Concealed Fan Coil Units DY18/KY018 thru DY60/KY TR thru 5 TR 5 kw thru 17.5 kw Cool & Heat pump models

Similar documents
GENERAL ELECTRIC CONCEALED SYSTEMS

Concealed Ducted Split Series R-407C MBH

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

GENERAL ELECTRIC VERTICAL PACKAGED UNITS

GENERAL ELECTRIC AIR HANDLING UNITS DIRECT EXPANSION. ABQ Series ABQ03 thru ABQ TR thru 30 TR 9 kw thru 105 kw

PACKAGE AIR CONDITIONER

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

PAJ3. Product Specifications

MACH N-407 Heat Pump Air-Cooled Chiller

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

Advance Release September 2009

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION

MAC N-407 Air-Cooled Chiller

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

2 shp 13 lc 1 36 t - 1 a

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw)

Commercial High-Efficiency Condensing Units

Product Specifications. Vertical Floor Consoles By First Co.

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

Commercial High-Efficiency Condensing Units

Product Data. 50ZP (60Hz) Single-Package. Air Conditioners 3-5 Nominal Tons

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

PC SERIES 50 Hertz PRODUCT SPECIFICATIONS. Self-Contained Packaged Air Conditioners. 4 and 5 Ton [14.1 kw to 17.6 kw]

PRODUCT SPECIFICATIONS 2YCC3048A1120A /1/ /

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

MAC-120HE-03 Air-Cooled Chiller

WineZone Ceiling Mount Ductless Split 15

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

All side discharge units are having high pressure switch (LP switch- Optional) and time delay relay. Compressors are scroll type, Copeland make.

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

CWA4 Chilled & Hot Water Fan Coil

CFFWA4P-16-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 48,000 BTUH

Your Climate. We're There. TM: MDB B 2140B. Ducted Split Systems. Models: MDB 075B - MDB750B MDB 075B/B - MDB500BR. Air Conditioning REGISTERED

CFFWA4P-12-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 36,000 BTUH

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

EHH SERIES DRAW THROUGH FAN COILS CFM

CFFWA4P-08-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 24,000 BTUH

VariCool VAV Engineering Guide

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH

38LB/38LF AIR COOLED CONDENSING UNIT

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

AIR COOLED PACKAGED CHILLER

SKYPAK II, 3 Ton Series, gives you a

Product Data. 50EES--ZP (50Hz) Single Package Air Conditioners 3-5 Nominal Tons

4YCC3048A3096A /3/ /

2YCC3060A1120A /1/ / YCC3060A1096A /1/ /

DUCTED SPLIT AIR CONDITIONERS 50Hz GCUN/GDS SERIES R 407C

Model 655A Sizes

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SPECIFICATIONS 4YCC3060A-SPEC-1A SINGLE PACKAGED GAS HEATING ELECTRIC COOLING 4YCC3060A1096/120B TAG:

CB18/CBS18 Bulletin # September 1994 Supersedes August 1986

WJH4 Product Specifications

SKYPAK II, 3 Ton Series, gives you a

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

ELITE Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,800 to 60,000 Btuh AIR CONDITIONERS EL16XC1 PRODUCT SPECIFICATIONS

EMI ENGINEERING SUBMITTAL

SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS

Product Data PH13(N,P)R FEATURES AND BENEFITS. SPLIT SYSTEM HEAT PUMP For Use With R Refrigerant 1---1/2 TO 5 TONS ( )

technical guide Water-Cooled Self-Contained Units

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

DRY CHARGE UNITS. 1.5 to 5 Tons. HEAT PUMP OUTDOOR UNITS lps13dc PRODUCT SPECIFICATIONS L P S 13 DC MODEL NUMBER IDENTIFICATION

4YCC3036A1075B /1/ / YCC3036A1064B /1/ /

GUIDE SPECIFICATIONS AQUARIUS ii

072, 090, 120, 180 & 240 MODELS C SERIES CONDENSING UNITS P SERIES HEAT PUMPS

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

PRODUCT SPECIFICATIONS 2YCC3036A1096A /1/ /

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Product Data. Features/Benefits. 40QKB024,036 40QKE024,036,048 Cooling Only and Heat Pump In-Ceiling Cassettes. 2to4NominalTons

Split System Heat Pump Product Data

General Description. Operation

C13-Series Engineering Guide

Model PA1Z SINGLE PACKAGED AIR CONDITIONERS. Size SS-PA1Z-01 DESCRIPTION FEATURES

CATALOG. SKYPAK Self-Contained Heating/Cooling Units

Product Data. 50ZP Single-Package Air Conditioners. 2 to 5 Tons

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

Transcription:

Concealed Fan Coil Units DY18/KY018 thru DY/KY0 1.5 TR thru 5 TR 5 kw thru 17.5 kw Cool & Heat pump models

FEATURES HYBRID DESIGN BETWEEN MINI SPLITS AND CENTRAL UNITS INDOOR UNIT : COMPACT DESIGN WITH LOW PROFILE HEIGHT RANGES FROM 9.6" TO 14.5" UNITS ARE FOR DUCTED APPLICATIONS LOW SOUND LEVELS DRAW THRU AIRFLOW CONFIGURATION 3 SPEED MOTORS REAR RETURN AIR FILTER EASY MAINTENANCE AND INSTALLATION G-90 GALVANIZED HEAVY GAUGE PANELS DIGITAL MICRO PROCESSOR CONTROL WIRED LCD DISPLAY THERMOSTAT (OPTIONAL WIRELESS REMOTE CONTROL) INDOOR UNIT - 'DY' SERIES OUTDOOR UNIT : G-90 GALVANIZED HEAVY GAUGE PANELS PAINT: ELECTROSTATIC POWDER COAT COOL GRAY COLOR HIGH EFFICIENCY TROPICAL DESIGN POWERFUL COMPRESSOR 24 VOLT CONTROL OPERATES UP TO 550 C AMBIENT TEMPERATURE EXTERNAL SERVICE VALVES WITH GAUGE PORTS LOW PRESSURE SWITCH OPTIONAL COPPER OR COATED ALUMINUM FINS COIL GUARD PROTECTION SIDE AIR DISCHARGE OUTDOOR UNIT - 'KY' SERIES (MODELS: KY042 - KY0)

INDEX Contents Page Model decoding... 2 Matching condensing units... 2 Indoor unit features... 3 Standard specifications... 3 Outdoor unit features... 4 Microprocessor controlled thermostat... 5 Physical data... 6 Cooling capacities... 7 Fan performance data... 8 Dimensions, indoor units... 9 Dimensions, outdoor units... 10-11 Typical schematic wiring diagram... 12-13 Installation, operation & maintenance... 14-15 Electrical... 16 System design... 16 Servicing instructions... 17 CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. 1

INDOOR UNIT 1 & 2 BASIC (SERIES) OUTDOOR UNIT 1 & 2 BASIC KY CONDENSING UNIT 3 & 4 COOLING CAPAC- ITY (x 1000 BTUH) 3, 4 & 5 NOMINAL COOLING CAPACITY (MBH) 018 024 030 036 042 048 0 5 ELECTRICAL SUPPLY (V-Ph-Hz) 6 ELECTRICAL SUPPLY ( V-Ph-Hz ) 7 REFRIGERA- TION CIRCUIT C : 208/230-1- S : SINGLE H : 208/230-3- M : 380-3- (4 WIRE) F : 4-3- MODEL DECODING 6 REFRIGERATION SYSTEM 8 COMPRESSOR TYPE R : HERMETIC RECIPRO- CATING 7 ACCESSORIES DY : DUCTED 18 C : 208/230-1- C : COOL ONLY N : STANDARD D : ALUMINUM FINS R : RH SIDE SPLIT FAN WITH ORIFICE (FACING AIR 24 COIL UNIT H : HEAT PUMP E : COATED FINS DISCHARGE) 30 WITH ORIFICE 36 F : COPPER FINS WITH ORIFICE 42 48 A : ALUMINUM FINS WITH CAPILLARY B : COATED ALUMINUM FINS WITH CAPILLARY C : COPPER FINS WITH CAPILLARY These options are for matching with DY18/24 heat pump units and also for matching with KXC or CX condensing units. 9 MODE C : COOL ONLY H : HEAT PUMP 8 FIN 10 CONDENSER MOTOR N : STANDARD L : LOW AMBIENT 9 COIL CONNECTION 11 CONDENSER COIL A : ALUMINUM FIN B : COATED ALUMINUM FIN C : COPPER FIN 10 FILTER N : NONE A : ALUMINUM C : SYNTHETIC 12 ACCESSORIES N : STANDARD UNIT F : STANDARD UNIT WITH FILTER DRIER & SIGHT GLASS 11 OPTION N : STANDARD UNIT 13 OPTIONS N : STANDARD UNIT NOTES: Applicable for KY030 - KY0 models only. MATCHING INDOOR/OUTDOOR UNITS INDOOR UNIT (FAN COIL UNIT) MODE INDOOR UNITS OUTDOOR UNITS DY18 DY24 DY30 DY36 DY42 DY48 COOL DY18CCNDRAN KY018CSRCNANN HEAT PUMP DY18CHNARAN KY018CSRHNANN COOL DY24CCNDRAN KY024CSRCNANN HEAT PUMP DY24CHNARAN KY024CSRHNANN COOL DY30CCNDRAN KY030CSRCNANN HEAT PUMP DY30CHNDRAN KY030CSRHNANN COOL DY36CCNDRAN KY036HSRCNANN HEAT PUMP DY36CHNDRAN KY036HSRHNANN COOL DY42CCNDRAN KY042HSRCNANN HEAT PUMP DY42CHNDRAN KY042HSRHNANN COOL DY48CCNDRAN KY048HSRCNANN HEAT PUMP DY48CHNDRAN KY048HSRHNANN COOL DYCCNDRAN KY0HSRCNANN DY HEAT PUMP DYCHNDRAN KY0HSRHNANN NOTE: Refer to indoor/outdoor model decoding for other available voltages. 2

INDOOR UNIT FEATURES COMPACT DIMENSIONS Low height units are ideal to fit into tight spaces. Maximum height of unit ranges from 9.6" to 14.5" (24cm to 37cm). EASY INSTALLATION WITH FLARE NUT CONNECTIONS No need for complicated brazing for connecting the refrigerant piping. EASY MAINTENANCE / ONE SIDE ACCESS Filters can be easily removed by lifting/sliding. Piping and controls are on one side for easy access. DIGITAL & MICROPROCESSOR CONTROL WITH LCD DISPLAY THERMOSTAT Programmable wired thermostat loaded with all required functions and features for safe and smooth operation. QUIET, PULSE FREE AIR SUPPLY Centrifugal fans that are statically and dynamically balanced, handle upto 0.5" w.g. (125pa) external static pressure allowing you to keep the unit away from your comfort zone. MATCHED WITH RELIABLE CONDENSING UNITS For optimum performance in cooling and heat pump applications. Quiet Operation Digital Thermostat Compact Dimensions High Cooling Capacity Easy Installation STANDARD SPECIFICATIONS UNIT CONSTRUCTION These ducted indoor fan coil unit consists of a coil, motor/blower assembly, aluminum filter and a drain pan securely mounted on heavy gauge galvanized steel housing. Steel sheet panels are zinc coated and galvanized by the hot dip process of lock-forming quality conforming to ASTM A 653 commercial weight G-90. This unit is designed for those concealed overhead installations which require supply ductwork. A 1.5" duct collar is provided into the front panel for supply air duct connection. Return air is from the rear side. Access to the blower assembly is provided through the removable bottom panel from where the complete fan/motor deck can be removed for servicing. The panels are insulated with 5/16" thick polyethylene acoustic and thermal insulation. 1/2" (13mm) thick washable type aluminum filter is provided. BLOWER ASSEMBLY The direct drive blower motor assembly is easily accessible for complete servicing after removal of fan deck from the unit. The blower wheels are large in diameter and are of the forward curved design. Constructed of steel, they are statically and dynamically balanced for quiet and smooth performance. MOTORS Motors are permanent split capacitor type with three speed tapped windings. The bearings are of sleeve type. COILS All cooling coils are of corrugated fin & tube type, constructed of enhanced copper tubes and mechanically bonded to aluminum fins. As an option to aluminum fins, coated aluminum fins or corrugated copper fins may be provided. Tube support sheets are of galvanized steel, formed to provide structural strength. Coils are provided with the orifice type refrigerant metering device on all models (except DY18/DY24 heat pump models). This provides for ease of serviceability. Unlike capillaries there is no need for de-brazing/brazing required for site replacements of the orifice pistons. Accurately sized pistons can be easily fitted for non-standard applications (e.g. high rise buildings). Also this metering device eliminates the need for check valves in reverse cycle heat pump applications. All coils are factory tested at 350 psig. DRAIN PAN The condensate drain pan is fabricated of 18 gauge galvanized steel. The drain pan is powder coat painted and the outer surface is thermally insulated. Since water never touches the metal pan, then possibility of corrosion is eliminated. 3

OUTDOOR UNIT FEATURES A. GENERAL The Zamil side discharge condensing units incorporate the latest innovative technology to provide quiet, reliable performance. The wrap-around coil not only adds to the aesthetical appeal, it also gives optimum heat transfer efficiency. The access panels provide access to the compressor and to the electrical control box. Removal of top panel gives access to fan motor and coil. These condensing units can be combined with a wide variety of evaporator coils and blower packages to provide quiet and dependable comfort. These units are availed as standard cool only models, and also as heat pump versions as an option for added comfort during cold season. Low Noise Level Powerful Reciprocating Compressor High Energy Efficiency Ratio B. UNIT ENCLOSURE All panels are of heavy gauge (G-90) galvanized steel sheet and completely weatherized for outdoor installation. Steel sheet panels are zinc coated and galvanized by the hot dip process of lock-forming quality conforming to ASTM A 653 commercial weight G-90, followed by baked on electrostatic polyester dry powder coat. C. COMPRESSOR Compressors are fully hermetic type and are provided with all the standard controls necessary for proper and safe operation. These compressors have a self-regulating crankcase heater, improved internal pressure relief valve which provides high pressure protection to the refrigerant system and rubber vibration isolators for quiet and efficient operation. D. AIR COOLED CONDENSER 1. The condenser coils are of the enhanced fin & tube type, constructed of enhanced copper tubes and mechanically bonded to aluminum fins. All copper tube return bends have 0.022" (0.56mm) wall thickness. As an option to aluminum fins, coated aluminum fins or corrugated copper fins may be provided. Tube support sheets are of galvanized steel, formed to provide structural strength. Tubes are circuited to ensure minimum pressure drop and maximum heat transfer. Each coil is completely dehydrated, charged and sealed at the factory upon completion of pressure tests. 2. The fans are propeller type and direct-driven, front discharge & provided with fan guards. 3. Units are equipped with totally enclosed fan motors for greater reliability and dependable performance for many years. Inherent thermal protection is automatic reset type. 4. For heat pump version units, fixed orifice expansion device is inherent within the condensing units as standard (except DY18/DY24 heat pump models where capillary is provided in the indoor units). E. SERVICE VALVES Both suction and liquid service valves are brass, back seating type with flare connections. Valves are externally located so refrigerant tube connections can be made quickly and easily. Each valve has a gauge pressure port for ease of checking refrigerant operating pressures. F. LOW PRESSURE SWITCH Auto reset SPST switch activated by refrigerant pressure - locks out the compressor, if the refrigerant pressure falls below 25 PSIG. Also provides additional protection against evaporator freeze up due to loss of indoor airflow. 4

MICROPROCESSOR CONTROLLED THERMOSTAT FEATURES Wired remote controller with Liquid Crystal Display (LCD) (Wireless controller - optional) FAN/HEAT/AUTO/COOL/DRY mode of operation Three speed fan with AUTO mode SLEEP mode Auto Restart Real Time Clock BENEFITS Unit operation controlled remotely with a large LCD display. 5 modes of operation with automatic shift between COOL & HEAT when on AUTO. Cover the whole range of CFM/capacity requirements. To raise/lower temperature setting by a maximum of 2 0 F during night time for added comfort and energy. Thermostat settings are preserved in the memory in case of power interruption and will be retrieved to operate the unit accordingly when power is restored. Display the day and time in AM/PM format. 7 Day Programmable Timer To select up to 7 days in advance when to start and when to stop operation. Hot Start Cold Stop De-icing Electronic Defrost cycle Child Lock No cold air blow in the room at start-up on HEAT mode. Use of the remaining thermal energy stored in evaporator coil after unit stop (HEAT mode). To avoid freezing of indoor coil during COOL cycle. Prevent freezing of outdoor coil during HEAT cycle. To restrict the number of persons tampering with the control. Room Temperature Display Both room & set point temperatures can be displayed in either 0 C or 0 F. ON/OFF status LED indicator To inform on the status of operation. 5

PHYSICAL DATA MODEL INDOOR UNIT DY 18 DY 24 DY 30 DY 36 DY 42 DY 48 DY OUTDOOR UNIT KY 018 KY 024 KY 030 KY 036 KY 042 KY 048 KY 0 PERFORMANCE Cooling capacity at high fan speed, BTUH/kW 18000/5.27 23000/6.74 31000/9.0 36200/10.6 44100/12.9 50000/14.6 58000/16.9 Total unit power input, kw/eer 2.2/8.0 2.8/7.9 3.7/7.9 4.1/8.4 5.0/8.4 5.7/8.4 7.3/7.5 Heating capacity at high speed, BTUH/kW 19000/5.56 23750/6.96 32000/9.37 300/10.55 42300/12.38 400/13.46 59000/17.27 Total unit power input, kw/cop 2.1/2.7 2.7/2.6 3.4/2.8 3.8/2.8 4.4/2.8 4.4/3.1 6.1/2.8 Evaporator airflow, CFM (high/medium/low) 650/550/450 750/650/550 1050/850/650 1250/1050/850 1400/1250/1000 10/1350/1100 1950/10/1350 Sound pressure level, dba (high/medium/low) 36/34/33 42/36/35 44/41/37 44/41/37 46/44/40 37/34/31 41/37/34 Minimum circuit ampacity, Amps (Indoor/Outdoor unit) 1.6/12.8 1.6/16.9 4.5/21.1 4.5/16.4 4.5/19.6 6/23.2 6/27.7 Maximum fuse size, Amps (Indoor/Outdoor) 15/20 15/25 15/35 15/25 15/30 15/35 15/45 INDOOR UNIT Power supply (V-Ph-Hz) 208/230-1- Blower quantity 2 2 2 2 2 2 2 Blower motor Watts - RPM 180-1270 220-1490 458-1400 480-1400 564-1500 695-1240 819-1400 FLA 1.3 1.3 3.6 3.6 3.6 4.8 4.8 Face area, ft 2 2.2 2.2 3 3 3 4.4 4.4 Evaporator coil Tube dia, inch 3/8 3/8 3/8 3/8 3/8 3/8 3/8 No. of rows/fpi 3/14 3/14 3/14 3/14 4/14 4/14 4/14 Suction - Liquid line, inch 5/8-3/8 5/8-3/8 3/4-3/8 3/4-3/8 3/4-3/8 3/4-1/2 3/4-1/2 Return air filter (1/2" thick) size, inch & quantity 8 x 16.5 (2) 8 x 16.5 (2) 9.5 x18.5 (2) 9.5 x 18.5 (2) 9.5 x 18.5 (2) 11 x 22.75 (2) 11 x 22.75 (2) Weight, Kg. 40 40 52 52 55 65 65 OUTDOOR UNIT Power supply (V-Ph-Hz) 208/230-1- 208/230-3- Compressor (hermetic type), RLA/LRA 9.7/52 13/73 15.6/90 11.8/67 13.1/80 16/97 19.6/105 Condenser airflow, CFM 1400 1400 2200 2200 4200 4200 4200 Condenser Fan HP - RPM 1/10-875 1/10-875 1/4-1000 1/4-1000 1/4-1000 (2) 1/4-1000 (2) 1/4-1000 (2) motor FLA 0.6 0.6 1.6 1.6 1.6 1.6 1.6 Face area, ft 2 5.6 5.6 6.5 6.5 10.5 10.5 10.5 Condenser coil Tube dia, inch 3/8 3/8 5/16 3/8 3/8 3/8 3/8 No. of rows/fpi 2/16 2/16 3/16 3/16 2/16 2/16 2/16 Refrigerant (R-22) charge, oz. 62 76 133 130 141 135 127 Suction - Liquid line, inch 5/8-3/8 5/8-3/8 3/4-3/8 3/4-3/8 7/8-3/8 7/8-3/8 7/8-3/8 Dimensions, mm (depth x width x height) 800 x 325 x 685 800 x 325 x 685 965 x 390 x 726 965 x 390 x 726 965 x 390 x 1158 965 x 390 x 1158 965 x 390 x 1158 Weight, Kg. 65 66 96 101 115 120 130 NOTE: 1. Cooling capacities & power input data @ 80 0 F (26.7 0 C) DB/67 0 F (19.4 0 C) WB indoor & 95 0 F (35 0 C) ambient temperatures. 2. Heating capacities & power input data @ 70 0 F (21.1 0 C) DB/ 0 F (15.6 0 C) WB indoor & 47 0 F (8.3 0 C) outdoor temperatures. 3. Sound pressure level @ 9 feet distance and 0.15 ESP. 4. Pipe sizes are for runs up to 25 feet (7.6 meters) to indoor unit. 6

COOLING CAPACITIES CONDENSER ENTERING AIR TEMP. ( 0 F) MODEL NUMBER (INDOOR UNIT/OUTDOOR UNIT) DY18/KY018 DY24/KY024 DY30/KY030 DY36/KY036 DY42/KY042 DY48/KY048 DY/KY0 EVAPORATOR AIRFLOW, CFM/DR 650/0.112 750/0.120 1050/0.127 1250/0.145 1400/0.090 10/0.070 1950/0.085 EVAPORATOR ENTERING AIR, WBE ( 0 F) 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72 TC 17.98 19.78 21.71 22.19 24.42 26.67 30.93 34.09 37.52 35.46 39.07 42.94 42.76 47.22 51.96 48.80 54.10 59.79 57.35 62.73 68.33 85 SC 17.83 14.88 11.68 21.07 17.52 13.85 29.81 24.80 19.71 34.31 28.48 22.56 41.15 34.21 27.10 47.99 39.90 31.65 56.56 47.04 36.79 kw 1.9 2 2.1 2.53 2.7 2.88 3.25 3.4 3.55 3.52 3.72 3.9 4.28 4.51 4.74 4.92 5.2 5.51 6.48 6.8 7.11 TC 16.31 18.01 19.78 20.88 23.02 25.15 28.09 31.00 34.08 32.84 36.25 39.87 39.90 44.12 48.64 45.04 50.01 55.38 53.02 57.99 63.12 95 SC 15.99 14.50 11.24 20.56 17.02 13.35 27.53 24.30 19.05 32.19 27.94 21.92 39.56 33.51 26.34 45.02 38.89 30.56 52.95 45.80 35.43 kw 2.09 2.2 2.31 2.61 2.8 2.98 3.53 3.7 3.86 3.89 4.11 4.32 4.74 5.01 5.27 5.37 5.7 6.05 6.93 7.31 7.66 TC 16.12 17.81 19.61 19.51 21.52 23.53 27.91 30.82 33.94 32.14 35.49 39.12 38.86 43.03 47.49 44.41 49.39 54.76 51.92 56.89 61.95 105 SC 16.05 14.20 11.02 18.74 16.02 12.46 27.35 23.72 18.62 31.97 27.10 21.24 38.12 32.73 25.67 43.65 38.02 29.85 51.18 44.80 34.57 kw 2.18 2.3 2.43 2.81 3.0 3.2 3.6 3.79 3.97 3.87 4.1 4.32 4.84 5.11 5.4 5.37 5.7 6.06 7.02 7.41 7.78 TC 13.99 15.50 17.12 17.22 19.02 20.85 26.31 29.09 32.09 30.28 33.49 36.96 36.78 40.79 45.08 41.97 46.68 51.86 49.20 53.93 58.75 115 SC 13.79 13.20 10.07 16.96 15.50 11.89 25.78 23.09 18.00 30.20 26.40 20.55 36.00 31.79 24.78 41.38 37.09 28.94 48.52 43.72 33.51 kw 2.26 2.4 2.54 2.9 3.1 3.3 3.78 3.98 4.19 4.16 4.41 4.66 5.01 5.31 5.62 5.55 5.9 6.29 7.2 7.6 8.01 TC 12.04 13.39 14.82 15.10 16.71 18.33 24.52 27.22 30.05 28.43 31.48 34.75 34.59 38.42 42.48 39.46 43.98 48.90 45.97 50.47 55.05 125 SC 11.81 12.38 9.29 14.80 15.00 11.32 24.03 22.33 17.26 28.38 25.67 19.82 33.94 31.01 23.97 38.89 36.06 27.92 45.33 42.39 32.26 kw 2.36 2.5 2.65 3.1 3.3 3.5 3.96 4.19 4.41 4.33 4.61 4.89 5.38 5.71 6.07 5.82 6.21 6.63 7.56 8.01 8.45 LEGEND: TC Total Capacity (1000 Btuh) Gross SC Sensible Heat Capacity (1000 Btuh) kw Total unit power input DR Wet Bulb depression ratio DBE Dry Bulb Temp. ( 0 F) of Air Entering Coil WBE Wet Bulb Temp. ( 0 F) of Air Entering Coil DBL Dry Bulb Temp. ( 0 F) of Air Leaving Coil WBL Wet Bulb Temp. ( 0 F) of Air Leaving Coil NOTES: 1. Capacities above are based on DBE = 80 0 F. For higher or lower DBE, add following Correction Factor = 1.08 x CFM (1 DR) (DBE 80). 2. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)]. 3. Multiply cooling capacities by 0.95 for heat pump units. MULTIPLIERS FOR LOWER CFM % of rated airflow 100% 95% 90% 85% 80% 75% 70% % TC 1 0.98 0.96 0.93 0.91 0.89 0.87 0.83 SC 1 0.965 0.93 0.90 0.87 0.845 0.82 0.78 kw 1 0.992 0.985 0.97 0.965 0.96 0.94 0.93 7

MODEL NUMBER BLOWER MOTOR SPEED FAN PERFORMANCE DATA CFM @ EXTERNAL STATIC PRESSURE (Inches of water) 0.0 0.05 0.1 0.15 0.2 0.25 0.3 0.4 0.5 HIGH 650 640 591 566 542 508 475 406 334 DY18 MEDIUM 552 528 514 478 452 421 390 333 255 LOW 470 445 420 395 375 345 - - - HIGH 750 729 698 670 643 613 584 510 427 DY24 MEDIUM 6 642 591 566 542 508 475 406 334 LOW 552 528 504 478 452 421 - - - HIGH 1050 987 9 934 908 886 864 804 741 DY30 MEDIUM 852 827 802 775 748 727 706 650 594 LOW 637 614 592 575 559 533 - - - HIGH 1250 1209 1184 1153 1122 1083 1044 966 894 DY36 MEDIUM 1050 987 9 934 908 886 864 804 741 LOW 852 827 802 775 748 727 - - - HIGH 1400 1362 1324 1291 1258 1218 1178 1102 1009 DY42 MEDIUM 1225 1192 11 1130 1100 1064 1028 958 877 LOW 995 975 955 928 902 876 - - - HIGH 10 1590 1571 1538 1505 1466 1426 1331 1245 DY48 MEDIUM 1366 1338 1310 1277 1244 1199 1153 1070 970 LOW 1100 1065 1030 992 954 912 - - - HIGH 1950 1900 1840 1780 1728 1690 1651 1558 1463 DY MEDIUM 1631 11 1571 1538 1505 1466 1426 1331 1245 LOW 1366 1338 1310 1277 1244 1199 - - - NOTE: Values include losses for dry coil and filters. 8

DIMENSIONS - INDOOR UNITS DY18 - DY 4 I 5 D A H 3/4" NPT(14TPI) DRAIN TUBE. 2 13 (0.50") 1 38 (1.50") END VIEW 6 TOP VIEW END VIEW 89 (3.50") 3 C G B E F FRONT VIEW NOTE: All dimensions are in mm (dimensions in brackets are in inches). DIMENSIONS MODEL A B C D E F G H I DY 18 904 (35.6) 610 (24) 244 (9.6) 9 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) DY 24 904 (35.6) 610 (24) 244 (9.6) 9 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1) DY 30 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) DY 36 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) DY 42 1011 (39.8) 762 (30) 318 (12.5) 1067 (42) 640 (25.2) 858 (33.8) 241 (9.5) 945 (37.2) 259 (10.2) DY 48 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) DY 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5) 1. Blower & motor assembly 2. Evaporator coil 3. Control box 4. Filter rack 5. Unit mounting brackets (4 Nos.) 6. Duct connection 9

DIMENSIONS - OUTDOOR UNITS KY018 & KY024 AIR IN 20 (0.788) 15(0.590) 406 (15.984) 325 (12.795) 366(14.4) AIR OUT 800(31.5) 49 (1.929) (0.551)48(1.890) 14 83 (3.268) AIR IN SUCTION VALVE LIQUID VALVE 70(2.755) SEE DETAIL -A DETAIL - A (TYPICAL AT FOUR PLACES) 442 (17.402) TOP VIEW POWER & CONTROL WIRE ENTRY 685(27) 9.5 ( 3 8 ") FLARE TYPE CONN. 16 ( 5 8") FLARE TYPE CONN. FRONT VIEW END VIEW AIR IN KY030 & KY036 20 (0.79) 15(0.59) 390(15.38) AIR IN 435(17.16) AIR OUT 133 (5.25) 698(27.5) TOP VIEW SEE DETAIL -A 70(2.76) DETAIL - A (TYPICAL AT FOUR PLACES) 965(38) ACCESS PANEL POWER & CONTROL WIRE ENTRY 727(28.63) 16(0.63) 9.5 ( 3 8") FLARE TYPE CONN. 82 (3.25) 431(17) 152 (6.0) FRONT VIEW 19(0.75) NOTE: All dimensions are in mm (dimensions in brackets are in inches). 19 ( 3 4") FLARE TYPE CONN. END VIEW 89 (3.5) 10

DIMENSIONS - OUTDOOR UNITS KY042, KY048 & KY0 AIR IN 20 (0.79) AIR IN AIR OUT SEE DETAIL-A DETAIL - A (TYPICAL AT FOUR PLACES) TOP VIEW POWER & CONTROL WIRE ENTRY ACCESS PANEL 863(34) 1158(45.63) 390(15.38) 435(17.16) 15(0.6) 70(2.76) 133 (5.25) 698(27.5) 965(38) 16(0.63) 9.5 ( 3 8") FLARE TYPE CONN. 22 ( 7 8") FLARE TYPE CONN. 146 (5.75) 82.(3.25) FRONT VIEW 27(1.06) 79(3.13) END VIEW NOTE: All dimensions are in mm (dimensions in brackets are in inches). 11

TO FUSE DISCONNECT SWITCH L2/N L1 GND 230VAC N1 LOW N2 MED HIGH LIVE TYPICAL SCHEMATIC WIRING DIAGRAM Refer to table below for Speed Connections. CN4 15 39A COM COMP COM ATB CAP 1 6 BRN BRN TO COOL MODELS COND.UNIT LCD CONTROL PANEL LEGEND ATB AUXILIARY TERMINAL BLOCK CAP CAPACITOR COMP COMPRESSOR COM COMMON ECB ELECTRONIC CONTROL BOARD FL FUSE LINK FM FAN MOTOR GND LUG GROUND HF HIGH FAN L1 LINE 1 L2 LINE 2 OR NEUTRAL LF LOW FAN MF MEDIUM FAN _ FIELD WIRING FACTORY WIRING SPEED WIRE COLOR MODEL HI BLK DY 18 DY 24 DY 30 DY 36 DY 42 DY 48 DY FM SPEED CONNECTIONS MED-HI VIO MED BLU MED-LOW ORN ID LOW LOWEST COM RED GRY YEL INDOOR DE-ICE SENSOR APPLICABLE FREQUENCY IN HERTZ CABLE CONNECTIONS AT LCD CONTROL PANEL TB 1) RED 5V 2) BLK GND 3) WHT TX RCV NOTES 1. POWER SUPPLY, REFER TO UNIT NAMEPLATE. 2. USE COPPER CONDUCTOR WIRES ONLY. 3. MOTORS ARE THERMALLY PROTECTED. 4. REFER TO INTERCONNECTING WIRING DIA- GRAM BEFORE INSTALLATION 5. DO NOT ROUTE ATB1(5) FROM CONDENSING UNIT INTERCONNECTING DETAILS BETWEEN INDOOR & OUTDOOR UNIT NOTE: Route wires according to diagram below & ignore all other terminal connection on outdoor unit. INDOOR UNIT DY SERIES ATB 1 6 1 6 ATB INDOOR UNIT DY SERIES OUTDOOR UNIT KY SERIES OUTDOOR UNIT KY SERIES ATB L N 1 5 4/6 1 5 6 ATB 12

TO FUSE DISCONNECT SWITCH L2/N L1 GND SPEED WIRE COLOR MODEL DY 18 DY 24 DY 30 DY 36 DY 42 DY 48 DY 230VAC N1 LOW N2 HI BLK LIVE HIGH TYPICAL SCHEMATIC WIRING DIAGRAM COM BRN Refer to table below for CAP BRN Speed Connections. ATB 15 1 39A 6 OF/I OF/O 4WVCOMCOMP OD 21 21A 21B FM SPEED CONNECTIONS VIO MED MED-HI ECB MED BLU CN4 ID MED-LOW ORN LOW RED HEAT PUMP MODELS 8 TO COND.UNIT T3A/N 37A NOTE: LCD CONTROL PANEL FIX THE OUTDOOR DE-ICE SENSOR TO THE TUBE PROVIDED ON THE RETURN BEND OF THE OUTDOOR COIL. OUTDOOR DE-ICE SENSOR LOWEST GRY INDOOR DE-ICE SENSOR COM YEL APPLICABLE FREQUENCY IN HERTZ CABLE CONNECTIONS AT LCD CONTROL PANEL TB 1) RED 5V 2) BLK GND 3) WHT TX RCV LEGEND ATB AUXILIARY TERMINAL BLOCK CAP CAPACITOR COMP COMPRESSOR COM COMMON ECB ELECTRONIC CONTROL BOARD FL FUSE LINK FM FAN MOTOR GND LUG GROUND HF HIGH FAN L1 LINE 1 L2 LINE 2 OR NEUTRAL LF LOW FAN MF MEDIUM FAN OF OUTDOOR FAN 4WV/RV FOUR WAY/REVERSING VALVE _ FIELD WIRING FACTORY WIRING NOTES 1. POWER SUPPLY, REFER TO UNIT NAMEPLATE. 2. USE COPPER CONDUCTOR WIRES ONLY. 3. MOTORS ARE THERMALLY PROTECTED. 4. REFER TO INTERCONNECTING WIRING DIA- GRAM BEFORE INSTALLATION 5. DO NOT ROUTE ATB1(5) FROM CONDENSING UNIT 6. T3A/N & 37A ARE TERMINAL MARKINGS FOR JP4 ON CONDENSER FAN MOTOR CONNEC- TION. T3A/N IS T1 ON SINGLE PHASE CON- DENSER UNITS. INTERCONNECTING DETAILS BETWEEN INDOOR & OUTDOOR UNIT NOTE: Route wires according to diagram below & ignore all other terminal connection on outdoor unit. Also route outdoor coil sensor wire from indoor to outdoor sensor holder ATB 1 6 8 T3A/N 37A ATB 1 6 8 T3A/N 37A INDOOR UNIT DY SERIES INDOOR UNIT DY SERIES OUTDOOR UNIT KY SERIES ATB 1 5 6 8 OUTDOOR UNIT KY SERIES ATB L N 1 5 4/6 8 T3A 37A T3A 37A 36A PNK C BLK COMP CAP 35A FM COMP S O/L R FM NOTE: T3A IS T1 ON 1PH CONDENSER UNITS 13

INSTALLATION - INDOOR UNIT The complete shipment should be inspected for damage. Any damage, visible or concealed, should be reported immediately to the delivery man or driver and noted on the shipping invoice. Place unit in position and make sure that unit is level. This is important to assure proper drainage and operation. Slots provided in the mounting brackets should be used for installing the units. Be sure that foreign material is not allowed to fall into or collect in the drain pan. Special care must be taken to prevent paint, plaster, insulation or other foreign material from being deposited on the motor or blower wheels. ELECTRICAL Please ensure power supply (V-Ph-Hz) to the unit is as per unit nameplate requirements. Caution: Operation of the unit on improper power supply will result in damage to the unit. Warning: Before installation or servicing, always TURN OFF all power to the unit. There may be more than one disconnect switch. Ensure all of them are turned off. Ground & Power wires Connect power wires as per wiring diagram. Connect ground wire to the ground lug inside the control box. Control wiring between outdoor & indoor units Use 16 gauge color-coded wire between the indoor and outdoor units (control wiring). Then match the auxiliary terminal block (ATB) numbers (indoor and outdoor units) to interconnect the two units. Note: 1. Field wiring to comply with local Safety and Fire codes. 2. Use copper wires of proper rating for all field wiring. 3. Install adequate branch disconnect switch as per NEC size requirements to handle unit starting current. Locate disconnect switch within sight and readily accessible from the unit. MAINTENANCE COIL: Coil may be cleaned by removing case and brushing between fins with a stiff wire brush. Brushing should be followed by cleaning with vacuum cleaner. The coil may also be cleaned by using a high pressure air, if compressed air source is available. It should be pointed out that if air filters are used and periodically cleaned, the coils will not be clogged up prematurely. DRAIN PIPE: Drain pipe should be checked before summer operation of unit is begun. If it is clogged, steps should be taken to clear the debris so that condensate will flow out easily. A standard pipe cleaner for 1/2" ID pipe may be used. Periodic checks of the drain pipe should be taken during summer operation, as there is a possibility of it becoming clogged with dirt. FILTER CLEANING: Remove access panel, slide filter out of filter rack, and clean as follows: Tap filter on solid surface to dislodge heavy particles. Wash under stream of hot water. If filter has been put to exceptional service, a mild solution of Sal-Soda, Tri-Sodium Phosphate or any other commercial solvent can be used. Set filter on end with slots in frame down, which allows it to drain. Filters should dry thoroughly before reuse. REPLACEMENT PARTS: When writing for replacement parts, refer to model number and serial number on the name plate of the unit. 14

INSTALLATION & START-UP INSTRUCTIONS - OUTDOOR UNIT SAFETY CONSIDERATIONS Improper installation, service, maintenance or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Check with your nearest Zamil dealer/sales office for information or assistance. Warning: Before installation or servicing the system, always turn off main power supply. Electrical shock can cause personal injury or death. INSTALLATION STEP-1: Check equipment and job site Unpack unit and move to final location taking care not to damage the unit. Remove screws holding the unit to wooden pallet and remove wooden pallet. STEP- 2: Location of unit Place the unit with minimum clearance as shown in figure below to enable space for installation, service and optimum performance of the unit. Be sure that the discharge air from the condenser is not restricted. Double the clearance when multiple units are installed at one location. Units may be installed using mounting pads on the floor, concrete slabs, steel frames with adequate strength. AIR IN 203mm (8") FOR KY018, 024 & 030 254mm (10") FOR KY036 AND ABOVE 203mm (8") FOR KY018, 024 & 030 254mm (10") FOR KY036 AND ABOVE AIR IN AIR OUT 610mm (24") CLEARANCE MINIMUM 914mm (36") CLEARANCE MINIMUM STEP-3: Piping connections Outdoor units should be connected to indoor units using field-supplied piping of refrigerant grade and correct size. The liquid and suction line diameters can be determined from the physical data table. For piping requirements beyond 25 ft (7.62 m), obtain information from your nearest Zamil dealer/sales office. If either refrigerant piping or indoor coil is exposed to atmospheric conditions, it must be dehydrated to 500 microns to eliminate moisture contamination in the system. It is advisable to size piping according to recommended ASHRAE methods. Install piping according to refrigeration standard practice. Run refrigerant pipes as directly as possible, avoiding unnecessary turns and bends. Install refrigerant pipes carefully to prevent damaging the suction pipe insulation and vibration transmission to the structure. Outdoor unit connected to factory matched indoor unit Outdoor unit contains correct system refrigerant charge for operation with matched indoor unit as given on cooling capacity table and when connected with up to 25 ft (7.62 m) of field-supplied piping. Check refrigerant charge for maximum efficiency. 15

STEP 1: INSTALLATION ELECTRICAL A) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements. Caution: Operation of the unit on improper power supply will result in damage to the unit. Note: Use copper wires of proper rating for all field wiring. Warning: Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than one disconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death. B) Ground & power wires Connect power wires to terminal block per wiring diagram. Connect ground wire to the ground lug inside the control box. C) Control wiring between outdoor & indoor unit Use 16 gauge color-coded wire between the indoor and outdoor units (control wiring). STEP 2: START-UP 1) Energize crankcase heater for a minimum of 12 hours prior to the system start-up. To energize crankcase heater only, set thermostat to "off" position and close electrical disconnect switch to the outdoor unit. 2) Fully open liquid/suction service valves. 3) Close electrical disconnect switch to energize the system. 4) Set room thermostat to desired temperature. SYSTEM DESIGN THE CONDENSING UNIT SYSTEM HAS BEEN DESIGNED BASED ON THE FOLLOWING: Intended for outdoor installation with free air intake and discharge. Minimum outdoor operating air temperature during cooling without low ambient operation option is 55 0 F (12.7 0 C). Maximum outdoor operating air temperature during cooling mode is 130 0 F (55 0 C). For reliable operation, unit should be level on horizontal plane. For interconnecting refrigerant pipe lengths greater than 25 feet (7.6 meters), check with your local Zamil sales office. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided. 16

50 CM SERVICING INSTRUCTIONS Access for blowers & motor 95 CM 30 CM Blower deck holding bolt Blower deck 50 CM Bottom panel NOTE: 1) Required indoor unit access clearances are shown as hatched area. 2) Free sevice access should be available from the bottom of the unit for removing & servicing the blower/motor deck. 3) Servicing instructions: a) Remove the bottom panel. b) Support the blower deck while unscrewing the 4 blower deck holding bolts and bring down the blower deck. 17

INDOOR UNITS PARTS LIST MODEL NUMBER DY18 DY24 DY30 DY36 DY42 DY48 DY FAN DECK ASSEMBLY 800-089-71 800-089-71 800-089-72 800-089-72 800-089-72 800-089-73 800-089-73 BLOWER MOTOR 800-547-51 800-547-51 800-547-52 800-547-52 800-547-52 800-547-53 800-547-53 FILTER 800-249-39 800-249-39 800-249-38 800-249-38 800-249-38 800-249-36 800-249-36 ORIFICE DISTRIBUTOR 800-194-10 800-194-10 800-194-14 800-194-14 800-194-14 800-194-16 800-194-16 ORIFICE PISTON 800-195-13 800-195-13 800-195-15 800-195-16 800-195-17 800-195-20 800-195-22 THERMOSTAT, COOL 800-645-95 800-645-95 800-645-95 800-645-95 800-645-95 800-645-95 800-645-95 THERMOSTAT, HEAT PUMP 800-645-97 800-645-97 800-645-97 800-645-97 800-645-97 800-645-97 800-645-97 OUTDOOR UNITS MODEL NUMBER KY018C KY024C KY030C KY030H KY030M KY030F COMPRESSOR, COOL ONLY 800-675-79 800-675-80 800-675-89 800-684-04 800-684-14 800-684-07 COMPRESSOR, HEAT PUMP 800-675-86 800-675-87 800-675-90 800-684-04 800-684-14 800-684-07 FAN MOTOR 800-555-32 800-555-32 800-545-97 800-545-97 800-545-97 800-545-96 FAN MOTOR CAPACITOR - - 800-353-15 800-353-15 800-353-15 800-353-15 CONDENSER FAN 800-224-19 800-224-19 800-941-41 800-941-41 800-941-41 800-941-41 COMPRESSOR CONTACTOR 800-736-01 800-736-01 800-097-00 800-095-00 800-095-00 800-095-00 TRANSFORMER (24V) 800-012-30 800-012-30 800-012-30 800-012-30 800-012-30 800-012-31 LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 MODEL NUMBER KY036C KY036H KY036M KY036F KY042C KY042H COMPRESSOR 800-684-01 800-684-04 800-684-14 800-684-07 800-684-02 800-684-05 FAN MOTOR 800-545-97 800-545-97 800-545-97 800-545-96 800-545-97 800-545-97 FAN MOTOR CAPACITOR 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15 CONDENSER FAN 800-941-41 800-941-41 800-941-41 800-941-41 800-941-41 800-941-41 COMPRESSOR CONTACTOR 800-097-00 800-095-00 800-095-00 800-095-00 800-097-00 800-095-00 TRANSFORMER (24V) 800-012-30 800-012-30 800-012-30 800-012-31 800-012-30 800-012-30 LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 MODEL NUMBER KY042M KY042F KY048C KY048H KY048M KY048F COMPRESSOR 800-684-09 800-684-08 800-684-03 800-684-06 800-684-09 800-684-09 FAN MOTOR 800-545-97 800-545-96 800-545-97 800-545-97 800-545-97 800-545-96 FAN MOTOR CAPACITOR 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15 CONDENSER FAN 800-941-41 800-941-41 800-941-41 800-941-41 800-941-41 800-941-41 COMPRESSOR CONTACTOR 800-095-00 800-095-00 800-097-00 800-095-00 800-095-00 800-095-00 TRANSFORMER (24V) 800-012-30 800-012-31 800-012-30 800-012-30 800-012-30 800-012-31 LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 MODEL NUMBER KY0C KY0H KY0M KY0F COMPRESSOR 800-672-59 800-672-51 800-672-52 800-672-52 FAN MOTOR 800-545-97 800-545-97 800-545-97 800-545-96 FAN MOTOR CAPACITOR 800-353-15 800-353-15 800-353-15 800-353-15 CONDENSER FAN 800-941-41 800-941-41 800-941-41 800-941-41 COMPRESSOR CONTACTOR 800-736-23 800-097-00 800-095-00 800-095-00 TRANSFORMER (24V) 800-012-30 800-012-30 800-012-30 800-012-31 LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00

PL-AP-DYS-06-2M-E