International Gas Detectors Ltd. Siting Gas Detectors. Gas detectors usually fall into three specific groups for placement

Similar documents
2-WIRE SYSTEMS OLIVER IGD. 2-Wire. Version 3.2 T750-INST. Addressable. Triton House Crosby Street Stockport SK2 6SH England

P R O D U C T D ATA S H E E T

TOCSIN 750 SERIES SAFE AREA GAS DETECTORS. 2-Wire Addressable Systems. 2 Core Cable Unscreened. 6 Standard 20mm Gland Entry Knockouts

GAS DETECTION International Gas Detectors CH4 NO

Xgard. Fixed detectors For flammable, toxic or oxygen gases

P R O D U C T D ATA S H E E T

ASHRAE Safety Standards. Mechanical Rooms and Gas Detection in Commercial Applications

P R O D U C T D ATA S H E E T

EAGLE 2. 6 Channel Capacity. Inlet fitting. Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility

IGD. O p e r a t i o n a n d M a i n t e n a n c e V International Gas Detectors. Triton House Crosby Street Stockport SK2 6SH England

GAS DETECTOR ST400EC PART.NO

Your trusted partner in providing the best fixed Gas Detection Sales and Service in Western Canada

TOCSIN 750 SERIES OLIVER IGD. Triton House Crosby Street Stockport SK2 6TS England

P R O D U C T D ATA S H E E T

Dräger Polytron Pulsar 2 Detection of flammable gases and vapours

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

Dräger REGARD -1 Control System

Quality. Water. Water Quality. Testing. Testing. Toxic Gas Detection. Toxic Gas. Detection. Air Quality. Monitoring. Monitoring. Monitoring.

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

Warranty Registration

UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY

CH 4 C 2 H 2 C 3 H 8 CO 2 H 2 H 2 S HFC NH 3 NO 2 O 2 O 3 SO 2

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS

BEP Marine Gas Detector 600-GDRV

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

Monitores Personales. Personal Monitor

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

BEP Marine Gas Detector FD-2

AGT 1 Confined Space. Authorised Gas Tester 1. Scienco Limited. Authorised Gas Tester 1 1

KAE Gas Alarm Operation Manual

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Certifications. The Fixed Gas Detection People

Dräger PIR 7200 Toxic Gas Detection Transmitter

KAB Gas Alarm Operation Manual

RAE Systems Systems. User Presentation. October Protection Through Detection

SMOKE CONTROL - NEW DIRECTIONS

OLC(T) 100 FIXED GAS DETECTOR

Safe Operation Manual. Honeywell IQ Force Gas Detector

Dräger REGARD -1 Control System

EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL

Gas Detection. - Disposable - Serviceable. Single Gas Detectors

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Aluminium or Stainless Steel version

3years. Detection of explosive gases, toxic gases and oxygen. Infrared XP IR version. SIL 2 high reliability IP 66.

Inc Series Digital Gas Detector/Controller. Operation Manual

HOW TO SPECIFY A DELPHIAN SYSTEM

up to 1.2 m or 3.9 ft. deep). So if you drop the Honeywell BW Ultra in a vat or take it into a dust-prone environment,

Gas Detection in Process Industry The Practical Approach

3M Oldham OLCT 100. Description. Fixed Gas Detector

Operation and Maintenance Manual

P R O D U C T D ATA S H E E T

TC100N. Fixed Gas Detector Operation Manual

Use of R1234yf, R744 (CO 2 ) and R134a in automotive air conditioning

Cadet Entry Level Award(ELA) Part Four. Fire Safety

Electrochemical (EC) DrägerSensors for Fixed Gas Detectors

DGS - Danfoss Gas Sensor Check / Calibration Procedure

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

Dräger X-am 5000 Multi-Gas Detector

Using CFD to Analyze Gas Detector Placement in Process Facilities

CH4 NO TOC-30A-AN1 TOC-30A-ANN TOC-30A-AN2 TOC-30A-AN3. Pepper Road Bramhall Technology Park Stockport SK7 5BW England. International Gas Detectors

AT-G-SENSE Gas Sensing System

GAS ANALYSIS / DETECTION Gas Detector

EC24. Operation Manual. (Type MWG 2411, MWG 2412, MWG 2413 and MWG 2414)

GL-CO-RFG Channel Gas Leak Alarm System

PRODUCT GUIDE. ionscience.com Unrivalled Gas Detection.

Maintenance Solutions from SE Controls

Zareba Metro Gas Detector

Dräger PIR 7200 Detection of toxic gases and oxygen

Dräger Polytron Pulsar 2 Detection of flammable gases and vapours

BP MAINTENANCE WORK INSTRUCTIONS FREQUENTLY ASKED QUESTIONS

OLCT 100 DETECTION DE GAZ FIXE. Certifications. Better detection. Better protection. Detection of Combustible, Toxic or Oxygen gases

The Art of Gas Detection

t w. marlowefireandsecurity.com e.

Datalogging as standard

Gas Detection. MeshGuard RAE Systems by Honeywell Battery-Powered Wireless Gas Detector

Portable Gas Detection Practice

P R O D U C T D ATA S H E E T

Process Control PIP PCEA001 Fixed Gas Detection Guidelines

Sieger Apex. Flexibility that meets your requirements

SAFESITE Multi-Threat Detection System

BUY IT! THE UK S No1 PID HIRE COMPANY PIDS MONITORS FOR: HEAT STRESS, VIBRATION, MULTIGAS, CONFINED SPACE, LANDFILL GAS, NOISE & SOUND, MERCURY VAPOUR

Microtector II G gas-detector with performance test approval. Worldwide Supplier Of Gas Detection Solutions

VENTIS PRO SERIES. Product Guide

Version Digital Gas Dector/Controller. Operation Manual

Ammonia Detection System Codes and Design Specifications

Understanding the practicalities of using gas detectors in confined spaces

Warranty Registration

Application Bulletin. LNG / LPG Facilities FLAME AND GAS DETECTION FOR LNG FACILITIES

intrinsically safe detector for hydrocarbon gases

CERTIFICATE OF FIRE APPROVAL

APPLICATION DATA SHEET

NG-9B NATURAL GAS ALARM

Dräger X-am 5000 Multi-Gas Detection

Version Inc Series Digital Gas Detector/Controller. Operation Manual

Operate the Mutli-Gas Monitor PID

:57: of 15 pages

Version Digital Gas Detector/Controller. Operation Manual

Polytector III G999 for Ex zone 0

An easy and flexible way to do gas detection.

APPLICATION DATA SHEET

Transcription:

Siting Gas Detectors Gas detectors usually fall into three specific groups for placement Plant Protection - Typically flammable gas detectors fall into this category. Aside from asphyxiation flammable gases are typically not directly toxic and so detectors are placed strategically where the gas is expected to accumulate based on its relative density to air (lighter or heavier). Process Monitoring - Typically gas detection systems in this section are used to monitor and either alarm or be part of processing control. This could be monitoring VOC (Volatile Organic Compounds) levels pre and post filtering, Solvent Vapour (LEL) monitoring in drying ovens, Ventilation control in car parks and building etc. Location of these detectors will usually be based on the individual application, after considering the process, gases or vapours, air movement and temperatures involved. Applications falling into this category usually need a good dialogue between IGD and the plant designers to ensure the best placement of the detectors for them to be highly effective. Life Safety Systems - In such systems, the concern is that an asphyxiant or toxic gas is directly hazardous to personnel. The position of the gas detectors is based on the normal operating zone for people in the area of application. It is worth noting at this point that there maybe two sets of detectors involved with a life safety systems. The first set of detectors perform as a process monitoring function, with the detection based on the relative density of the gas with respect to the air. This set of detectors is typically used to person some type of function, for example: bringing extra ventilation to clear a spill hazard. The second set of detectors are in the life safety zone and alarm for personnel protection. When planning the system, careful consideration needs to be given to the actual setting of alarm levels for the detectors. In general HSE document Eh40 lists hazardous gases, vapours and safe occupational exposure limits. IGD base our alarm recommendations on the published figures provided by Eh40. Where a detector is fitted into the breathing zone for a gas, which is much heavier than air, then the alarm is set at a lower level to offset the effect of the higher location. A typical example would be a Liquid Nitrogen Dewar fill room. In this application we know that spills will occur as Liquid Nitrogen is decanted. In this application the Lower-Level Oxygen detectors bring on extra ventilation at ground level to clear the Nitrogen spill as it evaporates into the atmosphere. If the ventilation cannot effectively clear the spill, then the detectors in the breathing zone are used to alarm and evacuate personnel in the area, until such a time that the atmosphere returns to normal safe levels. Please see Image 1: Placement of Gas Detectors and Zones and Image 2 Example of CO2 Gas Bottle Leak

Siting Gas Detectors Consider ceiling divisions, follow rules for smoke detectors LPG 0-100%LEL GAS DETECTOR SN:20235-1-1 ADD:4110 Lighter than air gases, detectors placed at highest ceiling points Consider fitting collector cones at lower level for gas bottle stores boiler plant and gas meters (see separate application note). Methane, Helium, Hydrogen, Ammonia etc 1800mm Life Safety Zone CO, CO2, O2 H2S, NO2, NO HCN, HCL, HF Nh3 etc 1000mm 400mm LPG 0-100%LEL GAS DETECTOR SN:20235-1-1 ADD:4110 LPG, CO2 Consider fitting splash/dust guards to protect low level sensors Consider sensors in under floor areas/voids/drains where heavier than air gases are present Image 1: Placement of Gas Detectors and Zones

Image 2: Example of CO2 Gas Bottle Leak Siting Gas Detectors 5M High Concentrations Local to Release Source or Cloud Development Scenario 5M is a Maximum Detection Distance and Will be Effected by Topography. Gas Levels Will Drop as Distance to Leak Source Increases Requiring Lower Alarm Set Points 100% CO2 For this CO2 Example use Detectors in the Life Safety Zone to Trigger Ventilation and Evacuation Alarms Heavier Than Air Gases Can Show a Gradient in Room Levels With Higher Concentrations at Floor Level or Slow Leak Scenario This Example Illustrating A CO2 Gas Release From A Storage Cylinder. Typical Scenario, Broken or Blown off Hose, Regulator Incorrectly Connected, Ruptured Gauge or Similar. For this CO2 Example Expect Higher Concentrations at Low Levels. Use for Ventilation Trigger and Pre-Alarms Ref BS023-1 Page 2 of 4

Cryogenic Gas Detection Specialised Sampling Gas Detectors As well as manufacturing diffusion based fixed gas detectors, IGD also produce a range of sampling gas detectors. These are utilised where it may be difficult or impractical to use a standard gas detector. Typical applications could be: hard to access areas due to height, accessibility or detector size; clean rooms ; where it is desirable to minimise surface areas inside the facility. IGD s sampling gas detectors are addressable modules that can be fitted alongside standard diffusion typ e detectors. These sample modules operate continuously using IGD s piezo pump technology. This technology has virtually no moving parts for enhanced reliability over standard pumps. In addition, the units can be set up to continuously check and correct the ir zero or calibration point (depending on detector) by drawing a clean filter air sample through a separate port. A diffusion based detector directly in the area of interest is always the best option, where it is required IGD s sampler modules offer an ex cellent alternative solution. 2-Wire Addressable

Cryogenic Gas Detection Careful consideration is required for gas detection for applications involving the use of cryogenically cooled gases such as Liquid Helium or Nitrogen. On initial release, cryogenically cooled gases can typically have a lower temperature and higher density compared to their surroundings and therefore, they will have a different behaviour than their gaseous state. In this instance it should be considered for two sets of detection for optimal safety, one for low level detection in the gases cooled state and one for the life safety zone. It is recommended to survey applications involving such gases. Area Coverage for Gas Detectors In a similar manner to smoke detectors, a gas detector can provide up to 75SQ M area coverage based on a 5M radius of operation. There are many factors affecting this, geometry of a room, equipment in the area, gas characteristics, ventilation air flows etc. IGD can support throughout the survey, design and installation process to ensure the best possible result on site. M ax 5M Ra di us Image 3: Area Coverage of IGD Gas Detectors Typically up to 75 SQ M Coverage Calibration and service Requirements for Gas Detection Systems All gas detection systems require regular checking and calibration to be in compliance with the UK factories act. The service and calibration period will be a function of the application based on environmental in service conditions. It is extremely important to ensure a service plan is in place for any gas detection system installed as part of a site safety system. IGD can work with operators to provide advice, service and spares to ensure an appropriate level of cover.

Calibration and service Requirements for Gas Detection Systems Regular checking and calibration in compliance with the UK Factories Act 1961 and BS EN 60079-292:2007 (in the near future Toxic Gas Detection will have a legal requirement to bee serviced on a regular basis) is required for all gas detection systems. The service and calibration period will be a function of the application based on environmental in-service conditions. Both IGD and BS EN 60079-29-2:2007 legislation states that gas detection systems must be serviced every 6 months. Furthermore, the PUWER 1998 (provision & Use of Work Equipment Regulation) states safety equipment needs to be effective and maintained. With these Acts/Articles in mind, it is essential to ensure that a service plan is in place for any gas detection system deployed as part of a site safety system. IGD can work with operators to offer advice, service and spares to ensure an appropriate level of cover. Service Engineer Competency: IGD run an approved engineer training scheme and strongly recommends that only IGD certified engineers who have passed the IGD Engineer Training Scheme, should service and calibrate IGD equipment. IGD offer 12-month or 24-month service contracts (2 service visits a year). IGD certified engineers will carry the below emblem (Image 4: IGD Approved Service Engineer Emblem) with a unique number, please consult IGD for proof of competency. Image 4: IGD Approved Service Engineer Emblem XXXX

Siting System Components Control Panels: Control Panels should be positioned outside of the hazardous area, protected by their connected gas detectors. They should be accessible such that when an alarm is triggered, it should be possible to evacuate the area and view the gas levels from the safety of the controller. Consider the application of HMI panels, mimic panels or GSM options supplied by IGD to provide additional remote indication/alarm, through email and text notifications. Audio-Visual alarms As a general rule if there is gas detection fitted to an area then there should be an audio-visual alarm (beacon sounder) to alert personnel who may be in the same area. Typically these will be standard beacon sounders where the sounder can be silenced from the control panel once an alarm is accepted. Standard LED beacon sounder modules are available from IGD and can be run from addressable I/O points to minimise cabling. Another option is to fit IGD s range of annunciators. Annunciators Annunciators are addressable devices typically fitted at door entry points. In the event of a gas alarm, a clear audible visual alarm is provided buy the annunciator to warn people from entering an area where a gas hazard could be present. Annunciators are advantageous in many ways when compared to the standard beacon sounder. They can be installed on standard dado trunking systems; cannot be confused with other alarms, can be fitted with slam switches and displayed alarm message and flashing colour display are unambigous

Siting System Components Gas Collector Cones and splash Guards Gas Collector cones can be considered for use in areas where detectors are placed above gas plant such as boilers or meters in rooms with high ceilings. They are fitted to detectors located just above gas plant to enhance the capability of detectors to sense gas leaks IGD Detector fitted with a Gas Collector Cone For detectors at low level, fitting splash guards may be appropriate to protect sensors from floor washing, rain splash dust ect. ATEX/IECEX Detector fitted with an IGD splash guard