PS SERIES PARALLEL RACK SYSTEM START UP GUIDE

Similar documents
PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers

BMG-HGP & BMG-SLP Model Bottom Mounted Full-Length Glass Door Refrigerator Merchandisers

Installation & Operations Manual for. BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers. 4/17 Rev.

Installation & Operations Manual for R-290 SERIES. BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers 2/

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Installation & Operations Manual. Master-Bilt Products 908 Highway 15 North New Albany, MS Phone: (800) REV: LN PN

Installation & Operations Manual Master-Bilt Products 908 Highway 15 North New Albany, MS Phone: (800)

A Complete Line Of Remote Rack Refrigeration Systems

Installation & Operations Manual

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

3/15 Rev B

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Refrigeration / Air Conditioning Systems Circuit Drawings. Student Resource Package No: NR 24

Beverage Air IMPORTANT

Rev 7 06-APR MultiFlex Condensing Unit Board (CUB-II and CUB-TD) Installation and Operation Manual

Air-Cooled Condensing Units with Compact Screw Compressors

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A

Walk-In Coolers and Freezers Installation & Operations Manual

Follett Performance Plus

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE

SEA FROST BAITFREEZER 110-VOLT AIR-WATER Twin Valve

Installation and Operations Manual for HORIZONTAL DISPLAY MERCHANDISERS

Condensing Unit Installation and Operating Instructions

Installation & Operations Manual. Master-Bilt Products 908 Highway 15 North New Albany, MS Phone: (800) /17 Rev.

CHILLER. Model CH3000. Operator s & Installation Manual

Condensing Unit and Refrigeration System Installation & Operations Manual R448A/R449A

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

Liebert CSU3000 Chiller

INSTALLATION, OPERATION & MAINTENANCE MANUAL BERG TEMPERATURE CONTROL UNIT

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS for HOAM and VOAM Open Air Merchandisers

REDI CONTROLS, INC. Installation, Operation & Maintenance Manual

Condensing Unit Installation and Operating Instructions

REFRIGERATOR SAFETY. Your safety and the safety of others are very important.

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

Installation & Operations Manual Master-Bilt Products 908 Highway 15 North New Albany, MS Phone: (800)

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

OPERATING INSTRUCTIONS

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

DISHWASHER INSTALLATION GUIDE SPECIFICATIONS, INSTALLATION, AND MORE

Installation & Operations Manual for. BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers. 6/17 Rev.

KRSCP Self-Contained Walk-In Unit Installation and Service Manual Addendum

MODEL URS-1: FACTORY RETROFIT PROGRAM

INSTRUCTION MANUAL (UNIT APPEARANCE MAY VARY FROM IMAGE) BEFORE USE, PLEASE READ AND FOLLOW ALL SAFETY RULES AND OPERATING INSTRUCTIONS.

500 EX Fusion Compressor Series

SECTION 50 - CAB CLIMATE CONTROL

MODELS LIST. Nominal Capacity RT

Contour TM Screw Compressors

Rev B, 9/2/2009. Kodiak Chiller Overview

PS & GPS SERIES PARALLEL RACK REFRIGERATION SYSTEMS

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

NO: 9-16 DATE: 2/11/16 EMERSON CLIMATE TECHNOLOGIES WHOLESALERS -EXECUTIVES -PRODUCT MANAGERS -EMERSON TM TECHNICAL SPECIALISTS -BRANCH PERSONNEL

347002K/177002K/34900

HPXA19. IMPORTANT Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.

YCIV Hz & Hz

TWLC - Tempered Water Logic Controller. The Intelligent Control

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

START UP FORM PACKET

Original Instructions Instucciones originales Consignes originales. Model: AC R-1234yf A/C Recover, Recycle, Recharge Machine

All Models INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE CENTRAL CHILLER

Tri-Stack Smart System

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

Air-Cooled Condensing Units with Screw Compressors. Technical Bulletin Low Temperature Models SSV DSV

OPERATING INSTRUCTIONS

MPT Electric Fire Pump Controller

Operation and Maintenance Haskris LX-Series, R-Series, WW-Series, OPC-Series

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

Refrigerant changeover guidelines

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Warm Case Troubleshooting Guide 9/18/2014

ULTRA LOW TEMPERATURE FREEZER. User Manual

Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors

User Guide ems25plus. Page 1. Normal operation. Product interface

MT Alliance Refrigeration Technician s Manual

R.A.S.E.R.S System. Installation Guide

Commercial Water Source Heat Pump Water Heater Operations and Installation Manual

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY (Corporate Sales) 85 Middle Road

Refrigerant Recovery Unit, Model RRU134

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO

WineZone Ceiling Mount Ductless Split 15

MR3CCUHV Temperature/Defrost Control

Prodigy Eclipse Cuber Technical Training

SPB*H4 Commercial Heat Pump

START UP FORM PACKET

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

π H-6621 INDUSTRIAL DEHUMIDIFIER WARNINGS SPECIFICATIONS uline.com WATER REMOVAL ELECTRICAL REQUIREMENTS BUILT-IN ELECTRICAL SAFETY

OPER LV Wheeler Way

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

Transcription:

PS SERIES PARALLEL RACK SYSTEM START UP GUIDE 5/16 Rev. A 57-02508 1

Contents INTRODUCTION... 3 WARNING LABELS AND SAFETY INSTRUCTIONS... 4 PARALLEL RACK NOMENCLATURE... 5 GENERAL RACK DESCRIPTION... 6 TYPICAL REFRIGERATION COMPONENTS... 6 TYPICAL CONTROL/ POWER COMPONENTS... 6 CONTROL THEORY... 7 PRE-START UP... 7 START UP... 7 CPC E2E Controller... 9 STARTUP TROUBLESHOOTING... 10 REFERENCE DOCUMENTS... 12 5/16 Rev. A 57-02508 2

INTRODUCTION Thank you for purchasing Master-Bilt refrigeration equipment. This manual contains important instructions for startup, and troubleshooting. Read this entire manual carefully before starting or servicing your Master-Bilt equipment. NOTICE Installation and service of the refrigeration and electrical components must be performed by a refrigeration mechanic or licensed electrician. DANGER Equipment MUST be properly grounded. Improper or faulty hook-up of electrical components of the refrigeration units can result in severe injury or death. All electrical wiring hook-ups must be done in accordance with all applicable local, regional or national standards. NOTICE Read this manual before installing your refrigeration equipment. Keep the manual and refer to it before doing any service. Failure to do so could result in personal injury or equipment damage. The portions of this manual covering refrigeration and electrical components contain technical instructions intended only for persons qualified to perform refrigeration and electrical work. This manual cannot cover every installation, use, or service situation. If you need additional information, call or write us: Parts and Technical Service Department Master-Bilt Products 908 Highway 15 North New Albany, MS 38652 Phone (800) 684-8988 Email: service@master-bilt.com 5/16 Rev. A 57-02508 3

WARNING LABELS AND SAFETY INSTRUCTIONS This is the safety-alert symbol. When you see this symbol, be alert to the potential for personal injury or damage to your equipment. Be sure you understand all safety messages and always follow recommended precautions and safe operating practices. NOTICE TO EMPLOYERS You must make sure that everyone who installs, uses, or services your refrigeration equipment is thoroughly familiar with all safety information and procedures. Important safety information is presented in this section and throughout the manual. The following signal words are used in the warnings and safety messages: DANGER: Severe injury or death WILL occur if you ignore the message. WARNING: Severe injury or death CAN occur if you ignore the message. CAUTION: Minor injury or damage to your refrigeration can occur if you ignore the message. NOTICE: This is important installation, operation or service information. If you ignore the message, you may damage your refrigeration. The warning and safety labels shown throughout this manual are placed on your Master-Bilt Products refrigeration at the factory. Follow all warning label instructions. If any warning or safety labels become lost or damaged, call your customer service department at (800) 684-8988 for replacements. This Label is located on the condensing unit 5/16 Rev. A 57-02508 4

PARALLEL RACK NOMENCLATURE PS E A C 5 2 Z C - XXXXX Quote Number Voltage A = 115/60/1 B = 208-230/60/1 C = 208-230/60/3 D = 460/60/1 E = 460/60/3 F = 200-220/50/3 G = 380-420/50/3 H = 208/60/1 J = 380/50/1 K = 200-220/50/1 or 220/50/1 L = 575/3/60 M = 200-230/60/3 R =265/60/1 T = 380/60/3 Refrigerant Z = R404A # Suction Groups 1 to 3 # Compressors 2 to 10 Condenser Location R = Remote I = Integrated C = Mounted on Common Frame Condensing Method A = Air Cooled W = Water Cooled Frame I = Interior E = Exterior Rack PS = Standard Rack GPS = Glycol Rack 5/16 Rev. A 57-02508 5

GENERAL RACK DESCRIPTION Master-Bilt PS series parallel rack systems operate with up to ten compressors in parallel design. A typical rack system has two separate suction groups and a common discharge and liquid circuit. One suction group is for low temperature equipment with an average temperature of -23 F SST. One suction group is for medium temperature equipment with an average temperature of +23 F SST. Each rack system has one common liquid circuit and one common discharge circuit. TYPICAL REFRIGERATION COMPONENTS 2-10 Scroll or Discus compressors Individual Compressor Dual Pressure Controls Individual Compressor Oil Level Controls Oil Pressure Differential Valve Oil Line Sight Glass Oil Filter Oil Separator Air Cooled or Water Cooled Condenser Head Pressure and Hot Gas Bypass Valves Liquid Receiver with Dual Pressure Relief Valves Replaceable Core Liquid Filter/ Drier Liquid Sight Glass Replaceable Core Suction Filter (one for each group) Suction Accumulator (one for each group) TYPICAL CONTROL/ POWER COMPONENTS 220V Control Circuit Main Disconnect Switch and Circuit Breaker Power Distribution Blocks GFCI Service Receptacle (115V) CPC E2E RX Rack Controller 1 or more CPC Relay Boards 1 or more Digital Compressor Controllers (one per suction group) Individual Compressor Circuit Breakers Individual Compressor Contactors Condenser Fan Contactors Phase Monitor 230V to 24V Transformers for CPC and Oil Controls Power Receiver Liquid Level Probe Suction, Discharge, and Drop Leg Pressure Transducers Suction, Discharge, Drop Leg, and Ambient Temperature Probes Walk in Cooler/ Freezer Temperature Probes 5/16 Rev. A 57-02508 6

CONTROL THEORY The CPC E2E controller receives pressure and temperature inputs from all devices and controls outputs to maintain set points. SST for a suction group is maintained by reading the pressure input from the suction group and switching or unloading compressors to maintain a programmed pressure set point. Inputs from discharge and drop leg pressure transducers are used to turn on and off fan banks on the condenser. Temperature inputs from walk in coolers are used to open and close solenoids on evaporators to control walk in box temperatures. All set points in the system are changeable in the E2E controller. PRE-START UP Pre-charge system with as much refrigerant as the system will take up to the holding capacity of the receiver using the following specifications: A vacuum of 500 microns or less must be pulled to properly dehydrate the refrigeration system. Use only refrigerant specifically designed for the rack system. This is typically R404A. Use high side charging method only. System is shipped with initial filter/drier cores installed. Ensure adequate oil charge before starting the compressors. Use manufacturer recommended oil type. Add until oil is shown in the upper glass on the oil reservoir. Ensure all refrigeration lines are clean and purged. Never allow liquid refrigerant to reach the compressors. Damage to the compressors may occur. START UP 1. Verify all breakers and switches are in the off position. 2. Verify all loads are in refrigeration mode. 3. Turn on condenser power switch and breaker. 4. Turn on all compressor toggle switches. 5. Turn on main power switch and breaker. 6. Turn on control power breaker (2 pole 240V). All compressor contactors should engage while E2E control is booting up. If a contactor did not engage, adjust dual pressure switch and ensure switch is closed. 7. Check the phase monitor to verify that the green light is illuminated. If red, measure input power and adjust voltage on phase monitor. If still red adjust phasing on main power. 8. Review the E2E rack controller. a) Hold Alt and press N. Verify that all relay boards are online. b) Press menu, 7, 1. Verify that all transducers and temperature probes are reading expected values. c) Verify that phase monitor input is an expected value. d) Press Home key to return to main screen. 9. On larger walk in freezers it may be necessary to reduce the temperature slowly to prevent damage to the freezer panels. If this is required follow the steps below. a) Set the initial temperature set point for the freezer at 50 F b) Reduce the temperature set point by 20 F every 24 hours until the required temperature is reached. 10. Turn on breaker for compressor 1 and ensure proper rotation of compressor. 11. Turn on breakers for all other compressors. 12. Monitor suction pressure and discharge pressure for expected operation. Suction pressure decreases with compressor operation and Discharge pressure increases. 5/16 Rev. A 57-02508 7

13. Compressors will cycle on and off at random while the system is in learning mode. The E2E is building a control algorithm for the compressor control. This is normal and could last up to several hours. 14. Add refrigerant to the high side of the system until the design charge is reached. a) Connect the fill line from a charging set to the liquid line filter port. b) Close the outlet valve on the receiver tank. This will allow liquid to go from the charging tank through the expansion valve and return as vapor to the suction line. The liquid will stack up in the receiver. c) Open and close the receiver outlet valve as required until the receiver has 20% liquid (during coldest condition) with the valve open. d) A vacuum charging core tool can be used to remove the Schrader valve to enable faster charging of refrigerant. 15. Verify the suction header pressure and discharge header pressure with an accurate refrigeration gauge set. Calibrate the E2E as necessary. 16. Set the head pressure valve (typically A8 valve) to achieve 200 psi head pressure. 17. Once all coolers are approximately at operating temperature. Set and check expansion valve superheat on each case and cooler. 18. Set each EPR valve where applicable. Adjusting the EPR valve will raise the pressure/ temperature of the evaporator. Suction header pressure must be lower than the EPR setting before performing this step. 19. Verify defrost settings including defrost times and termination temperatures. No more than 25% of the total load should be in defrosting mode at one time. 20. Check oil reservoir after two (2) days of operation and add oil as necessary. 21. After all adjustments have been made, check all valves for proper stem position and replace valve caps. 22. Change filter/ drier cores after start up (approximately 3 days). 5/16 Rev. A 57-02508 8

CPC E2E Controller Back Key Menu Key Home Key Alarm Key Help Key: Press for more information on items. Navigation Arrows E2 Shortcuts: All shortcuts below start at home screen (press home key anytime to return home) Log In/ Out: Press Log In/Out key. Username: USER, Password: PASS Function Key command values are shown on the LCD screen just above the function key. Press Help Key at any time to access instructional information. Check I/O board status: Menu, 7, 7, 1 Verify Inputs: Menu, 7, 1 Verify Outputs: Menu, 7, 2 Change rack suction pressure set point: Menu, 1, (use arrow to select group), Enter, F5, F2, F2 Change circuit temperature set point: Menu, 3, (use arrow to select circuit), Enter, F5, F2 Backup program to USB: Insert USB drive inside cover, Menu, 7, 3, 5, 6, 2, F1 View alarms: Press Alarm Key Clear Alarm: Alarm Key,(select alarm to be cleared), F3, A (for single), B (for all) Reset Alarm: Alarm Key,(select alarm to be cleared), F2, A (for single), B (for all) Notice: Never acknowledge alarms. Always reset or clear. CPC E2 Quick Reference Card can be found at the end of this manual or in the References Section. 5/16 Rev. A 57-02508 9

STARTUP TROUBLESHOOTING Compressor contactors don t engage when E2E calls for compressors: Check dual pressure switch on compressor. o Initial setting is 25 cut-in, 20 differential, 375 high cut out. o Adjust cut-in and differential to operate outside of E2E set points. Check voltage at each device along control circuit. See wiring diagram. Head pressure is too low/ high: Adjust A8 head pressure valve until 200 psi is reached. Evaporator pressure/ temperature too high: Fully open EPR valve at evaporators. Adjust suction set point downward in small increments until evaporator pressure is reached. o See E2 shortcuts above. Rack failure on phase loss: If phase monitor LED is red, adjust voltage range to match input voltage. If phase monitor LED is red, verify input phases are aligned to rack. If phase monitor LED is green, verify input logic is correct in program. o Log into controller with USER, PASS o Press: Menu, 7, 1 o Highlight the input to verify/ change o Press: Enter, Enter o Screen should be as shown o To reverse logic change Active Out to ON, Inactive Out to OFF Icon on when Logged in Hold Ctrl Press N to turn on Names Hold Alt Press F to turn on FULL I/O board relays are working with reverse logic. 5/16 Rev. A 57-02508 10

Verify wiring is NO or NC depending on device. Compressors are NC, Solenoids are NC, Defrost Heaters are NO. Verify failsafe dip switches are correct. NC relays are UP. NO relays are DOWN. State of Normally Closed (NC) Contacts on MultiFlex Relay Points Fail Safe Switch Light is ON Light is OFF Comm Loss Power Loss Up (ON) Closed Open Closed Closed Down (OFF) Open Closed Closed Closed State of Normally Open (NO) Contacts on MultiFlex Relay Points Fail Safe Switch Light is ON Light is OFF Comm Loss Power Loss Up (ON) Open Closed Open Open Down (OFF) Closed Open Open Open I/O boards not online: Verify board addressing Relay Number (Fail Safe Switch) S3 is Input Address 1-5 S4 is Relay Address 1-5 Add values from ON dip switches. Example: dip 1 and 3 are on. Value of dip 1=1 value of dip 2=0 value of dip 3=4. 1+0+4= 5. Network address is 5. Dip # 1 2 3 4 5 Value On 1 2 4 8 16 Value Off 0 0 0 0 0 5/16 Rev. A 57-02508 11

E2E locks out compressor on oil failure. Verify oil level in oil separator/ reservoir. Oil should be visible in top and bottom sight glass. Verify oil level at oil management control (OMB) at compressor. Level in sight glass should be at least half. Check LED on OMB control. Green LED= Level OK, Yellow LED=Solenoid open adding oil, Red= Fill time exceeded. If oil level is OK, reset or clear alarm in E2E controller. REFERENCE DOCUMENTS CPC E2E Operation and Installation Manual, Document 026-1614: http://www.emersonclimate.com/en-us/resources/technical_documentation/documents/mnl-0261614-rev5-e2-io-manual.pdf CPC E2E Quick Reference Card 026-1699: http://www.emersonclimate.com/documents/retail%20solutions/0261699.pdf CPC MultiFlex I/O Board Installation and Operation Manual, Document 026-1704: http://www.emersonclimate.com/en-us/resources/technical_documentation/documents/mnl-0261704-rev7-multiflex-io-board- Operation-Manual.pdf Parker Compact Wide-Range Pressure Regulators, Bulletin 25-94 G http://www.parker.com/parker/jsp/documentdisplay.jsp?mgmtid=427d42a204b83110vgnvcm10000048021dacrcrd Evaporator Pressure Regulating Valves, Bulletin 90-20, Form SD-73: http://www.parker.com/parker/jsp/documentdisplay.jsp?mgmtid=deec166a991b9210vgnvcm10000048021dacrcrd http://www.parker.com/parker/jsp/documentdisplay.jsp?mgmtid=a21d166a991b9210vgnvcm10000048021dacrcrd Oil Level Control System, Bulletin 110-10: http://www.parker.com/parker/jsp/documentdisplay.jsp?mgmtid=abcf166a991b9210vgnvcm10000048021dacrcrd 5/16 Rev. A 57-02508 12