Public Comment No. 20-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Similar documents
Public Comment No. 16-NFPA 13D-2014 [ Section No ]

FINAL REPORT* OF THE MOTIONS COMMITTEE 2015 ASSOCIATION TECHNICAL MEETING JUNE 22-25, 2015 CHICAGO, IL

The distances in shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking garages.

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Revise the metric values throughout the standard to follow the soft conversions provided by the metric task group

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

Public Input No. 11-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14

12/21/2015 National Fire Protection Association Report

Remove the "Exception" text to be consistent with direction provided in the MOS.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Technical Committee on Private Water Supplies

1 of /3/ :03 PM. Public Input No. 1-NFPA 13D-2015 [ Chapter 2 ]

Course FP100 BACKFLOW PREVENTERS (BFPs) 101 FOR AUTOMATIC FIRE SPRINKLER SYSTEM M. Nabeel Waseem, M.Eng, PE, CFPS 2018

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

CITY OF PASADENA FIRE DEPARTMENT

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

DIVISION 21 FIRE SUPPRESSION FIRE SUPPRESSION GENERAL PROVISIONS .1 PREPARATION OF CONTRACT DOCUMENTS

SECTION ELECTRIC-DRIVEN, FIRE PUMPS

NFPA 14. Standard for the. Installation of Standpipe and Hose Systems Edition

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Orange Township Fire Department Fire Prevention Bureau

A. This section includes design and performance information for fire protection and suppression systems.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

SECTION WET-PIPE SPRINKLER SYSTEMS

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 13-NFPA [ Section No ]

SECTION WET-PIPE SPRINKLER SYSTEMS

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12.

UMC El Paso Far East Clinic and Neighborhood Healthcare Center West Issue for Construction Page Project No and April 13, 2015

First Revision No. 82-NFPA [ Detail ] Submitter Information Verification Submitter Full Name: Organization:

SECTION DRY-PIPE SPRINKLER SYSTEMS

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ]

Design & Construction Standards, Revised January

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification


SECTION DRY-PIPE SPRINKLER SYSTEMS

Access Aisle (Van) (Flow Test) Water Mains (Location & Sizes) Building Entrances. Building, Facilities, Element. Curb Ramps (Built-up)

Public School Facilities Authority State of New Mexico 2019 Galisteo, Suite B Santa Fe, New Mexico 87505

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

SECTION SPRINKLER SYSTEMS

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

SPRINKLERS TABLE OF CONTENTS

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

AUTOMATIC FIRE SPRINKLER SYSTEMS

Port of St Helens SIA Aircraft Hanger Scappoose, OR

WET-PIPE SPRINKLER SYSTEMS

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

CONTRACT FOR USE OF FIRE PROTECTION SYSTEM

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

City of Vista Fire Department

SECTION FIRE-SUPPRESSION STANDPIPES

DIVISION 21 FIRE SUPPRESSION

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

DIVISION 21 - FIRE SUPPRESSION

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Environmental Health & Safety

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

Fire Pump Specification

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev

1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Second Revision No. 3-NFPA [ Section No. 2.3 ]

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

1 Exam Prep. Questions and Answers

TOWN OF SPENCER FIRE and EMERGENCY SERVICES

Transcription:

of 27 9/2/2014 9:27 AM Public Comment No. 20-NFPA 24-2014 [ Section No. 2.3.2 ] 2.3.2 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A 234/A 234M, Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and Elevated Temperatures, 2007 2013e1. ASTM A 53/A 53M Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless, 2001 2012. ASTM A 135/A135M Standard Specification for Electric-Resistance- Welded Steel Pipe, 2001 09(2014). ASTM A 795/A 795M Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized)Welded and Seamless Steel Pipe for Fire Protection Use, 2000 2013. ASTM B 16.5 Cast Bronze Threaded Fittings, 1985.?? ASTM B 43 Specification for Seamless Red Brass Pipe, 2009. ASTM B 75, Specification for Seamless Copper Tube, 2002 2011. ASTM B 88, Specification for Seamless Copper Water Tube, 2003 2009. ASTM B 251, Requirements for Wrought Seamless Copper and Copper-Alloy Tube, 2002 2010. IEEE/ASTM-SI-10, Standard for Use of the International System of Units (SI): The Modern Metric System, 2002 2010. Statement of Problem and Substantiation for Public Comment Update year dates Related Item First Revision No. 20-NFPA 24-2013 [Chapter A] Submitter Information Verification Submitter Full Name: Steve Mawn Organization: ASTM International Street Address: City: State: Zip: Submittal Date: Thu May 15 15:14:23 EDT 2014 Committee Statement Committee Action: Rejected but see related SR Resolution: SR-19-NFPA 24-2014 Statement: Update year dates. The deleted standard is an ASME Standard, not an ASTM Standard.

of 27 9/2/2014 9:27 AM Public Comment No. 16-NFPA 24-2014 [ Section No. 2.3.3 ] 2.3.3 Publications. American Water Works Association, 6666 West Quincy Avenue, Denver, CO 80235. C104, Cement Mortar Lining for Ductile Iron Pipe and Fittings for Water, 2008. C105, Polyethylene Encasement for Ductile Iron Pipe Systems, 2005. C110, Ductile Iron and Gray Iron Fittings, 2008. C111, Rubber-Gasket Joints for Ductile Iron Pressure Pipe and Fittings, 2000. C115, Flanged Ductile Iron Pipe with Ductile Iron or Gray Iron Threaded Flanges, 2005. C116, Protective Fusion-Bonded Epoxy Coatings for the Interior and Exterior Surfaces of Ductile-Iron and Gray-Iron Fittings for Water Supply Service, 2003. C150, Thickness Design of Ductile Iron Pipe, 2008. C151, Ductile Iron Pipe, Centrifugally Cast for Water, 2002. C153, Ductile-Iron Compact Fittings for Water Service, 2006. C200, Steel Water Pipe 6 in. and Larger, 2005. C203, Coal-Tar Protective Coatings and Linings for Steel Water Pipelines Enamel and Tape Hot Applied, 2002. C205, Cement-Mortar Protective Lining and Coating for Steel Water Pipe 4 in. and Larger Shop Applied, 2007. C206, Field Welding of Steel Water Pipe, 2003. C207, Steel Pipe Flanges for Waterworks Service Sizes 4 in. Through 144 in., 2007. C208, Dimensions for Fabricated Steel Water Pipe Fittings, 2007. C300, Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, 2004. C301, Prestressed Concrete Pressure Pipe, Steel-Cylinder Type, 2007. C302, Reinforced Concrete Pressure Pipe, Non-Cylinder Type, 2004. C303, Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, Pretensioned, 2002. C400, Standard for Asbestos-Cement Distribution Pipe, 4 in. Through 16 in. (100 mm through 400 mm), for Water Distribution Systems, 2003. C600, Standard for the Installation of Ductile Iron Water Mains and Their Appurtenances, 2005. C602, Cement-Mortar Lining of Water Pipe Lines 4 in. and Larger in Place, 2006. C603, Standard for the Installation of Asbestos-Cement Pressure Pipe, 2005. C900, Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in., for Water Distribution, 2007. C905, Standard for Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 14 in. Through 48 in. (350 mm Through 1200 mm), 2010. C906, Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through 63 in. (1575 mm) for Water Distribution, 2007. C909, Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe, 4 in. through 24 in. (100 mm through 600 mm), for Water, Wastewater, and Reclaimed Water Service2010 M11, A Guide for Steel Pipe Design and Installation, 4th edition, 2004. Statement of Problem and Substantiation for Public Comment Reference is made to the statement of problem and substantiation of Public Comment No. 2-NFPA 24-2014. Related Public Comments for This Document Related Comment Public Comment No. 2-NFPA 24-2014 [Section No. 10.1.1.1] Related Item First Revision No. 19-NFPA 24-2013 [Chapter 10] Relationship Concordance Submitter Information Verification Submitter Full Name: Ariel Carp Organization: On my behalf Affilliation: On my behalf Street Address:

of 27 9/2/2014 9:27 AM City: State: Zip: Submittal Date: Wed May 07 19:08:28 EDT 2014 Committee Statement Committee Action: Accepted Resolution: SR-3-NFPA 24-2014 Statement: Reference is made to the statement of problem and substantiation of Public Comment No. 2-NFPA 24-2014.

of 27 9/2/2014 9:27 AM Public Comment No. 15-NFPA 24-2014 [ Chapter 5 ] Chapter 5 Water Supplies

of 27 9/2/2014 9:27 AM 5.1* Connection to Waterworks Systems. 5.1.1 A connection to a reliable waterworks system shall be an acceptable water supply source. 5.1.2* The volume and pressure of a public water supply shall be determined from waterflow test data or other approved method. 5.2 Size of Fire Mains. 5.2.1 Private Fire Service Mains. Hydraulic calculations shall show that the main is able to supply the total demand at the appropriate pressure for systems with multiple hydrants. 5.2.2 Mains Not Supplying Hydrants. For mains that do not supply hydrants, pipe sizes less than 6 in. (152 mm) nominal size shall be permitted to be used subject to the following restrictions: (1) The main shall supply only the following types of systems: (a) (b) (c) (d) (e) Automatic sprinkler systems Open sprinkler systems Water spray fixed systems Foam systems Standpipe systems (2) Hydraulic calculations shall show that the main is able to supply the total demand at the appropriate pressure. (3) Systems that are not hydraulically calculated shall have a main at least as large as the riser. 5.3 Pressure-Regulating Devices and Meters. 5.3.1 Pressure-regulating valves shall not be used. 5.3.1.1 Pressure-regulating valves shall be permitted to be used when acceptable to the AHJ. 5.3.2 Where meters are required they shall be listed. 5.4* Connection from Waterworks Systems. 5.4.1 The requirements of the public health AHJ shall be determined and followed. 5.4.2 Where a backflow prevention device is installed to guard against possible cross-contamination of the public water system, it shall be listed for fire protection service. 5.4.2.1* Where a check valve or alarm check valve is permitted by the AHJ in lieu of a backflow preventer, it shall be listed for fire protection service. 5.5 Connections to Public Water Systems. Connections to public water systems shall be arranged to be isolated by one of the methods permitted in 6.2.9. 5.6* Pumps. Fire pump units installed in accordance with NFPA 20and connected to a water supply source complying with Sections5.5, 5.7, or 5.8 shall use an acceptable water supply source. 5.7 Tanks. Tanks shall be installed in accordance with NFPA 22. 5.8 Penstocks, Rivers, Lakes, or Reservoirs. Water supply connections from penstocks, rivers, lakes, or reservoirs shall be designed to avoid mud and sediment and shall be provided with approved, double, removable screens or approved strainers installed in an approved manner. 5.9* Remote Fire Department Connections. 5.9.1 General. Where the AHJ requires a remote fire department connection for systems requiring one by another standard, a fire department connection shall be provided as described in Section 5.9. 5.9.1.1 Fire department connections shall be permitted to be omitted where approved by the AHJ. 5.9.1.2 Fire department connections shall be of an approved type. 5.9.1.3 Fire department connections shall be equipped with approved plugs or caps that are secured and arranged for easy removal by fire departments. 5.9.1.4 Fire department connections shall be protected where subject to mechanical damage. 5.9.2 Couplings.

of 27 9/2/2014 9:27 AM 5.9.2.1 The fire department connection(s) shall use an NH internal threaded swivel fitting(s) with an NH standard thread(s.), except as permitted by 5.9.2.3 and 5.9.2.4. 5.9.2.2 At least one of the connections shall be the 2.5 to 7.5 NH standard thread specified in NFPA 1963. 5.9.2.3 Where local fire department connections use threads that do not conform to NFPA 1963, the AHJ shall designate the thread to be used. 5.9.2.4 Non-threaded couplings shall be permitted where required by the AHJ. Non-threaded couplings shall be listed for use as permitted in 5.9.2.4. 5.9.3 Valves. 5.9.3.1 A listed check valve shall be installed in the piping from each fire department connection. 5.9.3.2 Control valves shall not be installed in the piping from the fire department connection to the fire service main. 5.9.3.2.1* Control valves shall be permitted in the system piping downstream of the fire department connection piping. 5.9.4 Drainage. 5.9.4.1 The pipe between the check valve and the outside hose coupling shall be equipped with an approved automatic drain valve. 5.9.4.2 The automatic drain valve shall be installed in a location that permits inspection and testing as required by NFPA 25 and reduces the likelihood of freezing. 5.9.4.2.1 The automatic drip shall be permitted to be buried where permitted by the AHJ. 5.9.4.2.2 Where the automatic drip is buried as allowed by 5.9.4.2.1, the outlet shall discharge into a bed of crushed stone or pea gravel. 5.9.4.3 An automatic drain valve is permitted to be omitted from areas where the piping is not subject to freezing. 5.9.4.4 The automatic drip shall be permitted to be buried where permitted by the AHJ. 5.9.5 Location and Signage. 5.9.5.1* Remote fire department connections shall be located at the nearest point of fire department apparatus accessibility or at a location approved by the AHJ. 5.9.5.2* Remote fire department connections shall be located and arranged so that hose lines can be attached to the inlets without interference. 5.9.5.3* Each remote fire department connection shall be designated by a sign as follows: (1) The sign shall have raised or engraved letters at least 1 in. (25.4 mm) in height on a plate or fitting. (2) * The sign shall indicate the type of system for which the connection is intended. 5.9.5.4 Where the system demand pressure exceeds 150 psi (10.3 bar), a sign located at the fire department connection shall indicate the required inlet pressure. 5.9.5.5 Where a remote fire department connection only supplies a portion(s) of the building, a sign shall be attached to indicate the portion(s) of the building supplied. 5.9.5.6 Remote fire department connections shall not be connected on the suction side of fire pumps. 5.9.5.7 Where a remote fire department connection services multiple buildings, structures, or locations, a sign shall be provided indicating the buildings, structures, or locations served. Statement of Problem and Substantiation for Public Comment CC NOTE: The following CC Note No. 2 appeared in the First Draft Report as First Revision No. 15. The PRI TC should look at sections 5.9.4.4 and 5.9.4.2.1 to determine if these sections are redundant. Related Item First Revision No. 15-NFPA 24-2013 [Chapter 5] Submitter Information Verification

of 27 9/2/2014 9:27 AM Submitter Full Name: CC on AUT-AAC Organization: CC on Automatic Sprinkler Systems Street Address: City: State: Zip: Submittal Date: Tue Apr 29 13:32:47 EDT 2014 Committee Statement Committee Action: Rejected but see related SR Resolution: SR-4-NFPA 24-2014 Statement: This language is being deleted because it is already in Section 5.9.4.2.1.

of 27 9/2/2014 9:27 AM Public Comment No. 18-NFPA 24-2014 [ New Section after 5.1.2 ] 5.1.3 5.1.3* Where a waterflow test was conducted, the volume and pressure available for use for a fire protection system shall be determined from the following formula: P = (P 1 - P 2 )(Q/Q 1 ) 1.85 P 2 5.1.3.1 The pressure P shall be what is considered available from the water supply to use for a fire protection system that will be calculated for a given flow demand of Q. 5.1.3.2 The flow Q shall be demand flow of the fire protection system that will be used to calculate the available pressure from the water supply (P). 5.1.3.3* The variable P shall be the residual pressure measured during the waterflow test while the flow Q was discharging from 1 1 the water supply reduced by the specifying engineer or the water utility for daily and seasonal fluctuations. The reduction shall not be based on 100 year droughts or other extreme conditions. 5.1.3.4* The variable P shall be the static pressure measured during the waterflow test reduced by the specifying engineer or the 2 water utility for daily and seasonal fluctuations. The reduction shall not be based on 100 year droughts or other extreme conditions. 5.1.3.5 The variable Q shall be the flow associated with P. 1 1 5.1.3.6* Where the specifying engineer or the water utility does not provide the value for P 1 and P 2, see 5.1.3.7. 5.1.3.7* Where a waterflow test has been conducted and the specifying engineer or the water authority does not provide a value for P and P, the value of for P and P shall be calculated by taking the static pressure and residual pressure results from the flow test 1 2 1 2 and reducing them by 5%. Additional Proposed Changes File Name Description Approved Water_Supply_Adjustment_Proposal-E_S-24.pdf whole proposal with figures and equations Statement of Problem and Substantiation for Public Comment This is one of a series of proposals to make the adjustment to the data from a waterflow test required instead of recommended. If the adjustment is not required, contractors that do the right thing and adjust the data from tests are at a disadvantage from contractors that don't make any adjustment. It is fundamentally wrong to not make an adjustment to the data due to daily and seasonal fluctuations. This proposal makes a simple and easy to understand adjustment that is standardized so that there is no argument over what is supposed to happen. It is the intent to have this be the only adjustment. If the water utility has already performed the adjustment, or if the AHJ has already mandated a safety margin or safety factor to the waterflow data obtained from the test, this adjustment would not apply. Related Item Public Input No. 56-NFPA 24-2013 [New Section after 5.1.2] Committee Input No. 2-NFPA 24-2013 [New Section after 5.1.2] Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: NFSA E&S Committee Street Address: City: State: Zip: Submittal Date: Thu May 08 18:01:38 EDT 2014 Committee Statement Committee Rejected but see related SR Action: Resolution: SR-17-NFPA 24-2014 Statement: The NFPA 13 technical committees have been discussing the need for adjusting waterflow data for several revision cycles. This revision aims to make the adjustment to the data from a waterflow test required instead of recommended. If the adjustment is not required, contractors that do the right thing and adjust the data from tests are at a disadvantage from contractors that don't make any adjustment. It is fundamentally wrong to not make an adjustment to the data due to daily and seasonal fluctuations.

of 27 9/2/2014 9:27 AM This makes makes a simple and easy to understand adjustment that is standardized so that there is no argument over what is supposed to happen. It is the intent to have this be the only adjustment. If the water utility has already performed the adjustment, or if the AHJ has already mandated a safety margin or safety factor to the waterflow data obtained from the test, this adjustment would not apply.

NFSA Comment to NFPA 13 on Waterflow Test Adjustments 1) Delete A.5.1.2 A.5.1.2 An adjustment to the waterflow test data to account for the following should be made, as appropriate: (1) Daily and seasonal fluctuations (2) Possible interruption by flood or ice conditions (3) Large simultaneous industrial use (4) Future demand on the water supply system (5) Other conditions that could affect the water supply 2) Insert a new 5.1.3 and annex notes as follows: 5.1.3* Where a waterflow test was conducted, the volume and pressure available for use for a fire protection system shall be determined from the following formula: 1.85 Q 1 2 P Q 1 ( P P ) 2 P = + 5.1.3.1 The pressure P shall be what is considered available from the water supply to use for a fire protection system that will be calculated for a given flow demand of Q. 5.1.3.2 The flow Q shall be demand flow of the fire protection system that will be used to calculate the available pressure from the water supply (P). 5.1.3.3* The variable P 1 shall be the residual pressure measured during the waterflow test while the flow Q 1 was discharging from the water supply reduced by the specifying engineer or the water utility for daily and seasonal fluctuations. The reduction shall not be based on 100 year droughts or other extreme conditions. 5.1.3.4* The variable P 2 shall be the static pressure measured during the waterflow test reduced by the specifying engineer or the water utility for daily and seasonal fluctuations. The reduction shall not be based on 100 year droughts or other extreme conditions. 5.1.3.5 The variable Q 1 shall be the flow associated with P 1. 5.1.3.6* Where the specifying engineer or the water utility does not provide the value for P 1 and P 2, see 5.1.3.7. 5.1.3.7* Where a waterflow test has been conducted and the specifying engineer or the water authority does not provide a value for P 1 and P 2, the value of for P 1 and P 2 shall be calculated by

taking the static pressure and residual pressure results from the flow test and reducing them by 5%. A.5.1.3 Consider the following example. A waterflow test is conducted at a location where a city water main is going to be tapped for a new sprinkler system. During the test, the static pressure is measured at 70 psi, the residual pressure is measured at 50 psi while 1300 gpm was discharging from a nearby hydrant. The water utility is contacted and they indicate that a reasonable low static pressure accounting for typical daily and seasonal fluctuations in this area is 55 psi and that a reasonable low residual pressure accounting for typical daily and seasonal fluctuations in this area at a flow of 1300 gpm is 35 psi. The equation that describes the water supply available for a fire sprinkler system would be: P = Q 1300 1.85 ( 35 55) + 55 There are two ways to use this formula. One would be to assume two different values for Q, calculate P and then draw a graph on log 1.85 paper. Any fire sprinkler system demand falling on or below the line on this graph would be acceptable in accordance with NFPA 13 to work with this water supply. In this case, the two easiest flows to pick for Q would be 0 and 1300 gpm. When Q = 0, P is simply 55 psi. When Q = 1300 gpm, P = 35 psi. These two points can be plotted on log 1.85 paper as shown in Figure A.5.1.3. The second way to use this formula would be to calculate the fire protection system and determine the flow necessary to make the system work. Plug this flow into the formula above and see what the available pressure from the water supply will be at that flow. For example, if a sprinkler system connected to this water supply had a demand of 580 gpm, the available pressure from the water supply would be: P = 580 1300 1.85 ( 35 55) + 55 P = (-20)(0.225) + 55 P = 50.5 psi So, as long as the sprinkler system has a pressure demand less than or equal to 50.5 psi, it will work with this water supply.

Figure A.5.1.3 Available Water Supply Curve for Example in Section A.5.1.3 A.5.1.3.3 The purpose of the adjustment required by this section is to take into account reasonable fluctuations that occur on a daily and seasonal basis, but not to burden the building owner with extreme conditions. During an extreme condition such as a water main break or a severe drought, the impaired system provisions of NFPA 25 can be employed to mitigate the circumstances of the extreme condition. The intent of this section is to apply the adjustment to the raw data obtained by the flow test and not to apply adjustments to values that have already been adjusted by water utilities. If a water utility has already provided flow and pressure data for use in the design of fire protection systems that already includes adjustments for daily and seasonal water usage, there is no need to make any additional adjustments to this data. A.5.1.3.4 See annex note A.5.1.3.3. A.5.1.3.6 Water utilities are the entities that know their own supplies the best and know what appropriate adjustments need to be made to flow test data to provide reasonable fire protection. In the potential situation where the water utility will not make a definitive statement with regard to an adjustment, the fire protection engineer is the person that would need to make a statement with respect to adjustments to the raw data from a flow test. Due to the judgment involved in making such a decision, the licensing laws in most states within the United States would require the fire protection engineer to make this determination rather than the fire protection system contractor. It is expected that the engineer would make these statements in the specifications provided to the fire protection system contractor. In the absence of any information from any authority on the subject, section 24.2.2.2.2 provides a standardized method of making a decision. A.5.1.3.7 This section provides a standardized method of making a decision regarding the reduction of the results from a waterflow test to determine what pressure and flow are available from a water supply when the specifying engineer and the water utility have not provided adjustment information. An example of how to use this standardized method follows.

If a waterflow test is conducted at a location where a city water main is going to be tapped for a new sprinkler system and the static pressure is measured at 70 psi, with the residual pressure measured at 50 psi while 1300 gpm was discharging from a nearby hydrant. If there is no information from the specifying engineer or water utility regarding appropriate adjustments, the value of the static pressure and residual pressure need to be reduced by 5%. The static pressure would be adjusted from 70 psi to 66.5 psi (70 x 0.95 = 66.5). The residual pressure at 1300 gpm would be reduced from 50 psi to 47.5 psi (70 x 0.95 = 47.5). The results would be plotted on log 1.85 graph paper as shown in the lower curve on Figure A.5.1.3.7 and that curve would represent what the fire protection system contractor could use for a fire protection system. Figure A.5.1.3.7 Available Water Supply Curve for Example in Section A.5.1.3.7

0 of 27 9/2/2014 9:27 AM Public Comment No. 3-NFPA 24-2014 [ Section No. 5.2.1 ] 5.2.1 Private Fire Service Mains. Hydraulic calculations shall show that the main is able to supply the total demand at the appropriate pressure for systems with multiple hydrants. Statement of Problem and Substantiation for Public Comment The current wording appears to infer that pressures and flow are not material for single fire hydrant installations. A 6" line may be completely insufficient to supply a single hydrant at the end of a long dead end with a high fire flow condition. The PC removes the multiple hydrant constraint. Related Item First Revision No. 15-NFPA 24-2013 [Chapter 5] Submitter Information Verification Submitter Full Name: Anthony Apfelbeck Organization: Altamonte Springs Building/Fire Safety Division Street Address: City: State: Zip: Submittal Date: Thu Feb 20 21:04:49 EST 2014 Committee Statement Committee Accepted Action: Resolution: SR-16-NFPA 24-2014 Statement: The current wording appears to infer that pressures and flow are not material for single fire hydrant installations. A 6" line may be completely insufficient to supply a single hydrant at the end of a long dead end with a high fire flow condition. The PC removes the multiple hydrant constraint.

1 of 27 9/2/2014 9:27 AM Public Comment No. 6-NFPA 24-2014 [ Section No. 5.3.2 ] 5.3.2 Where meters are required they shall be listed for fire protection. Statement of Problem and Substantiation for Public Comment It is important to indicate the listing needs to be for fire protection. Related Item First Revision No. 15-NFPA 24-2013 [Chapter 5] Submitter Information Verification Submitter Full Name: Peter Schwab Organization: Wayne Automatic Fire Sprinkler Street Address: City: State: Zip: Submittal Date: Fri Apr 18 16:06:56 EDT 2014 Committee Statement Committee Accepted Action: Resolution: SR-6-NFPA 24-2014 Statement: It is important to indicate the listing needs to be for fire protection. The word "service" was added to the proposed language in PC-6 for consistency with the remainder of the standard.

2 of 27 9/2/2014 9:27 AM Public Comment No. 13-NFPA 24-2014 [ Section No. 5.9.2.4 ] 5.9.2.4 Non-threaded couplings shall be permitted where required by the AHJ. 5.9.2.4.1 Non-threaded couplings shall be listed for use as permitted in 5. 9.2.4. Additional Proposed Changes File Name LGK_NFPA_24-2013_Comment_5-9-2-4.pdf Description Approved PC Form Statement of Problem and Substantiation for Public Comment Editorial. The two separate provisions should be written in two separate sections. Additionally, as written in the First Draft Report, the second sentence of Section 5.9.2.4 is referring to its own section number. Related Item First Revision No. 15-NFPA 24-2013 [Chapter 5] Submitter Information Verification Submitter Full Name: Larry Keeping Organization: Professional Loss Control Street Address: City: State: Zip: Submittal Date: Thu Apr 24 13:50:51 EDT 2014 Committee Statement Committee Rejected but see related SR Action: Resolution: SR-7-NFPA 24-2014 Statement: The two separate provisions should be written in two separate sections. Additionally, as written in the First Draft Report, the second sentence of Section 5.9.2.4 is referring to its own section number.

3 of 27 9/2/2014 9:27 AM Public Comment No. 7-NFPA 24-2014 [ Section No. 5.9.2.4 ] 5.9.2.4 Non-threaded couplings shall be permitted where required by the AHJ. 5.9.2.4.1 Non-threaded couplings shall be listed for use as permitted in 5.9.2.4. Statement of Problem and Substantiation for Public Comment Manual of Style Related Item First Revision No. 15-NFPA 24-2013 [Chapter 5] Submitter Information Verification Submitter Full Name: Peter Schwab Organization: Wayne Automatic Fire Sprinkler Street Address: City: State: Zip: Submittal Date: Fri Apr 18 16:10:00 EDT 2014 Committee Statement Committee Rejected but see related SR Action: Resolution: SR-7-NFPA 24-2014 Statement: The two separate provisions should be written in two separate sections. Additionally, as written in the First Draft Report, the second sentence of Section 5.9.2.4 is referring to its own section number.

4 of 27 9/2/2014 9:27 AM Public Comment No. 14-NFPA 24-2014 [ Sections 5.9.4.2, 5.9.4.3, 5.9.4.4 ] Sections 5.9.4.2, 5.9.4.3, 5.9.4.4 5.9.4.2 The automatic drain valve shall be installed in a location that permits inspection and testing as required by NFPA 25 and reduces the likelihood of freezing. 5.9.4. 2.1 The automatic drip shall be permitted to be buried where permitted by the AHJ. 5.9.4.2.2 Where the automatic drip is buried as allowed by 5.9.4.2.1, the outlet shall discharge into a bed of crushed stone or pea gravel. 5.9.4. 3 An automatic drain valve is permitted to be omitted from areas where the piping is not subject to freezing. 5.9.4.4 The automatic drip shall be permitted to be buried where permitted by the AHJ. Additional Proposed Changes File Name LGK_NFPA_24-2013_Comment_5-9-4-2.pdf Description Approved PC Form Statement of Problem and Substantiation for Public Comment Neither PI No. 19 nor PI No.45 requested the text for 5.9.4.4. It appears to be a typographic error and it is redundant to the text proposed for 5.9.4.2.1, so it should be deleted. Regarding 5.9.4.2.1 and 5.9.4.2.2, this proposed text that would allow an automatic drain (ball drip) to be buried is contrary to the leading requirement 5.9.4.2 to make it accessible, as required by NFPA 25. If it is buried, it cannot be accessed. There is no reason to bury an automatic drain. Its function is to catch leakage from the Fire Department Connection s check valve if subject to freezing. Since NFPA 13 in Section 8.17.2.5.1 requires that the check valve must be installed in an accessible location, it cannot be buried. As per NFPA 13, A.8.16.1.1.3 check valves should be made accessible accessible for maintenance. This can be accomplished by a valve pit or any means that renders the valve accessible. Therefore, there is no reason to allow the corresponding ball drip to be buried. Further a ball drip is not required unless the FDC piping is subject to freezing, and buried FDC piping would not be subject to freezing unless it was buried at too shallow a depth. So again, there is no reason to bury the automatic drain/ball drip. Thus, 5.9.4.2.1 and 5.9.4.2.2 should also be deleted. Related Item Public Input No. 18-NFPA 24-2012 [New Section after 5.9.4.2] Public Input No. 19-NFPA 24-2012 [Section No. 5.9.4.3] Public Input No. 45-NFPA 24-2013 [Section No. 5.9.4.3] Submitter Information Verification Submitter Full Name: Larry Keeping Organization: Professional Loss Control Street Address: City: State: Zip: Submittal Date: Thu Apr 24 13:53:03 EDT 2014 Committee Statement Committee Rejected Action: Resolution: Many AHJ's require that fire department connections (FDC) are remote. NFPA suggests that the check valve for the FDC be located as close to the connection to the system as possible. This could leave long sections of underground piping with no pressure. This piping could get cut and one will not know about it until an NFPA 25 inspection is performed or the fire department pumps into the connection. Many AHJ's want water brought as close to the FDC as possible to avoid this situation. By requiring access to the ball drip, this could require a vault or deep meter box costing hundreds of dollars. This new section gives the AHJ an allowance to require the automatic drip close to the FDC and still have water on the underground piping for supervision. 5.9.5.4 Almost all the fire department connection plates indicating the connection type (autosprinkler, standpipe or both) are bought directly from the fire department connection manufacturers. Engraving these with the required inlet pressure is impractical. Also, since the sign referred to requires one inch high letters, it could be construed that the pressure information should also be the same size. In the fire sprinkler business, when a higher pressure requirement must be posted, we have custom made signs produced and placed on or at the FDC.

5 of 27 9/2/2014 9:27 AM Public Comment No. 8-NFPA 24-2014 [ Section No. 5.9.4.4 ] 5.9.4.4 The automatic drip shall be permitted to be buried where permitted by the AHJ. Statement of Problem and Substantiation for Public Comment This language is already in Section 5.9.4.2.1 Related Item First Revision No. 15-NFPA 24-2013 [Chapter 5] Submitter Information Verification Submitter Full Name: Peter Schwab Organization: Wayne Automatic Fire Sprinkler Street Address: City: State: Zip: Submittal Date: Fri Apr 18 16:13:09 EDT 2014 Committee Statement Committee Action: Rejected but see related SR Resolution: SR-4-NFPA 24-2014 Statement: This language is being deleted because it is already in Section 5.9.4.2.1.

6 of 27 9/2/2014 9:27 AM Public Comment No. 9-NFPA 24-2014 [ Section No. 6.2.1 ] 6.2.1 A valve in accordance with Section 6.1shall be installed in each pipeline from each water supply. 6.2.1.1 Control valves shall not be installed in the piping from the fire department connection to the point it connects to the fire service main. 6.2.1.2 Control valves shall be permitted in the system piping downstream of the fire department connection. Statement of Problem and Substantiation for Public Comment Modified the wording to indicate that the valve downstream of the FDC can only be in system piping. Related Item Public Input No. 88-NFPA 24-2013 [Section No. 6.2.2] Submitter Information Verification Submitter Full Name: Peter Schwab Organization: Wayne Automatic Fire Sprinkler Street Address: City: State: Zip: Submittal Date: Fri Apr 18 16:19:36 EDT 2014 Committee Statement Committee Action: Accepted Resolution: SR-8-NFPA 24-2014 Statement: Modified the wording to indicate that the valve downstream of the FDC can only be in system piping.

7 of 27 9/2/2014 9:27 AM Public Comment No. 2-NFPA 24-2014 [ Section No. 10.1.1.1 ]

8 of 27 9/2/2014 9:27 AM 10.1.1.1 Listing.

9 of 27 9/2/2014 9:27 AM Piping manufactured in accordance with Table 10.1.1.1 shall be permitted to be used.. Table 10.1.1.1 Manufacturing Standards for Underground Pipe Materials and Dimensions Ductile Iron Cement Mortar Lining for Ductile Iron Pipe and Fittings for Water Polyethylene Encasement for Ductile Iron Pipe Systems Rubber-Gasket Joints for Ductile Iron Pressure Pipe and Fittings Flanged Ductile Iron Pipe with Ductile Iron or Gray Iron Threaded Flanges Thickness Design of Ductile Iron Pipe Ductile Iron Pipe, Centrifugally Cast for Water Standard for the Installation of Ductile Iron Water Mains and Their Appurtenances Steel Steel Water Pipe 6 in. and Larger Coal-Tar Protective Coatings and Linings for Steel Water Pipelines Enamel and Tape Hot Applied Cement-Mortar Protective Lining and Coating for Steel Water Pipe 4 in. and Larger Shop Applied Field Welding of Steel Water Pipe Steel Pipe Flanges for Waterworks Service Sizes 4 in. Through 144 in. Dimensions for Fabricated Steel Water Pipe Fittings A Guide for Steel Pipe Design and Installation Concrete Reinforced Concrete Pressure Pipe, Steel-Cylinder Type Prestressed Concrete Pressure Pipe, Steel-Cylinder Type Reinforced Concrete Pressure Pipe, Non-Cylinder Type Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, Pretensioned Standard for Asbestos-Cement Distribution Pipe, 4 in. Through 16 in., for Water Distribution Systems Cement-Mortar Lining of Water Pipe Lines 4 in. and Larger in Place Plastic Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in., for Water Distribution Polyvinyl Chloride (PVC) Pressure Pipe, 14 in. Through 48 in., for Water Distribution Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through 63 in. (1575 mm) for Water Distribution Molecularly Oriented Polyvinyl Chloride (PVCO) 4 in. Through 12 in. (100 mm Through 600 mm) for Water Distribution Brass Specification for Seamless Red Brass Pipe Standard C104 C105 C111 C115 C150 C151 C600 C200 C203 C205 C206 C207 C208 M11 C300 C301 C302 C303 C400 C602 C900 C905 C906 C909 ASTM B 43 Copper

0 of 27 9/2/2014 9:27 AM Materials and Dimensions Specification for Seamless Copper Tube Specification for Seamless Copper Water Tube Requirements for Wrought Seamless Copper and Copper-Alloy Tube Standard ASTM B 75 ASTM B 88 ASTM B 251 Statement of Problem and Substantiation for Public Comment Same change is proposed for NFPA 13-2014. See Public Comment No. 222-NFPA 13-2014 Reference is made to First Revision No. 19-NFPA 24-2013 [Chapter 10]. First Revision No. 19-NFPA 24-2013 [Chapter 10] says that to select pipe for underground service there is the ability to use the Table 10.1.1.1 (former Table 10.1.1), the ability to use pipe specifically listed for underground use, and the allowance to use steel pipe between the FDC (Fire Department Connection) and the check valve. This statement is according NFPA 24-2013. Also the First Revision No. 19-NFPA 24-2013 [Chapter 10] says that the steel piping references were removed from the Table 10.1.1.1 since steel pipe is required to be listed except for the FDC line. This statement is not according NFPA 24-2013. According to NFPA 24-2013: - Steel pipe is not required to be listed except for general underground service. - Steel pipe is required to be listed except for the FDC line and except for not general underground service. According to NFPA 24-2013, not listed steel can be used for an underground pipe main, when that pipe main is used only for fire service. The paragraph 10.1.2 of NFPA 24-2013 says: Steel piping shall not be used for general underground service unless specifically listed for such service. A general service refers to a pipe main that it is used for fire service and also for purposes other than fire service. Not general service refers to a pipe main that it is used only for fire service and it is not used for other purposes. Steel piping can be used for general underground service if it is listed. If it is not listed, it can not be used for general underground service. If the service of the pipe main is not general, if it is for fire service only (e.g. it is not used for purposes other than fire service), then steel can be used. For fire service only: - if steel is listed, the proper condition of listing provides the ability to use it. - if steel is not listed, steel can be used (again: for fire service only) because its inclusion in the Table 10.1.1.1 provides the ability to use it. If steel is removed from the Table 10.1.1.1, the ability to use not listed steel for fire service only, also is removed. Removing steel from Table 10.1.1.1 implies that steel pipe will be required to be listed in order to be used for underground fire service. This is not a current requirement of NFPA 24-2013. Removing steel from Table 10.1.1.1 implies a change to the NFPA 24-2013. Currently there is the ability to use not listed steel for underground fire service only, but as a consequence of the proposal shown in First Revision No. 19-NFPA 24-2013 [Chapter 10], there will not be anymore the ability to use not listed steel for underground fire service. This is a change to the NFPA 24-2013. The statement included in the First Revision No. 19-NFPA 24-2013 [Chapter 10] : The steel piping references were removed from the table since steel pipe is required to be listed other than in the FDC line, is not according NFPA 24-2013. As NFPA 24-2013 Annotated explains: Accordingly, steel pipe can no longer be installed for general underground service, unless it is specially listed for the purpose. (bold letters included on purpose). NFPA 24-2013 Annotated also says: At this time, no such listings are available. This is also true today. UL and FM does not have steel pipe listed for underground use. There is no expectation that UL and/or FM will list the steel for underground use in the future. To live the ability to use steel for underground use, only if it is listed, introduces a constraint that it will be very difficult or impossible to surmount, and practically converts the steel for underground use in something unreal. To keep questioned the steel for underground use brings the existent firewater piping underground installations into question as well as other pipe underground installations that are made of steel. It is requested to keep the steel in the Table 10.1.1.1 in order to prevent doing a change whose current substantiation cause and effect that it is seems to not be foreseen in the First Revision No. 19-NFPA 24-2013 [Chapter 10]: steel pipe will not be able to be installed anymore for any underground service. Related Public Comments for This Document Related Comment Public Comment No. 16-NFPA 24-2014 [Section No. 2.3.3] Related Item First Revision No. 19-NFPA 24-2013 [Chapter 10] Relationship Submitter Information Verification

1 of 27 9/2/2014 9:27 AM Submitter Full Name: Ariel Carp Organization: On my behalf Affilliation: On my behalf Street Address: City: State: Zip: Submittal Date: Wed Feb 19 16:51:47 EST 2014 Committee Statement Committee Action: Resolution: Rejected The document has required steel piping for general underground service to be listed for the last few editions. If steel piping is to be used, the manufacturers installations instructions would need to be followed. Including the proposed data in the table does not add any value since the installation guidelines will cover all essential installation practices. Table 10.1.1.3 sufficiently addresses the allowance for the steel piping to be used in the fire department connection piping.

2 of 27 9/2/2014 9:27 AM Public Comment No. 10-NFPA 24-2014 [ Section No. 10.2.1.3 ] 10.2.1.3 Approved fittings shall be permitted to be used. Statement of Problem and Substantiation for Public Comment There are available fittings on the market that are listed or are in accordance with Table 10.2.1.1. This section allows practically anything as long as it is approved. Related Item Public Input No. 39-NFPA 24-2012 [Section No. 10.2] Submitter Information Verification Submitter Full Name: Peter Schwab Organization: Wayne Automatic Fire Sprinkler Street Address: City: State: Zip: Submittal Date: Fri Apr 18 16:38:45 EDT 2014 Committee Statement Committee Accepted Action: Resolution: SR-9-NFPA 24-2014 Statement: There are available fittings on the market that are listed or are in accordance with Table 10.2.1.1. This section allows practically anything as long as it is approved.

3 of 27 9/2/2014 9:27 AM Public Comment No. 11-NFPA 24-2014 [ Section No. 10.4.2.1.7.1 ] 10.4.2.1.7.1 Heat tracing not listed for underground use shall be permitted when piping is installed in accordance with 10.1. 4.2.2.5. Statement of Problem and Substantiation for Public Comment I believe this is the correct section to reference. Related Item First Revision No. 19-NFPA 24-2013 [Chapter 10] Submitter Information Verification Submitter Full Name: Peter Schwab Organization: Wayne Automatic Fire Sprinkler Street Address: City: State: Zip: Submittal Date: Fri Apr 18 16:44:48 EDT 2014 Committee Statement Committee Action: Accepted Resolution: SR-10-NFPA 24-2014 Statement: I believe this is the correct section to reference.

4 of 27 9/2/2014 9:27 AM Public Comment No. 12-NFPA 24-2014 [ Section No. 10.5.1.1 ] 10.5.1.1 * The requirement of 10 of 10.6 5.8 1 shall not preclude the bonding of the underground piping to the lightning protection grounding system as required by NFPA 780 in those cases where lightning protection is provided for the structure. Additional Proposed Changes File Name LGK_NFPA_24-2013_Comment_10-5-1-1.pdf Description Approved PC Form Statement of Problem and Substantiation for Public Comment Editorial correction. The reference was not revised during the Chapter 10 rewrite. Related Item First Revision No. 19-NFPA 24-2013 [Chapter 10] Submitter Information Verification Submitter Full Name: Larry Keeping Organization: Professional Loss Control Street Address: City: State: Zip: Submittal Date: Thu Apr 24 13:48:46 EDT 2014 Committee Statement Committee Action: Accepted Resolution: SR-11-NFPA 24-2014 Statement: Editorial correction. The reference was not revised during the Chapter 10 rewrite.

5 of 27 9/2/2014 9:27 AM Public Comment No. 19-NFPA 24-2014 [ New Section after A.5.1.2 ] A.5.1.3 Consider the following example. A waterflow test is conducted at a location where a city water main is going to be tapped for a new sprinkler system. During the test, the static pressure is measured at 70 psi, the residual pressure is measured at 50 psi while 1300 gpm was discharging from a nearby hydrant. The water utility is contacted and they indicate that a reasonable low static pressure accounting for typical daily and seasonal fluctuations in this area is 55 psi and that a reasonable low residual pressure accounting for typical daily and seasonal fluctuations in this area at a flow of 1300 gpm is 35 psi. The equation that describes the water supply available for a fire sprinkler system would be: There are two ways to use this formula. One would be to assume two different values for Q, calculate P and then draw a graph on log 1.85 paper. Any fire sprinkler system demand falling on or below the line on this graph would be acceptable in accordance with NFPA 13 to work with this water supply. In this case, the two easiest flows to pick for Q would be 0 and 1300 gpm. When Q = 0, P is simply 55 psi. When Q = 1300 gpm, P = 35 psi. These two points can be plotted on log 1.85 paper as shown in Figure A.5.1.3. The second way to use this formula would be to calculate the fire protection system and determine the flow necessary to make the system work. Plug this flow into the formula above and see what the available pressure from the water supply will be at that flow. For example, if a sprinkler system connected to this water supply had a demand of 580 gpm, the available pressure from the water supply would be: P = (-20)(0.225) 55 P = 50.5 psi So, as long as the sprinkler system has a pressure demand less than or equal to 50.5 psi, it will work with this water supply. Figure A.5.1.3 Available Water Supply Curve for Example in Section A.5.1.3 A.5.1.3.3 The purpose of the adjustment required by this section is to take into account reasonable fluctuations that occur on a daily and seasonal basis, but not to burden the building owner with extreme conditions. During an extreme condition such as a water main break or a severe drought, the impaired system provisions of NFPA 25 can be employed to mitigate the circumstances of the extreme condition. The intent of this section is to apply the adjustment to the raw data obtained by the flow test and not to apply adjustments to values that have already been adjusted by water utilities. If a water utility has already provided flow and pressure data for use in the design of fire protection systems that already includes adjustments for daily and seasonal water usage, there is no need to make any additional adjustments to this data. A.5.1.3.4 See annex note A.5.1.3.3. A.5.1.3.6 Water utilities are the entities that know their own supplies the best and know what appropriate adjustments need to be made to flow test data to provide reasonable fire protection. In the potential situation where the water utility will not make a definitive statement with regard to an adjustment, the fire protection engineer is the person that would need to make a statement with respect to adjustments to the raw data from a flow test. Due to the judgment involved in making such a decision, the licensing laws in most states within the United States would require the fire protection engineer to make this determination rather than the fire protection system contractor. It is expected that the engineer would make these statements in the specifications provided to the fire protection system contractor. In the absence of any information from any authority on the subject, section 24.2.2.2.2 provides a standardized method of making a decision. A.5.1.3.7 This section provides a standardized method of making a decision regarding the reduction of the results from a waterflow test to determine what pressure and flow are available from a water supply when the specifying engineer and the water utility have not provided adjustment information. An example of how to use this standardized method follows. If a waterflow test is conducted at a location where a city water main is going to be tapped for a new sprinkler system and the static pressure is measured at 70 psi, with the residual pressure measured at 50 psi while 1300 gpm was discharging from a nearby hydrant. If there is no information from the specifying engineer or water utility regarding appropriate adjustments, the value of the static pressure and residual pressure need to be reduced by 5%. The static pressure would be adjusted from 70 psi to 66.5 psi (70 x 0.95 = 66.5). The residual pressure at 1300 gpm would be reduced from 50 psi to 47.5 psi (70 x 0.95 = 47.5). The results would be plotted on log 1.85 graph paper as shown in the lower curve on Figure A.5.1.3.7 and that curve would represent what the fire protection system contractor could use for a fire protection system. Figure A.5.1.3.7 Available Water Supply Curve for Example in Section A.5.1.3.7 Additional Proposed Changes File Name Description Approved Water_Supply_Adjustment_Proposal-E_S-24.pdf Whole comment with equations and figures

6 of 27 9/2/2014 9:27 AM Statement of Problem and Substantiation for Public Comment This is one of a series of proposals to make the adjustment to the data from a waterflow test required instead of recommended. If the adjustment is not required, contractors that do the right thing and adjust the data from tests are at a disadvantage from contractors that don't make any adjustment. It is fundamentally wrong to not make an adjustment to the data due to daily and seasonal fluctuations. This proposal makes a simple and easy to understand adjustment that is standardized so that there is no argument over what is supposed to happen. It is the intent to have this be the only adjustment. If the water utility has already performed the adjustment, or if the AHJ has already mandated a safety margin or safety factor to the waterflow data obtained from the test, this adjustment would not apply. Related Item Public Input No. 56-NFPA 24-2013 [New Section after 5.1.2] Committee Input No. 2-NFPA 24-2013 [New Section after 5.1.2] Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: NFSA E&S Committee Street Address: City: State: Zip: Submittal Date: Thu May 08 18:15:01 EDT 2014 Committee Statement Committee Rejected but see related SR Action: Resolution: SR-17-NFPA 24-2014 Statement: The NFPA 13 technical committees have been discussing the need for adjusting waterflow data for several revision cycles. This revision aims to make the adjustment to the data from a waterflow test required instead of recommended. If the adjustment is not required, contractors that do the right thing and adjust the data from tests are at a disadvantage from contractors that don't make any adjustment. It is fundamentally wrong to not make an adjustment to the data due to daily and seasonal fluctuations. This makes makes a simple and easy to understand adjustment that is standardized so that there is no argument over what is supposed to happen. It is the intent to have this be the only adjustment. If the water utility has already performed the adjustment, or if the AHJ has already mandated a safety margin or safety factor to the waterflow data obtained from the test, this adjustment would not apply.