FX-PDD Duct Smoke Detector Installation Sheet

Similar documents
E-PDD Duct Smoke Detector Installation Sheet

SIGA-CC1 Single Input Signal Module Installation Sheet

Installation Instructions

Print Specification. Publication. Instructions. Specific requirements. General requirements

Application Data ! WARNING FACTORY INSTALLED SMOKE DETECTORS FOR SMALL AND MEDIUM ROOFTOP UNITS 2TO25TONS TABLE OF CONTENTS PART NUMBERS

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

INSTALLATION AND MAINTENANCE

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS

SK-Duct Air Duct Smoke Detector

Genesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet

Installation Instructions

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH100LP Air Duct Smoke Detector with Extended Air Speed Range

D343. Installation Instructions. Air Duct Smoke Housing

Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

D2E Duct Smoke Detector

DH100ACDCI Ionization Air Duct Smoke Detector

DH400 Air Duct Smoke Detector

DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range

DH100ACDCI Ionization Air Duct Smoke Detector

Duct smoke housing, 2-wire D340/D340P

DH500 Intelligent Air Duct Smoke Detector Housing

Duct smoke housings, 4-wire D341/D341P and D342/D342P

DH500ACDC Intelligent Air Duct Smoke Detector Housing

Addressable Detectors & Bases

Signature Series Auto-Sync Output Module (CC1S)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

SECTION FIRE ALARM SYSTEMS

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

DNRHS Intelligent Air Duct Smoke Detector

7251DH Intelligent Air Duct Smoke Detector

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

DNR Duct Smoke Detector

DNR Duct Smoke Detector

DNR-AUS Duct Smoke Detector

1400 Direct Wire Ionization Smoke Detector

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION

DNRECL Eclipse Duct Smoke Detector

PAD100-6DB & PAD100-4DB PAD100-PD

TrueAlarm Analog Sensing

Installation Manual. Detector Bases: PAD100-IB, PAD100-RB & PAD100-SB

DUCTSD Duct Smoke Detector

PRODUCT OVERVIEW SM-501 AT-A-GLANCE

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

TS93 EMR WITH SMOKE DETECTOR

PRODUCT OVERVIEW. SL-2000 AT-A-GLANCE MODEL NUMBER: SL-2000-N 4-Wire Ionization Duct Smoke Detector SL-2000-P 4-Wire Photoelectric Duct Smoke Detector

ESL 500N Series Smoke Detector Installation Sheet

R-Series Remote Annunciators and Expanders Installation and Operation Guide

TrueAlarm Analog Sensing

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

DH100ACDCLPX Air Duct Smoke Detector with Extended Air Speed Range

Control Relay Modules

, -9686, -9688, -9755, Duct Detector/Sensor Installation Instructions

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Installation Manual. Detector Base: PAD100-SPKB

SILENT KNIGHT. IntelliKnight Smoke Detector Cleaning and Testing Instruction. Equipment Needed. Testing Equipment. Cleaning Equipment

Addressable NAC Output Module D327A

Duct and Rough Service Carbon Monoxide Sensor

Wiring Instructions (01-09)

Photobeam 5000 ISC-FPB1-W60QS, ISC-FPB1-W120QS, ISC-FPB1-W200QS. en Installation and Operation Guide

TrueAlarm Analog Sensing

Booster Power Supply Manual

NetworX NX-548E Receiver Installation Instructions

Instructions. Duct Mount Accessory Q Rev: 11/

RF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors

ATS1235 Advanced Wireless DGP on 868 MHz AM Installation Sheet

Powers Controls Low Temperature Detection Thermostat

DD205RF/TX Detector Installation Sheet

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

TECHNICAL DATA OBSOLETE

TrueAlarm ES Analog Sensing

Photobeam 5000 ISC-FPB1-W60QF, ISC-FPB1-W120QF, ISC-FPB1-W200QF. en Installation and Operation Guide

D7052. Installation Instructions Multiplex Dual Input Module

4100U City and Relay Cards Installation Instructions

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

You in Control PRODUCT OVERVIEW SM-501 AT-A-GLANCE

30.45 Electric Release PDRP-2001

Installation Smoke Detector ELQZ , GOLD

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

You in Control PRODUCT OVERVIEW

Signature Series Component

LASER ASPIRATED SMOKE DETECTOR

MODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

LASER ASPIRATED SMOKE DETECTOR

0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS

DUCT SMOKE DETECTOR D4120

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for models:

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation and Operation Manual

TrueAlarm Smoke Detectors

Transcription:

FX-PDD Duct Smoke Detector Installation Sheet Table 2: LEDs LED Power LED Alarm/active LED Off when the detector is in the alarm state. Flashes intermittently when the detector is in the normal state. Indicates the detector is in the alarm/active state. Installation WARNINGS The duct smoke detector is not intended as a substitute for open area protection. The FX-PDD Duct Smoke Detector is designed for use in duct applications where temperatures can exceed standard detector capabilities. The device address is set using the two rotary switches located on the front of the unit. One device address is required. In installations where the controls and indicators are hidden from view, a remote test station or an LED indicator can be connected to the detector to provide these functions. Jumper settings The following jumper settings determine the operation of the detector. See Figure 6 for proper jumper location. Table 1: JP3 jumper settings Setting Alarm Supervisory LED operation Configures the detector for alarm latching operation. Configures the detector for supervisory operation. This is the factory default setting. Two LEDs, visible from the front of the detector, show its status. This detector does not operate without electrical power. As fires frequently cause power interruption, discuss further safeguards with the local fire protection specialist. The duct smoke detector does not operate as designed outside of the listed electrical and environmental specifications. The duct smoke detector does not sense smoke unless the ventilation system is operating and the sensor s cover is properly installed. The duct smoke detector may not operate as designed unless installed in accordance with these instructions and all applicable national and local codes as determined by the local authority having jurisdiction. Note: Read these instructions thoroughly before installing. Refer to Technical Bulletin P/N 3101107 for additional information regarding installation instructions. Installation guidelines To ensure correct operation, install the duct detector using the following guidelines: Install the duct smoke detector on a flat section of HVAC duct between six and ten duct widths from any bends or obstructions. Install supply-side detectors at a point downstream from the supply fan and after the air filter. Install return-side detectors at a point before the return air stream is diluted by outside air. Verifying the duct air velocity In order to verify the airflow direction and velocity, air must be moving through the HVAC system. 2013 UTC Fire & Security. All rights reserved. 1 / 6 P/N 3101069 REV 03 REB 23JAN13

To verify the duct air velocity: 1. Drill a small hole at the point where the duct smoke detector is being installed. 2. Using the SD-VTK Air Velocity Test Kit and a suitable air velocity meter, verify that the air velocity in the HVAC duct falls within the specified operating range of the detector and note which direction the air flows. 3. If the air velocity does not fall within the specified range, relocate the detector and seal the hole in the HVAC duct. Refer to Technical Bulletin P/N 3101107 for additional information pertaining to installation locations. Selecting an appropriate sampling tube: Select a sampling tube that extends at least two-thirds across the width of the duct. Refer to Table 3 below. For duct widths greater than 36 inches, use a sampling tube that is longer than the width of the duct. Sampling tubes are available in the following lengths: Table 3: Sampling tubes Model Length (in.) Model Length (in.) SD-T8 8 SD-T42 42 SD-T18 18 SD-T60 60 SD-T24 24 SD-T78 78 SD-T36 36 SD-T120 120 Figure 1: Duct detector assembly (9) (8) Exhaust tube socket Sampling tube socket Detector Coupling Sampling tube Figure 2: Sampling tube installation Plug Thick gasket (8) Thin gasket (9) Exhaust tube To assemble the detector: 1. Assemble the duct smoke detector as shown Figure 1. 2. Rotate the air sampling tube so the inlet holes face the direction of airflow. 3. The sampling tube is normally installed from the rear, but it can also be installed from the front of the detector as shown in Figure 2. This method requires that you remove the detector cover. Sampling tube socket Detector Sampling tube (fully assembled) To install the detector: 1. Attach the drill template to the HVAC duct at the desired mounting location. 2. Drill (or punch) the mounting holes where indicated. 3. Remove any rough edges from the holes. 2 / 6 P/N 3101069 REV 03 ISS 23JAN13

4. When using an air sampling tube that is longer than the width of the duct: Drill a 3/4 in. hole on the opposite side of the duct for the tube to pass through. Cut the tube so that approximately one inch of the tube extends through the duct. Seal the opening around the tube with an approved duct sealant as shown in Figure 3. Note: Support sampling tubes longer than 36 inches at both ends of the duct. See Figure 3. 5. Mount the duct smoke detector on the HVAC duct and secure it using the two sheet metal screws provided. See Figure 4. 7. Verify that all field wiring is free of opens, shorts, and ground faults. 8. Make all wiring connections as shown in Figure 6. 9. Set the module address as follows: Use a screwdriver to adjust the two rotary switches on the front of the module. See Figure 5. Set the TENS rotary switch (0 through 12) for the 10s and 100s digit. Set the ONES rotary switch for the 0 through 9 digit. For example: for device address 21, set the TENS rotary switch to 2, and then set the ONES rotary switch to 1. For a list of detector addresses, see Table 4 below. 10. Set jumper JP3 to the appropriate position. See Table 1 and Figure 6. 11. Verify that the air pressure differential value falls within the specified operating range of the detector in accordance with procedures specified in Verifying the air pressure differential on page 5. 12. After completing the installation of the duct smoke detector, test the detector in accordance with procedures specified in Testing the duct smoke detector on page 5 to ensure it is operating correctly. Table 4: Detector address Address Panel 01 to 64 64 point control panel 01 to 127 127 point control panel Figure 3: Sampling tube support HVAC duct Exhaust tube Detector Sampling tube 36 in. (0.92 m) Figure 4: Duct detector installation Airflow HVAC duct Detector Figure 5: Address switches Airflow Plug Sealant #10 sheet metal screws (2X) Sampling tube 4 5 6 3 2 1 0 7 8 9 10 12 11 3 4 5 6 7 8 0 9 2 1 Insert screwdriver here P/N 3101069 REV 03 ISS 23JAN13 3 / 6

Wiring Wire in accordance with NFPA 72 and CAN/ULC-S524. Be sure to observe the polarity of the terminals on the terminal block as shown in Figure 6. Figure 6: Duct detector wiring (8) (9) JP3 Auxiliary equipment. Power-limited unless connected to a nonpower-limited source. If the source is nonpower-limited, eliminate the power-limited mark and maintain a minimum of 0.25 in. (6.4 mm) space from power-limited wiring. For other mounting methods, see enclosure and bracket installation sheets to maintain separation of power-limited and nonpower-limited wiring. The wire size must be capable of handling fault current from the nonpower-limited source. or Use type FPL, FPLR, FPLP, or permitted substitute cables, ensuring that the power-limited cable conductors extending beyond the jacket are separated by a minimum of 0.25 in. (6.4 mm) space or by a nonconductive sleeve or nonconductive barrier from all other conductors. The wire size must be capable of handling fault current from the nonpower-limited source. Refer to NFPA 70 for more details. Remote alarm/active indicator. See Specifications on page 6 for a list of available model numbers. Connect only one remote test station or LED indicator to the detector. Wiring is unsupervised. Maximum wire resistance is 10 Ω per wire. Remote test station. See Specifications on page 6 for a list of available model numbers. Power indicator. Alarm Indicator. JP3 (shown in the factory default position, for supervisory mode). (8) Alarm position. (9) Supervisory position. 4 / 6 P/N 3101069 REV 03 ISS 23JAN13

Testing Verifying the air pressure differential In order to verify air pressure differential, air must be moving through the HVAC system. To verify the air pressure differential: 1. Connect a suitable air pressure differential meter to the sampling tube and exhaust tube openings as shown in Figure 7. 2. Verify that the air pressure differential reading falls within the specified operating range of the detector. See Specifications on page 6. 3. If the air pressure differential measured does not fall within the specified operating range of the detector, make sure the sampling tube air holes are not obstructed and are facing the HVAC system airflow. Figure 7: Air pressure differential Table 5: Replacement parts Model FX-SDPCB Cleaning the duct smoke detector PCB replacement kit for duct smoke detector Clean the duct smoke detector when it becomes 80% to 99% dirty or sooner if conditions warrant. Caution: Before cleaning the duct smoke detector, notify the proper authorities that the fire alarm system is undergoing maintenance and take steps to prevent the control panel from responding to a false alarm. To clean the duct smoke detector: 1. Disable the detector or zone to prevent false alarms. 2. Remove the detector s cover, and then power down the detector by disconnecting the SLC wiring. See Figure 6. 3. Using a vacuum cleaner, clean compressed air, or a soft bristle brush, remove loose dirt and debris from inside the detector housing and cover. 4. Remove dirt and other contaminants from the gasket on the detector s cover using isopropyl alcohol and a lint-free cloth. 5. Squeeze the retainer clips on both sides of the optic housing then lift the housing away from the printed circuit board. See Figure 8. 6. Gently remove dirt and debris from around the optic plate and inside the optic housing. 7. Replace the optic housing and the detector cover, and then connect the SLC wiring. 8. Test the detector and verify its sensitivity. For details, refer to Technical Bulletin P/N 3101107. Figure 8: Duct detector cleaning Airflow Sampling tube HVAC duct Exhaust tube opening Air pressure differential meter Sampling tube opening Testing the duct smoke detector After completing installation of the duct smoke detector, test the detector to ensure it is operating correctly prior to leaving the site. For details, refer to Technical Bulletin P/N 3101107. Maintenance Replacement parts The following table lists the replacement parts for the duct smoke detector. Sampling tube HVAC duct Detector housing Optic plate Retainer clip Optic housing Airflow P/N 3101069 REV 03 ISS 23JAN13 5 / 6

Specifications Communication line voltage Operating current Normal Alarm Inrush Common alarm relay/auxiliary equipment Quantity Type Rating Air velocity Air pressure differential Smoke sensitivity range Smoke detection method Alarm test response time Dimensions Wire size Operating environment Temperature Relative humidity Accessories SD-TRM SD-TRK SD-MAG SD-VTK R-LED 20 Vp-p max. 45 µa 45 µa 1 ma Unsupervised and power-limited 1 Form C 2.0 A at 30 VDC (resistive) 100 to 4,000 ft./min 0.005 to 1.00 in. of water 0.79 to 2.46%/ft. obscuration Photoelectric (light scattering principle) 5 seconds 8.70 5.45 1.90 in. 14 to 22 AWG wire 32 to 122 F (0 to 50 C) 0 to 93%, noncondensing Remote test-reset station, magnetic Remote test-reset station, keyed Test magnet kit Air velocity test kit Remote LED alarm indicator Regulatory information Manufacturer Year of manufacture North American standards Contact information Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA The first two digits of the product serial number (located on the product identification label) are the year of manufacture. UL 268A, CAN/ULC S529-02 For contact information, see www.edwardsutcfs.com. 6 / 6 P/N 3101069 REV 03 ISS 23JAN13