KC-400 KC-600 KC-700 KC-800 KC-900

Similar documents
CEMA CM20 Series Digital Controller Operation Manual CM24 CM22 CM21 CM23 CM25

TAIE. Features. FY900 (96mm X 96mm) Application:Control temperature,humidity, FY Series Digital PID Controller

TAIE. Features. FY600 (96mm X 48mm) Application:Control temperature,humidity, FY Series Digital PID Controller

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

Temperature Controllers

TEMPERATURE CONTROLLER OPERATION MANUAL

Multi-point Digital Controller MA900/MA901. Initial Setting Manual IMR01H03-E4 RKC INSTRUMENT INC.

Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e

Temperature Controller SA100. Initial Setting Manual IMR01J03-E1 RKC INSTRUMENT INC.

Series Temperature Controller Instruction Sheet

MICRO CONTROLLER S Z SERIES

Communications None RS-232C RS-422* RS-485* BCD Transmission output*/** (4 to 20 ma) E5AX- E5AX- L(M)A02 L(M)A03

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

F4 Process Controller Installation and Operation Guide

Instruction manual Temperature Controller KT7

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

DC1000 Series Digital Controller Product Manual August 2005

TEMPERATURE CONTROLLER OPERATION MANUAL

Hardware Instruction Manual. SR Mini HG SYSTEM. High-performance Multi-point Control System IMSRM15-E4 RKC INSTRUMENT INC.

I/A Series 716C 1/16 DIN Temperature Controller

Terwin Instruments Ltd.

MICRO CONTROLLER E Z SERIES

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER JCD-13A, JCR-13A

Serie Rugghölzli 2 CH Busslingen. Tel. +41 (0) Fax +41 (0)

Warning Caution INSTRUCTION MANUAL DIN RAIL MOUNTING TYPE INDICATING CONTROLLER

High Resolution Temperature Controller REX-F9000. Instruction Manual IM9000F01-E5 RKC INSTRUMENT INC.

SR Mini HG SYSTEM. High-performance Multi-point Control System. SR Mini HG SYSTEM. Hardware Instruction Manual IMSRM15-E6 RKC INSTRUMENT INC.

INSTRUCTION MANUAL Micro-computer based digital indicating controller

Non-contact voltage (for SSR drive): V DC DC current: 4 to 20mA DC Thermocouple: K, J, E Input. RTD: Pt100, JPt100

4TEMPERATURE CONTROLLER

Instruction manual for DIN rail mounting type indicating controller DCL-33A

Nov 08 PRODUCT SPECIFICATION SHEET

Instruction manual Micro-computer based digital indicating controller

4000 1/4 DIN /16 DIN /8 DIN

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

SYL-1512A PID TEMPEARATURE CONTROLLER INSTRUCTION MANUAL Version 2.1

Safety Information. Functional Description. Operation. DANGER Do not touch or contact the input/output terminals because it may cause electric shock.

DIGITAL INDICATING CONTROLLER FCS-23A INSTRUCTION MANUAL

TEMPERATURE CONTROL MODULE MODEL R3-TC2

Series Digital Controller Instruction Sheet

GCS-300 No.GCS31E

CONTENTS. Micro-controller X Model : PXR5/9. Instruction Manual. INP-TN1PXR5/9f-E

AE500 Instruction Manual

Universal controller for panel mounting Models CS6S, CS6H, CS6L

UDC 700 Universal Digital Controllers and Indicator Specifications

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER GCD-200, GCR-200

99 Washington Street Melrose, MA Phone Toll Free Visit us at

SA100. General Description. Features. Temperature Controller SA100. Corresponding to Various Applications. Simple Mounting on DIN Rail

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

02/11/2015

MC-5 Series Micro Processor Temperature Controller

NOVUS AUTOMATION 1/5. Range: -35 to 720 C (-31 to 1328 F) Range: -90 to 1300 C (-130 to 2372 F) Range: 0 to 1760 C (-32 to 3200 F)

CONTENTS. Micro-controller X Model : PXR4, PXR7. Instruction Manual. INP-TN1PXRj-E

CN4800 Series CONTROLLER

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER

VT4810 SINGLE / DUAL ZONE CONTROLLER INSTALLATION MANUAL

Model 96VTR ¼ DIN Process Controller

02/11/2015

SA200. General Description. Features. Temperature Controller SA200. Self-Tuning Algorithm. Close Vertical or Horizontal Mounting

Process & TeMPerATUre UniversAl input DigiTAl MeTers

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER FCS-23A

DCL-33A No.DCL31E To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

CONTENTS. Micro-controller X Model : PXR5/9. Instruction Manual

DIGITAL INDICATOR DI25

CB103/CB403/CB PRODUCT CHECK 2. MOUNTING - * - / /Y INSTRUCTION MANUAL WARNING. 2.1 Mounting Cautions CAUTION RKC INSTRUMENT INC.

AutomationDirect. PC35 Configuration Sheet

Carbon Monoxide Transmitter

VERTEX F4 Instruction Manual

Communications* None RS-232C RS-422 RS-485 BCD Transmission output** (4 to 20 ma)

+ A B V B NO NC V COM PV PV

CONTENTS. Micro-controller X. Instruction Manual. (Socket type) Model : PXR4 Socket INP-TN1PXR4S-E

TEMPERATURE CONTROLLER

Series SHR-5620 Digital Display Volumetric Meter Operation Instruction

DIGITAL INDICATOR JIR-301-M

Temperature Controller

The range of ATR243 controllers comes in three versions. Refer to the table below to easily select your preferred model.

Alarm Output None. Code 5 N Y N R2 R3 A AC/DC100~240V. 2 Relays 3 Relays R4 4 Relays O2 2 Open Collect O3 3 Open Collect O4 4 Open Collect

Specification , July 2015

1. PRODUCT CHECK 2. MOUNTING - * - / /Y

INSTRUCTIONS FOR THE 8500 SERIES MICROPROCESSOR BASED TEMPERATURE CONTROL

4/8/12/16 Channel Temperature Scanner with FREE Data Logging PC Software RS485

1. Model ACS 1 3 A / A, Series name: ACS-13A- /A (W48 x H48 x D62mm) Control action 3 PID A1 A Alarm type can be selected by keypad.

UDC100 Universal Digital Controller Specifications

Three-phase Thyristor Unit. 200 V AC Type THW-A1. Instruction Manual IMR02R01-E1 RKC INSTRUMENT INC.

DIN RAIL MOUNTED INDICATING CONTOLLER DCL-33A INSTRUCTION MANUAL

INSTRUCTION MANUAL FOR TOUCH PANEL MONITORING UNIT CMT-220-K

CONTENTS. Instruction Manual Micro-controller X Model: PXR4

OVEN INDUSTRIES, INC.

7EF/7HF/7EC/7ES Temperature Controllers

Analog Room Pressure Monitor RPC Series

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

UDC1000 & UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

1. PRODUCT CHECK 2. MOUNTING

CM 8. Temperature controllers with compact dimensions. Manual 42/61-71 EN Rev. 01

Table of Contents SECTION PAGE

DIGITAL METERS Large Display Temperature Meters Instruction Manual

Oakton TEMP 9500 Advanced Multiparameter Controller

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

Transcription:

KCE Series Micro Processor Controller Operation Manual KC-400 KC-600 KC-700 KC-800 KC-900 KCE

Contents 1 Safety Guide... 1 1.1 Specifications... 2 1.2 Model Selection Guide... 3 1.3 Model Guide... 3 1.4 Optional Spec.... 3 1.5 Dimension & Panel cutout... 4 1.6 Wiring Terminals... 5 1.6.1 KC-400... 5 1.6.2 KC-700... 6 1.6.3 KC-600... 7 1.6.4 KC-800... 8 1.6.5 KC-900... 9 1.7 Input Actuations... 10 1.8 Modify Input Type... 10 1.8.1 TC RTD Input type selection... 10 1.8.2 TC 4~20mA (Linear) Modify Hardware... 10 1.8.3 TC 4~20mA(Linear) Modify Software... 11 1.8.4 TC 0~10V Modify Hardware... 12 1.8.5 TC 0~10V Modify Software... 12 1.9 Panel Appearance... 13 1.9.1 LED Display... 13 1.9.2 Key and Lamp instruction... 13 Bar Graph indicators (Output 1.9.3... 13 percentage lamp instruction) 1.9.4 Auto tuning... 13 2 Parameters... 14 2.1 Level switch... 14 2.2 First Level list(user Level)... 15 2.3 Error information... 16 2.4 Second Level list (PID Level)... 17 2.5 LOCK (Security)... 19 2.6 Third Level list (INPUT Level)... 19 2.7 INPT Code( Input type selection )... 22 2.8 Fourth Level list (SET Level)... 23 Program Level list 2.9... 24 (Display in programmable controller ) 2.10 Event (Display in programmable controller)... 25

Contents Functions St 8 ~ 10 2.11 (Display in programmable controller)... 25 3 Applications... 26 3.1 Alarm time (ALA1/ALA2/ALA3)... 26 3.2 STAL... 26 Soft Filter 3.3 ( Available for output type SCR)... 26 3.4 Alarm mode (ALA1/ALA2/ALA3)... 27

1 Safety Guide Warning An external device must be installed if failure of this instrument could result damage to the instrument, equipment or injury to personnel. This instrument is not intended for use in locations subject to flammable or explosive gases. Do not touch high-voltage connections such as power supply terminals, ect. to avoid electric shock. All wiring must be completed before power is turned on to prevent electric shock, fire or damage instrument and equipment. This instrument must be used in accordance with the specifications to prevent fire or damage to instrument and equipment. KCE is not responsible if this instrument is repaired, modified or disassembled by other than factory-approved personnel. Malfunction can occur and warranty is void under these conditions. Caution This is a Class A instrument. In a domestic environment, this instrument may cause radio interference, in which case the user may be required to take adequate measures. This instrument is protected from electric shock by reinforced insulation. Provide reinforced insulation between the wire for the input signal and wires for instrument power supply, source of power and loads. If input/output or signal lines within the building are longer than 30 meters or If input /output or signal lines leave the building, regardless the length. Be sure to provide an appropriate surge control circuit respectively. This instrument is designed for installation in an enclosed instrumentation panel. All high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel. All precautions described in this manual should be taken to avoid damage to the instrument or equipment. All wiring must be in accordance with local codes and regulations. To prevent instrument damage of failure, protect the power line and the input/output lines from high currents with a protection device such as fuse, circuit breaker, ect. Tighten each terminal screw to the specified torque found in the manual to avoid electric shock, fire or malfunction. Do not connect wires to unused terminal as this will interfere with proper operation of the instrument. Do not connect modular connectors to telephone line. Maintenance All wiring must be completed before power is turned on to prevent electric shock, instrument failure, or incorrect action. The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again. Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid electric shock, fire or malfunction. For proper operation of this instrument, provide adequate ventilation for heat dispensation. Turn off the power supply before cleaning the instrument. Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or discoloration will occur. Use a soft, dry cloth to remove stains from the instrument. To avoid damage to instrument display, do not rub with an abrasive material or push front panel with a hard object. 1

1.1 Specifications Model KC-400 KC-700 KC-600 KC-800 KC-900 Size 48 48 mm 72 72 mm 96 48 mm 48 96 mm 96 96 mm Weight 170g 270g 250g 250g 330g Power Consumption General Specifications 3VA 3VA 4VA 4VA 4VA Rated Power Supply Voltage & Frequency Ambient Temperature& Humidity A85~265V,50/60Hz 0~50,20-85%RH(Non condensing) TC K,J,R,S,B,E,N,T,W,PLII,U,L PV Input Input Type RTD Linear PT100,JPT100,JPT50 0~1V,0~5V,0~10V,1~5V,2~10V,- 10~10 mv,0~10 mv,0~20 mv,0-50 mv,10~50 mv,4~20 ma,0~20 ma Input sampling Time 250ms Indication Control Mode Output Alarm Input Resolution PV/SP Indication Constant Value Storage System Indication Accuracy Proportional Band(P) Integral Time(I) Derivative Time(D) Cycle Time Dead Band Time Relay Output Relay Voltage Output Linear Output Alarm Output Alarm Mode Alarm Timer 16 bit (Each) 4-digit,7 segment display Non-volatile memory (E 2 PROM) 0.5%FS 0~200% (On/off action at P=3.0) 0~3600 sec (PD action at I=120) 0~900 sec (PI action at D=30) 0~150 se c(4~20ma 0,SSR 1,Relay 10) 0~1000 sec (Dead time compensation) Contact,SPDT,8A/240VAC Voltage Pulse,4VDC/20mA 4~20mA,0~5V,0~10V,1-5V,2-10V 3A,220V 17 alarm Modes Available Flicker Alarm Continued Alarm On Delay Timer Alarm 2

1.2 Model Selection Guide 1.3 Model Guide KC-900(96 96mm) KC-800(48 96mm) KC-700(72 72mm) KC-600(96 48mm) KC-400(48 48mm) 1.4 Optional Spec. Available Unavailable Model Function KC-400 KC-600 KC-700 KC-800 KC-900 1φZero Crossing Control(1φSCR-Z) 3φZero Crossing Control(3φSCR-Z) Output 1 Proportional Motor valve control 1φPhase Angle Control(1φSCR-P) 3φPhase Angle Control(3φSCR-P) Programmable RATE / SOAK Output 2 Alarm2 Alarm3 Heater Break Alarm (HBA) Transmission (TRS) Remote SV Communication DC 24V Power 3

1.5 Dimension & Panel cutout (Unit:mm) KC-400(48 48mm) KC-700(72 72mm) KC-600(96 48mm) KC-800(96 48mm) KC-900(96 96mm) 4

1.6 Wiring Terminals 1.6.1 KC-400 Terminals arrangement Power KCE Series Micro Processor Controller Operation Manual Output OUTI OUT2 Input OUT1 (1ψZero Crossing Control) OUT1 (Proportional Motor valve control) Alarm AL2 AL3 Transmission (TRS) Communication Double Output- Proportional Motor valve control 5

1.6.2 KC-700 Terminals arrangement OUTI Output OUT2 Power OUT1 (1ψZero Crossing Control) OUT1 (Proportional Motor valve control) OUT1(1φPhase Angle Control) Input Transmission (TRS) Remote SV Communication Alarm 6

1.6.3 KC-600 KCE Series Micro Processor Controller Operation Manual Terminals arrangement Input Power Output OUTI OUT2 Alarm OUT1 (Proportional Motor valve control) OUT1 (1ψZero Crossing Control) Communication Transmission (TRS) Remote SV 7

1.6.4 KC-800 KCE Series Micro Processor Controller Operation Manual Terminals arrangement Input Alarm Output OUTI OUT2 Power Transmission (TRS) OUT1 (Proportional Motor valve control) OUT1(1φPhase Angle Control) Communication Remote SV 8

1.6.5 KC-900 KCE Series Micro Processor Controller Operation Manual Terminals arrangement Alarm Input Power Communication Remove SV +Communication Output OUTI OUT2 Transmission (TRS) Remote SV OUT1 (1ψ Zero Crossing Control) OUT1 (3ψZero Crossing Control) OUT1 (Proportional Motor valve control) OUT1(1φPhase Angle Control) OUT1(3φPhase Angle Control) 9

1.7 Input Actuations K 0.0~200.0,400.0,600.0,800.0,1000, 1200 KCE Series Micro Processor Controller Operation Manual PT100Ω -199.9~600.0,400.0,200.0 0.0 ~200.0,400.0,600.0 J 0.0~200.0,400.0,600.0,800.0,1000, 1200 RTD J PT100Ω -199.9~600.0,400.0,200.0 0.0 ~200.0,400.0,600.0 TC R 0.0~1600,1769 S 0.0~1600,1769 AN1 JPT50Ω -199.9~600.0,400.0,200.0 0.0 ~200.0,400.0,600.0-10~10mv,±2V, ±5V,±10V B 0.0~1820 AN2 0-10mV E 0.0~800,1000 Linear AN3 0~20mV N 0.0~1200,1300 AN4 0~50mv,0~20mA,0~5V,0~10V T 0.0~400.0,200.0,0.0~350.0 W 0.0~2000,2320 AN5 4~20mv,1~5V,2~10V PLII 0.0~1300,1390 U -199.9~600.0,200.0,0.0~400.0 L 0.0~400.0,800.0 1.8 Modify Input Type 1.8.1 TC RTD Input type selection To select Input type at INPT in Level 3(SET Level). TC TC RTD RTD 1.8.2 TC 4-20 ma (Linear) Modify Hardware Please make S1 to be a short circuit as following drawing. 10

1.8.3 TC 4-20 ma (Linear) Modify Software Step: 1. Set St-2-2=1,Parameter INLO/INHI/DP will show in LEVEL 3 2. Set INPT from K2 to AN5 in LEVEL 3(INPUT Level) 3. Parameter DP can change the decimal point position KCE Series Micro Processor Controller Operation Manual 4. Use Multifunction Calibrator to adjust Level 4 St-2-2=1 Level 3 Into SET LEVEL Set St-2-2=1,Parameter INLO/INHI/DP will show in LEVEL 3 Into INPUT LEVEL Presumption value INLO=0 /INHI=5000 Adjust PVLO & PVHI Multifunction Calibrator INLO= ZERO INHI= SPAN Setting the measuring range: PVLO~PVHI Presumption value K2=0.0~400.0 AN5=0.0~100.0 4mA Input 4mA current Input 20mA current 20mA Adjust Parameter INLO until PV=PVLO Adjust Parameter INHI until PV=PVHI Adjusted SV by UP and DOWN key until PV = PVLO NO Check Input 4mA PV=PVLO Input 20mA PV=PVHI YES Calibration finished Adjusted SV by UP and DOWN key until PV = PVHI Ex1: Type AN5 =Input 4~20mA Setting range 0.0~100.0 PVLO=0.0 PVHI=100.0 INLO -212 INHI 4141 Ex2: Type AN4 =Input 4~20mA Setting range 4.0~20.0 PVLO=0.0 PVHI=20.0 INLO -1233 INHI 1293 *(The value will have individual differences ) 11

1.8.4 TC 0-10V (Linear) Modify Hardware 1. Please make S1 short circuit as following drawing. 2. Cut the line between S2 and put a resistance (2K) on S2 and fixed it by soldering. 1.8.5 TC 0-10V (Linear) Modify Software Step: 1. Set St-2-2=1,Parameter INLO/INHI/DP will show in LEVEL 3 2. Set INPT from K2 to AN4 in LEVEL 3(INPUT Level) 3. Parameter DP can change the decimal point position 4. Use Multifunction Calibrator to Calibration 12

1.9 Panel Appearance 1.1 Display KC-900 KC-800 KC-700 KC-600 KC-400 1.9.1 LED Display P V:Process Value, 4 LED display (Red color) S V:Set Value, 4 LED display (Green color) 1.9.2 Key and Lamp instruction Symbol Name Symbol Name Symbol Name SET key OUT1 Output1,Green color AL3 Alarm 3,Red color Auto/Manual key. OUT2 Output2,Green color MAN Manual,Yellow color Shift key A T Auto Tuning,Yellow color PRO Program,Yellow color Down key AL1 Alarm 1,Red color OUT% Output percentage Up key AL2 Alarm 2,Red color 1.9.3 Bar Graph indicators (Output percentage lamp instruction) Output segment(8 segment s) Output pattern(2 patterns) 1.9.4 Auto tuning When AT (USER LEVEL) is set to YES,auto tuning will start. When set to NO,auto tuning will close. 13

2 Parameters 2.1 Level switch First Level (USER Level) When LOCK=0,Press the + key, into third (INPUT) level Press the + key back to first (USER) level Press the 5 sec. Second Level (PID Level) When LOCK=0,Press the + key,into third(input) level Third Level (INPUT Level) When LOCK=1111,Press the + key,into fourth(set) level How to return First level: 1 The controller will return to First level If user without Fourth Level (SET Level) any operation within 60 seconds. 2 Press AUT/MAN key twice. 14

2.2 First Level list (USER Level) PV Process Value Note1 *PV Two SV display SV Set Value 100 / (Need add hardware) PV OFF /25 Press key to turn ON or OFF To enter PID Level (Press key 5 seconds) AT YES / NO AutoTuning Note2 *A 0.0 HBA (CT Fault Alarm) ALA1 0.0 (Need add hardware) Set Alarm 1 0 *ALA2 Set Alarm 2 0 Note3 OUTP 100.0 Press key *ALA3 to display Output percentage Set Alarm 3 0 *OUTL PV Press key to close SV Set Output Low Limit display (St-4-1=1) 0 OFF *OUTH 100 Set Output High Limit * Hiding function Return to PV Note 1: Two SV display Note 2: CT Fault Alarm (HBA) Note 3: Output percentage 15

2.3 Error information Display Description Note 1NER Input 1 error 2NER Temperature is too high INHI PV exceeds PVHI INLO PV under PVLO 2NHI 2NLO ATER PV2 exceeds PVHI PV2 under PVLO Auto tuning failed. When the error marked show up,please send it to the nearest sales office or retail dealer IFER Interface failed. ADER A/D convert failed. CJER Cold junction compensation failed. RDER RAM failed. 16

2.4 Second Level list (PID Level) Press key for 5 seconds to enter Second Level P-1 Range:0-200% HYS1 Proportional Band Time 1 3.0 Display when P1=0 0.0 Display when output 2 is provided I-1 Integral Time 1 120 D-1 Derivative Time 1 30 DB-1 Dead-band Time 1 100.0 AT-L Auto tuning offset value 5.0 CY-1 15 Cycle Time 1 Range:0-3600 seconds Range:0-900 seconds Range:0-100 Range:0-400 Relay 15 SSR 1 seconds SCR 0 seconds Hysteresis for output 1 ON / OFF Control OFF: PV > SV + HYS1 ON :PV < SV - HYS1 * P-2 Range:0-200% HYS2 Proportional Band Time 2 3.0 Display when P2=0 0.0 * I-2 Integral Time 2 120 * D-2 Derivative Time 2 30 * CY-2 15 Cycle Time2 * GAP.1 Control Gap 1 0.0 * GAP.2 Control Gap 2 0.0 LOCK Level Function Set 0 Return to P1 Range:0-3600 seconds Range:0-900 seconds Relay 15 SSR 1 seconds SCR 0 seconds Hysteresis for output 2 ON / OFF Control OFF: PV > SV + HYS2 ON :PV < SV - HYS2 Setting value of output 1 = SV - GAP.1 Setting value of output 2 = SV+ GAP.2 Change lock from 0 to 1111, than press Mode+ key to enter the fourth Level * Hiding function 17

2.5 LOCK (Security) This parameter specifies which level are protected. LOCK Available entering level First Level Second Level Third Level Value (USER Level) (PID Level) (INPUT Level) Fourth Level (SET Level) Available change parameters 0000 О О О All parameters(default value) 1111 О О О Level 1 2 4 0100 О О Level 1 2 0110 О О Only Level1 0001 О О SV and LOCK 0101 О О Only LOCK 18

2.6 Third Level list (INPUT Level) Press + key 5 sec. to enter Third Level(LOCK=0) Parameter Description Range Level INPT K2 * INLO 0 * INHI 5000 * DP 000.0 PVLO 0.0 PVHI 400.0 * 2NLO 0 * 2NHI 5000 A1D1 11 A1T1 99.59 * A2D2 0 * A2T2 99.59 Input type selection Analog input low limit calibration Analog input high limit calibration Decimal point position See the step 2.6 Input selection Range:-199.9 ~ 999.9 Range:0~999.9 Four Types: 0000,000.0,00.00,0.000 Third Level St-2-2 St-2-2 St-2-2 Lower set-point limit Range:-199.9~999.9 St-2-3 Upper set-point limit Range:-199.9~999.9 St-2-3 Remove input low limit calibration Remove input low limit calibration Alarm mode of AL1 Alarm time of AL1 Alarm mode of AL2 Alarm time of AL2 Range:-199.9 ~ 999.9 Range:-199.9~999.9 Refer to the step 3.4 Alarm action description Refer to the step 3.4 Alarm action description St-2-4 St-2-4 St-1-3 St-1-3 St-1-4 St-1-4 19

Parameter Description Range Level * A3D3 Alarm mode of AL3 St-2-1 0 Refer to the step 3.4 Alarm action description * A3T3 99.59 Alarm time of AL3 St-2-1 HYSA 0.0 LO01 200 HI01 3400 * LO02 200 * HI02 3400 * LO03 0 * HI03 5000 * R-Y 5 * W-T 0.0 * STAL 0000 Hystersis of all alarm Range:0~100 St-4-3 Output 1 low limit calibration Output 1 high limit calibration Output 2 low limit calibration Output 2 high limit calibration Retransmission low limit calibration Range:0~9999 Range:0~9999 Range:0~9999 Range:0~9999 Range:0~9999 St-4-4 St-4-4 St-5-1 St-5-1 St-5-2 Retransmission high limit calibration Range:0~9999 St-5-2 Full run time of proportional motor Range:5~200 Seconds St-5-3 Wait for continued operation(used for programmable controller) When need the alarm of " b point", can use this function 0=No wait Others=Wait value Range:0~1111 St-5-3 St-5-3 20

Parameter Description Range Level * ID. 2 ID number Range:0~255 St-5-4 * STOP 0-81 * BAUD 9600 SVOS 0.0 PVHS 0.0 * C-F C. S-F 600 PVHS 0.0 * H-C HEAT +- 0.0 FILT 2000 Return to INPT MODBUS Baudrate O-81,E-81,N-81 O-82,E-82,N-82 Selection:110,300, 1200,2400,4800,9600, 19200,38900bps St-5-4 St-5-4 SV compensation Range:-100~100 St-6-1 PV low compensation Range:-100~100 St-6-1 Unit of PV & SV C,F,A (Analog) St-6-3 Soft Filter Range: 50~5000 Output response adjustment (slower If Soft Filter is lower) St-6-4 PV high compensation Range:-50~50 St-6-1 Control mode Heating / Cooling St-7-2 Digital Filter offset value Digital Filter St-7-4 St-7-4 * Hiding function 21

2.7 INPT Code (Input type selection) Type 1 2 3 4 5 6 K K1,200.0 K2,400.0 K3,600 K4, 800 K5, 1000 K6, 1200 J J1,200.0 J2,400.0 J3,600 J4,800 J5,1000 J6,1200 R R1,1600 R2,1769 S S1,1600 S2,1769 B B1,1820 E E1,800 E2,1000 N N1,1200 N2,1300 T T1,400.0 T2,200.0 T3,350.0 W W1,2000 W2,2320 PL PL1,1300 PL2,1390 U U1,-199.9-600.0 U2,-199.9-2 00.0 U3,400.0 L L1,400 L2,800 JP 100Ω JP1,-199.9 600.0 JP2,-199.9 400.0 JP3,-199.9 200.0 JP4,200 JP5,400 JP6,600 DPT 100Ω dp1,-199.9 600.0 dp2,-199.9 400.0 dp3,-199.9 200.0 dp4,200 dp5,400 dp6,600 JP. 50Ω JP1,-199.9 600.0 JP2,-199.9 400.0 JP3,-199.9 200.0 JP4,200 JP5,400 JP6,600 AN1-5 AN1-5 An1/ -10~10mv -1999~-9999 An2/ 0~10mv 2-1999~9999 An3/ 0-20mv 2-1999~9999 An4/0~50mv 0~20mA 0~5V -1999-9999 22

2.8 Fourth Level list (SET Level) Press + Key to enter the fourth level ( LOCK =1111 ) 0 = Hide PV St-1 1 = Display SV 0 0 0 0 St-1-1 St-1-2 St-1-3 St-1-4 Description Default value 4 3 2 1 0110 St-1 ALA2,A2D2, A2T2 ALA1,A1D1, A1T1 AT OUTP,OUTL, OUTH 0100 St-2 2NLO,2NHI PVLO,PVHI 1NLO,1NHI,DP ALA3,A3D3, A3T3 0000 St-3 * * * * Display/Hiding Parameters 1100 St-4 LO01,HI01 HYSA (Hysterics of all alarm) SV1 / SV2 (Event) ON-OFF (OUT1 Controller switch) 0000 St-5 ID,BAUD,STOP R-Y,W-T,STAL LO03,HI03 LO02,HI02 Special Functions 1001 St-6 1000 St-7 0000 St-8 0000 St-9 1000 St-10 S-F (1= Automatic 0= Manual) FILT (Error value +1 or -1) C-F (UNIT= C,F,A) Power ON -Run AT 1=MODBUS 0= None H-C(Heat / Cool) PVOS,PVHS, SVOS OUT2 4-20mA Re-Transmission Program Function (Only available for programmable controller, refer to the step 2.11) Remote SV Setting 0 INP2 0 OUTY 0 = None 2 = 0~50mV/0~20mA/0~5V/0~10V 0 = Single output(out1) 2 = None 4 = 1 Phase angle control (1ψ SCR) 1 = 10~50mV/4~20 mv/1~5v/2~10v 4 = CT input 1 = Dual output(out1/ OUT2) 3 = Motor valve control 5 = 3 Phase angle control (3ψ SCR) (*=None function) 23

2.9 Program Level list (Display in programmable controller ) LEVEL 1 PROG 1 SET 1-0 TIMR 00.00 SV01 Program Pattern setting Range: 0~2 Display program segment (Pattern _Segment _) Display program countdown Range: 0~99 hour 59 min Seg.1 SV value setting Range: PVLO~PVHI TM01 00.00 OUT1 100 EVI Seg.1 time setting Range: 0~99 hour 59 min ( Change Unit "min.sec." at St-9-2) Seg.1 output limit setting Range:0~100% Seg.1 event setting SV08 TM08 00.00 OUT8 100 EV8 ( Seg.2~7 same as above ) Seg.8 SV value setting Range: PVLO~PVHI Seg.8 time setting Range: 0~99 hour 59 min Seg.8 output limit setting Range:0~100% Seg.8 event setting Return to LEVEL 1 24

2.10 Event (Display in programmable controller) Alarm mode select b (refer to the step 3.5 Alarm mode) 0 = OFF EV1 1 = ON 0 0 0 0 A1D1 A2D2 A3D3 None 2.10 Special Functions(Display in programmable controller) If the LEVEL 4 St-8-4 = 1, reopen will run from Seg.1 TM01 0 = None - - - - ----Not restart 2.11 Functions St 8 ~ 10 (Display in programmable controller) 4 3 2 1 St-8 0 = OFF 1 = Run from Seg.1 0 = Seg.1 run from 0 1= Seg.1 run from PV 0= No power failure option 1= With power failure option 0 =Program not repeat 1 = Program repeat St-9 0 = 4-20 ma Transmission 1 = 20-4mA Transmission 0 = PV Transmission 1 = SV Transmission Need to add Transmission function 0 = TM Unit "Hour : Min." 1 = TM Unit " Min : Sec." 0 = Manual Output percentage 1 = Automatic Output percentage St-10 0 = Motor valve closed and output relay use"b" contact (Default value) 1 = Motor valve closed and output relay use"a" contact 0 = Disable Remote SV function 1 = Enable Remote SV function 0 = Hide parameter RATE 1 = Display parameter RATE at LEVEL 1 Parameter ALA3 will be hide 0 = TTL Communication (Slave) 1 = TTL Communication (Master) Used for TTL Communication 25

3 Applications 3.1 Alarm time (ALA1/ALA2/ALA3) ALA1=0 ALA1=99.59 ALA1=000.01~99.58 Flicker alarm Continued alarm Delay Alarm time setting 3.2 STAL STAL (When LEVEL 4 St-5-3 =1, display in LEVEL 3 ) 0 = OFF PV STAL 1 = ON SV 0 1 1 1 ALA1 Relay reversely ALA2 Relay reversely ALA3 Relay reversely 0 = Program run alarm 1 = Program end alarm 3.3 Soft Filter (Available for output type SCR) Needed "b" contact, can use this function Only available for programmable controller PV S-F SV 0 1 1 1 LEVEL 4 St-6-4 = 1 ON (Default value = 600,Range: 50-5000) = 0 OFF When the value is low and the sensitivity will be diluted, suitable for slowly heating and equable environment. When the value is high and the sensitivity will be augmented, suitable for quickly heating and instability environment. (If AT run once,s-f value will auto-add 200. The value will start from 200 when arrive to 1000. ) 26

3.4 Alarm mode (ALA1/ALA2/ALA3) :SV Δ:Alarm start value 00 10 No alarm 15 Process high alarm 01 Deviation high alarm (with hold action) 06 Process low alarm (with hold action) Deviation high alarm Process low alarm 11 16 02 12 Deviation low alarm (with hold action) Deviation low alarm 07 Segment end alarm (Only available for programmable controller) 1. A1D1~3 set = 07 2. ALA1~3=Alarm Segment 3. ALT1~3 set as follows: = 0 Flicker alarm = 99.59 Continued alarm = others Alarm ON time Deviation high/low alarm (with hold action) Program run alarm (Only available for programmable controller) 03 17 Deviation high/low alarm System failed alarm (ON) 13 08 04 14 Band alarm 18 System failed alarm (OFF) 05 Process high alarm (with hold action) 09 RAMP a Heater Break Alarm( HBA ) b c d e f Programmable The function is expanded 19 SOAK 27 100428