Danfoss Gas Sensor DGS MODBUS

Similar documents
Danfoss Gas Sensor Type DGS-SC and DGS-IR with MODBUS

AT-G-SENSE Gas Sensing System

MGS Murco Gas Sensor EC / SC model Gas Detector and Transmitter. Installation & Operation* 08 ASH (1)

MGD - Murco Gas detector / Monitor. Installation & Operation* 08 ASH (1)

AquiTron DATA S HEET. AT-GU Commercial Refrigerant Sensor

Leak Monitors. Installation & Operation* 1- Installation Instructions. 2- Location Instructions. 3- Typical Settings. 4- Operating Instructions

AT-G-SENSE Gas Sensing System

LKD USER MANUAL. Detection and indication of refrigerant leaks MANAGEMENT AND MONITORING

Gas Detector. Installation and Operation Manual Instruction Revision 3 August Product Leadership Training Service Reliability

DGS - Danfoss Gas Sensor Check / Calibration Procedure

Integrated Area Monitor and Optional 16-Channel Controller Installation and Operation Manual Instruction Rev 1 March 2014

MGD Murco Gas Detector. Check / Calibration Procedure* 10 ASH (1)

MGS-350 Gas Detector Installation and Operation Manual Instruction Revision 1 February 2013 Product Leadership Training Service

Danfoss gas detection units

AT-G-DETECT Gas Sensing System

Installation & Operation

Gas detecting sensor Types GDA, GDC, GDHC, GDHF, GDH

Recalibrate the way you look at gas detection

Danfoss gas detection units

ST-IAM Sensor Transmitter Integrated Area Monitor. Check / Calibration Procedure* 10 ASH (1)

Operation Manual. Rev ART Infrared Refrigerant Transmitter.

GLD-30 Gas Leak Detector

Danfoss gas detection unit Type GD Heavy Duty

Gas Leakage Detector. Electronic fixed gas leak detectors. User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT!

Multi-Gas-Controller MGC2

Gas detectors for Industrial Refrigeration: Safety, efficiency and peace of mind

Controllers. Instruction Manual WARNING

DMFPM-2R MULTIFUNCTIONAL

Capacity controller EKC 331T REFRIGERATION AND AIR CONDITIONING. Manual

Carbon Monoxide Transmitter

IR200 INFRARED HCFC & AMMONIA (NH3) REFRIGERANT SENSOR. User Manual

Instruction Manual WARNING

MODEL A-316 CARBON MONOXIDE (CO) MONITOR AND ALARM FOR COMPRESSED AIR TESTING

Ax60+ Multi-Gas. Service Manual

Gas Detection Sensor type GDA, GDC, GDHC, GDHF, GDH REFRIGERATION AND AIR CONDITIONING. Technical leaflet

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

Analog Room Pressure Monitor RPC Series

RK-HC-04 M2A Transmitter Operator s Manual

Murco Core Product Guide Gas Leak Detection Solutions for all your building needs

Nitrogen Dioxide Stand-Alone Detector - Analog, ModBus

URD20SE. Gas detectors Carbon dioxide (CO 2 ) ATEX certified (II 2G Ex d IIC T6) Use. Operation. Ordering

Temperature controller for limitation for the discharge gas temperature EKC 319A REFRIGERATION AND AIR CONDITIONING. Manual

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670

CLEANROOM MONITOR CR3A Network - Installation Instructions

Ammonia Leak Detector Manual

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

DESIGN MANUAL. The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0)

INSTALLATION AND OPERATING INSTRUCTIONS

Product Manual SZ1144

Pioneer-R16 Gas Monitor Operator s Manual

M2A Transmitter Operator s Manual

Product Manual SZ1145

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

Two-Channel Gas Controller

Controller for operation of evaporator on water chiller EKD 316

Gas detection in refrigeration systems

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy.

HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL

RPM1600 Series Room Pressure Monitors

Gas Detection Unit (GDU) GDA, GDC, GDHC, GDHF, GDH

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

Inc Series Digital Gas Detector/Controller. Operation Manual

Capacity controller for water chiller AK-CH 650

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

PTE0705 Electric Fence Monitor

MVR-300 Refrigerant Gas Detector for Occupied Spaces

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

Macurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference

RAE Systems Systems. User Presentation. October Protection Through Detection

GL-CO-RFG Channel Gas Leak Alarm System

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES

SEC 2000 Millenium Infrared Gas Detector

Specifications, Applications, Service Instructions & Parts GAS DETECTION SENSORS, MONITORS & ALERT SYSTEMS. For Refrigerants and other Common Gases

M2 Transmitter Operator s Manual

Installation & Calibration Guide

Warranty Registration

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

Flopurge TS. Operation Manual

SENSIT HXG-2d. SENSIT TECHNOLOGIES 851 Transport Drive Valparaiso, IN Phone: (219) Fax: (219)

Macurco CM-21A Carbon Monoxide

MACURCO INC. CONTROLLERS & CARBON MONOXIDE DETECTORS SS103-3A, SS103-10A SS102H, SS102HC-1 INSTALLATION & OPERATING INSTRUCTIONS

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Warranty Registration

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

DIGITAL TEMPERATURE RELAY TR-100

Oxygen Monitor Operating Manual

RK-04 M2 Transmitter Operator s Manual

Public Safety DAS Annunciator Panel

3 Macurco Combustible Gas Detector, Controller and Transducer User Instructions

CO2 Monitor Operating Instructions

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

Fixed Gas Detector User Manual Installation Operation Configuration Troubleshooting

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

Ammonia Detection System Codes and Design Specifications

Model D12-IR. Digital Gas Transmitter...

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

GAS PLUS ALARM SYSTEM

Transcription:

Installation Guide Danfoss Gas Sensor DGS MODBUS ADAP-KOOL Refrigeration Control System

DGS - Location instructions Location of Sensors Sensors must be located within the appropriate wire lengths from the central control unit (if used). In all cases the sensor supplied is designed for maximum sensitivity to a particular gas. However, in certain circumstances false alarms may be caused by the occasional presence of sufficiently high concentrations of other gaseous impurities. Examples of situations where such abnormalities may arise include the following: Plant room maintenance activity involving solvent or paint fumes or refrigerant leaks. Accidental gas migration in fruit ripening/storage facilities (bananas - ethylene, apples - carbon dioxide). Heavy localised exhaust fumes (carbon monoxide, dioxide, propane) from engine-driven forklifts in confined spaces or close to sensors. It is recommended setting the alarm delay to minimise false alarms. Machinery rooms There is no absolute rule in determining the number of sensors and their locations. However, a number of simple guidelines will help to make a decision. Sensors monitor a point as opposed to an area. If the gas leak does not reach the sensor then no alarm will be triggered. Therefore, it is extremely important to carefully select the sensor location. Also consider ease of access for maintenance. The size and nature of the site will help to decide which method is the most appropriate to use. Locations requiring the most protection in a machinery or plant room would be around compressors, pressurised storage vessels, refrigerant cylinders or storage rooms or pipelines. The most common leak sources are valves, gauges, flanges, joints (brazed or mechanical), filling or draining connections, etc. When mechanical or natural ventilation is present, mount a sensor in the airflow. In machinery rooms where there is no discernible or strong airflow then options are: Point Detection, where sensors are located as near as possible to the most likely sources of leakage, such as the compressor, expansion valves, mechanical joints or cable duct trenches. Perimeter Detection, where sensors completely surround the area or equipment. For heavier-than-air gases such as halocarbon and hydrocarbon refrigerants such as R404A, propane, and butane sensors should be located near ground level. For lighter-than-air gas (e.g., ammonia), the sensor needs to be located above the equipment to be monitored on a bracket or high on a wall within 300 mm (12 in) of (or on) the ceiling provided there is no possibility of a thermal layer trapped under the ceiling preventing gas from reaching the sensor. NOTE: At very low temperatures (e.g., refrigerated cold store), ammonia gas becomes heavier than air. With similar density or miscible gases, sensors should be mounted about head high (about 1.5 m [5 ft]). With CO2 in a machinery room it is recommended to mount it 0.3-0.45 m (1-1.5 ft) above the floor as the air flow is low and CO2 slightly heavier than air. Make sure that pits, stairwells and trenches are monitored since they may fill with stagnant pockets of gas. For racks or chillers pre-fitted with refrigerant sensors, these should be mounted so as to monitor the compressors. If extract ducts are fitted the airflow in the duct may be monitored. Refrigerated Spaces In refrigerated spaces, sensors should be located in the return airflow to the evaporators on a sidewall (below head-high is preferred), not directly in front of an evaporator. With CO2 in a machinery room it is recommended to mount it 0.3-0.45 m (1-1.5 ft) above the floor. In large rooms with multiple evaporators, sensors should be mounted on the central line between 2 adjacent evaporators, as turbulence will result in airflows mixing. Chillers In the case of small water- or air-cooled enclosed chiller units mount the sensor so as to monitor airflow to the extract fans. With larger models also place a sensor inside the enclosure under or adjacent to the compressors. In the case of outdoor units: For enclosed air-cooled chillers or the outdoor unit for variable refrigerant volume and variable refrigerant flow (VRV/VRF) systems, mount the sensor so as to monitor airflow to the extract fan. With large units also place a sensor inside the enclosure under or adjacent to the compressors. In the case of non-enclosed outdoor units: If there is an enclosed machinery section locate a sensor there. In the case of units with enclosed compressors, mount sensors in the enclosures. Where you have protective or acoustic panels mount the sensor low down under the compressors where it is protected by the panels. With air-cooled chillers or air-cooled condensers with nonenclosed condenser sections it is difficult to effectively monitor leaks in the coil sections. With some designs it will be possible using an airflow sensor to monitor airflow to the start up fans in the front or rear sections. If there is a possibility of refrigerant leaks into a duct or air-handling unit install a sensor to monitor the airflow. Weatherproof sensors should be used for unprotected outdoor applications. Air Conditioning Direct systems VRF/VRV The DGS was not intended for use in occupied spaces (private housing, hotel rooms etc.) but may be used in such location. If so, special attention should be paid to ensurse compliance with EN378. Sensors should be positioned just far enough back from any high-pressure parts to allow gas clouds to form and be detected. Otherwise, a gas leak might pass by in a high-speed jet and not be detected by the sensor. 2 Installation guide RI8RV202 Danfoss 2017-04 DGS

Dimensions and mounting IP41 Sensor IP66 sensor mounting measurements mounting slots = 9 mm long x 6 mm wide use 5 mm - 6mm screws IP66 Remote Head, M42 thread, 3m Cable M42 thread Mounting locations as in IP66 DGS Installation guide RI8RV202 Danfoss 2017-04 3

DGS Installation Instructions Danfoss gas detectors can activate external systems such as fans or shut down and activate sirens, warning lights, activate dial out systems, or connect to BMS systems including Danfoss AK-SM 720/ AK-SM 350 and the AK-SM 800 series. To open the IP41 Sensor enclosure: turn the cable gland ½ turn anticlockwise to loosen the internal gland nut, depress the clip on top of the enclosure and open. Reverse to close. A retention strap fixates the sensor element during transportation. Remove it after opening the sensor enclosure by pulling the tap of the retention strap. IP66 is open and closed with a Torx size TX25. It is supplies without any retention strap. Power: The DGS can be used with 12-24V AC/DC, connect at positions 0V and +V at connector block CN1. Default factory setting is DC (J1 = OFF. J2 = ON) To select AC set J1 = ON. J2 = OFF. Sensor measurement The sensor measurement is available as a current or voltage output through connector CN2. Current is measured between 0V and I as a 4-20mA signal, whereas the voltage output between 0V and V is configurable. Set J7, J8, J9 or J10 to ON to select 0-5V, 0-10V, 1-5V or 2-10V respectively. Default factory setting is 1-5V. Alarm set point*: P1 sets the trip point for the relay and buzzer using the 0-5V scale (measure at test points TP3, 0V and TP1 alarm; 2.5V would be equivalent to half the range (500ppm on a scale of 0-1000ppm)). Default factory setting is typically around 50% of the full scale range but please refer to the label of the specific product for specific details. CAUTION For gas' with unlinear response to the semiconductor sensing technology, the maximum alarm threshold may be lower than the maximum measuring range. See data sheet or the product lable for specific details Time delay*: A time delay for the operation of the relay and buzzer can be selected using jumpers J5 and J6. Default factory setting is zero. Time delay (min) J6 J5 0 (default) Off Off 1 Off On 5 On Off 10 On On Network address To establish Modbus communication, configure the address using SW1 and SW2 and perform a network scan from the front end. The Baud rate may need changing too, e.g. it must be set to 19,200 baud when used with AK-SM 720/AK-SM 350. For further details on network integration, please refer to the Front End manual. ADDR = 16 x SW2 + SW1 Example: 40 = 16 x 2 + 8 SW1 = Least Significant Hex Character (0-F) = 0-15 SW2 = Most Significant Hex Character (0-F) = 0-15 Baud rate 9 A B C D E F 80 1 2 3 4 5 6 7 SW1 CAUTION To choose a Baud rate, set the address as shown below and reset the gas detector by temporarily shorting jumper J4 (or by cycling the power off and on). After the Baud rate is set, the desired Modbus address (1-247) can be selected by changing the switch settings and temporarily shorting jumper J4 (or by cycling the power off and on) ADDR S2 S1 BAUD RATE 254 F E 9,600 255 F F 19,200 253 F D 38,400 (Default) For more information about data communication see document RC8AC-- 9 A B C D E F 80 1 2 3 4 5 6 7 SW2 Danfoss 80Z730.10 Buzzer: The buzzer can be disabled using jumper J3. Default factory setting is enabled, which is in compliance with EN378. If you are connecting to a remote monitoring system the function may be disabled (buzzer). * Note: The alarm setpoint and time delay are also configurable via the Modbus interface. If the Modbus parameters are set to zero (default) then the hardware configuration is active. 4 Installation guide RI8RV202 Danfoss 2017-04 DGS

DGS -Installation and wiring diagram IR sensor DGS-IR Sensor Voltage Test Point INFRARED (IR) SENSOR PC BOARD GREEN LED TP2 (Vs) +V -V RX Delay P1 J5 J4 J6 TX Alarm SIGNAL P2 TP1 (Alarm) RED LED P4 4-20mA Zero Reset Addressing 0 1 2 3 4 5 6 7 8 9 A B C D E F SW1 0 1 2 3 4 5 6 7 8 9 A B C D E F SW2 Danfoss 80Z731.10 Audible Alarm and Relay Set Point Volage Test Point Board Ground Plane Test Point DC Select J2 P3 Span TP3 0V AC Select J1 CN1 CN4 _ G + MODBUS CN2 0V V+ Power 0V V I Supply Output Signal VOLTS 0 0 1 2 5 10 5 10 J7 J8 J9 J10 CN3 N / O COM N / C Relay Out Audible Alarm J3 Diagram 1 Semiconductor sensor DGS-SC SEMICONDUCTOR (SC) SENSOR PC BOARD Delay J5 J6 P1 Alarm J4 Reset TP1 (Alarm) Danfoss 80Z730.10 Audible Alarm and Relay Set Point Volage Test Point GREEN LED P2 RED LED P4 SW1 SW2 Addressing 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 A B C D E F Sensor Voltage Test Point Board Ground Plane Test Point TP2 (Vs) DC Select J2 Zero P3 Span TP3 0V AC Select J1 CN1 CN4 _ G + MODBUS CN2 0V V+ Power 0V V I Supply Output Signal 4-20mA J7 J8 J9 J10 0 0 1 2 5 10 5 10 VOLTS CN3 N / O COM N / C Relay Out Audible Alarm J3 Diagram 2 DGS Installation guide RI8RV202 Danfoss 2017-04 5

DGS -Operating instructions 1- On powering up it will sense for the presence of gas after an initial warmup delay of 5 minutes. A Modbus service parameter is set during the warm-up. 2- In alarm condition: (e.g. high gas level) the green LED stays on the red LED will be on the buzzer operates (if it has not been disabled and after a delay if this option has been selected) the relay output activates (after a delay if this option has been selected) the voltage or current output changes proportional to gas concentration 3- Fault condition: (e.g. sensing error) the green LED will be off the red LED will be on a voltage or current fault output will activate 2mA on the 4-20mA output 0.5V on the 1-5V output 1.0V on the 2-10V output DGS Sensor - Annual Test To comply with the requirements of EN378 and the F GAS regulation sensors must be tested annually. However local regulations may specify the nature and frequency of this test. If not the Danfoss recommended procedure should be followed. See the installation and operation guide for details. CAUTION Check local regulations on calibration or testing requirements. After exposure to a substantial gas leak, sensor should be checked and replaced if necessary. 4- Manual control It is possible to perform a manually control to verify the buzzer, LED's and alarm relay, see Menu Survey. NOTE: The DGS Modbus is calibrated at the factory. After installation, a zero adjustment may be required to DGS-SC due to differences in environmental conditions. DGS-IR should never need any adjustment immediately after installation. DGS - Bump Test Instructions Expose the sensors to test gas using a Danfoss ampoule (CO2) or test cylinder (appropriate to the installation). Or fully activate the valve of a cigarette lighter (only for Semiconductor units) without igniting it and hold it over the sensor element or for IP41 over the vent holes on the upper right side of the DGS. The gas is heavier than air and should fall into the DGS. This will put the system into alarm. The red LED will light showing the system is in alarm. The delay will prevent the buzzer sounding or relay switching for the preset delay, if delay is set. With a bump test you can see the functions of the sensor - the red led will light, the relay and buzzer will function, the output selected, say 0-10V- will show the gas level. To test the buzzer and or relay function, check the delay is set at zero using the header as shown on the installation diagram and expose to gas as above. You can mute the buzzer by removing the jumper J2. After the gas has cleared the red led, buzzer and relay will automatically reset. Before testing the sensors on site the DGS must have been powered up and allowed to stabilize. 6 Installation guide RI8RV202 Danfoss 2017-04 DGS

Menu Survey Function Min Max Factory Unit AKM name Gas level Actual gas level in % 0.0 100.0 0.0 % Gas level % Actual gas level in ppm (OBS note 1 ) 0 FS 2 0 ppm Gas level ppm Alarms Alarm settings Common indication of alarms (any alarms active excl. warnings) 0 1 0 - GD alarm 0 = No active alarm(s) 1 = Alarm(s) active Common indication of both alarms incl. warnings 0 1 0 - Common errors 0 = No active alarm(s) or warning(s) 1 = Alarm(s) or warning(s)) active Alarm limit in % if set to 0 hardware potentiometer configuration 0.0 100.0 0.0 % Alarm limit % is used (hardware configured limit will be shown). Alarm limit in ppm if set to 0 hardware potentiometer configuration 0 FS 2 0 ppm Alarm limit ppm is used (hardware configured limit will be shown). High alarm delay in minutes, if set to 0 hardware jumper configuration 0 10 0 min. Alarm delay is used (hardware configured delay will be shown). When set to 1, the alarm relay and buzzer are reset to no 0 1 0 - Reset alarm alarm indication (mute a connected indicator). When the alarm is reset or the timeout duration is exceeded, the value is reset to 0. OBS: The alarm condition is not reset only the buzzer and relay indications are reset. Used to mute an external alert (audible/visible) 0 = Alarm outputs not muted 1 = Alarm outputs muted Maximum duration of alarm reset before automatic re-enable 0 59 0 min Reset alarm time of external indicators (mute time out in minutes) a value of 0 disables ability to mute alarm. Warning limit in % 0.0 100.0 0.0 % Warning limit % Warning limit in ppm 0 FS 2 0 ppm Warning lim. ppm Enables warning alarm when Warning limit exceeded 0 1 0 min. Warning Enable Service Read out of refrigerant (Gas) for the DGS is used for 1 42 N - Refrigerant Value according to "Danfoss standard list". Gas Full scale in ppm 0 32000 0 ppm Fullscale ppm Hours since last calibration 0 32000 0 hours Burning hours Status of the sensor warm up period 0 1 0 - Startup flag 0 =Ready 1 = Warming Up When cleared, clears calibration due alarm and resets the 0 1 0 - Reset cal burning hours parameter 0 = Calibration valid 1 = Calibration due Failsafe operation of the Relay 0 1 0 - Relay failsafe 0 = Not failsafe 1 = Failsafe Enables Manual control of Relays, buzzer and LED's. 0 1 0 - Manual Control Automatically falls back to Off after 10 min. Status of the alarm relay 0 1 0 - Alarm Relay 0 = No alarm signal 1 = alarm signal Status of the buzzer 0 1 0 - Buzzer 0 = inactive 1 = active Status of the red LED 0 = off 1 = on 0 1 0 - Red LED DGS Installation guide RI8RV202 Danfoss 2017-04 7

Status of the green LED 0 = off 1 = on Alarms Limit alarm 0 = Alarm not active 1 = Alarm, gas limit exceeded 0 = OK 1 = Fault. Out of range under test 0 = OK, sensor in place 1 = Fault, Sensor out or removed 0 = OP, Sensor not due for calibration 1 = Warning, Due for calibration 0 = OK, Gas level below warning level 1 = Warning, Gas level above warning level and delay expired 0 1 0 - Green LED 0 1 0 - Limit alarm 0 1 0 - Sensor saturated 0 1 0 - Sensor out 0 1 0 - Calibrate sensor 0 1 0 - Warning limit al. 1 The communication system can only handle integer values in the range -32000 to 32000 and decimal values in the range -3200.0 to 3200.0. 2 Value equals fullscale range of specific product DGS - Troubleshooting Symptom Green and Red light off Red light on, green led off (indicates a fault) Possible Cause(s) Check power supply. Check wiring. DGS Modbus was possibly damaged in transit. Check by installing another DGS Modbus to confirm the fault. Sensor may be disconnected from printed circuit board. Check to see sensor is properly inserted into board. The sensor has been damaged or has reached the end of life and needs to be exchanged. Contact Danfoss for instructions and support The zero-adjustment has been reduced to achieve a zero-measurement in an environment with gas, typically CO2. Do a zeroadjustment with a zero-gas and a re-calibration. Alarms in the absence of a leak The zero-measurement drifts When changing potentiometer P1, the test point measurement is changing but the active alarm point is not changing If you experience alarms in the absence of a leak, try setting an alarm delay. Perform a bump test to ensure proper operation. The DGS-SC sensor technology is sensitive to the environment (temperature, moist, cleaning agents, gas' from trucks, etc). All ppm measurements below 75ppm should be disregarded, i.e. no zero-adjustment made. Any alarm limit configured via Modbus takes priority over the setpoint set electrically via potentiometer P1. To re-enable the setpoint adjustment via P1, set the Modbus parameter to '0' (zero). *Technician use only This unit must be installed by a suitably qualified technician who will install this unit in accordance with these instructions and the standards set down in their particular industry/country. Suitably qualified operators of the unit should be aware of the regulations and standards set down by their industry/country for the operation of this unit. These notes are only intended as a guide and the manufacturer bears no responsibility for the installation or operation of this unit. Failure to install and operate the unit in accordance with these instructions and with industry guidelines may cause serious injury including death and the manufacturer will not be held responsible in this regard. Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. ADAP-KOOL 8 Installation guide RI8RV202 Danfoss 2017-04 DGS