Water Safety Shut-Off Valve HON 790. Product information. serving the gas industry worldwide

Similar documents
Self-operated Temperature Regulators Series 43 Temperature Regulators Type 43-1 Type 43-2

Worldwide Contacts. Technical Data

opening trap 30 mm Space required for Space required for opening trap 30 mm MK 45-1 with flanged ends (to DIN)

Technical Data. Sizes 2 12 Inch (DN50 DN300)

Catalog. Self-operated Regulators Volume 2 Temperature Regulators

Honeywell Control Valve. HFP Asia Pacific

VIESMANN. VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW.

GESTRA Steam Systems DK 45. English. Installation Instructions Steam Trap DK 45

Yarway Narvik Steam Desuperheater Series 4300 TempLow

MK 45-1 MK 45-2 MK 45 A-1 MK 45 A-2

GESTRA Steam Systems BK 15. Installation Instructions Steam Trap BK 15, DN 40-50

Supplementary instructions Bypass 72 Bypass tube with VEGAFLEX level sensor

Temperature Sensor TRG Original Installation Instructions English

LINDOFLAMM thermal engineering.

Differential Pressure and Flow Meter. Media 5 Indicator 160 Ø PN 50

Conductivity Electrode LRG Original Installation Instructions English

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

Safety vacuum drying oven for flammable solvents

SMK 22 SMK SMK SMK 22-82

Level Electrode NRG Original Installation Instructions English

Deluge Valves. Model 68 DE\ EL. Electrically Actuated Remote-Reset Deluge Valve. Dorot Fire Protection Division. Certification & compliance by design

Technical Data. Sizes 2 in. (DN50) to 16 in. (DN400) Approvals UL and ULC Listed FM Approved

Rotameter series 250 metal tube variable area flowmeter

EW447-EW452 Series Mechanical Heat Meters FOR HEATING AND COOLING APPLICATIONS

Pekos Valves stocks on line

Mounting and Operating Instructions EB 2231 EN

PRODUCT INFORMATION. Liquid ring vacuum pumps Liquid ring compressors. Series LVP

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

Mechanical seals external, single or double, to DIN EN 12756

AM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74

SUBMERSIBLE PUMPS For water with particulate matter 2 pole - 50 Hz 2 ranges : SS 304 & SS 316 L

Proportioners for Stationary Extinguishing Systems

Care and Maintenance

CBU144. Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717. Product specification sheet

SERIES 46000E Bi-Directional In-Line Deflagration Flame Arrester

Operating Manual. Model: Float-Controlled Condensate Trap, PN Safety instructions. 2 General description and usage

Combi Modular System. Standardised centrifugal pumps EN 733 ISO 2858 ISO 5199 API 610

Operating Manual. Model: 1400 Model: 1400-N RIFOmat Float-Controlled Condensate Traps, PN Safety instructions. 2 General description and use

GESTRA Steam Systems BK 37 BK 28 BK 29. Installation Instructions Steam Trap BK 37, BK 28, BK 29 BK 37 ASME, BK 28 ASME, BK 29 ASME

COMPACT FLAME CONTROLLER CFC 1000

Level Electrode NRG NRG Original Installation Instructions English

Water level controller and limiter

Industrial Cast-in Circulation Heaters for ATEX/IECEx hazardous areas or in non-atex version

FLOAT AND THERMOSTATIC STEAM TRAPS FLT17 (DN 1/2 to 1 ; DN15 to DN25)

SIHI LPH-X - Liquid Ring Vacuum Pump One Stage

SIHI LPH-X - Liquid Ring Vacuum Pump One Stage

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

GESTRA Steam Systems ER 50-1, ER Installation Instructions Level electrode

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

NRG NRG NRG NRG

VST Series. INAIL approved and calibrated safety valves. Technical Data Sheet. WattsIndustries.com

Vacuum drying oven for non-flammable solvents

Installation & Operating Instructions

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

HTM Circulation Pumps acc. to DIN EN 733 Type NKX

Installation, Operation & Maintenance Instructions

Rosemount 3051CFP Integral Orifice Flowmeter

USER S MANUAL ATH WH220

FEEDWATER TANK WITH DEAERATOR DATASHEET. Capacity 1000 to lt Operating Pressure 0,5 bar

Each burner shall be equipped with a Micro-Processor Based Burner Management Flame Safeguard and Parallel Positioning Control System.

Instructions for Installation, Operation, Care and Maintenance

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

VALVES SECTION 15100

MANUAL Oil Level Sensor

(Alarm Valve) & ' ( ()& * +,, & +-,. /0-

Pekos Valves stocks on line

Köllemann GmbH Page 1 / 16

Cleaning System. Amajet. Type Series Booklet

Flame Rod Manual. Publication Rev A

OEM Sensors for HVAC manufacturers Heat recovery Chiller

Infrared Flame Detectors

COMPACT FLAME CONTROLLER CFC 2000

cooled, Non-heated ATH 1603 M, DN 200 CF-F, External drive electronics, Water cooled, Non-heated

Brazed heat exchanger, XB

PROTEGO Deflagration Flame Arresters. and Vent Caps. Volume 2. end-of line. Volume 2. for safety and environment

Temperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25)

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

THERMODYNAMIC STEAM TRAP

C19 UNIVEX. High Vacuum Experimentation Systems UNIVEX 300, UNIVEX 450 UNIVEX 350, UNIVEX 450 B Special plants

Corrugated Coated Stainless Steel Hoses for gas use with European Standard EN 15266:2007

One giant leap for safety: AZM400.

Single stage operation oil burner

Installation and maintenance manual

TRG 5-53 TRG 5-54 TRG 5-55 TRG 5-57

UV Flame Supervision System

Cartridge Heaters. Metric FIREROD Cartridge. Applications and Technical Data

Flow Measurement SITRANS F C

GESTRA Steam Systems LRG English. Installation Instructions Conductivity Electrode

Model: 1200 Model: 1200-G Model: 1200-N Float-Controlled Condensate Trap, PN 40

Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing

Model: 1100 Float-Controlled Condensate Trap, PN 25

TECHNICAL DATA. Wet 26a. February 22, 2009

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

VersaFlow Coriolis 100 Mass Flow Sensor Technical Datasheet. Specification

STEAM TRAPS

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C TYPES

Calypso exact. Thermostatic Radiator Valves With stepless precision presetting

Temperature controller for steam (PN 25) AVT / VGS - external thread

Operating Instructions

Transcription:

Product information serving the gas industry worldwide

Applications, characteristics, technical data Applications Installation in the hot water circuit of gas pre-heater systems for safeguarding of the boiler system Characteristics 2 Simple construction Activation with energy from the internal medium Low pressure loss Simple functional testing technical data Permissible pressure PS 160 bar, DN 200 = 250 bar Permissible temperature 140 C medium / environment Nominal width DN 25, DN 50, DN 80, DN 100, DN 150, DN 200 Type of connection Materials Supplemental fixtures (options) Function and strength Installation takes place between the flanges according to DIN EN 1092-1 -PN 10 to PN 40, without DN 200 or ANSI B 16.5 (DIN EN 1759-1) Class 300 RF, Class 600 RF, Class 900 RF/RTJ* and Class 1500 RF/RTJ* DN 200 only Class 600 RF or higher Main valve body Brass** only DN 200: Niro Internal parts Brass, Niro** Niro Seals FPM/FKM Electrical remote indication of the valve position CLOSE Electrical magnet release with application of current / current failure (solenoid valve parallel to the control device) DIN EN 14382 according to Explosion protection All mechanical components of this device are without inherent ignition sources. They are not subject to ATEX 95 (94/9/EC). All electronic accessories, on the other hand, meet ATEX requirements. CE mark in accordance with PED 8 * Version RTJ on request ** other materials on request Setting ranges of SSV control devices Control device Setpoint spring No. SSV setting range W d (bar) Accuracy group AG 1 2 3 2.0 2.5 2.5 3.5 3.5 16.0 5 2.5 2.5

Dimensions I Stud bolt Connection Gas pre-heater d Connection Boiler system Test connection I G1/4 Test connection II G1/4 3 Dimensions in mm Pressure stage Diameter d DN 25 DN 50 DN 80 DN 100 DN 150 DN 200 PN 10 162 218 PN 16 142 PN 25 73 107 168 224 PN 40 Class 300 178 247 148 Class 600 190 263 318 Class 900 165 285 356 ** 140 205 Class 1500* 171 280 350 Installation length l PN 10 140 160 160 160 240 280 Class 600 Class 900 Class 1500* ** 170 170 180 250 310 stud bolt for flange connection Pressure stage Stud bolt Nuts PN 10 to PN 40 DIN 2509 DIN EN ISO 4032 Class 300 to Class 1500* ASTM A 193 sz. B7 ASTM A 194 sz. B7 *) PS = 160 bar, DN 25 DN 150 **) DN 25 in pressure stage > Class 600 on request K VS value in m 3 /h DN 25 DN 50 DN 80 DN 100 DN 150 DN 200 Flow pipes 10 35 99 135 297 524 Return pipes 11 41 114 152 328 548

Construction and mode of operation 4 The safety shut-off device (SSV) HON 790 is installed in the hot water circuit of gas pre-heaters (supply and return). The device is a link between the gas pre-heater (heat exchanger), which is designed for the maximum permissible inlet pressure of the gas and the boiler system measured for a low pressure. If a defect in the gas pre-heater (heat exchanger) causes an overflow of gas into the hot water circuit and thus a pressure increase, the SSV HON 790 blocks the boiler system from the inlet-pressure-proof heat exchanger when the adjusted release pressure is reached. In the process, it does not matter whether the pressure increase in the hot water circuit takes place very slowly or abruptly. The SSV HON 790 consists of the main valve and the control device. The valve body is designed without flanges and is clamped in place with stud bolts between the connection flange of the heat exchanger and the connection flange of the supply and / or return line leading to the boiler. The valve body has an axial opening, wherein the surface of the valve cross-section nearly corresponds to the surface of the nominal connection width. Test connections I and II, which lead to the spaces above and below the valve seat, are provided for connection of control manometers and for the conducting functional tests. In normal operation, all spaces of the safety shut-off device are subjected to the boiler pressure in the hot water circuit of the natural gas pre-heater. In the process, the valve plate is held in the open position by the valve spring. The valve plate is shielded from the flow forces of the circulating hot water by a shielding disc so that unintended closing is prevented. If the pressure in the hot water circuit rises due to a leak in the heat exchanger, the control devices opens 0.3 bar to 1 bar before the adjusted release pressure is reached, and a small quantity of water is released. The limit pressure at which the control device opens depends on the nominal with and installation position of the SSV HON 790; refer to the Operating and maintenance manual, spare parts HON 790.20 for more specific details. The pressure in the intermediate chamber below the valve piston is maintained at a nearly constant level while the pressure in the remainder of the system above the valve piston continues to rise. Shielding disc Test connection I to the gas pre-heater Main valve body Valve plate with seal Valve seat Guide piece Remote indicator (option) Valve stem Valve piston Intermediate chamber Water stopper Setpoint adjuster Valve spring Test connection II to the boiler system Control device Discharge area

Construction and mode of operation Once the force acting on the valve piston from the pressure difference between the upper side of the piston (pressure in the heat exchanger) and the intermediate chamber (pressure regulated by the control device) is greater than the pre-tension force of the valve spring, the SSV closes. The valve plate is then forms a seal on the valve seat and assures the pressure-tight blocking of the hot water circuit. The closed status of the valve plate is indicated electronically in the version with remote indication. SSV release pressure Control device opens Pressure p approx. 0.3 1 bar Pressure in the preheater (heat exchanger) Pressure on the boiler side 5 Operating pressure of the Hot water circuit Pressure in the intermediate chamber Beginning of the fault SSV closes Time t The safety shut-off device (SSV) then opens again if the pressure in the heat exchanger (above the valve plate) is brought to a value below the release pressure of the control device (SSV release pressure minus 0.3 to 1 bar). The remote indication is available in two different versions depending on the temperature in the hot water circuit; it cannot be retrofitted up to DN 200. Pressure loss depending on the flow in the hot water circuit Pressure Druckverlust drop p p in in bar bar 1,00 0,70 0,50 0,30 0,20 0,10 0,07 0,05 0,03 0,02 DN 25 DN 50 DN 80 DN 100 DN 150 DN 200 p max Configuration Auslegung 0,01 1 3 4 5 7 10 20 30 50 70 100 200 300 400 500 2 Flow Durchfluss rate Q n in m 3 /h Example: Nominal width DN 100, flow rate Q = 45 m 3 /h > pressure loss p = 0.1 bar Observe: The pressure loss should not exceed 0.5 bar. The SSV is arranged in the supply and return. The pump should be designed to accommodate for 2 x the pressure loss.

Assembly, commissioning and maintenance DVGW worksheets G495 and G499 must be observed. The Operating and maintenance instructions, spare parts HON 790.20 contain detailed information on installation, operation, maintenance and spare parts. Only vertical installation is permitted for devices with nominal widths DN 150 and DN 200; with other nominal widths there is no limitation with respect to the installation position. The control connections must be freely accessible for functional tests in the system and equipped with a shut-off valve. With devices with electrical remote indicator (position indicator), it must be ensured that the remote indicator does not point down. Bear in mind that remote transmission equipment must not be covered with insulation. 6

Device designation Example HON 790a 50 300 F1 / F / E1 / S So NOMINAL WIDTH DN 25 25 DN 50 50 DN 80 80 DN 100 100 DN 150 150 Type Nominal width Pressure stage Control device with spring Electrical remote indication of the valve position CLOSE Electromagnetic release with application of current Stud bolt Special design 7 DN 200 200 PRESSURE STAGE PN 10 10 PN 16 16 PN25 25 PN40 40 Class 300 300 Class 600 600 Class 900 900 Class 1500 (PS = 160 bar, DN 25 DN 150) 1500 CONTROL DEVICE Spring Setting range W d in bar F 1 2.0... 2.5 F 1 F 2 2.5... 3.5 F 2 F 3 3.5... 16.0 F 3 REMOTE INDICATION Electrical remote indication of the valve position CLOSE ELECTROMAGNETIC RELEASE F Release with application of current E 1 Release with current failure E 2 STUD BOLT With stud bolts S SPECIAL DESIGN (MUST BE EXPLAINED IN MORE DETAIL) Special design So Subject to technical changes.

For More Information To learn more about Honeywell s Advanced Gas Solutions, visit www.honeywellprocess.com or contact your Honeywell account manager GERMANY Honeywell Process Solutions Honeywell Gas Technologies GmbH Osterholzstrasse 45 34123 Kassel, Germany Phone: +49 (0) 561 5007-0 Fax: +49 (0) 561 5007-107 HON 790.00 2017-01 2017 Honeywell International Inc.