ACHIEVING REDUNDANT INTRINSICALLY-SAFE FIELDBUS SEGMENTS FOR FISCO & ENTITY DEVICES

Similar documents
Fieldbus Non-Incendive Concept takes FISCO into Zone 2 and Division 2 hazardous areas. Phil Saward

Installing Foundation Fieldbus H1 in Hazardous Areas. Presented By: Jim Peterson Sr. Applications Engineer MTL/USA

Pepperl+Fuchs GmbH Lilienthalstrasse Mannheim Germany

Installing Foundation Fieldbus in Hazardous Areas. Understanding your Options and How to Use Them

D SYSTEM CONTROL DWG. APPROVED BY. OrCAD 6 ROSEMOUNT 2410

Page 1 Copyright by the Fieldbus Foundation All rights reserved.

Application Guideline. FOUNDATION TM fieldbus for LEPIU. Prepared by: Thomas Klatt Business Development Manager

PROCESS AUTOMATION APPLICATION AND SELECTION GUIDELINE FIELDCONNEX FIELDBUS INFRASTRUCTURE

Assembly. Host Sub-D Alarm

Segment design & and Bus Diagnostics

Safety instructions VEGADIF DF65.GX*****H/Z/P/F***** IECEx BVS

Instrumentation Products and Applications

SET Installation and Operating Instructions. Level switch for one sensor

explosion protection automation global partner of the process industry

Two global companies, one solution.

DB5 Intrinsically Safe Sounder Type DB-5

BA488CF Intrinsically safe Panel mounting Fieldbus Display

Fieldbus Foundation TM Bus diagnostics and troubleshooting

Intrinsically Safe or Explosionproof? Understanding the technology

INTERNATIONAL STANDARD

TESTS OF ADSIL COATING

5.1 Safety instructions for system configuration and explosion protection. Zone-specific conditions for system configuration

Enhanced FOUNDATION Fieldbus Physical Layer Diagnostics with the DeltaV System

Annubar Flowmeter Series

Integrated redundant fieldbus power for FBM228 Foundation fieldbus modules High-density, compact design Fully isolated

Today's world of increasing

RADAR LEVEL GAUGE SPECIAL SAFETY INSTRUCTION

Operating Instructions Edition 02/2007

Certificate of Compliance

Technical Data. General specifications. Rated operating distance s n 5 mm

Documentation. Explosion-Protection. for Smoke Detection Panels SDS-4, SDS-8, SDS-12 and Extension Panels SDS-E8, SDS-E12, SDS-E16, SDS-EC16

Product Information to the manual

Inductive slot sensor

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

Technical Data. Dimensions

Engineering Guideline. pac-carriers Type SIEMENS ET-200M Fail-safe signal modules

Features. Figure 1. Recommended Application

PROZESSAUTOMATION. Manual SEGMENT PROTECTOR R-SP-!12. Zone 1 Zone 2 / Div 2 FNICO

Engineering Guideline. pac- Carriers Type Universal

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

technical datasheet technical datasheet

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Tank Gauging System Special Safety Instruction

BA334D Intrinsically safe Externally powered pulse input field mounting rate totaliser Issue 13

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS

Intrinsically Safe Flame Detector Installation Guide

VACIE REFERENCE GUIDE REVISION 1.2.6

BA338C Intrinsically safe Externally powered pulse input panel mounting rate totaliser issue 13

Public Safety DAS Annunciator Panel

Model 144H. Product Data Sheet , Rev DB February Content

IECEx Certificate of Conformity

Partners in Process Automation with Emerson Process Management for Intrinsic Safety

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300

Safety Instrumented Systems

OilSET-1000 (12 VDC)

Rosemount 752 Fieldbus Remote Indicator

polar zone components and systems for extreme temperatures

INSTRUCTION MANUAL. SIL 3 - SIL 2 IIB Group Power Supply for Hazardous Area Equipment DIN-Rail Model PSD1001C PSD1001C

General Routing Interface

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

SITRANS T. SITRANS T Explosion protected temperature sensor. General information. Marking of the degree of protection. Range of uses.

... RD0-TI-Ex8.FF.* Temperature Multi-Input Device for Cabinet Installation. Features. Assembly. Function. Connection. Zone 1

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Temperature Solutions Line Card

RT FLOW RATE TOTALISER

FPS200 FPS200. April B. TRUNKGUARD Fieldbus Power Conditioner

SBEx-4 BISTATE SEPARATOR 1, 2, 3 or 4 channels in rail housing (TS35, 22,5mm width)

Real Time Pipeline Leak Detection on Shell s North Western Ethylene Pipeline

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

Technical Data. Dimensions

segment, redundant FISCO power supply system for Yokogawa CENTUM CS 3000 Control Systems. Instruction Manual INM9108

Declaration of conformity

Model 144H. Product Data Sheet , Rev DB February Content

THE FUTURE OF RETRACTABLE BOLLARDS BULLYBOY PRODUCT INFORMATION

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

User s Manual. EJA Series Differential Pressure and Pressure Transmitters Installation Manual. 1. Introduction. 2. Handling Cautions. 3.

FAN WALL Technology. Product

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

DL424/425 DirectLine Sensor Module for Dissolved Oxygen Probes Series DL5000 Specifications

Safety instructions VEGADIS DIS61.CC/O** VEGADIS DIS81.CC/O******

EOTec 2C32 Installation Guide

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

CONTACTORS FOR AEROSPACE GROW SMARTER AND MORE CAPABLE

Modular Fire Panel 5000 Series Just as flexible as your plans

Danfoss gas detection unit Type GD Heavy Duty

Temperature measurement with SITRANS T siemens.com/processinstrumentation

Technical Data. Dimensions

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm

Intrinsically Safe Solutions

Speed and Frequency Seite 1 von 7

Vocia VACIE. Reference Guide

Functional Safety Solutions

Safety instructions VEGAPULS 64

SET-2000 Hi Level/Oil

Software Version 2.01 LEVEL MONITOR MODEL 220

Trim Pump Impellers. Fredrick/Weinman Engineered Products 2-1/2 KH, 2-1/2 x 3 x 12

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Transcription:

Foundation Fieldbus End Users Council Australia Inc. P.O. Box Z5546 Perth AUSTRALIA 6831 ACHIEVING REDUNDANT INTRINSICALLY-SAFE FIELDBUS SEGMENTS FOR FISCO & ENTITY DEVICES Mike O Neill Director, MooreHawke Fieldbus, Division of Moore Industries-International, Inc During the last year or so, a variety of approaches have been released offering users new fieldbus segments with redundancy and FISCO device connectivity. This paper describes and compares those new designs with regard to segment capacity, MTBF, overall availability, installation areas and implementation cost. At first glance, fieldbus is mutually incompatible with intrinsic safety unless both compromise on segment design. Fieldbus works best when many devices are connected together on one segment and intrinsic safety is a design concept that minimises the available energy in any one cable. Many companies and approval bodies have collaborated to generate FISCO (Fieldbus Intrinsically-Safe Concept) designs but power supply redundancy as commonly used in non-intrinsically safe segments has not been possible. There are now new and novel designs that incorporate redundant I.S. power supplies, others that incorporate redundant power supplies with common I.S. sections, and still others that have redundant power with field-mounted I.S. interfaces. These complex products and designs need detailed comparison in order for users to make sense of the implications of any particular concept for their application. Keywords: Fieldbus, Redundant, Intrinsic Safety, FISCO Page 1 of 10

1. Introduction During the last year or so, a variety of approaches have been released offering users new fieldbus segments with redundancy and FISCO device connectivity. This paper describes and compares those new designs with regard to segment capacity, MTBF, overall availability, installation areas and implementation cost. At first glance, fieldbus is mutually incompatible with intrinsic safety unless both compromise on segment design. Fieldbus works best when many devices are connected together on one cable and intrinsic safety is a design concept that minimises the available energy in any cable pair. Many companies and approval bodies have collaborated to generate FISCO (Fieldbus Intrinsically-Safe Concept) designs but power supply redundancy as commonly used in most segments has not been possible. There are now new and novel designs that incorporate redundant I.S. power supplies, others that incorporate redundant power supplies with common I.S. sections, and still others that have redundant power with field-mounted I.S. interfaces. These complex products and designs need detailed comparison in order for users to make sense of the implications of any particular concept for their application. 2. Intrinsically Safe Fieldbus - AG163 With the active participation of a group of vendors and end-users, the Fieldbus Foundation has produced AG163 FOUNDATION Fieldbus Application Guide to 31.25Kb Intrinsically Safe Systems. AG163 Issue 2 provides considerable background to the development and performance of various intrinsically safe design concepts so only the overview will be described here. The output characteristics of the various intrinsically safe power supplies are shown in Figure 1. 2.1. Entity Entity systems may be described as classical intrinsic safety ; some sort of interface, (barrier or isolator) provides the source of power in the fieldbus segment, and the design has to take into account the fieldbus devices, the cable and all of their inherent capacitances and inductances in determining that the system is safe for the Gas Group and location required. Without describing the entire process, it is well documented that Entity systems initially used for fieldbus were only capable of delivering something like 80mA per segment. One significant advantage is that classical barriers used simple resistors as the current-limiting component and that design simplicity allows very high MTBF at little cost. The output characteristic is linear shown as Figure 1(a) and the systems architecture is shown as Figure 2(a). Mike O Neill Page 2 of 10

2.2. FISCO The Fieldbus Intrinsically Safe Concept (FISCO) initially established by PTB (Germany) replaces the traditional linear power supply with an electronic currentlimiting power supply in order to allow more current into that segment. The output characteristic is either trapezoidal or rectangular, illustrated as Figure 1(b) or 1(c). Systems using electronic current limitation can only achieve Exib approval and are thus restricted to Zone 2 and Zone 1. Typical systems architecture is shown as Figure 2(b). FISCO devices typically have parameters of at least 17.5V/380mA/5.32W. Commercially available FISCO power supplies can deliver 110mA in IIC and 265mA in IIB applications. Not only does FISCO allow more current into the segment, the design concept also allows the free use of cable and devices conforming to the FISCO specification with no regard to cable or device Entity parameters. This freedom is a consequence of an acceptance of a restriction in both cable type (see table) and of overall length (1000m total, 60m spurs). The use of electronic current limiting does lead to complex design and potentially expensive product, and also causes a very significant reduction in MTBF. Adding Entity devices (24V/250mA/1.2W) is also a problem, requiring an additional module per spur to incorporate further power limiting unless devices have an uncommon hybrid approval. 2.3. Split-Architecture This design concept takes its lead from previous generations of panel-board instruments whereby front-of-panel indicators were married to back-of-panel control modules. In split-architecture, the conventional I.S. barrier resistive component is split into two pieces, one at the power supply end and the other in the field at the spur. This is particularly advantageous in fieldbus applications where the trunk carries current for all devices on the segment and each spur may be restricted to a single device at a time. One commercially-available split-architecture design allows 350mA in the segment and each spur is intrinsically safe for IIC. Avoiding design complexity and retaining resistive limiting (albeit split into two pieces) keeps the system linear (and therefore suitable for Exia systems), avoids high cost and allows significantly enhanced MTBF compared to equivalent systems based on FISCO power supplies. A recent enhancement to this particular design is a revision to the certification allowing connection of FISCO devices to any spur, but without the limitations imposed by pure FISCO systems (segment is still 1900m overall, spurs are still 120m each). A drawback is that the trunk cable and device coupler location is only IIB-approved though the device connections are all IIC see Figure 2(c). This is overcome by a specific device coupler version which has Exe trunk terminals and thus allows IIC locations. Mike O Neill Page 3 of 10

2.4. Fieldbarriers These units are precisely that; I.S. barriers mounted in the field. An I.S. ground connection from a field enclosure is expensive and problematic even for experienced I.S. aficionados, so modern units replace the barrier with the equivalent of a galvanic isolator. The overall systems architecture (see figure 2(d)) therefore has one isolated power supply with fieldbus conditioning at the control panel with yet another isolated power supply with fieldbus conditioning in a box in the field. Since the field DC/DC isolator circuit has to be loop powered, this causes the minimum voltage for proper functionality to be raised, typically set at 16V for 10V at the spur. Overall, systems complexity is high, making for high cost and lower MTBF 4-spur fieldbarriers are particularly disadvantaged. In general, fieldbarriers are approved such that the spur connections are suitable for both FISCO and Entity devices. One further issue not commonly disclosed is that each segment cannot have a large number of connected fieldbarriers without compromising the allowable segment jitter ; each fieldbarrier introduces a significant amount of jitter to that segment and the segment is allowed only 3.2µs before H1 communications become untenable. 3. Redundancy in Fieldbus Standard fieldbus segments are based on multiple devices connected on one pair of wires, driven by a power supply and connected to a H1 card. The DCS vendors are generally delighted to offer dual H1 cards whereby the primary active H1 card has a low bus address and the secondary backup card is able to take over if that primary card fails. Similarly, there are fieldbus systems where the H1 communications cables are offered in redundant pairs such that communications, control and monitoring can be maintained should there be a cable failure. Making the fieldbus power supply redundant is simply a matter of connecting one or more power supplies together on the same fieldbus segment, at least, so long as the segment is not intrinsically safe. Having two intrinsically safe power supplies connected to the same segment at the same time is not possible without severely restricting their capability; if an I.S. power supply can safely deliver 100mA, it is highly unlikely that 2 units in parallel making 200mA available will also be intrinsically safe. In the same vein, if it permitted to have 100mA in a particular configuration, then each power supply in a redundant pair for that configuration can only safely deliver 50mA and the segment designer can only count on 50mA for devices in his segment analysis. There is another problem peculiar to FISCO; the FISCO design specifically allows only 1 active power supply in the segment, which makes redundant FISCO impossible to achieve with 2 permanently connected power supplies. Mike O Neill Page 4 of 10

4. Practical solutions There are several ways to get around these problems in allowing users of intrinsically safe segments the same confidence in their power supplies as nonintrinsically safe segment users. The following configurations are possible: redundant I.S. power supplies redundant power supplies with common I.S. section redundant power supplies with fieldbarriers 4.1. Redundant I.S. power supplies As described above, it is not possible to have two I.S. power sources simultaneously connected to one segment. However, it is possible to have multiple I.S. power sources connected via a switch so that only one is allowed access to the segment at any one time. There is now a commercially available configuration of this type whereby two power supplies are made available for a segment, each unit controlled by an external module with hand-shaking between the two units to ensure that only one power source can ever be connected to the segment see Figure 3(a). In practice, the overall MTBF is only slightly improved because the linked control modules are not truly independent and clearly, the overall cost is quite high since the configuration requires both 2 power supplies and two control modules with the attendant demand for back-of-panel space and power. A consequence of this configuration is that the control modules must themselves be powered from the power available within the segment to avoid additional design complications and wiring, which still further saps the power available to the field. 4.2. Redundant power supplies with common I.S. section In this configuration, the power supply can be whichever design is considered most appropriate; linear or switch-mode. They can be connected in parallel in the normal way and are then effectively load-sharing and hot-swappable pairs. One particular commercially available configuration uses conventional linear DC power supplies as the most cost effective design. The I.S. section is then made to be common to the two power supplies and here an Entity-type I.S. interface is the only practical solution see Figure 3(b). This configuration achieves high MTBF performance by retaining the simple resistive element, further improved by having passive coil power conditioning and straight transformer isolation. 4.3. Redundant power supplies with fieldbarriers In this configuration, the trunk is powered by redundant power supply modules, but there is no redundancy available at the fieldbarrier itself. Each fieldbarrier is in Mike O Neill Page 5 of 10

actuality a FISCO/ENITY power supply located in the field and as far as is known, no one has yet attempted to provide multiple switched I.S. power supplies at that point. In all probability, it is not commercially feasible to do so and would make for a very complex systems design. 5. Architecture Comparison Figure 3 compares the architecture of the two redundant I.S. systems described as 4.1.and 4.2 above. By adding the known MTBF s of the various components, the overall performance of each systems type can be evaluated - at time of writing, the MTBF of the Control Module in type 4.1 is estimated by the author, pending release of full information by that manufacturer. Table 1 provides a detailed analysis of the various configurations. The segment capacity is calculated for 20mA devices (some vendors use 15mA device loads, mentioned in small print), and segment lengths are based on Type A 0.8mm 2 cable. Price data is taken from available List Prices. Real life notes: 1. Most users stipulate that the minimum allowable segment voltage is at least 1V or 2V above the minimum 9V, which seriously penalises FISCO systems which tend to have low output voltage; 12.4V (IIC) to 13.1V (IIB). 2. The new FF standard to which fieldbus device couplers are being tested for registration (FF846-1) requires that the DUT minimum operational voltage must allow for reverse polarity diodes and other series components before the spur, and also include the effect of a single spur short-circuit on the segment; device couplers with current-limiting designs lose another 40mA or so from the segment capacity, whereas device couplers with fold-back spur short-circuit protection suffer no such loss. 6. Conclusion Redundant intrinsically-safe fieldbus systems are now available in a variety of architectures. Comparisons between the various configurations clearly shows that the split-architecture approach has all the required characteristics of power supply redundancy and simplicity for high MTBF, has I.S. approval for both FISCO and ENTITY devices, and supports standard fieldbus cable lengths of 1900m total and 120m spurs at up to 350mA. What is somewhat surprising is that this system has been available since 2000 (FISCO connections added in 2008) and is already installed in over 100 locations across the world with (nearly) all DCS vendors. This widespread acceptance demonstrates that smart design in fieldbus applications is finally able to overcome the dominance of the traditional I.S. interface suppliers. Mike O Neill Page 6 of 10

Figure 1. Intrinsically Safe Power Supply Output Characteristics. Mike O Neill Page 7 of 10

ENTITY FISCO ENTITY FISCO ENTITY FISCO Figure 2. Intrinsically Safe Fieldbus system designs. Mike O Neill Page 8 of 10

Figure 3. Redundant Intrinsically Safe Systems designs. (Figures refer to MTBF in years, estimated to MIL217K, comparative purposes only) Mike O Neill Page 9 of 10

APPENDIX 1 GUIDENCE OF SEGEMENT CALCULATIONS Every fieldbus segment design needs to be validated for performance. This is essentially an exercise in Ohms law, based on total segment load and total voltage drop. Vendor datasheets need to be consulted to get the base data for the calculation. Total segment load = (sum of all devices) + (current taken by device coupler) Total voltage drop = (source voltage) + (short-circuit load it is normal practice to assume 1 fault) - (source voltage drop due to impedance at segment load current) - (spur voltage drop due to impedance & protection circuit) - (minimum device voltage) Cable capacity (Ω) = Total voltage drop / Total segment load Cable length (m) = Cable capacity / Cable resistance (Ω / km / loop) Example: Base data: Device load assumed 17mA Device minimum voltage 11V Cable 44Ω/km/loop FISCO (Redundant, IIB) Split-Architecture (Redundant, IIB-IIC) Source voltage 12.9V 18.65V Source impedance not required 22Ω Device coupler load 3mA 25mA Short-circuit load 42mA 0mA Spur voltage drop 0.1V 1.0V No. of devices 2 4 6 8 10 12 14 16 Redundant FISCO Split Architecture Split Architecture (Dual Trunk) 660 426 315 249 206 176 1900 1125 690 439 275 160 75 9 1000 1000 1000 1000 874 690 550 439 Table 1. Segment Capacity (no. of devices vs segment length (m)) Mike O Neill Page 10 of 10