TRACI, A MULTIPURPOSE CO 2 COOLING SYSTEM FOR R&D

Similar documents
CO 2 COOLING FOR THE LHCB-VELO EXPERIMENT AT CERN.

DESIGN, MANUFACTURE AND TEST RESULTS OF THE VTCS CO 2 EVAPORATOR FOR THE LHCB EXPERIMENT AT CERN.

THE THERMOSIPHON COOLING SYSTEM OF THE ATLAS EXPERIMENT AT THE CERN LARGE HADRON COLLIDER

Cooling test results C-side replacement detector

CO 2 Cooling Seminar Desy Hamburg

Safety Analysis of the 3 main parts in the CO2 system

PoS(Vertex 2007)009. CO 2 cooling experience (LHCb) Martin van Beuzekom, Ann Van Lysebetten 1, Bart Verlaat

The Compact Muon Solenoid Experiment. Conference Report. Mailing address: CMS CERN, CH-1211 GENEVA 23, Switzerland

RIGID DC LIQUID CHILLER

Operational aspects of the VELO cooling system of LHCb

A CRYOGENIC TEST STATION FOR SUBCOOLING HELIUM HEAT EXCHANGERS FOR LHC

Aging Analysis of Micromegas Detectors for ATLAS New Small Wheel

RAMSES: THE LHC RADIATION MONITORING SYSTEM FOR THE ENVIRONMENT AND SAFETY

Data acquisition for the ILC

CO2 kick-off NIKHEF - Cooling activities organization at CERN

EN-CV: LHCb SciFi Common chiller. Martin Doubek September 25, 2017

NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS

Heat Pump Fluidised Bed Dryer with CO 2 as Refrigerant Measurements of COP and SMER

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

LHCb Rich Detectors Control and High Voltage Systems

arxiv: v1 [physics.ins-det] 20 Mar 2017

Transcritical CO2 Bottle Cooler Development

CHAPTER 1 INTRODUCTION

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

COMMERCIAL CO 2 HOT WATER HEAT PUMP FIELD TRIALS

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

R32 Compressor for Air conditioning and Refrigeration applications in China

Towards a Detector Control System for the ATLAS Pixeldetector

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Thermal Performance of a Loop Thermosyphon

Measured Performance of Four New 18 K Helium Refrigerators for the LHC Cryogenic System

Geothermal ORC Systems Using Large Screw Expanders

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

SCFM REFRIGERATED COMPRESSED AIR DRYERS. CRN Series

ATLAS Pixel Upgrade for HL-LHC

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

Parilla Thermal Storage Project Case Study. May Page 1 of 11

XRD XRD-1500 High-Temperature Oven. Innovation in Material Science...

Heat pump supplemental heating system for motor vehicles

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Ultra-Thin Flexible Heaters

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS

Ammonia. Background on ammonia as a refrigerant

2008 JINST 3 S The CMS experiment at the CERN LHC THE CERN LARGE HADRON COLLIDER: ACCELERATOR AND EXPERIMENTS.

THERMOSYS 4.3. Getting Started Guide

Development of the CMS Phase-1 Pixel Online Monitoring System and the Evolution of Pixel Leakage Current

Laird Thermal Systems Application Note. Bi-directional Microcontrollers Monitor and Protect Medical Equipment

Isotemp. Improve the productivity of your laboratory with accurate, efficient temperature control products from Fisher Scientific.

VTCS evaporator block design and prototyping. Status report July 2004

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

NON-CYCLING REFRIGERATED AIR DRYERS. RNC Series

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

The SLAC Detector R&D Program

R&D of GEM detector high rate for CBM Experiment at FAIR Muon Chamber R&D in India

Humidity sensors. Behavior in different environments. Supervisor: Vaclav Vacek Collaborators: Martin Doubek, Martin Janda and Michal Vitek 28.9.

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

RNC Series SCFM Global Air Treatment

Development of the Micro Capillary Pumped Loop for Electronic Cooling

Hot Reservoir Stainless-Methanol Variable Conductance Heat Pipes for Constant Evaporator Temperature in Varying Ambient Conditions

ABSTRACT. Title of Document: EXPERIMENTAL EVALUATION OF A. Laeun Kwon, Master of Science, Dr. Yunho Hwang, Mechanical Engineering

Expected needs in Electronics for the CERN Experiments. 5 October 2015

OPERATING MANUAL Enertronic Control System 2

ScienceDirect. Development progress of critical equipment in the CSNS cryogenic hydrogen system

cussons Refrigeration Assembly Range TECHNOLOGY REFRIGERATION AND AIR CONDITIONING CUSSONS TECHNOLOGY LABORATORY RECOMMENDATION

DART-Thermo LTQ/Orbitrap Interface Manual

LCTPC Setup at the DESY Testbeam. AWLC 14, Fermilab , R. Diener, DESY

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

4th IIR International Conference on Thermophysical Properties and Transfer Processes of Refrigerants 2013

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Phillips. HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Evaluation of HCFC Alternative Refrigerants

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

RNC Series SCFM Global Air Treatment

Pure Butane as Refrigerant in Domestic Refrigerator Freezer

COMPRESSOR LESS SOLAR REFRIGERATOR

Performance Assessment of Water Cooled Condenser Refrigeration System

Ultra low temperature freezers. -40 C and -86 C. Green Line

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

THE ALICE EXPERIMENT CONTROL SYSTEM

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

2 Overview of the Pixel Detector Control System

HFO-1234yf Performance in a Beverage Cooler

Available online at ScienceDirect. Physics Procedia 67 (2015 )

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Gas System for GIF in EHN1

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

ISO/TS TECHNICAL SPECIFICATION. Geotechnical investigation and testing Laboratory testing of soil Part 6: Fall cone test

Cold Energy Saver. Thermal Mass Cycling Refrigerated Air Dryers ( scfm)

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

food-retail.danfoss.com Overview Brochure ADAP-KOOL Evaporator Controllers Achieve best-in-class energy efficiency and food safety

How to Select and Size Enclosure Thermal Management Systems: White Paper, Title Page. How to Select and Size Enclosure Thermal Management Systems

Transcription:

Paper No: GL-208 RACI, A MULIPURPOSE CO 2 COOLING SYSEM FOR R&D B. Verlaat(a,b), L. Zwalinski(b), R. Dumps(b), M. Ostrega(b,c), P. Petagna(b) and. Szwarc(b,c) (a) National Institute for Subatomic Physics (NIKHEF) Amsterdam, NL 1098 XG 105, Netherlands, bverlaat@nikhef.nl (b)european Organization for Nuclear Research (CERN) CH 1211 Geneva 23, Switzerland, Lukasz.Zwalinski@cern.ch (c) adeusz Kościuszko, Cracow University of echnology Warszawska 24 St. 31-155 Cracow, Poland, omasz.szwarc@cern.ch ABSRAC CO 2 cooling is gaining interest as a cooling method for scientific equipment such as particle detectors. he merit of using CO 2 cooling is a high heat transfer capability resulting in small and efficient cooling channels. o support the many CO 2 research projects at CERN and its cooperating institutes, a multipurpose CO 2 cooling system named RACI (ransportable Refrigeration Apparatus for CO 2 Investigation) is under development. RACI is optimized for reduced costs and easy operation while keeping maximal flexibility. A new concept named I-2PACL (Integrated 2 Phase Accumulator Controlled Loop) is developed to minimize the piping and control, while maximizing the operational range for use. Several prototypes have been developed. he first results show that the I-2PACL method works well. An operational range of -35 C to +22 C was measured and a cooling capacity up to 250 watt was reached depending on the cooling temperature. A stable operation was observed with minimum control. wo prototypes have been handed over to clients and the operation of the system turned out to be easy and understandable by the non-expert users. his paper describes the design and test results of the current prototypes and will discuss the plans for the future. 1. INRODUCION High energy physics particle detectors like the ones constructed for the Large Hadron Collider (LHC) at CERN in Geneva (CERN 2009) need lightweight cooling systems to cool the wide spread silicon sensors and the attached read-out electronics. he cooling hardware inside the detector must be radiation hard and low mass as it may not obstruct the particle tracks. he cooling temperature is in general between -20ºC and - 40ºC as the silicon must be kept cold in general below -10ºC to avoid the outcome of radiation damage of the silicon sensors. Applications of room temperature cooling are also present in specific detector technologies. he current LHC detectors use mainly Fluorocarbon cooling systems both in single and 2-phase (Postema et. al. 2011); one detector was designed for evaporative CO 2 cooling. Both CO 2 and fluorocarbons are radiation hard, conventional refrigerants are not suitable in a radiation environment. CO 2 cooling has very good physical properties which allow small diameter tubing. With respect to the traditional Fluorocarbon systems the cooling system mass can be reduced by about 80% (Verlaat et. al. 2011). he successful demonstration of CO 2 cooling in the LHCb-Velo detector and the ability of saving a considerable amount of applied mass has convinced the particle physics community seriously to investigate CO 2 cooling as candidate for the future detector cooling. Almost all the new silicon detectors consider now CO 2 cooling as the baseline for their detector structures. New detectors considering CO 2 cooling are (Verlaat et al. 2011): the CMS upgrade pixel, the CMS racker upgrade, the Atlas IBL, the Atlas inner detector upgrade, and the KEKb Belle-2. 1

Paper No: GL-208 2. CO 2 COOLING RESEARCH New silicon detector development is focused on light weight thermal mechanical support structures to support the silicon sensors and the attached read out electronics. In general these are carbon based structures optimized for a good mechanical stability. hese structures need to accurately place the sensors in the 3D space of the detector. Mechanical stiffness, low mass and low thermal expansion are the important design parameters. hese support structures also need to conduct the heat from the electronics into embedded cooling structures. So the materials must have a high thermal conduction relative to their density. Popular materials are carbon foams and high conductive carbon fibers. Cooling pipes are often made from titanium as this metal has a low CE and density compared to other metals. A typical silicon detector thermo mechanical structure is shown in figure 1. Developments of silicon detector support structures are ongoing in many high energy physics laboratories all over the world. he heat transfer optimization to the evaporative CO 2 cooling in the cooling channels is an important research topic as the cooling channel must be designed as small as possible. A detector is composed in general of many similar substructures. ypical powers of these substructures are maximum a few hundred watts. o support the CO 2 cooling developments, a multipurpose easy-touse CO 2 system is needed to provide the high energy physics laboratories CO 2 cooling for their research. A system called RACI (ransportable Refrigeration Apparatus for CO 2 Investigation) is under development at CERN together with Nikhef. he design goal of RACI is a mobile CO 2 cooling station which is easy to operate and which can be produced in series by outside labs or companies for an affordable prize. RACI must give the user an evaporative CO 2 flow from room temperature down to -40 C for a cooling power up to a few hundred watts. hese requirements are in general enough to support the development of the detector substructures. Larger cooling plants are needed in the future to test assembled detector structures. 3. RACI I-2PACL CONCEP Figure 1: A typical silicon detector support structure, carbon fibers with carbon foam and a titanium cooling pipe (photo SLAC). he CO 2 cooling systems developed for high energy physics experiments so-far use a concept called 2PACL (2-Phase Accumulator Controlled Loop). his method is compliant with the requirements of a typical silicon detector and is used successfully in the LHCb experiment at CERN (Verlaat, 2008). A 2PACL is a pumped 2-phase loop where the saturation temperature is controlled in an accumulator filled with liquid and vapor. he pressure in the accumulator is controlled by cooling or heating the liquid vapor mixture. he circulating CO 2 in the loop is condensed and sub cooled in a heat exchanger cooled by an external cold source which is normally a commercial HFC chiller. In the RACI I-2PACL the cooling of the accumulator is achieved internally by the CO 2 liquid. All the liquid is pumped through a heat exchanger in the accumulator and is heated to the saturation temperature of the CO 2 in the accumulator. his approach is different than a standard 2PACL where the liquid is heated by an internal heat exchanger between the inlet and outlet of the connected evaporator. he integration of the heat exchanger into the accumulator makes the system easier to regulate over a wide range of temperature from the cold limit of the chiller all the way to room temperature. he I-2PACL principle is patent pending. 2

Accumulator Paper No: GL-208 Experiment connection 5 4 Flow regulation RACI layout P, 3 Experiment venting Concentric hose P 10 Local experiment box 6 condenser P 5 Heater compressor EV R-404A Chiller R404a Chiller R404a evaporator/ CO 2 condenser 1 CO 2 pump CO 2 loop Figure 2: RACI I-2PACL concept 3 4. RACI DESIGN At CERN two RACI prototypes are made to support the LHCb- Velo and Atlas-IBL experiment. Figure 3 shows a picture of the two units. RACI is constructed mainly with commercial off the shelve components. he design is made modular such that fabrication and integration are relatively easy. he chiller is a Danfoss air cooled R-404A condensing unit OP-LCHC015 with a custom assembled high pressure heat exchanger AXP10-10 from Alfa Laval (see figure 5). he refrigerant injection is done via a thermostatic expansion valve. he CO 2 piping is constructed in a two dimensional layout squeezed in-between compressed foam layers. One foam layer can easily be removed for easy access to the CO 2 tubing and accumulator. he CO 2 connection to the experiment is via a flexible concentric tube like the transfer tube used in a 2PACL (Figure 2). A small local box with two shut-off valves and a flow regulating valve is present on the other end of the concentric hose. his box will be placed near the experiment; the RACI unit itself can be placed up to 3m away from the attached experiment. 4.1 CO 2 system design he CO 2 piping is located in the foam box as shown in figure 4. Figure 3: wo RACI prototypes he prototypes are made of standard Swagelok connectors; the next version will be orbital welded with VCR fittings. he accumulator is made of a large pipe with 2 Swagelok connector as flanges. he accumulator heater is a Watlow firerod heater in a thermo siphon concept. he pump is a Gather 1M-J/6/X-SS/S/Q/K200/DLC gear pump suitable for a system pressure of 200 bar. he pump can provide a pressure head up to 5 bar and deliver a mass flow of about 3 g/s. he flow to the experiment is regulated by a Swagelok needle valve with

Paper No: GL-208 a Cv value up to 0.004. he condenser for the CO 2 is an Alfa- Laval high pressure heat exchanger AXP10-10 which is located outside the foam box in the chiller assembly. he tubes used are imperial sizes ⅛ for the liquid lines and ¼ for the vapor lines. Imperial sizes are used as Swagelok offers more variety of components for imperial sizes. 4.2 Electrical control design he control system is made of standard electrical components. No PLC is included; all the digital control logic is relay based and achieved by the digital output of PR4116 signal conditioners and PR5115 signal calculators from PRelectronics. One Watlow EZ-Zone S PID controller is included for the 250 watt accumulator heater. A second heater is mounted on the chiller evaporator outlet as dummy load in case of a too low load for the compressor is present. he dummy load heater switches on at a lower limit of the suction pressure controlled by one of the PR conditioners. Both heaters are protected in two faults for overheating via a serial thermal switch chain and internal thermocouples. he pump differential pressure is interlocked by two thresholds. An upper threshold (ca. 6 bar) and a lower threshold (1 bar) are protecting the pump for undesired flow conditions. At start-up the lower boundary is neglected via a set-reset mechanism made by relays. he pressure difference is calculated by the PR calculator using the suction and discharge pressure measurement. Figure 4: CO 2 piping covered in ice during the 1 st cooling test. (he foam layer was removed) All the sensors used for controls can be readout by a National Instrument integrated DAQ system via the 0-10 volt output of the PR conditioners. he DAQ system is only for monitoring, no computer is needed for operating the system. In total two pressure sensors and four temperature sensors are needed for the control. An additional 4 temperature sensors and a flow meter are optional and can be read-out via the free slots in the NI-DAQ. Figure 5: he Danfoss chiller and the Gather CO 2 pump Figure 6: he power distribution, the relays, and the heater controller. Figure 7: he PR conditioners and NI-DAQ 4

emperature ( C) Paper No: GL-208 he user interface is kept simple as inexperienced users must be able to operate the system. All the control buttons are integrated in the door panel and accessible from the outside. Figure 3 shows the units with the user interface clearly visible. he start-up and switch-off is done via a simple on/off buttons. he start-up procedure is controlled by the same PR conditioner/relay logic which also takes care of the interlocking. In total 4 interlocks are present (pump, compressor and the two heaters). he interlocks are indicated with lights integrated in the door panel and can be reset manually using reset-buttons next to the indication lights. he accumulator controller interface is also on the same door panel and is the small black square on figure 3. Emergency stop buttons and a general power switch are also present. he two RACI prototypes have a frequency control of the pump, but commissioning showed that a fixed flow for the pump is the best option. he flow regulation works by branching off manually the amount of needed CO 2. he remaining CO 2 flows via the by-pass back to the condenser. 5. COMMISSIONING he two prototypes were built for urgent use in experiments. Limited time was available for system commissioning. At the first run the system functioned well, only small parameter changes had to be made. Some attention points were discovered such as a reduced cooling capacity at lower temperatures. he next prototypes will therefore have improved insulation to increase the efficiency. he I-2PACL concept proved to be indeed a useful principle as it is self stabilizing over a large range of temperature. Limited user knowledge was needed to operate the system. 5.1 emperature regulation he temperature regulation was tested by adjusting several pressure set-points and switching the power of the attached experiment on or off. A measurement of several steps is shown in figure 8. Around 9:15 the system was started with a heating of the accumulator. he system pressure increased and the loop was filled with liquid consequently. he chiller starts directly and sub cools the liquid in the condenser. he pump starts as soon as the liquid arrives at the pump which is detected by measuring several degrees of sub cooling at the pump inlet. he cold liquid flow starts cooling down the accumulator and the system pressure decreases. Once the accumulator pressure reaches the set-point, the heater takes over and maintains the pressure at the given set-point. A stable temperature 30 20 10 0-10 -20-30 -40 CO2 Chart liquid temperature itle (at pump) CO2 temperature Accumulator saturation temperature 150 W on Power off -50 9:00 10:30 12:00 13:30 15:00 16:30 ime (hh:mm) Figure 8: emperature measurement of RACI to demonstrate the full temperature range. 150 W on around 0 C was achieved. Around 10:30 150 watt was applied to the attached experimental heater. he system was able to maintain the evaporator temperature of the system constant. he liquid temperature (blue line) increases due to the power input, but has no effect on the evaporator temperature in the experiment. Around 11:30 the set-point was lowered to about -20 C, around 12:20 the experiment power was switched off again. Under all conditions the temperature remains stable. Around 13:30 a set-point was requested which is too low for the system. It was unable to reach the set point as the accumulator approaches the liquid temperature. Per design the accumulator temperature cannot be similar to the liquid temperature so a guaranteed sub cooling is present for the pump. Around 15:00 the set point was increased and the power was switched on again. hree set points were chosen to demonstrate the temperature range up to room temperature. At all the set points and power cycles the system remained stable. 5

Heat load (watt) Paper No: GL-208 5.2 System capacity As shown in figure 8, there is a lowest temperature limit for the accumulator. his lower limit depends on the liquid temperature which is depending on the suction pressure of the chiller s compressor. In figure 9 a graph is shown of the minimum measured evaporator temperature as a function of the external applied power. RACI was able to cool the experiment down to -35 C. A maximum of 250 watt was cooled at -22 C. 300W 250W 200W 150W 100W 50W Heat Load without control Heat Load 6. SUMMARY AND CONCLUSIONS 0W -36-34 -32-30 -28-26 -24-22 -20 emperature ( C) o support the particle physics community for their detector cooling development a Figure 9: Capacity of the RACI prototype multipurpose CO 2 cooler is under development called RACI (Multipurpose Refrigeration Apparatus for CO 2 Investigation). A new concept called I-2PACL was developed to simplify the design and increase the temperature range from cold (chiller depended) to room temperature. he new I- 2PACL concept works as designed; a very stable temperature control was achieved with a standard heater controller. he operation of the system turned out to be relatively easy and understandable by non-experts. wo prototypes have been built and three new prototypes are under construction (see figure 10). Lessons learned from the two first prototypes have changed the design of the new prototypes. he initial cooling capacity was not achieved (100 W @ -40 C). he next prototypes will have therefore a larger chiller capacity and improved insulation to increase the cooling capacity at lower temperatures. he liquid by-pass will be done with a check-valve instead of a manual needle valve to simplify the flow control. A flow meter and an experiment heater interlock will also be added. For future development the cooling power will be increased, however the goal remains to have a small and affordable mobile unit. At the moment the chiller is a standard R-404A chiller, in the future it will be investigated how to make it full CO 2. Figure 10: he 3 new RACI prototypes under construction 7. REFERENCES CERN, 2009, he CERN Large Hadron Collider: Accelerator and Experiments Vol 1&2. ISBN : 978-92-9083-336-9 Postema H, Verlaat B, 2011, Cooling in HEP Vertex and racking Detectors, PoS(VEREX 2011)003, 20th International Workshop on Vertex detectors, Rust, Austria Verlaat B, Colijn A.P, Postema H, 2011, he Future of CO 2 Cooling in Particle Physics Detectors, ICR11- B2-309, International Conference of Refrigeration, Prague, Czech Republic Verlaat B. et al. 2008, CO 2 cooling for the LHCb- VELO experiment A CERN, 8th IIF/IIR Gustav Lorentzen Conference on Natural Working Fluids, Copenhagen, Denmark, CDP 16-3-08 6