RE: USE OF FIREPRO IN POTENTIALLY EXPLOSIVE ATMOSPHERES

Similar documents
Beamex. Calibration White Paper. Calibration in hazardous areas

Explosion-protected actuator Page 259 of 292

Hazardous Areas - EXPLOSIONPROOF SOLENOIDS

Beamex Calibration White Paper. Calibration in hazardous areas

Overview of Hazardous Locations as They Relate to Solenoid Valves

ATEX, NOMENCLATURE AND CODING

Hazardous Area Classification in Oil & Gas Industry. A Fire Prevention Tool

Implementation of ATEX Guidelines

REGULATIONS EUROPEAN ATEX DIRECTIVE. INTERNATIONAL SCHEME: IECEx AREAS CLASSIFICATION DEFINED BY DIRECTIVE 1999/92/EC

Drive Technology \ Drive Automation \ System Integration \ Services * _0817* Inquiry Forms for Explosion-Proof Gearmotors

ATEX, NOMENCLATURE AND CODING

Guide for hazardous areas

A GUIDE TO EUROPEAN (EEC) CERTIFICATION FOR ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS

The R. STAHL Technology Group Worldwide Success with Competence and Customer Support

UL HAZARDOUS LOCATIONS SERVICES

Airo Wireless Intrinsically Safe White Paper. Written By: David Schmitt

MICROpeL 75 Combustible Gas Sensor Part Number: PM

1. GENERAL TECHNICAL INFORMATION

[ TECHNOLOGY ] and does this definition affect a burner.

Weighing Solutions for Hazardous Areas FULL COMPLIANCE WITH ATEX DIRECTIVE

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT

Erik Leider Project Engineer Hazardous Locations, Gas & Oil Underwriters Laboratories

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

Guide to Hazardous Location Approvals:

Guide to Hazardous Location Approvals: MICRO SWITCH Hazardous Area Limit Switches

TRASCO ATEX Couplings

ANNEX GD-CERT-EX-EN SIT

ATEX GUIDE. A short introduction to ATEX Terminology. Equipment for use in flammable atmospheres. Directive 94/9/EC

Seat Ventilation offers an extensive range of ATEX certified products and is undertaking great efforts to extend this range even further.

Explosion protection Marijan Gorše, dipl. ing.

INSTRUCTION & SERVICE MANUAL

EtherCAT Box Modules (EPxxxx-xxxx)

Guide to Intrinsically Safe Portable Radios

ATEX Vacuum Pumps in Accordance with the Directive 94/9/EG (ATEX 95) Technical Information

Selecting a Safe Tank Gauging Product. Understanding Hazardous Area Definitions for Equipment Approvals

WHAT WHITE PAPER IS POTENTIALLY EXPLOSIVE ATMOSPHERE CERTIFICATION AND WHY YOU. June 2010

ATM Lighting sp. z o.o

Smoke detection in hazardous areas:

ESSENTIAL EXPLOSION PROTECTION

Ex Products Highest level of safety under the most difficult conditions

PYROS. Código: FT-PY01-I Revisión: TECHNICAL DATA. Polycarbonate tube of 4 mm. thickness LIGHT FITTING. Laquered steel painted white

Introduction to Hazardous Electrical Location Classifications

ATEX Safety Switches. More than safety.

Explosive. Atmospheres. Safety and Reliability

VSD AND SS DRIVING ATEX MOTORS February 2014

ATM Lighting sp. z o.o

Working safely with flammable liquids

4P75 CiTipeL Combustible Gas Sensor Part Number: PM

A guide to the use of electrical equipment in potentially explosive atmospheres To view this document in PDF format click here.

Phoenix Explosion-proof. Pan & Tilt heads and Camera Housings for potentially exposed environments. Answers for infrastructure.

S T R I T T & P R I E B E I N C.

Understanding Hazardous Locations Concepts

Hazardous Area Classifications and Protections

Intrinsic Safety. Intrinsically Safe Solutions. Accurate Weighing in Hazardous Areas

Meeting NFPA standards for

Flammable Liquid Storage

4P-90 CiTipeL Combustible Gas Sensor Part Number: PM

Practical information about ATEX

CENTRAL STATE HOSPITAL PLAN SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS

manual addendum DELPHI Ex

Certification Supplement Manual

INSTRUCTION MANUAL. D2xB1XH1 & D2xB1XH2 Xenon Beacons For use in Hazardous Locations

Explosion-protected network cameras Safety first

Guidelines for Market Surveillance of Equipment for Explosive Environments (Hazardous Locations)

Intrinsically Safe Solutions

DUST EXPLOSION CODES AND STANDARDS: Ensuring Regional Compliance and Global Consistency

Hazardous area descriptions

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

Dual certification! Air handling units for potentially explosive atmospheres

Selection of Explosion Protected Equipment for Hazardous Locations. Compiled by: Pieter Coetzee ZONE 2 ZONE 1 ZONE 0.

EUROPEAN DIRECTIVES Explosive atmospheres ATEX 2014/34/EU

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems

IRceL CH4 Methane (CH 4

Apparatus Groups are sometimes referred to, erroneously, as Gas Groups.

Competence for Safety. ATEX Category 3 Description. Example of a zone division for combustible fluids (gases) and combustible dust

4) Intrinsic Safety Certification

Technical Ventilation

EXPLOSIONPROOF LED LIGHT FITTINGS TO USE IN ZONES 1,21 & 2,22 KDB 15ATEX0049X NEW

standards: standards:

ATEX - GUIDE. A short introduction to ATEX Terminology. Equipment for use in flammable atmospheres C E R T I F I E D DANISH TECHNOLOGICAL INSTITUTE

HOW TO FIND THE RIGHT DEVICE FOR YOUR FACILITY

ESSENTIAL EXPLOSION PROTECTION

ATEX 137. What it means for motor users

Certification Supplement Manual

CLASS I LOCATIONS ZONE CLASSIFICATION

Phoenix Flameproof. Pan & Tilt heads and Camera Housings for potentially explosive environments.

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES. ET 105:2001 (Second Edition)

OPTIBAR P 1010/2010 C Supplementary instructions

INSTRUCTION MANUAL. E2xB05 & E2xB10 Xenon Beacons For use in Hazardous Locations

CCTV Portfolio. Phoenix Explosion-proof Range

Smart encoders & actuators

Fieldbus Non-Incendive Concept takes FISCO into Zone 2 and Division 2 hazardous areas. Phil Saward

ATEX - GUIDE. A short introduction to ATEX Terminology. Equipment for use in flammable atmospheres

ATEX Explained A brief Introduction

THE BELGIAN PIONEER IN GAS DETECTION

Understanding Hazardous and Explosion-Protection Environments

Flammable gases Detectors. Model DAX 03F DAX 03F- C DAX 03F- H. Note for installation, use and maintenance. Version 1.2

Relays for use in hazardous locations. Class I, Division 2 and ATEX

Certificate of Compliance

INSTRUCTION MANUAL (ATEX / IECEx)

Transcription:

Limassol 20 th August, 2015 RE: USE OF FIREPRO IN POTENTIALLY EXPLOSIVE ATMOSPHERES This document is intended to provide clarification on the use of FirePro Condensed Aerosol Generators in Potential Explosive Atmospheres (ATEX). ATEX derives its name from the French title of the 94/9/EC directive: Appareils destinés à être utilisés en ATmosphères EXplosives. Introduction: As of July 2003, organizations within the EU must follow the directives to protect employees from explosion risk, in areas with a potentially explosive atmosphere. The two ATEX directives available are the following: ATEX 95 equipment directive 94/9/EC, (Equipment and protective systems), ATEX 137 workplace directive 99/92/EC, (Minimum Health & Safety requirements). 99/92/EC directive requires that employers must assess and categorize the potentially hazardous explosive atmospheres into zones. The classification of each zone identifies the probability occurrence of an explosion and its time frame or duration, if it occurs. Zone classification includes both gas/vapors and dust as the combustible (or explosive) substance and the various classes are listed in table 1. Zone 0 (gas) and 20 (dust) marked yellow, represent the areas with highest explosive potential hazard. Combustible European and IEC Definition of zone or division North American Area in which an explosive mixture is continuously present or for Gases Zone 0 Class I/Division 1 long periods Area in which an explosive mixture is likely to occur in normal Gases Zone 1 Class I/Division 1 operation Gases Zone 2 Area in which an explosive mixture is not likely to occur in normal operation and if it occurs it will exist for a short time. Class I/Division 2 Dust Zone 20 Area in which an explosive mixture is continuously present or for long periods Class II/Division 1 Dust Zone 21 An area in which an explosive mixture is likely to occur in normal operation Class II/Division 1 Dust Zone 22 An area in which an explosive mixture is not likely to occur in normal operation and if it occurs it will exist for a short time. Class II/Division 2 Table 1 ( of Zones or Class with the relevant explosive hazard and its duration) Products intended to be installed within ATEX areas must have the equivalent Ex. Label. This procedure in general requires third-party testing (by an accredited certifying body), however manufacturers can self-certify Category 3 equipment (for zone-2/zone-22) and Category 2 nonelectrical equipment for (zone-1/zone-21) accordingly.

North American North American Class II Division 2 (dusts) Class I Division 2 (gases) Class II Division 1 (dusts) Class I Division 1 (gases) Class II Division 1 (dusts) Class I Division 1 (gases) Dusts Suitability for explosive areas (ATEX) AREA CLASSIFICATION ZONING Category 1 equipment Gases, vapours and mists A place in which an explosive atmosphere in the form of a cloud of combustible dust in air is present continuously, or for long periods or frequently. Zone 20: Zone 0: The part of a hazardous area in which a flammable atmosphere is continuously present or present for long periods. (As a guide for Zone 0, this can be defined as over 1000 hours/year or >10% of the time) for example inside liquid fuel storage tanks. IIIC Electrically conductive dusts IIIB Nonconductive dust IIIA Combustible flyings A place in which an explosive atmosphere in the form of a cloud of combustible dust in air is likely to occur in normal operation occasionally. Category 2 equipment Zone 21: Zone 1: That part of a hazardous area in which a flammable atmosphere is likely to occur in normal operation (As a guide for Zone 1, this can be defined as 10 1000 hours/year or 0.1 10% of the time) for example re-fuelling areas. IIA (Propane) IIB (Ethylene) IIC (Hydrogen) IIIC Electrically conductive dusts IIIB Nonconductive dust IIIA Combustible flyings A place in which an explosive atmosphere in the form of a cloud of combustible dust in air is not likely to occur in normal operation but, if it does occur, will persist for a short period only. Category 3 equipment Zone 22: Zone 2: That part of a hazardous area in which a flammable atmosphere is not likely to occur in normal operation, and if it occurs, it will only exist for a short period (As a general guide for Zone 2, unwanted substances should only be present under 10 hours/year or 0 0.1% of the time) for example solvent storage areas. The solvent is normal contained in sealed drums however, if a drum is damaged during the process of moving it then a potentially explosive atmosphere could exist for a short period. IIA (Propane) IIB (Ethylene) IIC (Hydrogen) European and IEC European and IEC FirePro suitability for explosive areas (ATEX) Non-hazardous: Areas that do not fall into any of the above (IS NOT SAFE AREA ) Max Surface Temperature ( C) / Ignition temperature of the flammable substance Temperature class CENELEC Acetic Acid (T1),Acetone(T1),Ammonia(T1),Butane(T2),Cyclohexane(T3),Ethanol (ethyl alcohol)(t2),kerosene(t3),methane (natural gas)(t1),methanol (methyl alcohol)(t2),propane(t1),propanol (isopropyl alcohol)(t2),toluene(t1),xylene(t1) 450 T1 Ethylene(T2),Methyl Ethyl Ketone (MEK)(T2),Tetrahydrofuran (THF)(T3) IIA IIB 300 T2 Hydrogen(T1),Acetylene(T2) IIC 200 T3 135 T4 100 T5 Notes: Loucas Michaelides 85 T6

FirePro Testing and Appraisal regarding ATEX environments: FirePro full range of Condensed Aerosol Generators were assessed for their safe operation in explosive atmospheres by the following international accredited institutions: 1. UL/ULC: Underwriters Laboratory USA and Canada Pyrotechnic Containment Test 2. GEMPI: Designated Testing Laboratory and Certification Organization Hungary 1. Pyrotechnic Containment Test (conducted by Underwriters Laboratory to be in compliance with UL2775 standard and part of the UL listing procedure). The test protocol no. 26 is described in Figure 1 (below). Figure 1 (Pyrotechnic Containment Test Protocol no. 26) Pyrotechnic Containment Test Summary: The aim of the test was to discharge the aerosol generators inside an enclosure with an explosive air gas mixture. The intention of this test is to avoid igniting the explosive mixture upon and during discharging of the aerosol generator. UL requires that each test must be repeated 3 times. Initially, the explosive gas mixture is ignited for 3 consecutive times to demonstrate that the concentration used is explosive. Then the aerosol generator is installed (inside the enclosure) where the gas mixture is introduced and measured with calibrated gas analyzers, to reach the explosive value. Finally the generator is electrically actuated and the aerosol agent is discharged inside the enclosure without causing any explosion but instead, the discharged aerosol forms an inert atmosphere. Results of this test can be found in UL Test Record EX6960.

2. GEPMI Number of Test Report: J-10302/2014 5 GÉPMI Kft. The GEPMI test was conducted as a single and multiple configuration set-up, as illustrated in Figure 2 and 3 respectively (below). Test Protocol The installation is set-up by placing the electrical components of the system (module, sequential activators and battery) outside the ATEX zone, whilst the sensors (Linear Heat Cable and Aerosol Generators) are installed within. The fire rated linear heat cable (LHC) acts as the sensor thus allowing current to flow to the generators (from the battery) when the heat within the ATEX enclosure increases past the LHC temperature rating. The termination of the linear heat detector cable (within ATEX enclosure) is done using a termination box that has ex-certification of Ex II 2GD Eex e II with standard terminal blocks. Test Summary The FirePro aerosol generators, the linear heat detector cable and the Ex II 2GD ATEX termination box can be used in a) Zone 1 and 2 with presence of gases of IIA, IIB and IIC hazard groups and b) Zone 21 and 22 with presence of dusts of IIIA, IIIB and IIIC hazard groups. The FPC-4 control module can only be installed outside explosion hazardous areas, together with any power supply inside a case that has a minimum of IP 54 protection. The FP-BTA type can be used in Zone 1, 2, 21 and 22, because it does not contain any external source of ignition. Results of this test can be found at Test Report No. J-10302/2014 5 GÉPMI Kft. Conclusions: As a result of the above two (2) test reports, it can be concluded that FirePro Condensed Aerosols can be used in the following ATEX zones: a) Zone 1 and 2 with presence of gases of IIA, IIB and IIC hazard groups b) Zone 21 and 22 with presence of dusts of IIIA, IIIB and IIIC hazard groups.

Case Study: Assessment of Diesel Generator Rooms & Fuel Storage Areas as Potentially Explosive Areas Diesel is a combustible fuel and widely used in many industry applications from power generators to engines for (vehicle, railway, pumps, marine, etc.). Although Diesel is confined within the storage tank, fuel hoses and the engine cylinders, spillages may still occur (within the enclosure) either through 1) minor leakages (such as wetted seals) or 2) failures (such as breakdown of pump seals, gaskets, injectors or any other accidents). ATEX zone assessment for Diesel Generator rooms take into account A1) the release rate of the fuel, A2) flash point, A3) ignition temperature and A4) air ventilation. Each of the individual factors (A1 - A4) is explained further below. A1) The release rate of the fuel (or spillage) is proportional to the explosive hazard. Release rates are measured in hours and grouped as follows: Zone 0: Large spillages > 1000 hours Zone 1: Medium spillages = 10 1000 hours Zone 2: Small spillages < 10 hours NOTE: An oil spillage within a generator room or fuel storage area will not exceed 10 hours. A2) The definition of the Flash Point is the lowest temperature at which sufficient vapors are given off a liquid as to form a flammable mixture (with air), that can be ignited by an arc, spark, naked flame, etc. The danger to create a potential explosive air-gas mixture is when the room ambient temperature increases beyond the Flash Point temperature of the substance. Diesel has a flash point above 60 C. NOTE: The expected ambient temperature within a generator room or fuel tank area is not expected to exceed 50 C. A3) The Auto Ignition Temperature is the one at which the combustible substance will automatically ignite. Diesel has an Auto Ignition Temperature of 257 C. NOTE: The surface temperature of the generator itself is not expected to exceed 150 C. A4) Ventilation plays a major factor on the concentration build-up of potentially explosive fumes within the enclosure itself. Diesel generator rooms and fuel storage areas are typically designed to accommodate excessive air movement within the area. NOTE: Diesel generator rooms and fuel storage areas are typically designed to accommodate excessive air movement within the area.

Results: Taking into consideration the assessment factors A1 A4, it can be concluded that Diesel Generator Rooms and Fuel Storage Areas can be classified as Zone 2 according to ATEX classification, but typically they are classified as non-hazardous areas because of the low spillage duration time, high flash point, very high auto ignition temperature and excessive ventilation rates. Furthermore, NFPA 37 Standard for the installation and use of stationary combustion engines and gas turbines identifies safety methods to avoid the development of potentially explosive conditions within these areas such as cut-off fuel supply prior to agent discharge and ventilation requirements. References and Extracts NFPA 2010 engineering guidelines for fixed aerosol fire-fighting systems NFPA 37 - standard for the installation and use of stationary combustion engines and gas turbines UL Test Record EX6960. Test Report No. J-10302/2014 5 GÉPMI Kft.