Acetylene, C 2 H 2 40 80 Ammonia, NH 3 100 0 Carbon Dioxide, CO 2 5000 0 Chlorine, Cl 2 2 0 Ethanol, C 2 H 5 OH 2000 5 Hydrogen, H 2 100 20 Hydrogen Sulphide, H 2 S 25 0 Iso Propanol, C 3 H 8 O 200 0 Nitric Oxide, NO 50 8 Nitrogen Dioxide, NO 2 50-1,0 Sulphur Dioxide, SO 2 50 < 0,5 * The table doesn t claim to be complete. Other gases, too, can have an influence on the sensitivity. The mentioned cross sensitivity data are only reference values valid for new sensors. We reserve the right to make changes in our products without any notice which may effect the accuracy of the information contained in this leaflet.