VRF SYSTEM INDOOR UNIT ENTERING AIR TEMPERATURES ( F) CAPACITIES (kbtuh) Max SOUND ELECTRICAL WEIGHT TOSHIBA-CARRIER COOLING HEATING Airflow PRESSURE, MARK NO. TYPE ROOM TOTAL SENSIBLE HEATING V / Ø / HZ RLA MOCP (LB) MODEL DB WB WB (CFM) LOW (db) REMARKS FCU-6 MMU-AP0362H2UL 4-Way Cassette Zone 6 74.2 62.2 73.4 31.71 23.87 14.10 1160 37 208/1/60 1.0 15 59 1, 2, 3, 4, 5, 7, 8 VRF-1 FCU-7 MMU-AP0302H2UL 4-Way Cassette Zone 7 74.1 62.2 73.2 24.06 17.48 9.80 730 34 208/1/60 0.8 15 48 1, 2, 3, 4, 5, 7, 8 FCU-8 MMU-AP0242H2UL 4-Way Cassette Zone 8 73.9 62.1 70.0 20.11 13.52 2.91 670 31 208/1/60 0.8 15 48 1, 2, 3, 4, 5, 7, 8 FCU-9 MMU-AP0121MH2UL Compact 4-Way Cassette Zone 9 73.9 62.2 70.0 9.91 7.09 1.64 330 32 208/1/60 0.4 15 35 1, 2, 3, 4, 5, 7, 8 FCU-10 MMD-AP0094BH2UL Medium Static Ducted Zone 10 73.9 62.2 70.0 7.09 5.40 1.18 312 28 208/1/60 0.8 15 64 1, 2, 3, 4, 5, 7, 8, 10 VRF-2 FCU-11 MMD-AP0184BH2UL Medium Static Ducted Zone 11 74.1 62.2 70.6 15.15 12.00 3.08 635 29 208/1/60 0.9 15 93 1, 2, 3, 4, 5, 7, 8, 10 FCU-12 MMD-AP0184BH2UL Medium Static Ducted Zone 12 73.9 62.2 70.0 14.78 10.39 2.36 635 29 208/1/60 0.9 15 93 1, 2, 3, 4, 5, 7, 8, 10 FCU-13 MMU-AP0181MH2UL Compact 4-Way Cassette Zone 13 73.9 62.2 70.0 15.95 11.24 2.56 450 36 208/1/60 0.5 15 35 1, 2, 3, 4, 5, 7, 8 FCU-14 MMD-AP0724H2UL High Static Ducted Zone 14 74.8 62.4 74.7 49.57 45.86 34.73 2470 47 208/1/60 7.1 15 353 1, 2, 3, 4, 5, 7, 8, 10 FCU-15 MMU-AP0212H2UL 4-Way Cassette Zone 15 74.6 62.4 74.5 15.43 15.39 14.63 670 31 208/1/60 0.8 15 48 1, 2, 3, 4, 5, 7, 8 VRF-3 FCU-16 MMU-AP0181MH2UL Compact 4-Way Cassette Zone 16 74.1 62.2 73.5 16.40 11.70 8.38 450 36 208/1/60 0.5 15 35 1, 2, 3, 4, 5, 7, 8 FCU-17 MMU-AP0182H2UL 4-Way Cassette Zone 17 74.1 62.2 73.6 16.94 12.24 8.91 550 31 208/1/60 0.6 15 46 1, 2, 3, 4, 5, 7, 8 FCU-18 MMD-AP0364BH2UL Medium Static Ducted Zone 18 74.3 62.3 74.2 28.40 23.36 21.67 1088 35 208/1/60 1.8 15 119 1, 2, 3, 4, 5, 7, 8, 10 FCU-19 MMU-AP0212H2UL 4-Way Cassette Zone 19 74.9 62.5 70.5 14.64 14.02 0.58 670 31 208/1/60 0.8 15 48 1, 2, 3, 4, 5, 7, 8 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. PROVIDE VRF DIRECT-EXPANSION INDOOR UNIT WITH DC INVERTER DRIVEN FAN MOTOR, PIPING CONNECTORS, PULSE MODULATING VALVE (METERING DEVICE), INTEGRAL LEAVING/RETURN TEMPERATURE SENSORS, AND HANGING BRACKETS. UNIT SHALL BE PROVIDED WITH FACTORY INSTALLED RETURN AIR TEMPERATURE SENSOR. PROVIDE INTERNAL CONTROL SYSTEM WHICH EMPLOYS AN ALGORITHM FOR TEMPERATURE CONTROL TO AN ACCURACY OF 0.9 F. PROVIDE METERING DEVICE THAT SHUTS OFF COMPLETELY WHEN THE ZONE IS SATISFIED. PROVIDE WIRED ZONE CONTROLLER RBC-AMS51E-ES. PROVIDE WIRED REMOTE SENSOR TCB-TC21LUL. PROVIDE CONDENSATE LIFT AND OVERFLOW SAFETY SWITCH. PROVIDE FACTORY SUPPLIED BRANCHING KITS CONSISTING OF EITHER Y JOINTS AND/OR HEADERS TO ENSURE EVEN REFRIGERANT FLOW. INSULATE UNITS WITH 1" RUBATEX SHEET USING AN ADHESIVE. KEEP ALL UNITS SCREWS ACCESSIBLE FOR UNIT MAINTENCE. PROVIDE AUXILLARY DRAIN PAN UNDER UNIT AND FLOAT SWITCH. DRAIN PAN SHOULD BE A MINIMUM OF 3" LARGER THAN UNIT ON ALL SIDES. TOSHIBA-CARRIER VRF HEAT PUMP - OUTDOOR EQUIPMENT SCHEDULE MARK OUTDOOR UNIT CAPACITY QUANTITY MIN # OF NOMINAL COOLING NOMINAL HEATING ELECTRICAL POSITION SYSTEM NAME MODEL MANUFACTURER RANK OUTDOOR INDOOR IEER COMPRESSORS CAPACITY (BTUH) CAPACITY (BTUH) V / Ø / Hz RLA MOCP WEIGHT (LB) REMARKS VRF-1 VRF Condensing Unit 1 MMY-AP0724HT6UL TOSHIBA-CARRIER 6 TON 1 3 11.2 2 72,000 81,000 CENTER 460/3/60 6.7 20 621 1, 2, 3, 4, 5, 6, 7, 8, 10 VRF-2 VRF Condensing Unit 2 MMY-AP0724HT6UL TOSHIBA-CARRIER 6 TON 1 5 12.2 2 72,000 81,000 CENTER 460/3/60 6.7 20 621 1, 2, 3, 4, 5, 6, 7, 8, 10 VRF-3 VRF Condensing Unit 3 MMY-AP1684HT6UL TOSHIBA-CARRIER 14 TON 2 6 11.2 6 168,000 189,000 CENTER 460/3/60 8.8 / 6.7 25 / 20 817 / 621 1, 2, 3, 4, 5, 6, 7, 8, 10 NOTES: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. OUTDOOR TEMPERATURE COOLING/HEATING 95 F / 43 F. SCHEDULED EFFICIENCIES ARE MINIMUM REQUIRED. PROVIDE INVERTER DRIVEN TWIN ROTARY COMPRESSOR CAPABLE OF FULL RANGE OF CONTROL TO A LEVEL OF 0.1 HZ. ALL COMPRESSORS SHALL BE OF THE SAME TYPE. PROVIDE DIRECT DRIVE INVERTER DRIVEN OUTDOOR FAN MOTOR. PROVIDE 4 SIDED OUTDOOR COIL WITH FACTORY APPLIED CORROSION RESISTANT FINISH. PROVIDE FACTORY MOUNTED COMPRESSOR SOUND BLANKETS, CRANKCASE HEATERS, OVER-TEMPERATURE OPERATION PROTECTION, HIGH/LOW PRESSURE SWITCHES, AND INVERTER OVERLOAD PROTECTOR. PROVIDE FUSES, FUSIBLE PLUG, OVER CURRENT RELAY FOR COMPRESSORS, THERMAL PROTECTORS FOR COMPRESSOR AND FAN MOTOR, COMPRESSOR TIME DELAY, OIL RECOVERY SYSTEM, OIL LEVEL SENSOR, OVER-CURRENT SENSOR, COMPRESSOR SUCTION AND DISCHARGE TEMPERATURE AND PRESSURE SENSOR. PROVIDE AN OIL MANAGEMENT SYSTEM THAT BALANCES OIL BETWEEN COMPRESSORS WITHIN A MODULE, REPLENISHES OIL FROM THE OIL SEPARATOR, AND ALLOWS MOVING OIL AND REFRIGERANT BETWEEN TWINNED UNITS, EVEN IF ONE OF THE UNITS IS NOT RUNNING. PROVIDE CENTRAL WEB BROWSER CONTROL SYSTEM BMS-SM1280HTLUL. TOSHIBA-CARRIER VRF - INDOOR EQUIPMENT SCHEDULE FOR COMPLETE ACCURATE WIRING AND PIPING DIAGRAM, ENGINEERING SUPPORT, AND SALES ASSISTANCE CONTACT TOSHIBA-CARRIER, CHRIS SMELLEY, AT 713-939-6001. 1A 1B 1C 1D 2 3 4 5A 5B 5C 6A 6B 6C 7 8 9 10 11 12 13 15 16 17 18 19 20 21 22 23 R N-0 20-3 -0-E B0 9-1 6A: UAD E-U 0F-D RF- D0A -DH FAH YF - 00-0 0C0 000 AB Tag: OAU-1 5000 CFM with Wheel Job Information Job Name: Job Number: Site Altitude: Refrigerant Static Pressure External: Evaporator: Filters Clean: Dirt Allowance Re-Heat Coil Cooling Section NRG Call Center Job #1253 0 ft R-410A 1.00 in. wg. 0.25 in. wg. 0.09 in. wg. 0.35 in. wg. 0.03 in. wg. Unit Information Approx. Op./Ship Weights: Supply CFM/ESP: Final Filter FV / Qty: Exhaust CFM/ESP/TSP: Outside CFM: Ambient Temperature: Economizer: Heating: Cabinet: Heatwheel: Total: Heating Section 3544 / 3544 lbs. (±5%) 5000 / 1 in. wg. 240.00 fpm / 6 5000 / 0.25 / 1.49 in. wg. 5000 98 ºF DB / 80 ºF WB 0.11 in. wg. 0.11 in. wg. 0.05 in. wg. 0.95 in. wg. 2.93 in. wg. Equivalent Total Capacity: Gross Net 468.42 MBH 458.81 MBH PreHeat Type: Std (No Preheat) Total Capacity: Sensible Capacity: Latent Capacity: HW Total Cooling Capacity: Mixed Air Temp: Entering Air Temp: Lv Air Temp (Coil): Lv Air Temp (Unit) Digital Comp. Capacity Ratio: Supply Air Fan: SA Fan RPM / Width: Exhaust Air Fan: EA Fan RPM / Width: Evaporator Coil: Evaporator Face Velocity: Energy Recovery Wheel: Rating Information 237.51 227.90 MBH 153.77 144.16 MBH 83.74 MBH 230.91 MBH 82.41 ºF DB 69.18 ºF WB 82.41 ºF DB 69.18 ºF WB 53.39 ºF DB 53.19 ºF WB 55.15 ºF DB 53.92 ºF WB 100% 1 x 220 @ 3.38 BHP 1496 / 4.871" 1 x RM220A @ 1.99 BHP 1322 / 4.920" 19.9 ft² / 6 Rows / 12 FPI 251.7 fpm 1 x ERC-5262C Cooling Capacity (MBH): 238.0 Cooling EER: 12.3 Cooling IEER: 14.8 Rated in accordance with AHRI 340/360 Application EER @ Op. Conditions: 19.7 Electrical Data Rating: Unit FLA: 460/3/60 85 Heating Type: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Input: Heater Qty: Electric Heat FLA: Re-Heat Coil: Electric Heat 5000 204.8 MBH 27.0 ºF DB / 25.0 ºF WB 72.0 ºF DB / 60.0 ºF WB 57.5 ºF DB / 50.3 ºF WB 95.4 ºF DB / 64.7 ºF WB 60.0 kw 6 72.2 Capacity: 90 MBH LA DB / WB: 70.00 ºF / 59.68 ºF RH: 55% Minimum Circuit Amp: Maximum Overcurrent: Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 16.7 Compressor 2: 1 460 3 16.7 Condenser Fans: 2 0.75 460 3 1080 1.8 Supply Fan: 1 5.00 460 3 1760 7.6 Exhaust Fan: 1 3.00 460 3 1760 4.8 Heatwheel: 1 0.1667 460 1 1770 0.6 88 100