GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

Similar documents
GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

MGC Dock User s Manual

CO2 RESPONDER Portable Carbon Dioxide Detector QUICK REFERENCE GUIDE

OI-2400-DOCK Multi Gas Docking Station. Operation Manual trevision 2.2w

MGC Dock User s Manual

Single Gas Clip and SGC Plus User s Manual Rev 2.1 READ FIRST BEFORE OPERATION WARNING STATEMENTS / AVERTISSEMENT Activating tthe detector for the

RK Carbon Monoxide Transmitter Operator s Manual

Single Gas Clip and SGC Plus User s Manual Rev 2.3

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual

QUICK REFERENCE GUIDE

RK-02 Multi Point Detector Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual

RK/ RK Oxygen Detector Operator s Manual

RK CO 2 Transmitter Operator s Manual

RK-05 Carbon Monoxide Transmitter Operator s Manual

! "! # Please read these installation and operating instructions completely and carefully before starting.

RK-05 Combustible Gas Transmitter Operator s Manual

CT-7 Series Toxic Gas Transmitter Operator s Manual

RK Combustible Gas Transmitter Operator s Manual

Macurco Single-Gas XL Series Monitor, CM-1XL Carbon Monoxide (CO), HS-1XL Hydrogen Sulfide (H2S) User Instructions

RK/ RK Oxygen Detector Operator s Manual

GasAlertMicro 5. 1, 2, 3, 4, and 5 Gas Detectors. Quick Reference Guide

RK Multi Point Detector Operator s Manual

RK-05 Carbon Monoxide Detector Operator s Manual

RK / RK Methane Detector Operator s Manual

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

Controllers. Instruction Manual WARNING

RK/ RK Carbon Monoxide Detector Operator s Manual

NH 3 RESPONDER Portable Ammonia Leak Detector QUICK REFERENCE GUIDE

Beacon 800 Gas Monitor Operator s Manual

RK-03 Hydrogen Detector Operator s Manual

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

RK Transmitter Technical Notice

Instruction Manual WARNING

RK/ RK Combustible Gas Detector Operator s Manual

Operator s Manual. 1, 2, 3, and 4-Gas Detector

1228s Multidrop INSTRUCTIONS. Installation and Operation of the AMC-1228s Electrochemical Sensor Module For Use With Multidrop AMC Monitors

RK / RK CO 2 Detector Operator s Manual

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

CMF, CMX & CMA series

Document No

NH3 RESPONDER PORTABLE AMMONIA LEAK DETECTOR. Quick Reference Guide

RK-CH4-4 Combustible Gas Transmitter Operator s Manual

Carbon Dioxide Sample-Draw Detector Operator s Manual

ANALOX 101 D2 PORTABLE OXYGEN MONITOR USER MANUAL

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

MACURCO INC. CONTROLLERS & CARBON MONOXIDE DETECTORS SS103-3A, SS103-10A SS102H, SS102HC-1 INSTALLATION & OPERATING INSTRUCTIONS

Combustible Gas Sample-Draw Detector Operator s Manual

Single Gas Detector. Quick Reference Guide

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Operator s Manual. 1, 2, 3, and 4-Gas Detector

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

User s Manual and Warranty Information for Counterweighted Chain Drive ThyssenKrupp Access

RK-OXY Oxygen Sample-Draw Detector Operator s Manual Part Number: RK Revision: P1 Released: 7/18/02

Remote Relay Module (RRM)

GasAlertMicro 5 and GasAlertMicro 5 PID O 2, CO, H 2 S, PH 3, SO 2, Cl 2, NH 3, NO 2, HCN, ClO 2, O 3, VOC, and Combustibles

Blade Series Heat Exchanger Operation and Installation

VX SERIES Wireless Thermostat with Occupancy Sensor

Macurco HD-11 Hydrogen Gas Detector

Macurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference

Beacon 110 Gas Monitor Operator s Manual

Carbon Monoxide Sample-Draw Detector Operator s Manual

INSTRUCTION MANUAL P Heating and 1 Cooling

CO Guardian LLC Document: E. AIRPORT DRIVE Date: 11/15/05 OWNERS MANUAL

LV-S-5. Instruction Manual DIRECT CONTACT STRAY VOLTAGE DETECTOR GENERAL DESCRIPTION HOW IT WORKS

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL

OWNERS MANUAL. CARBON MONOXIDE DETECTOR MODELS Panel Mount & Remote Detectors (R) Guardian Avionics 1951 E. AIRPORT DRIVE TUCSON, AZ.

OWNERS MANUAL MODEL 451 (-101 & -201)

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

MaxLite LED VAPOR TIGHT LINEAR FIXTURES

INSTRUCTION MANUAL TS21. 2 Heating and 1 Cooling

Warranty Registration

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

AT-G-DETECT Gas Sensing System

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

SEC 2000 Millenium Infrared Gas Detector

SEC Millenium Carbon Dioxide Gas Detector

DGS - Danfoss Gas Sensor Check / Calibration Procedure

Humidity Monitor model 01080

USE AND CARE GUIDE FOR MODEL MEK1, MEK15. Express Cordless Kettle

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model COSTAR 24VC-e Single Relay

Transcription:

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

Operating and Installation Manual Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration Technologies, the protection provided by the equipment may be impaired. This equipment should be installed by qualified personnel. 2

Operating and Instruction Manual Table of Contents General description. 4 Installation. 4 Locating the sensor. 4 Installation guidelines 5 Wiring... 6 Operation... 7 Start-up... 7 Calibration... 7 Maintenance... 9 Specifications...10 Warranty...11 For technical support, contact: Calibration Technologies 920 N Trade Winds Pkwy Columbia, MO 65201 866-394-5861 sales@ctiengineering.com www.ctiengineering.com 3

Operating and Installation Manual General Description The GasGuard SO2 sensor is a +24 VDC, three-wire, 4/20 ma sensor for sulfur dioxide which utilizes proven electrochemical sensor technology for fast and accurate detection. The 0-20 ppm detection range of the GasGuard SO2 provides real-time continuous monitoring of Sulfur dioxide concentrations accurately down to 1 ppm without false alarms. The GasGuard SO2 provides an industry standard linear 4/20 ma output signal compatible with most gas detection systems and PLCs. The output signal is not affected by drastic temperature and moisture variations that occur during daily process cycles. The transmitter circuit board is sealed in potting compound, protecting sensitive electronic components and copper tracing from corrosion. The specially vented chemical-resistant polycarbonate (or optional stainless steel) enclosure protects the sensor from accidental damage, weather and direct hose-hits from clean-up crews. Installation Locating the sensor One of the most important considerations when installing GasGuard SO2 sensors is that they must be easily accessible for calibration and maintenance. Sulfur dioxide is almost twice as heavier than air and will tend to accumulate in low-lying areas in poorly ventilated rooms. For optimum personnel protection (representative concentration reading that an employee would be exposed to), mount the sensor at a height no higher than the breathing zone of the employees. It would typically be about 4 to 5 feet off the ground, which also allows easy access. As a general rule of thumb, try to mount sensors within 30 feet of SO2 gas sources. Caution: Remove protective label. The sensor is shipped with a label installed over the gas diffusion port of the electrochemical cell to preserve cell life. The cell will not detect SO2 vapors with this label installed. Remove label and discard during installation. 4

Operating and Instruction Manual Installation Guidelines: Remove and discard protective cell cover Always mount the sensor vertically. Must be easily accessible for calibration and maintenance. Mount the sensor close to the potential leak source. For optimum personnel protection, mount sensor in the breathing zone (5 feet above floor). Take air movement and ventilation patterns into account. To prevent electrical interference, keep sensor and wire runs away from mercury vapor lights, variable speed drives, and radio repeaters. Protect sensor from physical damage (forklifts, etc). If mounting on a wall with studs, the mounting screws should be screwed into the studs. Never mount the sensor in CA (controlled atmosphere) rooms because normal atmospheric levels of oxygen are required for operation. For highly critical locations more than one sensor should be installed in each room. Mount sensor enclosure through the mounting holes as shown in Figure 1. Figure 1: Mounting dimensions 5

Operating and Installation Manual Wiring (Figure 2) Electrical wiring must comply with all applicable codes. Electrical Power: 24 VDC regulated, 350 ma max. Output: Linear 4/20 ma output. Monitoring equipment may have a maximum input impedance of 700 ohms. Cable Recommendation: 20/3 shielded cable (General Cable C2525A or equivalent). Length of cable to sensor should be no greater than 1,500 feet. Monitoring: Monitoring equipment must be configured to indicate a fault if the signal is below 1 ma. All signals over 20 ma must be considered high gas concentrations. Alarm setpoints should not be lower than 10% of full-scale range. Wiring Guidelines: Always use 3-conductor, insulated, stranded, shielded copper cable. Do not pull sensor wiring with AC power cables. This can cause electrical interference. If cable runs cannot be made without a splice, all splice connections should be soldered. Ground the shield at the main control panel. Connect the shield wire in the sensor terminal block labeled SHLD. Always disconnect power at the controller before performing any wiring at the sensor. To case ground of monitoring equipment (earth ground) To ground terminal of power supply To +24V terminal of power supply To signal input of monitoring equipment 6 Figure 2: Wiring diagram

Operating and Instruction Manual Operation Start-up Allow 60 seconds for power up time delay of sensor to end (green power LED will flash during power up). Sensor can be response tested after power-up, but best to wait 1 hour to zero or span sensor after power up. Start-Up Test: One person exposes each sensor to calibration gas. The second person stays at the control unit to determine that each sensor, when exposed to the target gas, is connected to the proper input and responds, causing appropriate alarm functions. LED functions (see Figure 3 on page 8) Calibration The GasGuard SO2 sensor comes factory calibrated and should require only minimal adjustments after installation. There are two pots on the preamp that are used for calibration (see Figure 3). Note: Never measure sensor output in ma. Always use mvdc or VDC voltmeter settings. Zero Calibration: After the sensor is installed and has been powered up for 1 hour, the unit can be zero calibrated by the following: Be sure the unit is in clean air. If unsure, apply Zero Air gas at 0.5 to 0.8 L/min. Adjust the Zero pot until the sensor outputs 40 mv from Test [-] to Test [+] (see Figure 3). Span Calibration: If span adjustment is required, use the following procedure: To enter calibration mode (disables all filtering and averaging), turn the Zero pot clockwise 1/4 turn and then back again. Successful entry into calibration mode will be indicated by the Power (green) LED blinking twice per second. Calibration mode will time out automatically after 4 minutes. Apply span gas at 0.5 to 0.8 L/min (span gas must be in air, not nitrogen or other carrier). Sensor should react to gas within 15 seconds. Once the output signal has peaked (or 3 minutes maximum) adjust the Span pot until the correct output is achieved (see Figure 3). With full-scale span gas, the calculated span value is 200 mv. ((span gas / sensor range * 16 + 4) (ma output)) Note: Below are a few response characteristics which may be an indication that the gas sensor is at or near the end of its useful life. If any of these are observed, the cell should be replaced: Slow response to / recovery from calibration gas. Failure of the output to reach 50% of the calibration gas value prior to span adjustment if last calibration was 6 months ago or less. Unable to achieve correct output during span. 7

Operating and Installation Manual Cell Sensor cable plugs into socket here. Span adjustment Zero adjustment 40-200 mv mvdc Black _ Red + Fault (red) LED: On steady if supply voltage is too low (<10VDC) or hardware failure. Status (amber) LED: Blinks once per second if RFI is detected. Power (green) LED: On steady to indicate power. Blinks once per second for 60 seconds during power-up. Blinks twice per second in calibration mode (4-minute timeout delay). Figure 3: Sensor board components and zero/span adjustments 8

Operating and Instruction Manual Maintenance The GasGuard SO2 was designed for long life and minimal maintenance. For proper operation it is essential that the test and calibration schedule be adhered to. Calibration Technologies recommends the following maintenance schedule Maintenance Guidelines: The sensor is shipped with a factory calibration. Sensor should be calibrated 6 months from purchase date. Calibrate the detector at least once every 6 months. Calibration should be performed with certified calibration gas. Calibration kits and replacement cylinders are available from Calibration Technologies. All tests and calibrations must be logged. Always disconnect power at the controller before performing any wiring at the sensor. Sensor Life: These electrochemical cells are extremely reliable, but several things can cause the cell chemicals to become depleted including: a period of time exposure to high temperatures continuous, long term exposure to sulfur dioxide When the cell becomes depleted, the unit will give no indication of failure other than that the sensor will not respond. For this reason, it is absolutely essential that these sensors be calibrated on a regular basis. Typical cell life will be two to three years. When the cell becomes depleted, a replacement cell can be obtained from Calibration Technologies. Simply unplug the cell s ribbon cable from the transmitter, pull the old cell from the spring clip, discard the old cell and replace it with a new one. Replacement cell order #: GG-SO2-RC 9

Operating and Installation Manual Specifications Input Power: +24 VDC, 350 ma Detection Principle: Electrochemical Detection Method: Diffusion Gases: Sulfur Dioxide (SO2) Ranges: 0/20 ppm (standard) Output Signal: Linear 4/20 ma (max input impedance: 700 Ohms) Response Time: T50 = less than 30 seconds T90 = less than 90 seconds Accuracy: +/- 5% of full-scale, but dependent on calibration gas accuracy and time since last calibration Zero Drift: Less than 0.1% of full-scale per month, noncumulative Span Drift: Application dependent, but generally less than 3% per month Linearity: +/- 0.5% of full-scale Repeatability: +/- 1% of full-scale Temperature Range: -40 F to +122 F (-40 C to +50 C) Humidity Range: 5% to 100% condensing Dimensions: 7.7 high x 6.7 wide x 3.8 deep Weight: 3.0 lbs Power (green) LED: Blinks once per second for 60 seconds during power-up. If supply voltage is too low (<10VDC) or improperly grounded, will blink once per second continuously. Stays on steady to indicate power. Blinks twice per second in calibration mode (4-minute timeout delay). Status (amber) LED: Blinks once per second if RFI (radio frequency interference) is detected. Fault (red) LED: Stays on steady if supply voltage is too low (<10VDC) or hardware failure. Wiring Connections: 3-conductor, shielded, stranded, 20 AWG cable (General Cable C2525A or equivalent) up to 1500 ft. Terminal Block Plug (Field Wiring): 26-12 AWG, torque 4.5 lbs-in. Enclosure: Injection-molded, NEMA 12 Washdown- Duty, polycarbonate sensor housing with hinged lid and captive screw. For non-classified areas. Optional 18 GA, NEMA 3RX Washdown-Duty stainless steel enclosure with hinged lid and captive screw. For nonclassified areas. 10

Limited Warranty & Limitation of Liability Calibration Technologies, Inc. (CTI) warrants this product to be free from defects in material and workmanship under normal use and service for a period of two years (including the cell), beginning on the date of shipment to the buyer. This warranty extends only to the sale of new and unused products to the original buyer. CTI s warranty obligation is limited, at CTI s option, to refund of the purchase price, repair, or replacement of a defective product that is returned to a CTI authorized service center within the warranty period. In no event shall CTI s liability hereunder exceed the purchase price actually paid by the buyer for the Product. This warranty does not include: a) routine replacement of parts due to the normal wear and tear of the product arising from use; b) any product which in CTI s opinion, has been misused, altered, neglected or damaged by accident or abnormal conditions of operation, handling or use; c) any damage or defects attributable to repair of the product by any person other than an authorized dealer or contractor, or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on: a) proper storage, installation, calibration, use, maintenance and compliance with the product manual instructions and any other applicable recommendations of CTI; b) the buyer promptly notifying CTI of any defect and, if required, promptly making the product available for correction. No goods shall be returned to CTI until receipt by the buyer of shipping instructions from CTI; and c) the right of CTI to require that the buyer provide proof of purchase such as the original invoice, bill of sale or packing slip to establish that the product is within the warranty period. THE BUYER AGREES THAT THIS WARRANTY IS THE BUYER S SOLE AND EXCLUSIVE REMEDY AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. CTI SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, INCLUDING LOSS OF DATA, WHETHER ARISING FROM BREACH OF WARRANTY OR BASED ON CONTRACT, TORT OR RELIANCE OR ANY OTHER THEORY. 11

GG-SO2-DOC1-0 20170712