Backflow Prevention for Fire Sprinkler Systems. State of Illinois Plumbing Code

Similar documents
Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/

Course FP100 BACKFLOW PREVENTERS (BFPs) 101 FOR AUTOMATIC FIRE SPRINKLER SYSTEM M. Nabeel Waseem, M.Eng, PE, CFPS 2018

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%

1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review

FIRE PROTECTION BASIC MATERIALS AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

BACKFLOW PREVENTION GUIDE FOR COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL DEVELOPMENTS

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

BERMAD Fire Protection

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

Port of St Helens SIA Aircraft Hanger Scappoose, OR

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

Water Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings

Fire Sprinkler Plan Submittal Form

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

HOW COMMERCIAL FIRE PROTECTION SPRINKLER SYSTEMS REALLY OPERATE

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

SECTION SPRINKLER SYSTEMS

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

SPRINKLER SYSTEM DRY WET

FIRE SUPPRESSION SPRINKLER SYSTEM

AUTOMATIC FIRE SPRINKLER SYSTEMS

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

Sprinkler Permit Applications

SECTION WET-PIPE SPRINKLER SYSTEMS

FIRE SPRINKLER SYSTEMS POLICY

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

23-Backflow in Fire Systems: Balancing Flow Rate with Protection Peter McLennan

MONTECITO FIRE PROTECTION DISTRICT

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

PLAN REVIEW SUBMITTAL GUIDE

FIRE SPRINKLER SYSTEMS POLICY

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

SECTION DOMESTIC WATER PIPING SPECIALTIES

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, Dual-Purpose Water Supply, Domestic and Fire Sprinkler System General Description

ADDENDUM #1 ITB# Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015

PRIVATE FIRE SERVICE INSTALLATION PACKET

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

APPLICATION FOR INSTALLATION OF SPRINKLER SYSTEM.,. :" ROCHESTER, NH FIRE DEPARTMENT FIRE PREVENTION DIVISION

Self Inspection Program

EXISTING FIRE SPRINKLER SYSTEMS ARE THEY HAZARDS? HOW CAN WE APPROACH THEM?

PLAN REVIEW CHECKLIST

CITY OF PASADENA FIRE DEPARTMENT

A. This Section includes the following domestic water piping specialties:

THE BASICS OF BUILDING FIRE PROTECTION DESIGN. RES Symposium April 18, 2017

MODULE 2. Water-Based Suppression System Basics

EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5

SECTION WET FIRE SPRINKLER SYSTEMS

False Sense of Security???

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

HYDRONIC SPECIALTIES TACO MPT Tank(s) 05/30/2012. A. Multi-Purpose Tank buffer tank, air separator, and hydraulic decoupler

FIRE CODE. Coal City Fire District International Fire Code Update. 35 S. DeWitt Place Coal City, IL

Gas Station & C Store SECTION CWM Job No

DIVISION 21 - FIRE SUPPRESSION

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

Manufacturing safety solutions

New Construction Fire Inspection Process

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

SECTION FIRE-SUPPRESSION STANDPIPES

HIGH-RISE RETROFIT ORDINANCES - NO and NO

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TECHNICAL DATA. Wet 26a. February 22, 2009

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems

Freezing of Water-Based Fire Protection Systems

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

SPRINKLER ORDINANCE Town of Yarmouth, Maine Recodified: 1/15/98 Amended: 4/19/01 Amended: 6/18/15

May 1, Dear Fire Suppression System Contractor/Designer:

McMAHON FP200 OUTAGAMIE COUNTY ADMINISTRATION CENTER S. WALNUT & W. 8TH, APPLETON, WI ALTERATION / ADDITION

MOHICAN. MOHICAN 4-Pass Water Boiler, HP, PSI Section

B. Section Identification for Fire Suppression Piping and Equipment.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

WALL ESCUTCHEON PIPE SEAL WITH APPROVED FIRE CAULKING (SEE SPECIFICATIONS) NOTE: 12" 12" 24"

Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems

Inspection, testing, and maintenance (ITM) Fixed fire protection and detection July 2016

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

Transcription:

Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code

Backflow Prevention Fire safety systems connected to a public water supply will require a backflow prevention device between the fire safety system and the public water supply.

Types of Valves Check Double Check Reduced Pressure

Check Valve A valve which permits flow in one direction, from the supply to the end use.

State of Illinois Plumbing Code The State of Illinois requires a DDC (Double Detector Check) valve on all fire protection systems.

Double Check Valve Assembly-DDC or DCVA This assembly consists of two internally loaded check valves, either spring or internally loaded, weighted, installed as a unit between two tightly closing resilientseated shutoff valves as an assembly, and fittings with properly located resilient seated test ports or cocks.

Diagram

Reduce Pressure Zone (RPZ) or Reduced Pressure Backflow Assembly (RPBA) Two independently acting check valves together with a hydraulically operating, mechanically independent pressure differential relief valve located between the check valves and below the first check valve. These units are located between two tightly closed resilient seated shutoff valves, as an assembly, and are equipped with properly located resilient seated test cocks.

State of Illinois Plumbing Code The State of Illinois requires an RPZ/RPBA valve on all fire protection systems when the following conditions exist.

If the system contains anti-freeze or other chemicals, then an RPZ device is required. If water can be pumped from a nonpotable water supply such as a retention pond or lake then an RPZ is required If there is a permanent or emergency connection whereby water can be pumped into the fire safety system-rpz

Location of the DDC or RPZ Normally the DDC or RPZ is located on the incoming water supply before connection to the fire system If there is a Fire Pump, the RPZ or DDC should be located on the discharge side of the pump

Graph s: compliments of FSI

Retrofitting DDC s or RPZ s The devices will add from 4-15 psi on the average to the fire protection system hydraulic calculation demand. Most sprinkler systems are hydraulically calculated to within 5 psi of the available water supply.

Who Can Test or Repair an RPZ or DDC A licensed plumber who is also a certified cross control detector inspector.

Diagram

NFPA 25- Backflow Preventors Maintenance Section 9-6 Conducted by trained individual following manufacturer s instructions Certified Cross Control Detector Inspector (CCCDI). Rubber parts replaced in accordance with frequency required by authority having jurisdiction and manufacturer s instructions

NFPA 25- Backflow Preventors Inspection Section 9-6 Weekly for valves supervised with seals Monthly for other supervision methods Verify: in normal open position All RPZ devices must be inspected weekly to determine that the relief port is not discharging

1998 NFPA 25 7-3.8 Other Devices Other devices, such as check valves, detector check, and backflow preventors that are installed on the fire sprinkler system shall be inspected and maintained so that they do not impede the flow of water and fire main pressure.

9-6.2 Testing, Backflow 9-6.2.1 All backflow preventors shall be tested annually A) A forward flow test shall be conducted at the system demand B) A backflow certification test, as required by the authority having jurisdiction shall be conducted at the completion of the forward flow test.

Sample of Backflow Test form

NFPA 25- Control Valves Section 9-3 Annual Test Forward flow test at system demand Exceptions to Forward Flow Test When connections for system demand are not available, run test at maximum flow For 2 inch or smaller valves, run test without measuring flow Where water rationing is in effect for more than 1 year, internal inspection can substitute for flow Flow Test not required where pump testing causes demand flow through backflow device Backflow certification test (after flow test)

Forward Flow Test NFPA 13 1999 10-2.6 The backflow prevention assembly shall be forward flow tested to ensure proper operation. The minimum flow rate shall be the system demand, including hose stream where applicable. This is a requirement also called out in NFPA 25 1998 Edition

Underground Piping Tests HYDROSTATIC TEST 200 PSI FOR 2 HOURS From the street line non-indicating valve to the first supply side valve in the protected building.

Underground Flush Test This test is to be conducted before the underground pipe is connected to the fire sprinkler system. Flow the required rate of water listed by the AWWA until the water is clear and there is no collection of material in a burlap bag which is to be placed on the end of the pipe. Flow rates shown on the next slide

Sprinkler Pipe Tests Flow rates: 390 gpm for a 4 line 880 gpm for a 6 line 1,560 gpm for a 8 line 2,440 gpm for a 10 line 3,520 gpm for a 12 line

Why is this Important?

To remove any sand, grit, or debris from underground that may disturb valves or obstruct fire sprinkler head water flow

To insure that the PROPER water supply is available as it was designed