Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Thermometer. Hot Water Inlet. Cold Water Inlet G3600LF

Similar documents
Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Tempered Water Outlet. Hot Water Inlet.

Installation, Operation and Maintenance Guide G3600 Series Thermostatic Mixing Valves

Installation, Operation and Maintenance Guide AP3900 Series Thermostatic Mixing Valves

TA-300, TA-300-LF, TA-350, TA-350-LF

INSTALLATION SETUP AND OPERATING INSTRUCTIONS THERMOSTATIC WATER MIXING VALVE SYSTEM * TM-500A, TM-550A

MODEL TA. TA-SB 117.5mm mm HOT INLET. TA mm mm mm mm

INSTALLATION SETUP AND OPERATING INSTRUCTIONS THERMOSTATIC WATER MIXING VALVE SYSTEM TM-500, TM-550

OUTLET HOT INLET COLD INLET INSTALLATION

INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20, TM-20-LF (As furnished with models TM-554, TM-356, TM-356-W/HA)

INSTALLATION ADJUSTMENT SERVICE

INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20* (As furnished with models TM-554, TM-356, TM-356-W/HA Valve is ASSE 1017 listed

INSTALLATION ADJUSTMENT SERVICE HIGHLOW THERMOSTATIC WATER MIXING VALVE SERIES XL-32, XL-82

INSTALLATION ADJUSTMENT SERVICE THERMOSTATIC WATER MIXING VALVE SERIES LV-981 & LV-982

INSTALLATION ADJUSTMENT SERVICE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

MEGATRON MODEL 2, 3, 4, and 5

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20 (As furnished with models TM-554, TM-356, TM-356-W/HA, TM PRV, 8015, 12520, 15020)

INSTALLATION SETUP AND OPERATING INSTRUCTIONS THERMOSTATIC WATER MIXING VALVE SYSTEMS TYPE *TM-600, TM-650, *TM-800, *TM-850, TM-5100, TM-5125

HOT INLET COLD INLET INSTALLATION

OUTLET LEONARDH THERMOSTATIC INSTALLATION

MEGATRON MODEL TA, TA-LF

MODEL 210, 210-LF THERMOSTATIC WATER MIXING VALVES INSTALLATION SETUP AND OPERATING INSTRUCTIONS

SS-7600 THERMOSTATIC MODEL INSTALLATION INSTRUCTIONS

INSTALLATION ADJUSTMENT SERVICE NEXT-GENERATION MANIFOLD SYSTEMS TM-520B-LF, TM-820B-LF, TM-920B-LF, TM-1520B-LF

DOMESTIC OUTLET. kg/cm 2 11 psi LEONARD LEONARD -10 C F LEONARD R THERMOSTATIC LEONARD LEONARD C F C F 60 COLD INLET HOT INLET

OUTLET LEONARD THERMOSTATIC INSTALLATION

MEGATRON MODEL 2NB-LF, 3NB-LF, 4NB-LF, 5NB-LF NEXT GENERATION MANIFOLD SYSTEMS TM-520B-LF, 820B-LF, 920B-LF, 1520B-LF

INSTALLATION ADJUSTMENT SERVICE THERMOSTATIC WATER MIXING VALVE TM-200 (NEW STYLE) TMS-200 (VALVE ONLY)

30 R -10 C F H C INSTALLATION. Maximum Operating Pressure 125PSI (860 KPA) for Hot and Cold Water. CAUTION

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD SYSTEMS TM-420A Valve assemblies are ASSE 1017 listed

INSTALLATION ADJUSTMENT SERVICE TM-1520A-DT, TM-2020A-DT PARALLEL SYSTEMS

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD SYSTEMS TM-420A Valve assemblies are ASSE 1017 listed

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD SYSTEMS TM-520, TM-820, TM-920, TM-1520A TM-520-LF TM-820-LF, TM-920-LF, TM-1520A-LF

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B, TM-2020B-LF

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B, TM-2020B-LF

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B, TM-2020B-LF

INSTALLATION ADJUSTMENT SERVICE MEGATRON MODEL 8N-LF. Valve assemblies are ASSE 1017 listed

INSTALLATION ADJUSTMENT SERVICE 2PS TM-2020B-2P, TM2020B-2PS-LF PARALLEL SYSTEMS

INSTALLATION ADJUSTMENT SERVICE 2P TM-2020B-2P, TM2020B-2P-LF PARALLEL SYSTEMS

INSTALLATION ADJUSTMENT SERVICE TM-1520A-2P, TM-1520A-2P-LF TM-2020B-2P, TM2020B-2P-LF PARALLEL SYSTEMS

Installation S

Installation S

Installation Manual. Models 99168, 99169, 99170

Installation S

Installation S

Installation S

Installation S HL2X2 High Capacity Manifold System. Table of Contents Rev. B; ECN Bradley Page 1 of 8 11/10/2014

Mini Tank water heater Electric undersink Water heaters GL GL 4 - GL 6+

Model Combination Shower Eye/Face Wash

Whole House Filter Model: WH-LD


Installation Instructions PP-AS20 Anti-Scale System

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

REIMERS ELECTRA STEAM, INC. INSTRUCTION MANUAL JG & JJ MODELS

Installation Instructions / Warranty

Installation Instructions / Warranty. Metris 31060XX XX XX1

MP-MBA-45T-1/60T-1 / 75T-1

5 (34) 10 (69) 45 (170) 64 (242) 65 (246) 92 (348) 90 (341) 127 (481) 85 (322) (227) 80 (303) 113 (428) 148 (560) 105 (397) 141 (534) 100 (379)

User Manual. Hot Water Dispenser. Models: 177HWD15G 12/2018. Please read and keep these instructions. Indoor use only.

Installation, Operation, and Maintenance Manual

CSD-1 CRN Electra Steam, Inc. Instruction Manual for JR06 Steam Generator, JG- and JJ- Models

TUB AND SHOWER FAUCET

Model /8320CRP Shower and Eye/Face Wash

INSTALLATION, OPERATION AND MAINTENANCE

TWIN-FLOIII HEATER INSPECT THE SHIPMENT IMMEDIATELY WHEN RECEIVED TO DETERMINE IF ANY DAMAGE HAS OCCURRED DURING SHIPMENT.

LEONARD -10 LEONARD VALVE CO. CRANSTON RI USA. TYP TM US. P aten ts 2.970, 3,06 1, , " Maximum Operating Pressure 125PSI (8.6 Bar).

Installation Instructions / Warranty. Massaud

INTERMEDIATE GUIDE BRACKET

SEISCO SUPERCHARGER EXTENDER/BOOSTER INSTALLATION GUIDE & OWNERS MANUAL

B.I.C.A Built-In Coffee Appliance

Installation S IMPORTANT! Bradley Thermostatic Mixing Valve for Individual Showers. Table of Contents

AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions

Model 8300FP Freeze Resistant Combination Shower Eye/Face Wash

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMPACT POINT-OF-USE ELECTRIC WATER HEATER

OPERATING AND INSTALLATION MANUAL

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

TRU-TEMP VALVE. Tru-Temp Pressure Balance 1/2" Rough-In Valve Owner's Manual 3001-RIV-PB-ORB 3001-RIV-PB-BN 3001-RIV-PB-CH 3003-RIV-PB-ORB

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER

Model /8300CRP-8309CRP Shower & Eye/Face Wash

Model 7656WCC Eye/face Wash

MEGATRON MODEL 2N, 3N, 4N, 5N HIGH-LOW MANIFOLD SYSTEMS TM-520, TM-820, TM-920, TM-1520A TM-520-LF, TM-820-LF, TM-920-LF, TM-1520A-LF

Peerless Partner PV Series Indirect Fired Water Heater

OPERATING AND INSTALLATION MANUAL

Serial No.: and Up OPERATING INSTRUCTIONS MODEL AR. STEAM GENERATORS CAUTIONS:

36 IN. ELECTIC FIREPLACE FMI MODEL # LEF36 Mounting Base Feet and Wall Mounting Bracket Included

Installation Instructions / Warranty

Carbon Dioxide Sample-Draw Detector Operator s Manual

Storage Tanks. Instruction Manual. To the Installer: Please attach these instructions next to the water heater.

Controlled Energy Corp. 340 Mad River Park Waitsfield, VT TOLL FREE

Electric Mini Tank Water Heaters ME10 ME25 ME40 ME60

Model 8356WCSM Pull-Down Shower Eye/Face Wash

MASTER. Water Conditioning Corp. MP-TS-10T/20T with the 255/762 Logix Control Valve With Vortech. Installation and Operation Manual

Transcription:

Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Thermometer 1/2" OD Copper Tube Inlets Hot Water Inlet Cold Water Inlet G3600LF Installation 1. Install valve in a location where it may be easily cleaned, adjusted or repaired. 2. Inlets are clearly marked on valve body casting. Connect hot water to inlet marked "HOT" and cold water to inlet marked "COLD." 3. Included angle checkstops must be installed on both supply lines (see above). 4. Use solder or pipe cement sparingly. Flush supply pipes before connecting valve. Flush outlet pipe and valve once valve is connected. Maximum operating pressure is 125 PSI (860 KPA) for hot and cold water. Maximum hot to cold water pressure differential is 5%. Note: Should piping be exposed to excessive hot or cold conditions, it may be necessary to insulate piping to prevent freezing or scalding water. IMPORTANT: THESE SYSTEMS ARE DESIGNED TO PROVIDE MIXED WATER FROM 60 TO 90 F (15 TO 32 C) FOR EMERGENCY EYE OR EYE/FACE WASH APPLICATIONS ONLY IN ACCORDANCE WITH ASSE 1071. rev. 1215 / 2015 1

Adjustment and Service thermostatic mixing valves may be easily cleaned, adjusted and repaired. Servicing may be possible without disconnecting valve. Note: Thermostatic water mixing valves are regulating mechanisms which must be regularly maintained to provide best performance. Local water quality and usage conditions dictate cleaning frequency. (See Maintenance Guide and Record card included with valve shipment and reference ANSI Z358.1) To Reset Adjustable High Temperature Limit Stop: Handle Web 1. Remove handle, retaining ring, loosen set screw, and remove stop. 2. Activate emergency fixture. Set Screw Stop Retaining Ring 3. Replace handle and adjust to reach desired maximum temperature. Note: Temperatures above 90 F are not recommended. Consult a medical advisor for correct temperature settings. 4. Replace stop such that it rests against the web on the left side of the cover. 5. Tighten set screw and reassemble. Hold a thermometer under water flow to verify maximum temperature has been set appropriately. Then set desired operating temperature. WARNING: THIS THERMOSTATIC MIXING VALVE HAS AN ADJUSTABLE HIGH TEMPERATURE LIMIT STOP WHICH MUST BE CHECKED. IF TEMPERATURE IS TOO HIGH, THE INSTALLER MUST RESET THIS STOP IMMEDIATELY. ALWAYS CHECK THE TEMPERATURE OF THE MIXED WATER WHEN THE LEVER HANDLE IS TURNED TO FULL HOT. EXCESSIVE HOT WATER TEMPERATURE IS DANGEROUS AND MAY CAUSE SCALDING. THE HIGH TEMPERATURE LIMIT STOP IS FACTORY SET AT APPROXIMATELY 90 F (32 C) WITH AN INCOMING HOT WATER SUPPLY TEMPERATURE OF 135 F (57 C). IF THE INCOMING HOT WATER TEMPERATURE IS HIGHER THAN 135 F (57 C), THE VALVE (WHEN TURNED TO FULL HOT) WILL DELIVER WATER IN EXCESS OF 90 F (32 C) AND THE HIGH TEMPERATURE LIMIT STOP MUST BE RESET. Troubleshooting Symptom Component Type Part No. Description Leak between valve cover and body. Packings and Gaskets 6806 Cover Gasket Leak at lockable dial. Packings and Gaskets MU-5A O-Ring Valve outlet temperature cannot be adjusted or will not mix consistently. Port Sleeve Assembly TAG-1M or RK3600A Port Sleeve Assembly or Repair Kit After cleaning or replacing port sleeve assembly, valve will not hold temperature. Thermostat Group 6810 or RK3600A Thermostat Group or Repair Kit Hot water bypass into cold line. Checkstops Supplies cannot be shut off completely. Checkstops RK3600B Checkstop Kit Leak at checkstop bonnet. Checkstops If installed on a circulated hot water system, verify the valve is piped according to Required Piping Method on page 3. See page 5 for complete parts breakdown and parts kits. rev. 1215 / 2015 2

Required Piping Method Required when hot water must be circulated to a thermostatic mixing valve that is a substantial distance from the hot water source. Recommended hot water inlet temperature is 135 F (57 C). Thermometer 1/2 OD Copper Tube Inlets Hot Inlet Cold Inlet Hot Supply Cold Supply To Hot Water Source G3600LF This unit must be cycled each time the emergency equipment is inspected (See ANSI Z358.1, Maintenance and Training section). 1. Set the thermostatic mixing valve to full hot. 2. Activate eye or eye/face wash and verify outlet temperature does not exceed 90 F (32 C). 3. Turn thermostatic valve to full cold and wait ten seconds. 4. Turn thermostatic valve to full hot and wait ten seconds. 5. Verify outlet temperature does not exceed 90 F (32 C). 6. Turn thermostatic mixing valve to full cold and wait ten seconds. 7. If necessary, adjust high temperature limit stop (see page 2). Then set mixing valve to desired operating temperature and deactivate emergency equipment. rev. 1215 / 2015 3

To Dismantle Valve: Turn off hot and cold water supplies to valve. Remove four cover screws and remove cover and thermostat group. (Figure 1) After replacing parts, lockable dial must be reset to obtain correct temperature range from Cold to Hot. (see "To Reset Adjustable High Temperature Limit Stop" on page 2). Figure 1 Base Stud Cover Screws Thermostat Group Stop Handle To Clean Port Sleeve Assembly: Remove base stud (Figure 2). Twist port sleeve nut into valve body, slide port sleeve assembly toward port sleeve nut, and lift from valve body to clean. Clean with non-corrosive agent and soft cloth. DO NOT USE ABRASIVES. Wash parts thoroughly after cleaning and reassemble. Reinstall port sleeve assembly with long slot end nearest port sleeve nut. Tighten port sleeve nut to complete reassembly. DO NOT OVERTIGHTEN. To Clean Thermostat Group: Loosen set screw and remove handle (Figure 1). Remove retaining ring and stop. Push rod through cover to remove thermostat group. DO NOT PULL COILS OUT OF SHAPE. Use brush and cleaning solution (non-corrosive and grit-free) to remove any depost build-up from thermostat coil. Wash thoroughly before reassembly. Reassemble by reinstalling base stud, then place thermostat group 6810 on base stud. PORT SLEEVE ASSEMBLY DRIVING BALL MUST BE INSERTED INTO HOLE ON LOWER COIL BRACKET(Figure 3). Verify thermostat moves back and forth. Replace cover and screws and turn hot and cold water supplies on. See page 2 "To Reset Adjustable High Temperature Limit Stop." Note: After installation, adjustment, and cleaning, always verify valve temperature with thermometer when turned to full hot. If necessary, adjust temperature of hot water source. EXCESSIVE HOT WATER TEMPERATURE (OVER 90 F) IS DANGEROUS AND MAY CAUSE SCALDING. Figure 2 Figure 3 Port Sleeve Assembly Long Slots Base Stud Port Sleeve Nut Port Sleeve Nut Port Sleeve Assembly Driving Ball Coil Bracket rev. 1215 / 2015 4

Thermostatic Mixing Valve Parts 8 10 1 3 7 6 9 2 4 5 Checkstop Parts Thermostat Group RK3600B Repair Kit* RK3600A Repair Kit 11 12 13 14 15 16 * Includes parts to repair both hot and cold checkstops Lockable Dial 8 10 7 6 9 Set Screw Notes: 1. After installing new parts, the adjustable high temperature limit stop must be reset (see page 2). 2. G3600LF valves are furnished with lockable dials. Item Part Number Description 1 TA-5 Base Stud 2 MU-2C Cover Screw 3 6810 Thermostat Group 4 6820 Stop 5 68240 Handle 6 MU-5A Stem O-Ring 7 3009 Cover O-Ring 8 TAG-1M Port Sleeve Assembly Item Part Number Description 9 6806 Cover Gasket 10 3402 Port Sleeve Nut 11 LVC-8A Check Bonnet Packing 12 MU-6A Lower Stem with Packing 13 MU-9A Check Spring 14 MU-5A O-Ring 15 MU-4A Upper Check Stem 16 192700 Check Bonnet rev. 1215 / 2015 5

Flow Capacities 50 G3600LF System Pressure Drop (PSI) 37.5 25 12.5 0 1 2 3 4 5 6 7 8 9 10 Flow Rate (GPM) MODEL IN OUT G3600LF 1/2" 1/2" MINIMUM FLOW (GPM) INTERNAL COLD WATER BYPASS MINIMUM SYSTEM PRESSURE DROP 5 10 15 20 25 30 35 40 45 PSI L/MIN 0.3 0.7 1.0 1.4 1.7 2.1 2.4 2.8 3.1 BAR 2 4 2.0 2.7 3.5 4.5 5.5 6.5 7.5 8.5 9.0 GPM 7.6 15 7.6 10 13 17 21 25 28 32 34 L/MIN MAXIMUM FLOW CAPACITY G3600LF HAS 1/2" NOMINAL SWEAT CONNECTIONS. CAUTION: ALL THERMOSTATIC MIXING VALVES HAVE LIMITATIONS. THEY WILL NOT PROVIDE THE DESIRED ACCURACY OUTSIDE OF THEIR FLOW CAPACITY RANGE. CONSULT CAPACITY CHART AND DO NOT OVERSIZE. MINIMUM FLOW MUST BE NO LESS THAN SHOWN ABOVE. IMPORTANT: THESE SYSTEMS ARE DESIGNED TO PROVIDE MIXED WATER FROM 60 TO 90 F (15 TO 32 C) FOR EYE OR EYE/FACE WASH APPLICATIONS ONLY IN ACCORDANCE WITH ASSE 1071. Limited Warranty warrants the original purchaser that its products will be free from defects in materials and workmanship under normal usage conditions, and when properly installed and maintained according to manufacturer's instructions for a period of two years from date of shipment. During the warranty period, will (at its discretion) repair or replace any product or part thereof, which shall be returned, freight prepaid to Guardian's factory and determined by the manufacturer to be defective in materials or workmanship. There are no warranties, expressed or implied, which extend beyond verbiage contained herein. There are no implied warranties of merchantability or fitness for a particular purpose. will not be held liable for labor, incidental or consequential damages. Any alteration or improper installation or improper use of the product will void this limited warranty. rev. 1215 / 2015 6