QAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR

Similar documents
QAS-101 SERIES SINGLE CHANNEL CONTROLLERS

MODEL QTS-1800 SERIES WALL MOUNT DIGITAL AND ANALOG TRANSMITTER/SENSOR

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

1022 R/T Remote Monitor

GAS MONITOR Model Model

RAM3 Remote Alarm Module

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

Warranty Registration

Model 4001 Series Single Channel Controller

AMC-RAM-4. Refrigerant Alarm Module USER MANUAL. Please read the installation and operating instructions completely and carefully before starting.

! "! # Please read these installation and operating instructions completely and carefully before starting.

Model OEM-2 INSTRUCTIONS FOR USE

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

CMF, CMX & CMA series

INSTALLATION AND OPERATING INSTRUCTIONS

1228s Multidrop INSTRUCTIONS. Installation and Operation of the AMC-1228s Electrochemical Sensor Module For Use With Multidrop AMC Monitors

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

Warranty Registration

M3050 Detector Operator s Manual

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model COSTAR 24VC-e Single Relay

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

Operation Manual. Rev. D GEM-II Self-Contained Gas Detector.

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

ANALOX 101 D2 PORTABLE OXYGEN MONITOR USER MANUAL

RK-02 Multi Point Detector Operator s Manual

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

RK Multi Point Detector Operator s Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

Operation Manual. Rev. E GEM-II Self Contained Gas Detector.

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

RK Carbon Monoxide Transmitter Operator s Manual

Controllers. Instruction Manual WARNING

MACURCO INC. CONTROLLERS & CARBON MONOXIDE DETECTORS SS103-3A, SS103-10A SS102H, SS102HC-1 INSTALLATION & OPERATING INSTRUCTIONS

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

RK-05 Carbon Monoxide Detector Operator s Manual

Gas Monitor 1A1 Series

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

RK Carbon Monoxide Transmitter Operator s Manual

RK-05 Combustible Gas Transmitter Operator s Manual

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

RK Carbon Monoxide Transmitter Operator s Manual

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

RK/ RK Combustible Gas Detector Operator s Manual

Installation Manual. Expansion Module 0100 Version 1.0 EXP HBX Control Systems Inc.

User s Guide HHAQ-109. Portable Multi-gas Detector. Shop online at omega.com SM

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

Macurco HD-11 Hydrogen Gas Detector

MODEL QTS-8000 SERIES NON-INTRUSIVE CALIBRATION INDUSTRIAL TRANSMITTER/SENSOR

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

Instruction Manual WARNING

RK CO 2 Transmitter Operator s Manual

RK/ RK Carbon Monoxide Detector Operator s Manual

For the Safety of Your

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

GL-CO-RFG Channel Gas Leak Alarm System

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

RK Combustible Gas Transmitter Operator s Manual

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

3 Macurco Carbon Monoxide Detector CM-16A

MST, INC. MODEL 2002 CARBON MONOXIDE MONITOR (AMBIENT-TYPE) OWNER S MANUAL

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

SEC 2000 Millenium Infrared Gas Detector

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

Danfoss gas detection units

MST MODEL S1 AIRLINE "CO" MONITORING AND LOW PRESSURE WARNING SYSTEM MANUAL

Carbon Monoxide Sample-Draw Detector Operator s Manual

Macurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference

OPERATION & MAINTENANCE MANUAL

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Warranty Registration

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

AMC-CD2. Human Occupancy Detector INSTRUCTION MANUAL. Please read these instructions completely and carefully before starting.

RAM 50 Series Operation Manual

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

Instruction Manual PCS-400-XY. Pump Controller. Y=2: 4-20 ma Y=6: 0-10 VDC X=5: 1-5 VDC. 4 Pump Control Relays 1 Alarm Relay 1 Signal Fail

MST, INC. MODEL 2002 CARBON MONOXIDE MONITOR OWNER S MANUAL

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

SBS-H2. Hydrogen Gas Detector Kit. For battery charging rooms and other areas where hydrogen gas may be present

RK/ RK Oxygen Detector Operator s Manual

Model D12-IR. Digital Gas Transmitter...

Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit

Operation Manual. Rev. I SCC Self Contained Controller.

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006

Automatic Humidity Controller. Model 512 (Revision C) Operating Manual

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

Product Specifications Warning Light Control Cabinet

TG-10 Wall Mount Installation and Operation Manual. High Output Ozone Generator

Series 3300 TELEDYNE ANALYTICAL INSTRUMENTS. The 3300 series of low cost, microprocessorbased

MANUAL 8/12/05. Model BKP TM 100 INSTALLATION, OPERATION & MAINTENANCE. Commercial High Efficiency Heat Pipe Dehumidifier

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

Two-Channel Gas Controller

Transcription:

QAS-10000 SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR INSTALLATION, OPERATION AND MAINTENANCE MANUAL QUATROSENSE ENVIRONMENTAL LTD. 5935 OTTAWA STREET, PO BOX 749, RICHMOND, ONTARIO, CANADA. K0A 2Z0 PHONE: (613) 838-4005 FAX: (613) 838-4018 www.qelsafety.com email: QEL@QELsafety.com

GENERAL SPECIFICATIONS: MODEL NUMBER: SERIAL NUMBER: OPERATING RANGE: GAS TYPE ALARM SETTING LOW HIGH Carbon Monoxide 50 ppm/ve 100 ppm/ve Propane 10% LEL 20% LEL Ammonia 35 ppm 300 ppm Freon 500 ppm 1000 ppm Other SENSOR: Solid State Semiconductor Onboard Switch Setting: A B OFF ON OFF ON 1 X 1 X 2 X 2 X 3 X 3 X 4 X 4 X 5 X 5 X 6 X 6 X 7 X 7 X 8 X 8 X 9 X 9 X 10 X 10 X TIME DELAYS: RELAYS: HIGH RELAY Immediate HIGH RELAY Not Energized LOW RELAY Immediate LOW RELAY Not Energized AUX / FAIL RELAY Immediate AUX / FAIL RELAY Energized i

TABLE OF CONTENTS 1. SPECIFICATIONS:...1 2. THEORY OF OPERATION:...2 3. INSTALLATION:...3 4. TURN-ON AND TROUBLE SHOOTING:...7 5. CALIBRATION PROCEDURE:...8 6. WARRANTY STATEMENT:...9 ii

QAS-10000 SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR 1. SPECIFICATIONS: Power Supply: 120 VAC, +10% - 15%, 50 TO 60 Hz 5VA per module Relays: Audio Alarm: Three DPDT dry contacts: Lo, Hi, Fail/Aux 240 VAC/30 VDC 5 Amp Resistive, 3.7 Amp Inductive Field configurable latching, or non-latching Field configurable energized, or not energized Field configurable time delays 85 db at 1 foot Panel Indicators: Power ON Green LED High Set point Red LED Low Set point Yellow LED Aux Set point Red LED Sensor Fail indication Red LED Sensor: Calibration: Expected Sensor Life: Environment: Solid State Semiconductor Recommended once per year. In excess of 5 years Temperature -30 C to 40 C Humidity 0 to 90 % non-condensing Recommended mounting height: Carbon Monoxide 4 to 6 feet above floor Propane 1 foot above floor Ammonia 9 to 18 below ceiling Freon 1 foot above floor Other Consult Factory Do not mount near fans or doors where high velocity drafts occur, or where clean air enters area.

2. THEORY OF OPERATION: The QAS-10000 series is a modular multi point hydrocarbon detector/controller designed for generalpurpose applications. The QAS-10000 series detects hydrocarbons and controls three relays (DPDT) that may be used to actuate fans, alarms, etc. An internal audio alarm will sound if the sensor fails, if a high, or aux. alarm state exists (field configurable). The sensor is a broad spectrum, economical, highly reliable sensor, with a practical life expectancy of five years minimum. The semiconductor material in the sensing element is heated to about 300 C. In the presence of a reactant gas a chemical reaction occurs at the surface, altering the quantity of Oxygen atoms adsorbed onto the surface of the semiconductor. This causes a change in the resistance of the material. The change in resistance is measured and compared to the set points to actuate relays. These sensors are 'broad spectrum' sensors in that they respond to virtually all hydrocarbons. They are also affected to a much lesser amount by humidity and temperature. The solid-state sensor responds to all components of vehicle exhaust. Although Carbon Monoxide is a major factor in vehicle exhaust recent research has show that the unburnt fuel has long-term exposure hazards. With a sensor response relationship of 1 part CO signal to 3 parts hydrocarbon signal, we use a times 4 compensation factor for calibration gases when this sensor is used for vehicle exhaust e.g. 200 ppm CO calibration gas calibrates for 50 ppm CO in vehicle exhaust. This calibration ensures that the atmosphere remains clean of carbon monoxide and of fuel residuals. 2

3. INSTALLATION: CO: Automobile-parking garages: Mount 4-6 feet above the floor. Bus and truck barns: Mount where vehicles exhaust upwards, it is often useful to mount the units on the ceiling. C3H8: Propane is heavier than air. Mount close to the floor and take note of any low points where gas may pool or collect. NH3: Mount at ceiling height. For high ceilings, two sensors are recommended, the second about 6 feet above the floor. Freon: Freon gases are heavier than air. Mount near the floor and take note of any low points where gas may pool or collect: Always try to mount the unit with sensor point downwards. Do not mount near fans, doors, or other places where high velocity occurs or where clean air enters. Most users will find it useful to have a time delay on fan starting off 5 to 10 minutes to prevent nuisance alarms.. 3

SENSOR INSTALLATION: 3-wire sensor. Shipped lose, the sensor must be removed and mounted to the enclosure, or placed remote from the unit mounted to a standard 2 x 4 electrical junction box. : Red to sensor '+' (Terminal 15) : Black to sensor '-' (Terminal 13) : Yellow to signal 'sig' (Terminal 14) Maximum loop resistance is 35 ohms for remote sensor placement (over 4000 ft for 16 AWG standard) 4

FUNCTION CONTROL SWITCHES: The QAS-10000 series has switches on the circuit board for controlling a number of functions: relay action, time delays, buzzer enable, relay actuation in case of sensor failure. Turn off power and pull the card module from the enclosure to set these switches. Function Switch A Function Switch B Low and High Relay Aux/Fail Relay Delay Switches Delay Switches 1) Low Relay 1) Buzzer 1) 34 seconds 1) 136 seconds On = Not normally energized On = Sounds w/aux. Off = Normally energized Setpoint 2) Low Relay 2) Buzzer 2) 68 seconds 2) 273 seconds On = Latching On = Sounds w/high Off = Non-latching Relay 3) Low Relay 3) Buzzer 3) 136 seconds 3) 546 seconds On = Instant actuation On = Sounds w/aux. Off = Delayed actuation Relay 4) High Relay 4) Buzzer 4) 273 seconds 4) 1092 seconds On = Not normally energized On = Latching Off = Normally energized 5) High Relay 5) Aux. Setpoint 5) 546 seconds 5) 2184 seconds On = Latching On = Ordinary setpoint Off = Non-latching Off = Fail or deficiency 6) High Relay 6) Buzzer 6) 1092 seconds 6) 4368 seconds On = Instant actuation On = Sounds after High Off = Delayed actuation Delay. 2B must Be off 7) Aux. Relay 7) High Relay 7) 2184 seconds 7) 8737 seconds On = Not normally energized On = Latches after Off = Normally energized Delay 8) Aux. Relay 8) Aux. Setpoint 8) 4368 seconds 8) 17475 seconds On = Latching On = Activates High Off = Non-latching Relay 9) Aux. Setpoint 9) Aux. Setpoint On = Instant actuation On = Activates Low Relay 10) Aux. Setpoint 10) Aux. Relay On = Delayed actuation On = High setpoint activates Aux. relay in delay mode Note: The LED s will always turn on immediately, regardless of switch settings. 5

RELAY WIRING: The relays are double pole, double throw, meaning that each relay is two relays in one. Each "side" having one normally open contact, and one normally closed contact arranged about a common center pin. 6

4. TURN-ON AND TROUBLE SHOOTING: Upon unit power up, there is a characteristic turn-on cycle. As the sensor comes up to operating temperature and stabilizes, the signal may rise to high alarm before settling again to zero. This takes two or three minutes. (If relay time delays are turned on, this phase should pass without activating the relays). If the unit has been off for more than three days, it is best to wait three days before calibration to ensure that it has stabilized fully. If the unit has been off for only an hour or two wait at least an hour before calibrating. TEST SWITCH: Pressing the test switch on the front panel will simulate a high alarm condition. This tests the LED and relay actuation. If time delay switches are active, then the relays will activate after their proper delays. SENSOR FAIL DETECTION: The fail circuit detects when the sensor fails or connecting wiring is broken. The audio alarm will sound during fail, providing that the appropriate switches are on. The low and high relays may be selected to engage during a fail condition providing the appropriate switches are on. 7

5. CALIBRATION PROCEDURE: You will need two concentrations of the target gas (three if Aux. is used as a setpoint) for low and high setpoints. See General Specifications on page i for concentrations. Apply the gas at the concentration you wish to set alarm actuation, allow 1-2 minutes for the sensor to stabilize (monitor the voltage at terminals 13 and 14 on the panel if necessary) and adjust the potentiometer on the front of the QAS-10000 monitor until the appropriate LED just turns on. The sensors are quite variable from sensor to sensor and very non-linear in response to gas. The sensors are somewhat affected by ambient humidity; but the gas supplied for compressed air cylinders is completely dry. Use a small humidifier when calibrating to give approximately ambient humidity. QEL s humidifying calibration caps give about 60% RH when fully wetted. Note that bubbler type humidifiers can give the reverse problem, which is fully saturated humidity. A voltage reading is supplied on the panel terminal blocks for each channel. Measure between Auxiliary Setpoint Signal (Terminal 16) and Neg. (Terminal 13.). FAIL is set at 0.15 Volts at the factory. 8

6. WARRANTY STATEMENT: The information contained in this manual is based upon data considered accurate; however, no warranty is expressed or implied regarding the accuracy of this data. All QEL equipment is warranted against defects in material and workmanship for a period of two years from date of shipment with the following exceptions: Electrochemical Sensors (Toxic) Catalytic Sensors (Combustible) Six Months One Year During the warranty period we will repair or replace, at our discretion, any components or complete units that prove, in our opinion, to be defective. We are not liable for consequential or incidental damage to auxiliary interfaced equipment. A returned material authorization number should be obtained from the factory prior to returning any goods. All return shipments must be shipped freight prepaid and a copy of the maintenance records should accompany the unit concerned. Warranty should be considered F.O.B. the factory. Labour and travel time are chargeable for any field site visits required for warranty work. LIMITED LIABILITY All QEL systems shall be installed by a qualified technician/electrician and maintained in strict accordance with data provided for individual systems in the form of installation/maintenance manuals. QEL assumes no responsibility for improper installation, maintenance, etc., and stresses the importance of reading all manuals. QEL shall not be responsible for any liability arising from auxiliary interfaced equipment nor any damage resulting from the installation or operation of this equipment. QEL s total liability is contained as above with no other liability expressed or implied, as the purchaser is entirely responsible for installation and maintenance of systems. This warranty is in lieu of all other warranties, expressed or implied, and no representative or person is authorized to represent or assume for QEL any liability in connection with the sales of our products other than that set forth herein. NOTE: Due to on-going product development, QEL reserves the right to change specifications without notice and will assume no responsibility for any costs as a result of modifications. For further information or assistance, contact: QUATROSENSE ENVIRONMENTAL LTD. 5935 Ottawa Street, PO Box 749 Richmond, Ontario K0A 2Z0 Tel: (613) 838-4005 Fax: (613) 838-4018 Email: QEL@QELsafety.com Web: www.qelsafety.com 9