Heat recovery units -W-450 Dimensions 160 710 725 797 Elementy dachowe Description The -W-450 heat recovery unit is designed for single-family houses up to 200 m 2 in usable floor area. 610 630 Key performance features: Maximum heat recovery ratio 90.5%, tested as per EN 308 by TÜV SÜD Plastic counter-flow heat exchanger Automatic air flow bypass Freeze protection Modbus connectivity: all unit control functions can be managed via a PC or a central automation system Preheater and secondary heater control connectivity Programmable week control timer Filter clogging indicator Class EU4 filters in standard (class F7 filters available on request) Supported sensor typees: CO 2, RH, and a pressure switch Wall-mounted or free-standing Various duct connection versions available: EA, SA, OA, RA Metal duct connections with EPDM gaskets for air tightness class D EBM PAPST energy-efficient fans Control * All All measurement dimensions are values in mm. are mm. When ordering, specify the control type. There are two versions of control available - wired and wireless: -W-450 - with a wired controller -W-450W - with Wi-Fi control 1 Control 1 Air supply & exhaust filters Bypass Counter-flow heat exchanger Housing Air supply & exhaust fan http://www.alnor.com.pl/produkty_pl/kanaly-i-ksztaltki-okragle.html ALNOR systemy wentylacji jest prawnie chronionym znakiem i technicznym patentem. Prawo do zmian zastrzeżone. 685
Heat recovery units -W-450 Technical specifications -W-450 Air flow rate (m 3 /h) * 470 Rated power supply (V/Hz/Ph) 230 / 50 / Maximum power consumption (W) 180 Maximum current consumption (A) 1.54 Maximum sound pressure level (db (A)) ** 48 Weight (kg) 41 Filters * The static pressure is 0 Pa. ** Measured at 1.5 m away from the unit. Class G4 filter as per EN 779 (class F filter available on request) The total power consumption is measured as the consumption by two (air supply and air exhaust) fans. The Specific Fan Power is expressed in kw/m 3 /s as per EN 13779 (Ventilation for non-residential buildings). SFP: Specific Fan Power Performance curve Total SFP = Całkowity powet consumption pobór mocy (kw) Przepływ Airflow powietrza (m 3 /s) (m 3 /s) 500 450 Static External pressure Pressure (Pa) (Pa) 400 350 300 250 200 150 100 50 686 0 0 50 100 150 200 250 300 Low speed Speed Medium speed Speed High speed Speed Boost Air flow rate (m 3 /h) 350 400 450 500 550 Air Volume (m 3 /h)
Heat recovery units -W-450 Technical specifications Sound level chart Speed Octave Sound Pressure Level (db: Overall A Scale ) db(a) 60 50 40 30 20 Sound pressure Hz 63 125 250 500 1000 2000 4000 8000 Speed boost 24 30 48 52 50 47 41 40 High speed 21 32 47 51 47 45 39 37 Medium speed 18 28 46 45 38 38 32 27 Low speed 16 28 34 36 30 29 20 14 Octave sound pressure level (db: general A) NR10 NR0 10 63 125 250 500 1000 2000 4000 8000 Hz Central Frequency (Cycle per Second) Low Speed Low speed Medium Speed Medium speed NR20 NR30 NR50 NR40 High Speed Boost Medium speed Boost 687
Heat recovery units -W-450 Technical specifications Air tightness test The nominal air flow rate of the unit is 400m 3 /h. The following table lists the internal and external air leak rates and percentage vs. the overall air flow rate: Test No. P stst (Pa) Air leak rate (m 3 /h) Inner air leak Percentage ratio (%) Air leak rate (m 3 /h) Outer air leak Percentage ratio (%) 1-300 1.8 0.4 2.1 0.5 2-250 1.6 0.4 1.9 0.5 3-200 1.3 0.3 1.7 0.4 4-100 0.7 0.2 1.1 0.3 5-50 0.4 0.1 0.8 0.2 6 0 0.0 0.0 0.0 0.0 7 50 0.3 0.1 0.8 0.2 8 100 0.6 0.2 1.1 0.3 9 200 1.2 0.3 1.7 0.4 10 250 1.5 0.4 2.0 0.5 11 300 1.7 0.4 2.2 0.5 Thermodynamic test The following temperature coefficients were measured for the -W-450 heat recovery unit: Air supply rate [m 3 /h] 71.0 197.0 320.0 378.0 Air exhaust rate [m 3 /h] 76.0 217.0 344 426.0 Temp. coeff. (air supply) eta tsup [%] 94.7 90.3 86.5 86.8 Humidity coeff. (air supply) eta tsup [%] Temp. coeff. (air exhaust) eta teha [%] 80.3 82.1 80.9 77.9 Humidity coeff. (air exhaust) eta teha [%] Mean temp. coefficient eta tepb [%] 87.5 86.2 83.7 82.4 688
Heat recovery units -W-450 Energy class -W-450 A 57 db 450 m 3 /h ENERGIA ЕНЕРГИЯ ΕΝΕΡΓΕΙΑ ENERGIJA ENERGY ENERGIE ENERGI 2016 1254/2014 689
Heat recovery unit controller manual controller HRU-MinistCONT-Man Function Description Availability Fan speed control Fan speed boost Filter clogging indicator Automatic air flow bypass Electric heater control Sensor (VOD) Sensor (Humidity) Freeze protection Preheater control BMS connectivity Modbus connectivity Programmable week control timer Air supply and air exhaust fans are provided with a 3-speed control system. This function increases the fan speed: Option 1: Press the BOOST button on the control panel Option 2: Activated with an external dry relay input or an external 230 V input (activated e.g. by a lamp switch in the kitchen, bathroom, etc.) on the controller s PCB. Two filter clogging indicator options: Option 1: The filter clogging indicator counts down the unit's operating time to a preset value. When the preset value is reached, a filter change request indicator is activated on the control panel. Option 2: Filter clogging can be monitored with a pressure switch. When the filter reaches the clogging limit, the pressure switch activates a filter change request indicator on the control panel. The filtered fresh air is supplied indoors, bypassing the heat exchanger. The interfaced electric heater can have the output automatically switched between a maximum of 2 levels the selection of which depends on the desired temperature setting and the actual indoor temperature. The fans are operated continuously by the control output of a CO2 sensor or an air quality sensor. The fans are operated continuously by the control output of an indoor air humidity sensor. If the outdoor temperature is low, the freeze protection function is activated to protect the heat exchanger from freezing. If the outdoor temperature is low, the fresh air supply is treated by a preheater upstream of the unit. This function protects the heat exchanger from freezing. IN: The unit can be turned on and off using an external control panel. OUT 1: Unit status output OUT 2: Unit fault alarm output This feature allows operating all controls of the unit via a PC or a central automation system. The unit can be programmed to operate at specific hours in a weekly cycle. 3 speeds (all fans) (High / Medium / Low) Optional Optional Optional Data logging This function allows logging all available operating options of the unit. Fire mode This function activates a special operating status in the case of a fire alarm. Alarms - Filter change required - Fan failure - Preheater failure - Heater failure (Error code display) Child lock Locks the control keypad to prevent inadvertent operation. 690
Heat recovery unit controller HRU-MinistCONT-WiFi controller Kontroler HRU-MinistCONT-WiFi umożliwia zdalne starowanie centralami rekuperacyjnymi z serii HRU-MinistAIR - oznacza to, że z dowolnego miejsca na świecie możesz wybrać rodzaj trybu pracy centrali rekuperacyjnej odpowiadający Twoim aktualnym potrzebom w zakresie jej funkcjonowania. Wraz z zakupem centali, dokupując HRU-MinistCONT-WiFi otrzymujesz zainstalowaną puszkę sterującą wraz z adresem internetowym oraz danymi do zalogowania się i obsługiwania zdalnie Twojej centrali. Function Description Availability Fan speed control Fan speed boost Filter clogging indicator Automatic air flow bypass Electric heater control Sensor (VOD) Sensor (Humidity) Freeze protection Preheater control BMS connectivity Modbus connectivity Programmable week control timer Air supply and air exhaust fans are provided with a 3-speed control system. This function increases the fan speed: Option 1: Press the BOOST button on the control panel Option 2: Activated with an external dry relay input or an external 230 V input (activated e.g. by a lamp switch in the kitchen, bathroom, etc.) on the controller s PCB. Two filter clogging indicator options: Option 1: The filter clogging indicator counts down the unit's operating time to a preset value. When the preset value is reached, a filter change request indicator is activated on the control panel. Option 2: Filter clogging can be monitored with a pressure switch. When the filter reaches the clogging limit, the pressure switch activates a filter change request indicator on the control panel. The filtered fresh air is supplied indoors, bypassing the heat exchanger. The interfaced electric heater can have the output automatically switched between a maximum of 2 levels the selection of which depends on the desired temperature setting and the actual indoor temperature. The fans are operated continuously by the control output of a CO2 sensor or an air quality sensor. The fans are operated continuously by the control output of an indoor air humidity sensor. If the outdoor temperature is low, the freeze protection function is activated to protect the heat exchanger from freezing. If the outdoor temperature is low, the fresh air supply is treated by a preheater upstream of the unit. This function protects the heat exchanger from freezing. IN: The unit can be turned on and off using an external control panel. OUT 1: Unit status output OUT 2: Unit fault alarm output This feature allows operating all controls of the unit via a PC or a central automation system. The unit can be programmed to operate at specific hours in a weekly cycle. 3 speeds (all fans) (High / Medium / Low) Optional Optional Optional Data logging This function allows logging all available operating options of the unit. Fire mode This function activates a special operating status in the case of a fire alarm. Alarms - Filter change required - Fan failure - Preheater failure - Heater failure (Error code display) Child lock Locks the control keypad to prevent inadvertent operation. 691
Heat recovery unit controller HRU-MinistCONT-Wifi Controller Login panel: All users receive their personal user names and passwords for remote access to the device they purchase. Alnor ventilation controller configuration pane: The wizard's steps guide the user through the commissioning and local network configuration of the device. Heat recovery unit start and stop: ON / OFF 692
Heat recovery unit controller HRU-MinistCONT-Wifi Controller Heat recovery unit work mode selection: adjust the continuous operation of the unit to your needs, or use the predefined options as follows: STANDARD MODE: continuous air change. Enables work mode selection for the AIR SUPPLY fan and the AIR EXHAUST fan. AIR EXHAUST MODE: controls the air exhaust fan only. Fan work modes: speed 1, 2, 3 or OFF. Start the function to extract stale air from the area and return to the air change mode by selecting STANDARD. 693
Heat recovery unit controller HRU-MinistCONT-Wifi Controller AIR SUPPLY MODE: controls the air supply fan only. Fan work modes: speed 1, 2, 3 or OFF. Start the function to supply fresh air indoors and return to the air change mode by selecting STANDARD. VOD MODE: in the Ventilation On Demand mode, the air supply and air exhaust rates depend on the humidity readout from the optional indoor air humidity sensor connected to the heat recovery unit. The sensor is sold separately. Remote temperature setting: choose the indoor temperature for the room. Indoor air temperature: shows the actual temperature of the air exhausted from the area, which is changed by the controller via the heat recovery system to match the remote temperature setting. The outdoor air intake temperature. The temperature of the air supplied by the heat recovery unit to the area. 694 Alarm code: displays the error code of the heat recovery unit. (See the error code definitions in the User Manual.) BY-PASS FUNCTION: the heat recovery unit supplies fresh and filtered outdoor air bypassing the heat exchanger. When this indicator is checked, the By-Pass Mode is running. ONLINE: shows the status of the data connection between the controller and the heat recovery unit. When this indicator is lit, the data connection is correct.
Heat recovery unit accessories F7 filter EU4 filter EU7 (F7) filter elements are fine filters with the rated separation efficiency at 80 90% for 0,4 µm particulates. Product code Filter class Dimensions (mm) HRF-Mair-250-F7 F7 150x360x30 HRF-Mair-400-F7 F7 215x605x45 Product code Filter class Dimensions (mm) HRF-Mair-250-EU4 EU4 150x360 HRF-Mair-400-EU4 EU4 215x605 Humidity sensors An air humidity sensor can operate a heat recovery unit by regulating the air fan speed via its output signals. The air fan is switched between three 3 speeds which correspond to air humidity presets. H7015B1060 duct air humidity sensor Maintenance-free and automatic humidity and temperature measurement Power supply Humidity measurement range Output signal Temperature measurement range Protection rating Wiring length 24 V 0 to 100% RH 1 to 10 V 0 to +50 C IP65 200 m 695
Heat recovery unit accessories T7560C1006 room air humidity sensor CO 2 sensors Automatic humidity and temperature measurement Power supply Humidity measurement range Output signal Temperature measurement range Protection rating Sensor typee CO 2 (carbon dioxide) sensors allow regulating -W-450 heat recovery units according to the indoor or duct CO 2 concentration levels (depending on where the sensor is installed). 24 V 10 to 95% RH 1 to 10 V +6 to +40 C IP30 20 kω NTC AQS71-KAM-T duct CO 2 sensor Maintenance and calibration free Power supply Test Measurement accuracy Temperature measurement range Output signal 24 V 0 to 2000 ppm +/- 50 ppm 0 to +50 C 1 to 10 V C7110D1009A room CO 2 sensor Automatic humidity and temperature measurement Self-calibration algorithm Power supply Test Measurement accuracy Temperature measurement range Output signal Sensor typee 24 V 0 to 3000 ppm +/- 50 ppm 0 to +50 C 1 to 10 V 20 kω NTC 696