GAS PLUS ALARM SYSTEM

Similar documents
Model D12-IR. Digital Gas Transmitter...

Operation and Maintenance Manual

PrimaX IR Gas Transmitter Designed for Reliable Performance in Extreme Conditions

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Combustible Gas Detection and Control System

Two-Channel Gas Controller

SIL 2. Ultima X Series Gas Monitors CERTIFIED

Dräger Polytron 5700 IR Detection of flammable gases and vapours

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

Toxic Gas Detection. Model F12. Toxic Gas Detection

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety

Model D12. Digital Gas Transmitter

ALTAIR 5X Multigas Detector Product Specification

Dependable Solutions for Gas Detection

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

FREEDOM SERIES 5000 AND 5600 GAS TRANSMITTERS

INSTRUCTIONS. PointWatch Infrared Hydrocarbon Gas Detector PIR9400

Oxygen (O2) Single-Point Gas Detection System

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

ESD3000IR ESD3000IR. Infrared Gas Detector

OLCT 700 & 710. Certifications FIXED GAS DETECTION. Better detection. Better protection.

Dräger Flame 2500 Flame Detection

SEC Millenium Hydrocarbon Gas Detector

S5000 Gas Monitor. GMS5000.com

Dräger Polytron 8700 IR Detection of flammable gases and vapors

MERIDIAN UNIVERSAL GAS DETECTOR

Installation and Wiring 1.

Operation and Maintenance Manual

Dräger Flame 2100 Flame Detection

MICROpeL 75 Combustible Gas Sensor Part Number: PM

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases

Dräger Polytron 8310 IR Detection of flammable gases and vapour

ULTIMA X5000. MSAX5000.com

Danfoss gas detection units

M2 Transmitter Operator s Manual

Hydrocarbon Gas Detector

APPLICATION DATA SHEET

SIMRAD GD10 IR GAS DETECTOR

Instructions

SEC SIGNATURE ETO MONITOR TRAINING SENSOR ELECTRONICS CORPORATION

Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY

Dräger Polytron 5200 CAT Detection of flammable gases and vapours

SEC 5000 IREvolution Gas Detector

ESD3000 ESD200 Combustible / Toxic Gas Detector

Products and performance

4P-90 CiTipeL Combustible Gas Sensor Part Number: PM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

Meridian. Universal Gas Detector. Description. Features. Minimal drift High specificity Digital ID Broader toxic gas detection

M2A Transmitter Operator s Manual

SEC 2000 Millenium Infrared Gas Detector

4P75 CiTipeL Combustible Gas Sensor Part Number: PM

Danfoss gas detection units

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

Air Check EX LEL Gas Monitor Instruction Manual

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

ULTIMA XIR ULTIMA X 3 ULTIMA XE. ULTIMA X Series. [ State-of-the-Art Gas Monitoring]

GLD-30 Gas Leak Detector

Warranty Registration

IR4000. Point Infrared Combustible Gas Detection System. The Reliable and Flexible Safety Solution That s Low Maintenance

Dräger Polytron 8700 IR Detection of flammable gases and vapors

ESD500. ESD500 Combustible / Toxic Gas Detector

Danfoss gas detection unit Type GD Heavy Duty

Inc Series Digital Gas Detector/Controller. Operation Manual

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SAFEYE XENON 700. Hydrocarbons and ethylene detection. Heated optics. 10-year Warranty for the Xenon flash bulb. SIL 2 according to IEC 61508

Gas Detection System TOX ALARM DG2000-Garage

GasAlertMicroClip X3 Specifications

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

Detection, Protection, Innovation

Dräger Polytron Pulsar 2 Detection of flammable gases and vapours

Instructions Model MIR MSHA Approved IR Gas Detector 3.1 7/

Dräger Polytron 8200 CAT Detection of flammable gases and vapors

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL

Rig Protector. Multipoint Critical Gas Detection and Monitoring System

DET-TRONICS. SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION FEATURES

RK-04 M2 Transmitter Operator s Manual

Industrial Grade Gas Detection

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

RK-HC-04 M2A Transmitter Operator s Manual

SIMRAD GD10PE IR GAS DETECTOR

Dräger X-am 7000 Multi-Gas Detection

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Multi-Gas-Controller MGC2

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

Xgard. Fixed detectors For flammable, toxic or oxygen gases

Lamp Supply (Recommended)

SenSmart Universal Gas Detector Series

Industrial Grade Gas Detection Detecting The Difference

SafEye OPEN-PATH GAS DETECTION SYSTEM XENON 700. We INVENTED it... We PERFECTED it! Patent No. US 5,281,816; US 6,061,141; EP

GAS DETECTION MANUFACTURED BY. Aerionics, Inc. Sioux Falls, SD Phone:

Combustible and Toxic Gas Detection Solutions. Performance and Safety Beyond Compliance

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES

Transcription:

GAS PLUS -IR SERIES 4688-IR COMBUSTIBLE GAS OR CARBON DIOXIDE TRANSMITTER

GAS PLUS -IR TRANSMITTER SERIES 4688-IR COMBUSTIBLE GAS OR CARBON DIOXIDE TRANSMITTER The Scott Gas Plus -IR Model 4688 IR Gas Transmitter is a rugged, reliable solution for hydrocarbon or carbon dioxide gas detection. Designed with extensive user input, the instrument is extremely flexible, easy to use, and easy to maintain. This infrared technology is ideally suited for applications where traditional catalytic bead sensors cannot be used due to poisoning and in areas where minimal maintenance is desired. Principle of Operation An infrared source emits pulses of radiation into the instrument s optical bench, which contains a known volume of gas. This radiation is reflected onto two detectors, one tuned to measure a wavelength absorbed by organics and the other tuned to a reference band that is not absorbed. The outputs of the detectors are compared and used to compute gas concentration. Fault conditions are detected by the sensors when radiation intensity falls below a threshold level for a set period of time. Use and Maintenance Operation of the Scott Gas Plus -IR Model 4688 IR Gas Transmitter is simple and intuitive. All settings and adjustments, such as alarm set points, gas measured, etc., are non-intrusive, performed at the instrument with a magnetic screwdriver or remotely through the instrument s RS-485 interface. Password protection prevents unauthorized personnel from tampering with the settings. Minimal maintenance is necessary. All span information is preset at the factory, and never needs to be adjusted. Zero adjustment is a quick, non-intrusive procedure. On-board diagnostics continuously check transmitter electronics, optics, and software for faults and indicate corrective action should a fault be detected. The field serviceable infrared emitter is replaced with a simple plug-in connection. Features of the Gas Plus 4688-IR Low Maintenance No span calibration required. Zero adjustment is a quick, non-intrusive procedure. Flexible Many parameters are user-adjustable, including gas to be detected, decimal precision, damping, and engineering units. Rugged Design Conformally coated electronics, stainless steel optics protects components against corrosion, and harsh industrial environments. Extensive Self Diagnostics Instrument compensates for detector contamination and aging. Optics are heated to prevent moisture formation. Detailed fault codes aid in troubleshooting. Multiple Output Choices 4-20mA and RS-485 (Modbus protocol) outputs are standard features. Relays with user adjustable set/reset points, and time delays are available as an option. User-Friendly Display Large LCD display shows gas concentration, engineering units, alarm relay status, alarm inhibit, and more. Low Cost of Ownership An excellent price/performance ratio and low long-term cost of ownership.

Why IR Technology? IR technology provides numerous advantages that may be beneficial for your application s conditions. Reduced maintenance (no span calibration required) No saturation from high gas concentrations No oxygen required for operation Continuous sensor fault monitoring Sensor lifetime not reduced by exposure to gas Rapid speed of response Minimal temperature and humidity effects No poisoning from silicone or other catalyic bead poisons GAS PLUS ALARM SYSTEM Engineered to handle difficult industrial environments yet incredibly easy to operate and maintain, the Scott Gas Plus Alarm System provides visual and audible local alarm annunciation in a rugged steel enclosure. Designed for easy use and maintenance, the Gas Plus Alarm System can be equipped with the Scott 4688IR infrared combustible gas or CO 2 transmitter. Built-in strobe lights and an 80 db horn respond to two levels of alarm to quickly alert personnel of dangerous, build-ups of combustible gas or CO 2. Three 10 amp relays provide additional response support for your facility, and a front panel light provides continuous visual indication of system status. The built-in 110 VAC power supply provides simple plug-in electrical connection. Since all system adjustments are non-intrusive, the rugged, painted enclosure never needs to be opened after installation.

INSTALLATION DRAWINGS ELECTRICAL: Current Sinking Mode 6 5 4 3 2 1 TB1 Current Sourcing Mode 6 5 4 3 2 1 TB1 Alarm Relay Connections Fault(C) Fault(NO) AL 2 (C) 6 5 4 18-28 VDC 18-28 VDC AL 2 (NO) 3 Gnd 4-20 ma RS - 232 Tx ;RS-485 B(+) RS - 232 Rx ;RS-485 A(-) Gnd 4-20 ma RS - 232 Tx ;RS-485 B(+) RS - 232 Rx ;RS-485 A(-) AL 1 (C) AL 1 (NO) TB2 2 1 DIMENSIONS: 3/4 NPT Conduct Entrance (1 Each Side) 5.44 [138] Mounting Spacer Plate (074-0289), must be installed behind either the transmitter, or the Junction Box (If option is ordered) [145] 5.71 Bump Test Adapter P/N 096-2289 2.38 [60mm] Modified 4600-IR Tranmitter Housing (096-2150) (2).312 DIA [7.9] Mounting Holes Rain Shield Filter Cage (074-0340) 4.06 [103] Case Fitting Assembly (096-2159) 9.20 REF. [234] Mounting Surface 1/8 NPT x 1/4 Barbed Fitting 2.75 [70mm] Porex Rainshield Outer Filter (077-0209) See Note 2. Porex Filter Membrane (077-0210) Front View (Shown removed From Inside Bottom Of Rain Shield) See Note 2. 5.69 [144] 6.19 [157] REF. Side View 0.50 [13] Notes: 1. All Dimensions ae shown in inches [mm] and are normal. 2. Replacement filter kits may be ordered as follows: Porex rainshield outer filter replacement kit #096-2274-1 (Qty. of 5 #077-0209 Filters) Porex filter membrane replacement kit #096-2274-2 (Qty. of 5 #077-0210 Filters) Porex main sensor filter (not shown) replacement kit #096-2214 (Qty. of 5 #077-0166 Filters)

Alphanumeric Display Magnetic "Enter"Switch Magnetic "Zero" Calibration Switch Security Indicator Gas Concentration Units Alarm Indicators Magnetic Menu Up/Down Switch Typical Specifications 1. General. Transmitter shall be approved by a nationally recognized testing laboratory for Class 1, Division 1 Group B, C, and D hazardous locations. All parameter settings shall be password protected. A large integral display shall provide visual indication of gas concentration, engineering units, alarm relay and inhibit status. 2. Temperature and Power. Transmitter shall operate over an input range of 18-28VDC in ambient conditions of -40 C to 60 C and shall consume no more than 4.0W maximum. 3. Output. Transmitter shall provide an isolated, 4-20mA signal, and shall be digitally addressable using MODBUS protocol with RS-485 data transmission. Two SPST alarm relays shall be available as an option. User shall be able to separately adjust alarm set points, reset points, set delays, and reset delays. All alarm parameters shall be password protected and be non-intrusively adjustable through transmitter s front panel via a manufacturer supplied magnet. 4. Diagnostics. Transmitter shall conduct self-diagnostics of electronics, software, and sensor at least twice per second. Fault conditions shall be indicated with a specific fault code on the instrument display and with a user-adjustable analog signal. One SPST fault relay shall be available as an option. User shall be capable of testing the alarm and fault relays from the instrument s front panel or remotely via RS- 485 communications interface. 5. Calibration. All span calibration data shall be preset, with no additional span calibration required by user. Nonintrusive zero calibration shall be performed via magnet. Transmitter shall provide the ability to inhibit its output. A time-out feature shall automatically return the unit to normal operation mode after a preset amount of time. The calibration curve for the gas being monitored shall be user selectable in the field through the transmitter s front panel via a manufacturer supplied magnet. 6. Sensor. Sensor shall be non-dispersive infrared type using no moving mechanical parts. Linearity and repeatability shall be ±2% below 40% of full scale, and ±5% at or above 40% of full scale. Infrared emitter shall be field replaceable.

SPECIFICATIONS SERIES 4688-IR COMBUSTIBLE GAS OR CARBON DIOXIDE TRANSMITTER GENERAL Sensor Type..............Non-dispersive infrared Detection Range...........See Gas Types Linearity..................± 2% below 40% full scale ± 5% from 40% to 110% full scale Repeatability.............± 2% below 40% full scale ± 5% from 40% to 110% full scale Response Time............T90 < 5 seconds (without rain shield) Start Up Time.............30 seconds Self-Diagnostic Test........2x per second Calibration................Span: none (factory set) Zero: every 3 to 6 months User Interface.............Non-intrusive via magnet Display..................4 digit LCD with user-adjustable contrast. Numeric display of gas concentration and faults; icons for alarms, lock, and inhibit Weight...................6.5 lbs (3.0 kg) Warranty.................2 years OUTPUTS Analog...................Isolated, 4-20mA, max loop load 900ohms at 24 VDC (current source or sink) Programmable Inhibit.....1.5 to 20.0mA or RS-485 Programmable Loop Test...1.0 to 20.0mA Digital...................RS-485 using Modbus RTU or Modbus ASCII protocol Relay (optional)..........3 SPST relays (2 concentration, 1 fault), 5A at 250 VAC. User selectable latching/ non-latching, energized/de-energized, set/reset delay, and set/reset point ELECTRICAL Input Voltage.............18-28 VDC Power Consumption.......3.1W, nominal / 6.0W, max Connections.............3 wires or 4 wires (with RS/485 or RS/232 configuration ); 18-22 AWG nominal RFI/EMI.................Certified to EN50082-1 ENVIRONMENTAL Operating Temp...........-40 F to 140 F, (-40 C to 60 C) Operating Humidity........0 to 100% RH ENCLOSURE Enclosure Material.........Copper-free cast aluminum, baked epoxy finish Optical Bench Material.....Stainless steel APPROVALS Enclosure.................Explosion proof; UL/FM/CSA, Class 1 Group B,C,D / Class 2, Group E, F / Class 3, NEMA-4X, NEMA-7B, C,D; NEMA-9 E,F,G; IP66 System..................ETL listed to UL2279 and UL3111-1 (Class 1, Div 1, Group B,C,D),CE Marked, CSA approved to Class 1, Zone1,Groups IIB+H2;Class I, Groups E,F,&G; Class III, CENELEC approved to EExd[ib] IIc T6 GAS TYPES For Standard Gases (built-in) Butane 0-1.9% v/v Ethane 0-100% LEL or 0-3.0% v/v Hexane 0-100% LEL or 0-1.1% v/v Methane 0-100% LEL or 0-5.0% v/v Pentane 0-100% LEL or 0-1.5% v/v Propane 0-100% LEL or 0-2.1% v/v Propylene 0-100% LEL or 0-2.0% v/v Acetone 0-100% LEL or 0-2.5% v/v MEK 0-100% LEL or 0-1.5% v/v Isopropyl Alcohol 0-100% LEL or 0-2.0% v/v Pure Methane 0-100% LEL or 0-1.9% v/v Methanol 0-100% LEL or 100% 0-6% v/v Toluene 0-100% LEL or 0-1.1% v/v Butadiene 0-100% LEL or 0-2.0% v/v Ethylene 0-100% LEL or 0-2.7% v/v Ethanol 0-100% LEL or 0-3.3% v/v Isobutynol 0-100% LEL or 0-1.7% v/v Hexane 0-20% v/v Benzene 0-100% LEL or 0-1.2% v/v Xylene 0-100% LEL or 0-1.1% v/v Carbon Dioxide 0-2% v/v Digital Protocol RS-485 Accessories Part # Description 077-0120 Magnetic Screwdriver 096-2201 RS-485 Termination Board 096-2191 1/4 turn flowcell (Requires Gas Test Adaptor, #096-2192) 074-0321 Rainshield 096-2192 Gas Test Adaptor 096-2289 Bump Test Adaptor 096-2187 Zero Adjustment Kit (includes regulator, tubing, and carrying case - does NOT include methane "bump gas") 096-2190 Gas test kit (2 ft tubing, zero air and methane bump gas, cal adaptor, regulator, and carrying case) 096-2215 Porex dust filter (for rainshield) pack of 5 096-2214 Porex dust filter (for sensor) pack of 5 077-0161 Emitter replacement tool 096-2193 IR Emitter (plug-in, includes emitter replacement tool) Optical Bench Assembly Mirror Housing assembly 096-2159 Inner Filter 096-2274 Rain Shield Cage 074-0340 Filter Disk 096-2274-2 Outer Filter 096-2274-1 Monroe Corporate Center P.O. Box 569 Monroe, NC 28111 Telephone: 800.247.7257 Facsimile: 704.291.8330 www.scotthealthsafety.com sh-sale@tycoint.com H/S 6524 A 4/08 ISO 9001 Registered. All rights reserved.