Characterising the smoke produced from modern materials and evaluating smoke detectors

Similar documents
Research into multi-sensor detector capabilities and false alarm reduction

The performance of multi-sensors in fire and false alarm tests

UL268 7 th challenge with single infrared smoke detector

7.1 Smoke Detector Performance

ISO/TS TECHNICAL SPECIFICATION. Fire detection and alarm systems Part 9: Test fires for fire detectors

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

Investigation of the Potential Use of Blue Light in Forward Scattering Optical Smoke Chambers to Detect all UL217 Fires in the New Standard

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios

InstrumentationTools.com

MR300 OPTICAL SMOKE DETECTOR RANGE PRODUCT APPLICATION & DESIGN INFORMATION

Impact on Smoke Alarm Performance Considering New Nuisance and Fire Tests

COMITÉ EUROPÉEN DES ASSURANCES

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS

Fire Detection System: An Overview

Effect of Contamination on the Sensitivity of Optical Scatter Smoke Sensors

Optimization of Sensitivity Characteristics of Photoelectric Smoke Detector to Various Smokes

ISO INTERNATIONAL STANDARD. Fire detection and alarm systems Part 20: Aspirating smoke detectors

False alarms research work Raman Chagger (BRE Global) 18 th June 2015 Firex International. Part of the BRE Trust

LEARNING SPECIAL HAZARD DETECTION TYPES

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

ISO INTERNATIONAL STANDARD

Keywords: Fire detection, smoke alarm, nuisance, UL 217, polyurethane foam

Abstract. Introduction

Loss Prevention Standard

Potential Impact of New UL Fire Test Criteria

Wireless Sensor Networks for early Fire Detection

IQ8Quad. The right sensor for every environment. The detection principles of the IQ8Quad detector. Fire detection technology

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

AGEING STUDY ON SMOKE ALARMS

ISO INTERNATIONAL STANDARD. Smoke alarms using scattered light, transmitted light or ionization

NEBOSH International Technical Certificate in Oil and Gas Operational Safety

Polarized Light Scattering of Smoke Sources and Cooking Aerosols

SMOKE ALARM SUMMIT Technological Advances in Smoke Alarms Richard Roberts Honeywell Fire Safety Industry Affairs Manager

Active Fire Protection Market Report - UK

DETERMINATION OF SMOKE QUANTITIES TO BE USED FOR SMOKE DETECTION PERFORMANCE GROUND AND FLIGHT TESTS

Carbon Monoxide Alarms Smoke and Carbon Alarms Upgrade Requirements for Single and Two Family Dwellings

3.1 Introduction. 3.1 Introduction

Australian Standard. Fire detection and alarm systems. Part 6: Carbon monoxide fire detectors using electro-chemical cells

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Meeting NFPA standards for

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

Model DRD-AS Conventional Infrared Flame Detector User Manual Ver. 1.0

Test One: The Uncontrolled Compartment Fire

Safety Engineering. Fire Protection Systems and Life Safety Systems

Large-scale fire test for interior materials of the Korean high speed train

Fire Performance of external thermal insulation for walls of multistorey buildings

Recent BRANZFIRE enhancements and validation

ALK-V PHOTOELECTRIC SMOKE SENSOR

UL Conference Atlanta May 21 22, 2014 Polyurethane Foam Association presentation

Fire and Security Products and Services

A Comparison of Aspirated Smoke Detectors

Keywords: VEWFD; Smoke detection; Smoke production; In-situ testing.

WELCOME TO ROSEVILLE UNIVERSITY

This document is a preview generated by EVS

IFD-E Flame Detector User Manual

FAÇADE FIRE TESTS Towards a new European standard method

Smoke Alarm Research at NIST

IMO Resolution MSC 61(67): Annex 1: Part 2

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

Chapter 17, Initiating Devices

IFD-E Flame Detector User Manual

optical detector multisensor detector heat detector mounting bases product guide

Department for Communities and Local Government Research Report:

HYDROCARBONENGINEERING June June 2015

FULL-SCALE FIRE TESTS OF A TWO-STORY CROSS-LAMINATED TIMBER STRUCTURE

EVALUATION ON PERFORMANCE OF PHOTOELECTRIC SMOKE DETECTORS IN THE ZONE DETECTION SYSTEM

Smoke Alarms. Rev. A Copyright 2011 James D Peisker

Results from a Full-Scale Smoke Alarm Sensitivity Study

Evolution Analogue Addressable Fire System

Investigation report. Radiation resistance of fire detectors under the influence of radioactive gamma radiation

Smoke Alarm Research at NIST

Development of a European approach to assess the fire performance of facades

Fire and Extinguishing Tests on Computer Equipment

BEYOND COOKING: SMOKE ALARM NUISANCE SOURCES EVALUATED. Joshua B. Dinaburg, P.E. Dr. Daniel T. Gottuk, P.E. SUPDET 2016 March 4, 2016

False Alarm Management. Graham Simons FIA Technical Manager

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Test Report: ICL/H18/9039 Rev 1

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Smoke Alarms: Comparing the Differences in Response Times and. Nuisance Alarms. Chris Kasperczyk. University of Cincinnati.

Frequently Asked Smoke Alarm Questions

Combinational Smoke Detector

PRODUCT GUIDE & INFORMATION. Professional Fire & Carbon Monoxide Solutions

Laser Technology Smoke Detector

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

Global flammability standards.

TSI AEROTRAK PORTABLE PARTICLE COUNTER MODEL 9110

Aspirating Gas Detection CFD Modelling Predicts Application Performance

An experimental study of the impact of tunnel suppression on tunnel ventilation

The six tests conducted included three smoldering and three fast flaming type tests.

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Notifier by Honeywell: SMART Detection. SMART Detection. The Ultimate in False Alarm Technology...Make the SMART choice

Selecting the AFUMEX range guarantees quality and offers the widest choice and the greatest safety.

Trials of Vexo inhibitor in domestic central. heating systems

RRC SAMPLE MATERIAL MANAGING FIRE SAFETY LEARNING OUTCOMES

SUSTAINABLE DEVELOPMENTS IN SWEDEN. Lynne Ceeney

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report

Review Fire Test Report

PASSIVE AND ACTIVE FIRE PROTECTION OF THE AIR HEATED SOLAR HOUSES

Transcription:

www.bre.co.uk Briefing Paper Characterising the smoke produced from modern materials and evaluating smoke detectors Raman Chagger

01 Contents Abstract 02 Introduction 02 Background 03 The current test fires 04 Methodology 05 Results 06 Analysis 09 Summary of results 11 Conclusions and recommendations for further research 12 References 12 Acknowledgements 13

02 Abstract Introduction The test fires that are used to assess ionisation and optical smoke detectors were developed in the 1980s, but the materials now found in modern service environments have changed since then. There is now a greater use of plastics and flame retardant foams in modern buildings, but little information exists on the response of detectors to smoke generated by the burning or smouldering of such materials. The object of this research project was to investigate the smoke profiles generated in fire tests specified in the EN 54-7 (commercial) and EN 14604 (domestic) smoke detector standards, and compare them with smoke produced from burning or smouldering materials commonly found in today s service environment. The intention was to establish whether the current test fires are adequate for assessing smoke detector performance in a broad range of fires involving modern materials, and if not to make recommendations. The research work was conducted in two phases. The first comprised of a review to identify the materials and burning conditions that would be used in Phase 2, during which fire tests were conducted. Twelve approved smoke detectors (commercial and domestic) were installed in a fire test room on the ceiling and the walls. Twenty-nine fire tests were performed using a variety of materials in flaming and smouldering conditions. In tests that produced sufficient smoke, 97.8% of devices responded with an appropriate alarm. It was confirmed that ionisation and optical smoke detectors are attuned to detecting different types of fires. However, sufficient evidence was found to demonstrate that these detectors nevertheless respond appropriately to a broad range of fires, both within and beyond the limits of the test fires currently used to assess them.

03 Background Both ionisation and optical smoke detectors are used in commercial and domestic environments. They use different techniques to detect smoke, making them more attuned to detecting different types of fire. Ionisation detectors use a small radioactive source (americium-241) inside an ionisation chamber that contains charged electrodes. The chamber is arranged to allow a flow of air from outside. As the air enters it becomes ionized, generating an electric current between the charged electrodes. When smoke particles pass into the chamber the ions become attached to them and are carried away, leading to a reduction in the current. More ions are stripped away when there are many small particles, such as those generated during flaming fires. When a material is smouldering it tends to produce fewer but larger particles than it does when in flames. As these cause less current reduction, ionisation detectors are inherently less responsive to the large smoke particles generated during smouldering fires. Optical smoke detectors typically use a smoke scatter chamber, which contains an LED source with a collimated lens that produces a beam. A photodiode is located at an angle to the beam. As smoke particles enter the chamber they interrupt the beam and the light is scattered and detected by the photodiode. This results in a voltage that can be used to determine an alarm condition. Optical detectors respond to smouldering fires very quickly, as the larger particles generated cause more scattering. Optical scatter chambers are less sensitive to small particles and become progressively less sensitive as the smoke particle size approaches the LED wavelength used. Therefore optical smoke detectors are slower at detecting the small smoke particles generated from flaming fires. These detectors are less likely to produce false alarms from cooking fumes and steam than ionisation detectors. As both technologies contain inherent strengths and weaknesses, this research project aimed to determine whether ionisation detectors perform poorly in certain types of smouldering fires, and if optical detectors are less responsive to certain types of flaming fires.

04 The current test fires Both EN 54-7 and EN 14604 use the same methodology to identify the most challenging conditions under which to test smoke detectors. Physical tests conducted in a smoke tunnel are used to establish the orientations at which the detector is least sensitive, and to select the four least sensitive detectors from a batch of twenty. During the fire tests the four worst performing samples are installed in the fire test room (as specified in the relevant standard) at the least sensitive orientation on the ceiling or wall. Four fire tests are then performed as follows: TF2: smouldering wood, TF3: glowing smouldering cotton, TF4: flaming plastics (polyurethane) and TF5: flaming liquid (n-heptane) fire. The conditions in the fire test room are tightly controlled and the intention is to produce reproducible test fires. The average smoke profiles produced from the four test fires are shown in Figure 1. The y-axis (m) represents the optical density (measured in db/m) and indicates the quantities of larger particles generated during smouldering fires. The x-axis (y) is a dimensionless quantity that represents the amount of ionisation taking place and represents the number of smaller particles generated during flaming fires. The four test fires produce a broad range of smoke types with different properties. These are used to assess the smoke entry characteristics and the sensitivity levels of smoke detectors. Materials such as plastics and flame retardant foams will generate smoke with different properties when flaming and when smouldering depending on the type of smouldering (e.g. near a radiant heat source or sustained contact with hot surface). The research aimed to establish whether smoke from such fires was effectively covered by existing fire tests, and to assess the performance of ionisation and optical detectors when responding to smoke of this kind. 2.0 1.8 Smouldering Wood Smouldering Cotton TF2 TF3 1.6 TF4 1.4 1.2 Flaming Polyurethane TF5 m (db/m) 1.0 0.8 Flaming heptane 0.6 0.4 0.2 0 0 1 2 3 4 5 6 y Figure 1: Average m:y profiles of the four currently used test fires

05 Methodology During phase 1 papers were reviewed and many experts were contacted to determine whether there were any known cases of detectors not responding to certain types of smoke. The data gathered during this exercise helped to establish the test fires to be performed and the supplementary measuring equipment to be used. The equipment specified in the smoke detector standards (thermocouples near the floor and in the arc, obscuration meter and MIC in the arc) was used in the fire test room. In addition the following equipment was installed to gather further data: Two flowmeters Thermocouple locations CO = Carbon monoxide measuring instrumentation F1, F2 = Flow meters 1 & 2 OBS = Obscuration meter MIC = Measuring Ionisation Chamber CO F1 OBS MIC F2 Test Fire Location 3m 11m 7m CO measuring equipment Secondary obscuration meter Ten additional thermocouples Twelve approved smoke detectors and smoke alarm devices from undisclosed manufacturers were used in the fire tests. These comprised of eight domestic smoke alarm devices (four ionisation and four optical) with two ionisation and two optical devices being installed on the walls and ceiling. Additionally, four commercial smoke detectors (two ionisation and two optical) were installed on the ceiling. To define end point of the tests, guidance was taken from the EN 54-7 and EN 14604 standards, which specify end of test limits for smouldering and flaming fires that are m=2 db/m or y=6 respectively. Figure 2: Location of measuring equipment in the fire test room 4m (10) (9) 1m 1m 1m (3) (2) (1) 11m Figure 3: Location of the thermocouples in the fire test room DOMESTIC COMMERCIAL (4) (5) (6) (7) (8) 11m Thermocouple locations: (1)-(4) as shown 1cm from ceiling (5) 4.5cm from ceiling (6) 8cm from ceiling (7) 11.5cm from ceiling (8) 15cm from ceiling (9) 10cm from floor (10) 30cm from floor Thermocouple = Ions = Opticals 1 2 3 4 Test Fire Location 60º 7m Devices 1 8 - Ceiling mounted 3m 5 6 7 8 Devices 9 12 - Wall mounted 12 11 10 9 Figure 4: Location of the detectors in the fire test room

06 Results Twenty-nine test fires were conducted including the four test fires specified in EN 54-7 and EN 14604. Of these 11 were smouldering fires, 16 were flaming fires and two started off smouldering and went on to become flaming fires (shown as S-F in the table right). The table right summarises the tests that were conducted, the fuels that were used and the mode of smoke production. All devices were periodically replaced, as exposure to the smoke from a number of tests could cause contamination in the smoke chambers that could potentially affect their response. The second column indicates when all 12 were replaced with brand new devices of the same model, i.e. at tests 1, 10 and 22. Table 1: The 29 tests conducted in the EN fire test room Test no. Device set Fuel Mode of smoke production 1 1 of 3 TF2- Beech wood sticks Smouldering 2 1 of 3 TF4- Non flame retardant PU Flaming 3 1 of 3 TF5- N-heptane + Toluene Flaming 4 1 of 3 TF8- Decalin (from ISO 7240-9) Flaming 5 1 of 3 TF3- Cotton wicks Smouldering 6 1 of 3 TF1- Wooden sticks (from ISO 7240-9) Flaming 7 1 of 3 Regular unleaded petrol Flaming 8 1 of 3 Premium unleaded petrol Flaming 9 1 of 3 MDF Flaming 10 2 of 3 TF2- Beech wood sticks Smouldering 11 2 of 3 PVC cable Smouldering 12 2 of 3 Flame retardant PU foam Flaming 13 2 of 3 Flame retardant PU foam Smouldering 14 2 of 3 Flame retardant PU foam Smouldering (radiant) 15 2 of 3 Sunflower oil S-F 16 2 of 3 Newspaper Smouldering 17 2 of 3 Bedding Polyester Smouldering 18 2 of 3 Bedding Polyester Flaming 19 2 of 3 Nylon (small) Flaming 20 2 of 3 Nylon (medium) Flaming 21 2 of 3 Nylon Smouldering 22 3 of 3 Bedding Polyester Smouldering 23 3 of 3 ABS Flaming 24 3 of 3 Polystyrene S-F 25 3 of 3 Polycarbonate Flaming 26 3 of 3 Polycarbonate Flaming 27 3 of 3 Polyethylene Flaming 28 3 of 3 Polyethylene Flaming 29 3 of 3 ABS Smouldering Unless otherwise specified all smouldering fires were conducted in the sustained mode with the fuel in contact with a hot surface that was increasing in temperature throughout the test.

07 The results from two of these tests are shown in Figures 5 and 6 (right). Test 9 demonstrates the rapid response of the ionisation detectors (both commercial and domestic) to the small particles generated during the flaming fire. The response from the opticals is slightly delayed until the fire increases in size and the radiant heat leads to more smouldering particles being produced from the MDF. All detectors respond before the defined end of test for a flaming fire (y=6) is reached. Test 24 demonstrates the difference in response between ionisation and optical detectors to a smouldering then flaming fire. At first the polystyrene fuel is smouldering due to the increasing temperature of the steel plate on which it rests. This leads to all 6 photoelectric detectors responding before the defined end of test for a smouldering fire (m=2 db/m) is reached. When the temperature of the polystyrene reaches ignition point (shown as S-F on the chart) the fuel combusts. Within a few seconds the first ionisation detector responds and all ionisation detectors are in alarm before the defined end of test for a flaming fire (y=6) is reached. m (db/m) and y 10 8 6 4 2 2.5 0 150 200 250 300 350 400 450 500 550 600 650-2.5-2 Commercial Ceiling Domestic Ceiling Domestic Wall # Device number Photo Ion Figure 5: Test 9- MDF in flaming mode m (db/m) and y 8 7 6 5 4 3 2 1 Commercial Ceiling Domestic Ceiling Domestic Wall # Device number Photo Ion Time (sec) 37.5 32.5 27.5 22.5 17.5 12.5 7.5-7.5 70 60 50 40 30 20 10 CO (ppm) CO (ppm) 0 0 900 950 1000 1050 1100 1150 1200 1250-1 -10 Time (sec) Figure 6: Test 24- Polystyrene first smouldering then flaming

08 Figure 7: Tests 1 & 10- Smouldering beech wood sticks (TF2) in the fire test room Figure 8: Test 3- Flaming n-heptane fire (TF5) in the fire test room

09 Analysis Of the 29 test fires conducted five (shown in Table 2) produced too little smoke (17 Polyester smouldering, 18 Polyester flaming, 19 Nylon, 25 Poly-carbonate and 27 Polyethylene); these were repeated with more fuel. In this context too little smoke would be considered to be either well before m=2 db/m or y=6 or if all devices that would be expected to respond had not responded. The results from the remaining 24 tests are arranged in order of increasing m:y and are shown in Table 3. Sixteen of the 24 test fires (shaded in the table) fall within the m/y limits specified by the TF2-TF5 test fires from EN 54-7. From these tests only two negative responses were recorded with 190 positive responses. For the four tests that had a high mean m/y ratio, the detectors responded for all fires except for domestic wall ionisations 10 and 12, which did not respond to test fire 13, and domestic ceiling opticals 2 and 6 that did not respond to test fire 29. Table 2: Tests that produced too little smoke Test Type Final m* Final y* Mean m/y No. of device alarms 17 Polyester (S) 0 0 0 0 18 Polyester (F) 0.06 0.23 0.2715 1 19 Nylon (F) 0.11 0.42 0.2126 6 25 Polycarbonate (F) 0.12 0.44 0.2733 6 27 Polyethylene (F) 0.38 1.58 0.2032 8 * These values indicate the m and y levels achieved after the last device operated or when the test was abandoned. Table 3: Tests that produced sufficient smoke Test Type Final m * Final y * Mean m/y No. of device alarms 6 TF1 (F) 1.27 16.4 0.0794 12 12 FR PU (F) 0.47 4.56 0.0938 12 9 MDF (F) 1.18 8.1 0.148 12 20 Nylon M (F) 0.17 1.23 0.1679 7 2 TF4 (F) 1.32 7.71 0.1962 12 16 Paper (S+F) 0.17 0.62 0.1991 12 7 Petrol L (F) 2.19 10.72 0.2094 12 3 TF5 (F) 1.7 8.07 0.2164 12 8 Petrol S (F) 0.94 3.8 0.2308 12 28 Polyethylene L (F) 1.51 5.36 0.2596 11 4 TF8 (F) 0.9 3.29 0.2665 12 26 Polycarbonate L (F) 0.35 1.14 0.2726 12 5 TF3 (S) 2.08 5.27 0.3429 11 15 Oil (S,F) 1.33 3.98 0.4911 12 23 ABS (F) 2.66 4.14 0.583 12 11 PVC (S) 1.16 1.73 0.7063 12 10 TF2 #2 (S) 1.53 1.66 0.8226 12 24 Polystyrene (S,F) 5.58 7.67 0.8435 12 14 FR PU (S-R) 1.67 1.59 0.8516 12 1 TF2 #1 (S) 2.32 2.29 0.9384 12 22 Polyester (S) 1.23 0.95 1.58 12 21 Nylon (S) 2.48 1.5 1.67 12 13 FR PU (S-S) 1.34 0.97 1.88 10 29 ABS (S) 6.53 2.24 3.04 10 * These values indicate the m and y levels achieved after the last device operated or when the test was abandoned.

10 For the four tests that had a low mean m/y ratio the detectors responded for all fires except for five optical devices that did not respond to test 20. This is most likely due to the relatively small size of the fire, as the peak m and y values generated during this fire were significantly lower than the other three fires. It is suspected that if enough smoke had been generated during test fire 20 then all 12 devices would have responded. However this result has not been qualified, so from the results of the remaining 23 fires we effectively have six no responses and 270 responses. This represents positive responses 97.8% of the time. The six no responses are attributed to the inconsistent response of one particular type of detector and suspected contamination for the remaining ones. Even though no statistical data was gathered by repeating the same tests, the results do provide evidence of the response characteristics for the types of detectors (optical or ion) to a variety of smoke types produced in smouldering and flaming modes. Data gathered from the additional equipment installed in the fire test room suggests that the limits specified in EN 54-7 in terms of the working volume and temperature distribution are adequate and do not need to be refined. However, the following recommendations are made: Assess whether the number of directional dependence measurements should be increased for domestic smoke detectors due to the asymmetrical design. To improve reproducibility between test laboratories, the location at which the temperature near the floor is measured should be more clearly specified in EN 54-7. m (db/m) m (db/m) 2.0 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0 1.2 1.0 0.8 0.6 0.4 0.2 m:y (db/m) TF5 = 0.18 Nylon = 0.168 MDF = 0.148 FR PU = 0.094 TF1 = 0.0794 0 0 1 2 3 4 5 6 y m:y (db/m) TF2 = 1.22 Polyester = 1.58 Nylon = 1.67 FR PU = 1.88 ABS = 3.04 0 0.5 1 1.5 y Figure 9: The four smouldering fires with m/y values outside the TF2 range TF5 (average) Nylon MDF FR Polyurethane TF1 TF2 (average) Polyester Nylon FR Polyurethane ABS Figure 10: The 4 flaming fires with m/y values outside the TF5 range

11 Summary of results Of the 29 test fires, five were considered to be too small and had to be repeated with more fuel. Of the completed 24 test fires: 16 were found to be within the m/y range of smoke types bounded by TF2 and TF5; four smouldering fires were found to be beyond the (m/y) limits for a TF2; four flaming fires were found to be beyond the (m/y) limits for a TF5. The m/y ratio for the TF1 flaming fire was found to be the worst case of all the flaming fires. This indicates that a defined fire exists for the flaming test fire limit assuming m/y is the appropriate measurement. However, it should be noted that smouldering fires can continue for a long time with only one material being involved, potentially leading to the production of toxic gases in fatal concentrations. An example of this would be bedding in contact with a heat source such as a lit cigarette. In this case an ionisation detector may not respond and therefore should not be sited in locations where such a scenario is possible. In contrast a flaming fire will eventually produce sufficient heat that will radiate onto other materials and lead to the production of smouldering smoke to which the optical detectors would be expected to respond. Twelve smoke detectors, eight of which were installed on the ceiling and four on the wall, were exposed to the smoke from a variety of test fires and responded with a 97.8% pass rate. For the smouldering tests carried out beyond the TF2 limit, no defined test exists. The m/y ratio for the smouldering ABS fire (29) was significantly higher than the others. The test fires TF2-TF5 do cover most general purpose applications as a real fire is unlikely to involve only a single type of material. As more materials with different smoke characteristics are involved in the fire the likelihood of detection increases.

12 Conclusions and recommendations for further research References The aim of this research was to measure the smoke characteristics of a number of test fires using modern materials, and assess them against the test fires specified in EN 54-7 and EN 14604. The research has demonstrated that commercial and domestic approved ionisation and optical smoke detectors respond to a broad range of fires with m/y ratios within and beyond the fire test limits of EN 54-7 and EN 14604. The fire tests specified in EN 54-7 and EN 14604 are considered to be appropriate and are sufficiently wide in terms of distribution of smoke characteristics. (1) EN 54-7: 2000 + A1 June 2002 + A2 July 2006. Fire detection & fire alarm systems Part 7: Smoke detectors point detectors using scattered light, transmitted light or ionization. European Committee for Standardisation. Central Secretariat, Rue de Stassart 36, B-1050 Brussels. (2) EN 14604: 2005. Smoke alarm devices. European Committee for Standardisation. Central Secretariat, Rue de Stassart 36, B-1050 Brussels. (3) ISO/TS 7240-9:2012(en) Fire detection and alarm systems Part 9: Test fires for fire detectors. Both ionisation and optical smoke detectors are attuned to detecting certain types of fire. In order to ensure that the most appropriate type of device is installed, guidance on the appropriate use of ionisation and optical smoke detectors should be sought from relevant codes of practice. Recommendations for further work Assessment of the performance of a variety of optical heat multi-sensor detectors to some of the fires conducted during this research programme. Research into a repeatable smouldering fire with an m/y ratio > 3.0 db/m with a better m/y profile. Research into an alternate realistic flaming fire with an m/y ratio < 0.1 db/m such as flaming flame retardant poly-urethane.

13 Acknowledgements The author would like to thank the following for their voluntary contributions to this research project: Gent by Honeywell Hochiki Europe (UK) Ltd Protec Fire Detection PLC Sprue Safety Products Ltd System Sensor Europe Tyco Fire Protection Products Xtralis The author would also like to thank the BRE Trust for the funding it provided for this research project

BRE Trust Watford, Herts WD25 9XX T +44 (0)333 321 8811 E enquiries@bre.co.uk W www.bre.co.uk BRE Trust The BRE Trust uses profits made by BRE Group to fund new research and education programmes, that will help it meet its goal of building a better world together. The BRE Trust is a registered charity in England & Wales: No. 1092193, and Scotland: No. SC039320. 79216 Test Fires Briefing Paper BRE 2014