FIRE PREVENTION. by Thomas Frank, P.E. A Handful of Dust Can Destroy Your Facility

Similar documents
Prevention of Fires and Explosions in Wood Pellet Facilities. Allen Wagoner, FLAMEX, Inc.

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Hot Work Permit. Can this job be avoided? Is there a safer alternative? Permit No.:

Making sense of risk Risk engineering. Metalworking operations

Prevention of Fires and Dust Explosions within the Biomass Handling Process. PFI July 20, 2015

Industrial Dust Explosions Causes & Case Studies. Presented by Geof Brazier at Expocorma, Concepcion, Chile 10th November 2017

Combustible Dust Hazard Recognition and Control NFPA Standards for Combustible Dusts

COMBUSTIBLE DUST HAZARD MITIGATION

Managing Combustible Dust

Protecting Facilities Against Explosions. Since 1956

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

HOT WORK OPERATIONS March 23, 2018

COMBUSTIBLE DUST SAFETY PROGRAM

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials

Ontario Fire Code SECTION 5.10 COMBUSTIBLE DUST PRODUCING PROCESSES. Illustrated Commentary. Office of the Ontario Fire Marshal

FLAMMABLE FINISHES CHAPTER 24

Progressive Safety Services LLC 2

TECH UPDATE - Spark Detection, Dust Suppression, and Fire Suppression Equipment

TABLE OF CONTENTS. Site preparation 2 Placement. 2 Chimney and stove pipe connections. 2

Protecting Critical Facilities Against Explosions

There are always options in the management of explosion risks!

First Revision No. 15-NFPA [ Chapter 2 ]

Inspection Checklist Mechanical Rough in

SEMICONDUCTOR FABRICATION FACILITIES

APPLICATION PROFILE EXPLOSIONS IN CEMENT PLANTS EXPLOSIONS IN CEMENT PLANTS CEMENT PLANT EQUIPMENT WITH HIGHEST EXPLOSION POTENTIAL. Form No.

SEMICONDUCTOR FABRICATION FACILITIES

Branch Solution Wood based panel plants. Fire protection solutions for wood based panel plants

AUTOMATIC FIRE SUPPRESSION SYSTEMS

WELDING, CUTTING, AND BRAZING SAFETY PROGRAM

Hot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope

Up on the Roof Fire Prevention BY David Laks, P. Eng., CFPS, ARM, RRC

Industrial Explosion Suppression Technology

SEMICONDUCTOR FABRICATION FACILITIES

Progressive Safety Services LLC 1

Spray Painting and Coating

The correlating committee has revised the numbering in these sections to provide clarity for the next edition of the document.

Chapter 12 HOT WORK OPERATIONS. Purpose:

Wood Pellet Mills: Dust suppression, spark detection, and extinguishing systems equipment

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations

Fire Prevention Policy

PRIMATECH WHITE PAPER PROCEDURE FOR DUST HAZARD ANALYSIS (DHA)

SEMICONDUCTOR FABRICATION FACILITIES

INTRODUCTION TO DUSTS AND THEIR EXPLOSIVE PROPERTIES

POLICY STATEMENT: Policy Number: Section 600 Physical Plant. Date Adopted: May 7, Date(s) Revised: September 4, 2012

Soot Mitigation Strategies

Combustible Dust Issues

PROTECTING YOUR PROPERTY INVESTMENT BEFORE DISASTERS OCCUR ARE YOU PREPARED?

Chapter 18 Welding Table of Contents

Minifog PressProtect Fire protection solutions for industrial presses BRANCH SOLUTION

ADMINISTRATIVE SERVICES MANUAL

Combustible Dust Hazards- Awareness

Property risk solutions

Explosion Prevention & Suppression James Maness JEM Safety Consulting Rehoboth, DE.

Fire Prevention STANDARD. LME-12: Uen Rev A

GASEOUS HYDROGEN SYSTEMS

Flammable and Combustible Liquids

1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed.

Combustible Dust Hazards: Awareness & Safeguarding. Forest Industry Task Force on Mill Safety May 2012

Combustible Wood Dust Management Program Development Guide

Dust Explosion Hazard Overview

Explosion Protection Engineering Principles

COMBUSTIBLE DUST HAZARD RECOGNITION

FIRE SAFETY PRACTICES AND PROCEDURES

Stillwater Area Community Services Center Inc.

2660 Horizon Drive SE Grand Rapids, MI FIRE PREVENTION FACILITATOR S GUIDE

Safe Operating Procedure

THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY

DUST COLLECTION TRAINING. Revision 2013

Hot Work Program & Operational Guidelines. Environmental Health, Safety and Emergency Management (828)

Fluid Collections at the Smithsonian. Michael Kilby, P.E. Joshua Stewart, P.E. Office of Safety, Health & Environmental Management (OSHEM)

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

Dust Explosions. health & environmental sciences failure analysis & prevention

Workplace FIRE SAFETY

Notable Changes in the Mechanical Codes

DSEAR - Requirements

Solutions. Fire risk under control in welding fume extraction systems

Safe installations are also cost effective installations

Specifying a Dust Collector For a School Wood Shop

Application Bulletin. LNG / LPG Facilities FLAME AND GAS DETECTION FOR LNG FACILITIES

User s Information Manual

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

Conducting a NFPA 652 Dust Hazard Analysis (DHA): Practical Tips & Approaches

Fire Prevention Plan

HOT WORK SAFETY PROGRAM:

Contractor Safety. Workplace Safety & Environmental Division

Emergency shutdown systems. Procedures for bypassing ESD s

International Symposium. OSHA Combustible Dust NEP Inadequacies. John Astad

Above Ground Fuel Tank Requirements

Fire Prevention Plan

Before proceeding with the selection process, let s briefly look at the various explosion protection options:

Propane Flame Projector Safety instructions and operating manual

FIXED PROTECTION FOR OIL AND CHEMICAL PLANTS

FGR. Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM. FGR-8 through FGR-22 (25 HP to 1000 HP)

USER'S MANUAL PGE Single Package Rooftop

OBC INDUSTRIAL CLASSIFICATION OBOA ANNUAL MEETING AND TRAINING SESSIONS LONDON ON OCTOBER 4, 2011

FIRE PREVENTION 29 CFR Ursinus College, Collegeville, PA

Safe working with flammable substances

2How does a vibratory fluid-bed dryer work?

NFPA Mexico Fire Expo April 20, Learning Objectives. Combustible Dust Explosions History

John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES

Transcription:

FIRE PREVENTION by Thomas Frank, P.E. A Handful of Dust Can Destroy Your Facility A perfect recipe for a mill disaster could be this: start with a building with thin, barely visible layers of combustible dust. Add unvented equipment that draws in suspended dust. Let a few airborne particles stray and find a spark. Add the spark to the dust and you ve set your recipe ablaze! The first explosion ruptures the equipment, releasing building dust into the air; a second explosion deflects the building walls and roof. Deflection could partly collapse the building and break sprinkler piping. And as soon as the sprinkler protection is disabled, your fire is out of control. Combustible dust may appear benign, but it s a beast that can devastate your facility and business unless you control it. Because airborne dust burns fiercely, all it takes is a quarterinch layer of dust to fuel an explosion strong enough to blow out walls or roof panels of a building. A study of fires in plywood and composite panel facilities insured by Allendale Insurance, Arkwright, and Protection Mutual Insurance between 1986 and 1997 showed that about 90 percent of the 80 major incidents (in excess of $1 million each) involved wood dust. Losses totaled close to $141 million in gross damage. (See tables below.) The study also revealed that: Boilers, heaters, dryer fireboxes, and hot dryer exteriors topped the list of ignition sources. Veneer dryers, thermal oil systems, grinders, and flakers were leading equipment involved in severe incidents. Loss investigations show that the two most hazardous areas for dust to collect are at the roof or over big hydraulic presses in both plywood and OSB plants, and inside sander dust collection systems for the finished panels. Flash fires at ceiling areas almost always start in or on equipment at lower elevations. Often resinous, combustible dust deposits, accumulating as steam releases from the process equipment, cause flash fires above veneer dryers and hot presses. Widespread accumulations of dust at ceiling levels can easily fuel a flash fire. The roof itself contributes to the firespread because as heat from the fire plume rises it has nowhere to go except laterally when it reaches the roof. Fire can spread rapidly across the dust deposits, and even stir up the dust, possibly triggering a dust explosion. Eliminating or minimizing the ingredients that fuel both flash fires and dust explosions requires a solid loss prevention program with three prime objectives: Keep it clean. Control ignition sources. Evaluate protection with the hazards in mind.

COMBUSTIBLE DUST LOSS STATISTICS Plywood/Composite Panel Facilities, 1986-1997 Cause No. of Losses Est. Gross Amount ($1,000 1998$) Hot Dryer Exterior 1 $ 37,775 Hot Surface of Heat Transfer System Valve 1 36,655 Machine Part Friction 5 29,654 Overheated Dryer/Kiln 8 5,127 Hot Work 4 4,505 Dryer Exhaust Stack Spark 1 4,427 Boiler/Heater/Dryer Firebox Spark 10 4,167 Hot Surface of Boiler Firebox 1 2,869 Spontaneous Ignition 5 2,840 Miscellaneous Overheating 5 2,828 Electrical Defect 7 2,626 Mechanical Spark 6 2,492 Miscellaneous Sparks 5 2,201 Other 9 1,658 Unknown/No Data 12 761 Totals 80 $140,585 FIRES BY EQUIPMENT TYPE Plywood/Composite Panel Facilities, 1986-1997 Equipment No. of Losses Est. Gross Amount ($1,000 1998$) Veneer Dryers 12 $ 46,054 Thermal Oil System 6 41,797 Grinder, Flaker et. al. 7 29,506 Particleboard Press 16 8,491 Veneer Lathe 3 4,092 Conveyor/Bucket Elevator 4 3,988 Wood Chip Dryer 5 3,729 Plywood Veneer Press 1 1,183 Sander 2 1,173 Dust Collector 4 912 Mobile Equipment (loader/power shovel) 2 452 Air Compressor 4 283 Process/Heat Boiler 3 278 Electrostatic Precipitator 1 239

Keep It Clean Schedule housekeeping programs. If you don t have the dust, you don t have the threat. How often you clean depends upon how fast dust accumulates. Look for wood dust deposits that accumulate on overhead structural members, piping, ducts, and other equipment. Vacuuming is the best way to remove dust. If you use air hoses, be sure to shut down any heat-producing process. Removing resinous deposits over veneer dryers and hot presses frequently requires more tedious methods like high-pressure water spray or scraping. Part of effective housekeeping involves good maintenance. Keeping cutting tools sharp helps reduce fires originating from saws, sanders and other milling equipment. To reduce the number of fires originating inside dryers, operate the equipment within the design operating temperatures and clean it frequently where deposits or waste can accumulate. In addition, use electrical equipment suitable for the environment, particularly where dust accumulations are present. A well-designed dust collection system can capture dust before it migrates to hard-to-reach ceiling areas. Fires and explosions can ignite in areas around equipment like trim saws and sanders that lack an effective dust collection system. New building and equipment designs can affect your housekeeping program. An explosion in an outside dust collector can penetrate into the building. If the equipment and building are not designed for this possibility, sprinkler or hazardous processing piping (e.g. natural gas, thermal oil, hydraulics, etc.) could break and cause an uncontrolled fire or building explosion. Also during the design state, minimize surfaces where dust can accumulate to reduce the number of areas requiring cleaning. Control Ignition Sources The key to minimizing ignition is to detect and isolate sparks. In a dusty environment, prohibit any spark that can lead to catastrophe. Sources of sparks can come from people or equipment. Loss history shows that people doing hot work--any operation that produces open flames, heat or sparks, such as cutting, grinding, brazing, welding, soldering, thawing pipe, torchapplied roofing--have triggered some of the most severe flash fires. About half of documented losses involve outside contractors. A flawless hot work permit system is the answer, but too often plant permit systems aren't rigorously practiced. Workers (often contractors) sometimes take shortcuts or fail to follow up jobs with required precautions. Management support and constant vigilance by those administering the program are essential. Ongoing training and review with those who do the hot work are critical. Detecting and isolating sparks as they move to the collection equipment also is very important. Ignition sources almost always originate at the processing machinery and move through the collection system ductwork to cyclones or bag filters where a fire or explosion occurs. The key to minimizing ignition is to detect and isolate sparks as they move to the collection equipment. Provide automatic sprinklers or waterspray nozzles to protect the dust collectors from fire damage. Sensitive infrared detectors can sense glowing wood embers in a blowpipe and activate an intermittent waterspray system to extinguish the sparks while they are still in the blowpipe. If the spark is extinguished, no system shutdown is necessary. Additional "fail-safe" spark detectors often can be used further downstream to check that the spark was extinguished. If not, the extinguishing system can activate some of the following additional protection equipment:

High-speed abort gates are used on positive pressure blowpipe systems to divert the airflow to atmosphere prior to any dust collectors, thus averting fire or explosion. They are also used to divert airflow to atmosphere on the return air duct on systems that return filtered air back to the plant for energy conservation. Steel-tipped rotary airlocks isolate fires and explosions from downstream equipment. (Rubber-tipped airlocks cannot be relied upon for this function.) Reversing fire dump screws are used along with steel-tipped airlocks to not only isolate downstream equipment, but also to empty burning material safely from the system Explosion vents release explosion pressures to atmosphere before serious damage can occur to the equipment. Explosion suppression systems quench the explosion before damaging pressures can be developed. Backblast dampers (basically a check valve with a built-in explosion vent) prevent explosions from blowing back through the conveying ductwork into the building or into other equipment. Evaluate Protection with Hazards in Mind Provide draft curtains without openings. A draft curtain is a noncombustible, solid curtain attached to the bottom of a ceiling or underside of a roof to impede the flow heat to the area on the other side of the curtain. Without such a barrier, a flash fire will spread to the limits of the dust deposits ahead of the automatic sprinklers. Only backup water supplies or immediate and effective fire department response can control a flash fire s damaging effects. Make sure draft curtains fit tightly against the roof. They should be at least one-eighth the distance from the roof to the floor (four feet minimum). Draft curtains in noncombustible buildings should be made of noncombustible materials. In sprinklered, combustible buildings, combustible materials such as plywood may be used. It s not a good idea to use steel sheeting thinner than 26 gauge (0.0179 in. [0.455 mm]), aluminum, fiberglass reinforced plastic (FRP) or other plastic materials as draft curtains in sprinklered or unsprinklered buildings. Design sprinklers for the fire area. Make sure the required sprinkler discharge for the protected area is available from all sprinklers that might operate. Make sure sprinklers are located over the largest curtained area if draft curtains are provided, or entire area of dust deposits if draft curtains are not provided.

Thermal Oil Can Pose New Harzard in Modern Mills A thermal oil spill can have horrific consequences. And because this hazard is fairly new to the industry, it is not always addressed with sufficient understanding or precaution. If you ve ever seen a small spill of gasoline ignite, it s not hard to envision the flammability of heat transfer fluid (HTF) like thermal oil. Once HTF spills and ignites, it erupts into fire sweeping an area in seconds. Can this defeat the ability of an automatic sprinkler system to control it? Absolutely. Consider three factors of HTF systems flash point of the thermal oil, potential spill size, and pumping flow rate. Flash point. All flammable liquids have a flash point--the minimum temperature at which enough flammable vapors have evaporated from the liquid surface to form a flammable mixture with air. Fluids commonly used in HTF systems have very high flash points, usually between 300 to 450 F, and at room temperature are not easily ignited. But, HTF are frequently heated to as much as 100 F above their flash points in process heaters. So, the only way to reliably extinguish an HTF pool fire with water is to cool the entire spill surface below the flash point of the HTF. The amount of water needed varies, depending on the properties of the HTF (i.e., flashpoint temperature, heat content, and operating temperature) and the amount spilled. Spill size. One gallon of spilled HTF will typically spread out and cover about 15 to 20 sq. ft. of floor area. A typical heating system might contain 10,000 to 20,000 gallons of HTF. Even if only 500 gallons spill onto the floor, it s enough to fuel a fire spanning a 10,000-square-foot area. Even with automatic sprinkler protection, your property might not survive such a fire because sprinkler systems for engineered wood product facilities are typically designed for smaller operating areas (3,000 to 5,000 square feet). Flow rate. A major HTF pipe rupture could spill flammable liquid into a fire four or five times faster than the water flow used to extinguish it. HTF fluids may be pumped at flow rates of 7,000 to 8,000 gallons per minute (gpm) in heating loops for large OSB presses. By comparison, water typically flows from a fire hose at 250 gpm and discharges about 1500 gpm from a sprinkler system designed for this hazard. Solving the Problem It is essential to consider HTF hazards when designing new buildings and arrange processing with HTF hazards in mind. 1. Isolate the HTF heater and pumps from other manufacturing areas. Locate the HTF heater and pumps in separate buildings detached from the main plant facility. Where this is not feasible, an alternative is to locate heater and pumps at an exterior wall of the main building and install two-hour rated fire walls to separate the HTF system from adjacent manufacturing areas. 2. Provide containment areas for possible HTF spills. Use curbs or dikes around pumps or other sources of possible leaks. Or, include a room with a lower floor grade than adjacent areas, or a floor slope or drainage that does not expose major equipment or structures to the spill. 3. Design sprinkler protection for the higher HTF spill hazard. Engineered wood product facilities are normally designed with a 0.20-gpm-per-square-foot sprinkler density over 3000 square feet for a wet pipe system (4000 square feet for a dry system). Areas subject to an HTF spill need a 0.25 density over 3000 square feet for wet systems (5000 square feet for dry), assuming you are providing oil leak detection and loop isolation. In addition, consider using special protection for important HTF process equipment. For example:

HTF heater internal fire suppression. Automatic waterspray activated by two separate fire risk indicators (to minimize false tripping) is recommended. For example, loss of oil from the system and high flue gas temperature or combustibles indicate a likely HTF spill fire in the heater. Provide gaseous suppression such as CO 2 as an alternative to waterspray. But be aware that it lacks cooling ability and needs to have a very long extended discharge period (many hours with refractory lined heaters) to inert the heater volume until surfaces cool well below the oil flash point. HTF leak detection and automatic isolation of secondary loops. You can monitor loss of fluid in secondary loops by using differential flow detection across the loop supply and return piping. Although this can identify which loop is leaking oil, it cannot detect small leaks. Leaks could drain the entire HTF expansion tank before a low-level interlock can stop the pumping or close the loop isolation valves. Continuous level detection in the HTF expansion tank using a hydrostatic pressure probe is becoming a popular way to detect both small and large HTF leaks. This method detects leaks more quickly, but because it does not identify which loop is leaking, it becomes necessary to shut down pumps and close isolation valves on all secondary loops. Press pit fire suppression that covers all shielded areas. Press pits provide excellent containment for an HTF spill. Unfortunately, the spill will be directly below the press, and the press is a critical piece of equipment that can take up to a year to replace. Because the entire surface of an HTF spill fire must be cooled in order to extinguish the fire, be aware of obstructions in the pit that might block the sprinkler spray pattern. Automatic waterspray with a 0.25-gpm-per-square-foot density is needed over the entire pit floor area where an oil spill could accumulate. A sprinkler is also needed at each steel column supporting the press, loader, unloader, or floor above. A ring of sprinklers located only around the pit perimeter is usually insufficient protection because a large oil spill can flow into shielded areas under the press and under the flexible caul return conveyor commonly present in OSB press pits. Other common obstructions, such as piping and cable trays, must be carefully considered in the design stage. Pay attention to how and where these are routed. If some obstructions still exist, reposition them or add more sprinklers to assure that the entire spill surface is cooled. Minimize HTF spill potential. Use welded pipe for HTF wherever possible. Eliminate unnecessary use of direct HTF heating. For example, don't heat buildings by pumping HTF to space heaters throughout a facility. Instead, use the HTF to heat a water/glycol mixture through a central heat exchanger in a cutoff room, and pump the non-hazardous water/glycol solution throughout the plant. Thomas Frank, P.E., is a principal consulting engineer--forest products for Factory Mutual Engineering Association (FMEA), a property loss prevention, control engineering, research and training organization based in Norwood, MA. He assists FM field engineers and companies insured by Allendale Insurance, Arkwright, and Protection Mutual Insurance with engineering issues affecting forest products facilities worldwide.