KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

Similar documents
SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

SECTION AUTOMATIC SPRINKLER PIPING

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

Design & Construction Standards, Revised January

SPRINKLERS TABLE OF CONTENTS

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION AIR DUCT ACCESSORIES

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

Agent Tanks PCL PCL PCL PCL - 600

Types of Detection. Fusible Link Detection - Most Common

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

UTILITY DISTRIBUTION AND CANOPY VENTILATING SYSTEMS

FIRE SUPPRESSION SPRINKLER SYSTEM

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 10 - SPECIALTIES

B. Section Identification for Fire Suppression Piping and Equipment.

D. Reference Standards (Utilize latest editions available):

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

UTILITY DISTRIBUTION AND CANOPY VENTILATING SYSTEMS

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

Data/ Specification Sheet

Design and Construction Standards SECTION PLUMBING EQUIPMENT

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

SECTION (15833) - HVAC POWER VENTILATORS

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

SECTION DRY-PIPE SPRINKLER SYSTEMS

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS

ADDENDUM NO. 3 March 19, 2018

SECTION FIRE-SUPPRESSION STANDPIPES

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

SECTION PLUMBING EQUIPMENT

SECTION WET-PIPE SPRINKLER SYSTEMS

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

Gas Station & C Store SECTION CWM Job No

SECTION DRY-PIPE SPRINKLER SYSTEMS

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

SECTION COMMERCIAL-KITCHEN HOODS

DIVISION 21 - FIRE SUPPRESSION

B. Related Sections: The following Sections contain requirements that relate to this Section.

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION SPRINKLER SYSTEMS

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION DUCTWORK

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

DIVISION 21 - FIRE SUPPRESSION

UNIFIED FACILITIES GUIDE SPECIFICATIONS

DONALD H. BERG, ARCHITECT

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

FM-200 In-Cabinet Series

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

SECTION SPRINKLER SYSTEMS

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009.

POLK COUNTY SCHOOL BOARD Issue Date: DESIGN AND CONSTRUCTION STANDARDS These Standards are for guidance only. DCS Ӏ DIVISION 15 FP TOC

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

CORE Protection Fire System Specification

SECTION FAN COIL UNITS

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SECTION FIRE PUMP AND CONTROLS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

WET-PIPE SPRINKLER SYSTEMS

SECTION HEATING BOILERS

Mercury Plastics New Building February TABLE OF CONTENTS

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

15900 HVAC INSTRUMENTATION AND CONTROLS

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

Transcription:

PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories. B. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 11420 - Utility Distribution and Canopy Ventilating Systems. 3. 15300 - Fire Protection. 4. 16721 - Fire Alarm Detection System. 1.02 REFERENCES A. Comply with applicable standards of the following: 1. American Society for Testing and Materials (ASTM) A53-96 Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless. 2. Underwriters Laboratories (UL). 3. National Electrical Manufacturers Association (NEMA). 4. National Fire Protection Association (NFPA). a. 17A. b. 70 (National Electrical Code [NEC]). c. 96. 5. Florida Department of Education, Office of Educational Facilities - State Requirements for Educational Facilities - 1997 (SREF). 6. Florida Statutes (FS) 633. 7. State Fire Marshal (SFM) Rule 4A-21. 1.03 SYSTEM DESCRIPTION A. Performance Requirements: System shall be capable of automatically extinguishing grease fires occurring on equipment, cooking surfaces, hood, and ductwork. Project No. SPECIFICATION GUIDELINES 15371-1

1. Upon detection of products of combustion, the sensing devices shall: a. Activate the discharge head. b. Shut-off the electrical and gas supplies to cooking equipment under the hood. c. Shut-off supply fans on hoods with fire dampers. Hood exhaust fans shall continue to operate after the suppression system has been activated unless fan shutdown is required by a listed component of the ventilation system or by design of the extinguishing system. 2. The building fire alarm shall be activated upon operation of fire suppression system. 3. The automatic gas shut-off valve shall be of the mechanical type and be capable of manual reset to assure gas pilots are reactivated before renewal of gas flow. Electrical solenoid gas shut off valves are not allowed. 1.04 SUBMITTALS A. Submit properly identified manufacturer's literature before starting work. B. Submit Shop Drawings on the following: 1. UL 300 listed automatic wet chemical fire suppression system. 2. Control panel and actuators. 3. Discharge nozzles. 4. Detectors. 1.05 QUALITY ASSURANCE A. Fire protection equipment and devices shall be UL listed for service intended. Install equipment according to the standards of NFPA and as specified. Electrical installation shall copply with National Electrical Code (NEC). B. Equipment location shall be coordinated with A/E. C. Comply with UL 300. 1.06 WARRANTY A. During the 1 year warranty period, perform a semiannual and annual inspection of installation to verify its proper Project No. SPECIFICATION GUIDELINES 15371-2

operation. B. Actuation components include remote manual pull station, mechanical or electrical devices, detectors, actuators, etc. and shall be checked for proper functioning during inspection. C. Fusible links shall be replaced at the annual inspection. D. Complete inspection shall be performed according to NFPA 17A and NFPA 96. E. Forward to the Board, A/E, insurance company, and local Fire Department results of inspections and tests. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Kitchen Hood and Duct Fire Suppression Systems: 1. Amerex KP 3.75. 2. Ansul R-102. 3. Kidde Fenwal WHDR Series. 4. Pyro Chem PCL Series. B. Automatic Controls: Grinnell or accepted equivalent. C. Joint Compound: White Tite Seal or accepted equivalent. 2.02 EQUIPMENT A. Materials used in system shall be approved by manufacturer of base equipment. B. Piping: 1. Under 1 inch size: Galvanized steel, standard weight, schedule 40, ASTM A53; 1 inch and larger: Schedule 80. 2. Exposed: Chrome-plated or stainless steel pipe. C. Fittings: 1. Galvanized threaded malleable iron; 1 inch or larger extra heavy; chrome-plated malleable iron or stainless steel fittings compatible with type of pipe used; 2-1/2" and larger: threaded 300 PSI black steel, or flanged 600 PSI black steel. Project No. SPECIFICATION GUIDELINES 15371-3

2. Flanges 2-1/2" and larger: 600 PSI, black steel. D. Gaskets: Stainless steel, similar to Flexitallic. E. Extinguisher Cylinders: Totally self-purging, with remote manual and automatic releasing mechanism in separate cabinet to allow discharge of wet agent. Size and type depending on cooking equipment and exhaust hood used. F. Discharge Nozzles: Suitably shielded, jet outlet type corrosion and deformation resistant to high temperatures designed to insure even distribution of wet agent without turbulence, of proper shape for their location, and provided with proper size orifices. 1. Nozzle openings on concealed piping shall be flush with hung ceiling with flanged ceiling connection or escutcheon. 2. Use flanged type nozzles connected to ductwork. G. Electric Switch: Provide trip lever operated, 2 single pole double throw switches to sound the building fire alarm, shut off electric and gas supply to equipment (manual reset relay), and shut off supply fans serving protected space. H. Automatic Controls: Fusible links, for 360 degrees F. operation or as appropriate to the type of equipment being protected. I. Manual Pull Box: Provide at outside of each protected space and where noted, surface-mounted red enameled cast iron or cast aluminum alloy pull boxes with glass or breakable plastic shield and having handle connected to releasing device through suitable corrosion resisting cable run in 3/8" galvanized standard weight steel pipe conduit with enclosed type corner pulleys at changes in direction. PART 3 EXECUTION 3.01 INSTALLATION A. Perform work by a Florida licensed company possessing a Class D license issued by the State Fire Marshall with Class 4 permitted technicians according to FS 633 and SFM Rule 4A-21 and according to local and state codes and NFPA 17A and NFPA 96. 1. Installation shall be certified in writing by the installer to: Project No. SPECIFICATION GUIDELINES 15371-4

a. The Board's insurance rating authority. b. Local fire authority. c. The Board. d. The manufacturer. B. The fire protection system provided shall be capable of detecting fire in the hood and duct, and automatically discharge non-toxic wet extinguishing agent into hidden areas behind the plenum chamber filters, the exhaust system, and cooking appliance area. C. Piping: 1. Run piping enclosed where possible in wall chases, recesses, pipe shafts, wall partitions, and ceilings where provided. a. Non-concealed piping shall run as inconspicuously as possible in schedule 40 chrome-plated (CP) piping or stainless steel piping. 1) Chrome-plated piping shall not show tool marks or more than one thread at fittings. 2) Fittings, valves on CP piping shall be CP finish, or compatible with the type of pipe used. 2. Use reducing fittings for changes in pipe size. Bushings are not allowed. 3. Use extra heavy pipe for nipples where unthreaded portion is less than 1-1/2". Close nipples are not acceptable. Use shoulder nipples. 4. Provide unions and flanges for connections to equipment. D. Joints: 1. Make joints in screwed piping with acceptable compound on male threads only. Do not use lamp wick in joints. Threads shall be perfect, clean cut and of proper length. Pipe shall be properly reamed after cutting and threading. 2. Make flanged joints with full face rubber gasket or stainless steel. E. Hangers and Supports: 1. Properly support piping by accepted type hangers and Project No. SPECIFICATION GUIDELINES 15371-5

supports: a. To secure piping in place. b. To prevent vibration. c. Of ample size to carry pipe. 2. Chain, straps, perforated bar, or wire hangers not allowed. 3. Hangers and supports in exposed CP piping shall be CP finish. 4. Provide necessary supplemental steel for proper support or attachment of hangers. F. Escutcheons: 1. Unless otherwise noted, provide exposed pipes with acceptable type chrome plated brass or chrome plated steel escutcheons where they pass through walls, partitions, floors, or ceilings. Hold in place by set screws. 2. At CP piping provide satin CP finish escutcheons. G. Sleeves: 1. Provide sleeves large enough to fit pipe passing through floors, ceiling, walls, or partitions. 2. Penetrations by fire protection water lines through fire rated floors and walls shall be installed and firestopped using UL classified through-penetration firestopping and fire and smoke barrier caulking as specified in Section 07270, Firestopping and Fire and Smoke Barrier Caulking. 3. The fire rating of the firestopping and caulking shall be equivalent to or greater than the fire-rating of the floor or wall penetrated. 4. Install firestopping and caulking according to manufacturer's instructions. H. Fusible Links: Mounted on brackets centered in exhaust duct maximum 20 feet downstream, above cooking appliances, and above and within the perimeter of the appliance. I. Cuttings and Patching: 1. The installer of the automatic wet chemical fire suppression system shall be responsible for: a. Cutting and patching. b. Preparatory work required for the reception of the Project No. SPECIFICATION GUIDELINES 15371-6

system. c. Cleaning up and restoration of construction and finishes defaced, marred, or otherwise disturbed because of the installation. J. Clean equipment, piping, and other exposed work as directed. Perform cleaning work in stages if required to facilitate work of others. 1. Plated, polished, bronzed, or painted work shall be bright and clean. 2. Blow out piping with air or nitrogen after installation and before nozzle settings. 3. Adjust equipment and discharge nozzles for proper operation. 4. Tension cables with pulleys without overloading. 3.02 FIELD QUALITY CONTROL A. During the Board's substantial completion inspection, conduct a full-scale "bag test" of system to verify the system works as intended, including the interface that activates the building fire alarm system when the fire suppression system discharges. END OF SECTION Project No. SPECIFICATION GUIDELINES 15371-7