INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER FCS-23A

Similar documents
INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER JCD-13A, JCR-13A

DIGITAL INDICATING CONTROLLER FCS-23A INSTRUCTION MANUAL

GCS-300 No.GCS31E

Instruction manual Micro-computer based digital indicating controller

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER GCD-200, GCR-200

INSTRUCTION MANUAL Micro-computer based digital indicating controller

Instruction manual for DIN rail mounting type indicating controller DCL-33A

Instruction manual Temperature Controller KT7

Non-contact voltage (for SSR drive): V DC DC current: 4 to 20mA DC Thermocouple: K, J, E Input. RTD: Pt100, JPt100

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

Warning Caution INSTRUCTION MANUAL DIN RAIL MOUNTING TYPE INDICATING CONTROLLER

DCL-33A No.DCL31E To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

INSTRUCTION MANUAL FOR TOUCH PANEL MONITORING UNIT CMT-220-K

DIGITAL INDICATOR JIR-301-M

DIN RAIL MOUNTED INDICATING CONTOLLER DCL-33A INSTRUCTION MANUAL

1. Model ACS 1 3 A / A, Series name: ACS-13A- /A (W48 x H48 x D62mm) Control action 3 PID A1 A Alarm type can be selected by keypad.

DIGITAL INDICATOR DI25

TEMPERATURE CONTROLLER

F4 Process Controller Installation and Operation Guide

Communications* None RS-232C RS-422 RS-485 BCD Transmission output** (4 to 20 ma)

Communications None RS-232C RS-422* RS-485* BCD Transmission output*/** (4 to 20 ma) E5AX- E5AX- L(M)A02 L(M)A03

Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e

DIGITAL INDICATING CONTROLLER. BCx2 INSTRUCTION MANUAL

Series Temperature Controller Instruction Sheet

TEMPERATURE CONTROL MODULE MODEL R3-TC2

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

Temperature Controllers

PLC INTERFACE UNIT CIT-200 INSTRUCTION MANUAL

Universal controller for panel mounting Models CS6S, CS6H, CS6L

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

SA100. General Description. Features. Temperature Controller SA100. Corresponding to Various Applications. Simple Mounting on DIN Rail

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

R Air flows from high pressure side to low pressure side. This principle can be applied to keep clean-air in the room or, alternatively, not to leak p

Specification , July 2015

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER

SYL-1512A PID TEMPEARATURE CONTROLLER INSTRUCTION MANUAL Version 2.1

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Nov 08 PRODUCT SPECIFICATION SHEET

Model 96VTR ¼ DIN Process Controller

I/A Series 716C 1/16 DIN Temperature Controller

Safety Information. Functional Description. Operation. DANGER Do not touch or contact the input/output terminals because it may cause electric shock.

Communications type RS-232C RS-422 RS-485 E5AJ-A2H02 E5EJ-A2H02

CN4800 Series CONTROLLER

Interchangeable thermistor (THE types) Output Contact E5CS-R1KJX-F E5CS-R1PX-F E5CS-R1GX-F Voltage E5CS-Q1KJX-F E5CS-Q1PX-F E5CS-Q1GX-F

High Resolution Temperature Controller REX-F9000. Instruction Manual IM9000F01-E5 RKC INSTRUMENT INC.

MICRO CONTROLLER S Z SERIES

Temperature Controller

99 Washington Street Melrose, MA Phone Toll Free Visit us at

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

Table of Contents DIGITAL DRYING OVEN. Features. Setup. Cautions. Description of the parts. Temperature Controls. Maintenance and Storage

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with Thermocouple Input

VERTEX F4 Instruction Manual

MICRO CONTROLLER E Z SERIES

User Manual. Digi-Sense TC9600 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

Oakton TEMP 9500 Advanced Multiparameter Controller

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

4TEMPERATURE CONTROLLER

Serie Rugghölzli 2 CH Busslingen. Tel. +41 (0) Fax +41 (0)

Multi-point Digital Controller MA900/MA901. Initial Setting Manual IMR01H03-E4 RKC INSTRUMENT INC.

Series Digital Controller Instruction Sheet

Example of Applications and Parameter Functions

Table of Contents SECTION PAGE

SA200. General Description. Features. Temperature Controller SA200. Self-Tuning Algorithm. Close Vertical or Horizontal Mounting

TC515 and TC600 Installation Manual. a Winters company

Series 945 User s Manual

Warning Caution. Safety Precautions (Be sure to read these precautions before using our products.)

UDC 700 Universal Digital Controllers and Indicator Specifications

CB103/CB403/CB PRODUCT CHECK 2. MOUNTING - * - / /Y INSTRUCTION MANUAL WARNING. 2.1 Mounting Cautions CAUTION RKC INSTRUMENT INC.

No.THD51E To prevent accidents arising from the use of this product, please ensure the operator using it receives this manual.

1. PRODUCT CHECK 2. MOUNTING

370, boulevard de Balmont LYON Tel Fax Web:

7EF/7HF/7EC/7ES Temperature Controllers

ISOLATOR SGI SGIW INSTRUCTION MANUAL

1. PRODUCT CHECK 2. MOUNTING - * - / /Y

Hardware Instruction Manual. SR Mini HG SYSTEM. High-performance Multi-point Control System IMSRM15-E4 RKC INSTRUMENT INC.

VT4810 SINGLE / DUAL ZONE CONTROLLER INSTALLATION MANUAL

AutomationDirect PM24. Microprocessor - Based Process/Temperature Limit Controller. Operator s Manual. Technical Support.

OVEN INDUSTRIES, INC.

LA type soldering iron controller

+ A B V B NO NC V COM PV PV

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

User s Guide CN616A. Universal 6 Channel ¼ DIN Process Controller. Shop online at omega.com

AutomationDirect. PC35 Configuration Sheet

Mark 25 Ultrapure Water Conductivity Analyzer

General Specifications

COMMANDER 150. User Guide Universal Process Indicator A1

02/11/2015

SR Mini HG SYSTEM. High-performance Multi-point Control System. SR Mini HG SYSTEM. Hardware Instruction Manual IMSRM15-E6 RKC INSTRUMENT INC.

02/11/2015

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

User s Guide. CN616 Series 1 4 DIN Economical 6-Zone PID Temperature Controllers. Shop online at omega.com SM

INSTRUCTIONS FOR THE 2600 SERIES MICROPROCESSOR BASED TEMPERATURE /PROCESS CONTROL

NOVUS AUTOMATION 1/5. Range: -35 to 720 C (-31 to 1328 F) Range: -90 to 1300 C (-130 to 2372 F) Range: 0 to 1760 C (-32 to 3200 F)

CONTENTS. Micro-controller X Model : PXR5/9. Instruction Manual. INP-TN1PXR5/9f-E

UDC100 Universal Digital Controller Specifications

Cat. No. H113-E1-03B E5ZN. Temperature Controller OPERATION MANUAL

TECHNICAL BULLETIN [ 1/9 ]

SR70 (SR ) Series Digital controller Instruction Manual

Transcription:

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER Thank you for your purchase of our Microcomputer based Temperature Indicating Controller. This manual contains instructions for the mounting, functions, operations and notes when operating the. For model confirmation and unit specifications, please read this instruction manual carefully before starting operation. To prevent accidents arising from the use of this controller, please ensure the operator using it receives this manual. 1

NOTES TO USERS ***** Note to users ***** Before operating this controller, make sure you have understood the following. Warning Turn the power supply to the instrument OFF before wiring or checking. Working or touching the terminal with the power switched ON may result in an Electric Shock which could cause severe injury or death. Moreover, the instrument must be grounded before the power supply to the instrument is turned on. Caution Do not apply a commercial power source to the sensor connected to the input terminal nor allow the power source to come into contact with the sensor, as the input circuit may be burnt out. This instrument should be used according to the specifications described in the manual. If it is used outside the specifications, it may malfunction or cause fire. Be sure to follow the warnings, cautions and notices. If not, it could cause serious injury or malfunction. Specifications of the FCS-1A and the contents of this instruction manual are subject to change without notice. Care has been taken to assure that the contents of this instruction manual are correct, but if there are any doubts, mistakes or questions, please inform our sales department. Be sure to turn the power supplied to the instrunment OFF when cleaning. Wipe the instrument using dry soft cloth. (If the paint thinner is used for wiping, the instrument may be deformed or discolored.) The display parts are more easily damaged. Do not strike them with hard objects or press hard on them. Any unauthorized transfer or copying of this document, in part or in whole, is prohibited. Shinko Technos is not responsible for any damages or secondary damages incurred as a result of using this product, including any indirect damages. Setup by the DIP switch and the rotary switch inside of the controller is required before the power is turned on. The product is factory adjusted as [Sensor input: K, Control action: Fuzzy self-tuning PID, Heating action, Alarm (A1): No alarm action, no standby function, Unit: and Program starting form: manual]. Refer to Chapter. Setup (page 9). It is recommended that the PID auto-tuning be performed on the trial run. It is advised to provide the protective device against such environmental conditions which may cause damage to the device or contribute to the deterioration of its parts. 2

CONTENTS --- CONTENTS --- 1. Model names 1.1 Model names ---------------------------------------------------------------------------- 5 1.2 How to indicate the model nameplate ----------------------------------------------- 6 2. Name and functions of the sections --------------------------------------------. Setup.1 Taking the internal assembly out ------------------------------------------------------ 9.2 Switch setting (multi-function) --------------------------------------------------------- 9. Insertion of the internal assembly ---------------------------------------------------- 12. Operations.1 Operating flow chart -------------------------------------------------------------------- 1.2 Operations (1) PV/SV display mode ------------------------------------------------------------------ 15 (2) Main setting mode --------------------------------------------------------------------- 16 () Sub setting mode Setting value memory number selection ----------------------------------------- 16 Auto-tuning Perform/Cancel --------------------------------------------------------- 16 Proportional band setting ------------------------------------------------------------- 1 Integral time setting -------------------------------------------------------------------- 1 Derivative time setting ----------------------------------------------------------------- 1 Proportional cycle setting ------------------------------------------------------------- 1 Manual reset setting ------------------------------------------------------------------- 18 Alarm 1, 2 (A1, A2) settings ---------------------------------------------------------- 18 Loop break alarm time setting ------------------------------------------------------- 19 Loop break alarm span setting ------------------------------------------------------ 19 () Auxiliary function setting mode 1 Setting value lock designation ------------------------------------------------------ 20 Main setting value high limit setting ------------------------------------------------ 21 Main setting value low limit setting ------------------------------------------------- 21 Sensor correction setting ------------------------------------------------------------- 21 Instrument number setting ----------------------------------------------------------- 21 Transfer rate selection ---------------------------------------------------------------- 22 Communication protocol selection ------------------------------------------------- 22 (5) Auxiliary function setting mode 2 Scaling high limit value setting ------------------------------------------------------ 2 Scaling low limit value setting ------------------------------------------------------- 2 PV filter time constant setting ------------------------------------------------------- 2 Main output high limit setting -------------------------------------------------------- 2 Main output low limit setting --------------------------------------------------------- 2

CONTENTS Main output ON/OFF action hysteresis setting --------------------------------- 2 Alarm 1, 2 (A1, A2) action Energized/Deenergized selections ------------- 2 Alarm 1, 2 (A1, A2) hysteresis settings ------------------------------------------- 25 Alarm 1, 2 (A1, A2) action delayed timer settings ------------------------------ 25 Display selection when control output is off ------------------------------------- 26 Main setting value rising rate setting ---------------------------------------------- 26 Main setting value falling rate setting --------------------------------------------- 2 (6) Program mode Program control change -------------------------------------------------------------- 29 Step 1 to time setting --------------------------------------------------------------- 29 () Control output OFF function -------------------------------------------------------- 1 (8) Output manipulating value and Step rest time indication mode ----------- 2 5. Setting value memory number external selection ----------------------- 6. Running 6.1 When using the as a Temperature controller ------------------------- 6.2 When using the as a Simplified program controller ----------------- 5. Action explanations.1 Standard action drawings --------------------------------------------------------------- 6.2 ON/OFF action drawings ----------------------------------------------------------------. Pattern end action drawing -------------------------------------------------------------. Alarm 1, 2 (A1, A2) action drawings ------------------------------------------------- 8 8. Control actions 8.1 Fuzzy self-tuning -------------------------------------------------------------------------- 0 8.2 Explanations of PID ---------------------------------------------------------------------- 1 8. PID auto-tuning of this controller ----------------------------------------------------- 2 9. Other functions ---------------------------------------------------------------------------- 10. Mounting to control panel 10.1 Site selection ------------------------------------------------------------------------------- 10.2 External dimension drawing ------------------------------------------------------------ 10. Panel cutout drawing --------------------------------------------------------------------- 10. Mounting ------------------------------------------------------------------------------------- 5 11. Wiring connection 11.1 Terminal arrangement -------------------------------------------------------------------- 6 11.2 Wiring connection examples ------------------------------------------------------------ 8 12. Specifications 12.1 Standard specifications ------------------------------------------------------------------ 9 12.2 Optional specifications ------------------------------------------------------------------- 52 1. Troubleshooting --------------------------------------------------------------------------- 55 1. Character table ----------------------------------------------------------------------------- 58

MODEL NAME 1. Model names 1.1 Model names Standard models F C S 2 A / M Series name: FCS-20 Control action PID control (*1) Alarm A Alarm action (*2) R Relay contact output Output S Non-contact voltage output A Current output Input M Multi-range input (*) *1: Fuzzy self-tuning PID, PID, PD and ON/OFF action are selectable by internal DIP switch. *2: 12 types of alarm action and no alarm action are selectable by internal rotary switch and DIP switch. *: 12 types of input, Thermocouple, RTD are selectable by internal rotary switch and DIP switch. Alphanumeric character to represent the functions or type is applied to the. [Example] - R / M, A2, LA Loop break alarm output Alarm 2 (A2) output Relay contact output Optional code Code Specification A2 Alarm 2 output (including the pattern end output 2) LA Loop break alarm C5 Based on EIA RS-85 Serial communication C Based on EIA RS-22C SM Setting value memory number external selection BK Color: Black BL Screw type mounting bracket IP Dust-proof drip-proof TC Terminal cover (See page 52 for the options in detail.) 5

MODEL NAME Warning Do not take the inner assembly out nor touch the terminal with the power supply on. Touching the terminal with the power switched ON may result in an Electric Shock which could cause severe injury or death. 1.2 How to indicate the model nameplate Model nameplates are put on the case and the left side of the inner assembly. (1) (2) () [Model name plate] R/M A 2 L A N o. [Example] Relay contact output, Multi-range input Alarm 2 (A2) output Loop break alarm output (1): Model name (2): Option codes (): Instrument number (Indicated only on the internal assembly) 6

NAME AND FUNCTIONS OF THE SECTIONS 2. Name and functions of the sections (1) () () (2) (5) (6) [Fig. 2-1] (1) PV display Indicates the Process variable (PV) with the red LED. (2) SV display Indicates the Setting value (SV), Manipulating value (MV) or Time (TIME) with the green LED. () Control output indicator ( OUT) The green LED is lit when the Control output is on. (For the current output type, it blinks corresponding to the manipulating value at 0.125 seconds of period.) () Alarm 1 (A1) output action or Pattern end 1 output indicator ( A1) The red LED is lit when the Alarm 1 (A1) output or Pattern end 1 output is on. (5) Alarm 2 (A2) output action or Pattern end 2 output indicator ( A2) [Option] The red LED is lit when the Alarm 2 (A2) output or Pattern end 2 output is on. (6) Auto-tuning action indicator ( AT) The yellow LED blinks during auto-tuning.

NAME AND FUNCTIONS OF THE SECTIONS Increase key Decrease key Mode key OUT/OFF key : Increases the numeric value on the SV display during setting mode. : Decreases the numeric value on the SV display during setting mode. : Selects the setting mode. : Performs the control output ON or OFF, or program control Start or Stop. In any mode, if the key is pressed for approx. 1 second, the Control output OFF function will work. When the function is working, the function cannot be released. Even if the insrument power is turned off and on again, and the function is not released. To release the function, press the key for 1 second. The setting value is registered by pressing the key. In any setting item, if the key is pressed for approx. seconds, the mode returns to the PV/SV display. 8

SETUP. Setup.1 Taking the internal assembly out Before the power supply to this instrument is on, take the internal assembly out from the case by pushing the hook (bottom of the instrument) in the direction indicated by the arrow and holding the notches. [Fig..1-1].2 Switch setting (multi-function) Using a small slotted screwdriver and tweezers, set the Sensor input, Alarm 1 action, Alarm 2 action, Control action, Heating (reverse)/cooling (direct) action, Alarm 1 and 2 standby functions, Unit / and Program starting form Auto/Manual change by rotary switch and DIP switch by the following procedure. The rotary switch A2 (SW01) is equipped only when the option A2 is applied. Control action designation Heating/Cooling action designation Alarm 1 standby action designation Alarm 2 standby action designation / designation Sensor input designation Program start Auto/Manual designation Alarm 2 action type designation Alarm 1 action type designation Sensor input designation Rotary switch DIP switch [Fig..2-1] 9

SETUP The following items can be designated by the DIP switch (SW0). Factory adjusted as all switches OFF [ ]. [Table.2-1] Item Sw. No. Designation Switch status Control action Heating/Cooling action 1 and 2 Fuzzy self-tuning PID action No.1: OFF No.2: OFF PID action No.1: ON No.2: OFF PD action No.1: OFF No.2: ON ON/OFF action No.1: ON No.2: ON Heating (reverse) action No.: OFF Cooling (direct) action No.: ON No standby action No.: OFF Alarm 1 (A1) standby action Standby action No.: ON Alarm 2 (A2) standby action (*1) / 6 Sensor input (*2) Program start Auto/Manual No standby action No.5: OFF 5 Standby action No.5: ON 8 K, J, R, B, N, PL-, Pt100, JPt100 (With decimal point) S, E, T, C, Pt100 (Without decimal point) Manual start Automatic start No.6: OFF No.6: ON No.: OFF No.: ON No.8: OFF No.8: ON *1: The standby function will not work if the option A2 is not applied. *2: The sensor input can be designated by the combination of this item and the rotary switch sensor input (SW0). (See page 11.) Program start: This item is available for the program control. Manual start : Program starts by pressing the key. Automatic start : Set program is automatically started from step 1 by turning the power supply to the instrument on (after 2 seconds of warm-up status). 10

SETUP Select the sensor type by rotary switch sensor input (SW0). Factory adjusted as K, [ ]. [Table.2-2] Rotary Sw. No. DIP Sw. No. Type of sensor Scale range 0 OFF K -200 to 10-20 to 2500 1 OFF J -200 to 1000-20 to 1800 2 OFF R 0 to 160 0 to 200 OFF B 0 to 1820 0 to 00 OFF PL- 0 to 190 0 to 2500 5 OFF N 0 to 100 0 to 200 6 OFF Pt100-199.9 to 850.0-199.9 to 999.9 OFF JPt100-199.9 to 500.0-199.9 to 900.0 0 ON S 0 to 160 0 to 200 1 ON E 0 to 1000 0 to 1800 2 ON T -199.9 to 00.0-199.9 to 50.0 ON C (W/Re5-26) 0 to 215 0 to 200 ON Pt100-200 to 850-20 to 1560 11

SETUP The alarm action type and the pattern end output when program control can be designated by the rotary switch A1 (SW02) and A2 (SW01). The rotary switch A2 (SW01) is equipped only when the option A2 is applied. Rotary switch A1 (SW02): Alarm 1 (A1) action or Pattern end 1 output. Rotary switch A2 (SW01): Alarm 2 (A2) action or Pattern end 2 output. Factory adjusted as No alarm action, [ ]. [Table.2-] Alarm 1 action A1 Rotary Sw. (Sw02) No. Alarm 2 action A2 Rotary Sw. (Sw01) No. No alarm action 0 No alarm action 0 High limit alarm 1 High limit alarm 1 Low limit alarm 2 Low limit alarm 2 High/Low limits alarm High/Low limits alarm Hi/Lo limit range alarm Hi/Lo limit range alarm Process high alarm 5 Process high alarm 5 Process low alarm 6 Process low alarm 6 Pattern end 1 output Pattern end 2 output. Insertion of the internal assembly When the setup is completed, insert the internal assembly into the case. Firmly insert the assembly until it is locked by the hook at the bottom of the instrument. (There will be a clicking sound.) Caution Do not confuse the top and bottom of the internal assembly. If inserting the assembly into the case by force in the wrong direction, the PCB may be damaged. 12

OPERATIONS. Operations.1 Operating flow chart Instrument power ON Warm-up status (For approx. 2s, displays as shown on page 15.) PV/SV display mode 1s s Control output OFF function Output manipulating value Step rest time *1 + + s [Main setting mode] [Sub setting mode] [Auxiliary function setting mode 1] Main setting Setting value memory No. selection Setting value lock PV PV designation Auto-tuning Perform/Cancel PV *2 PV Main setting value Proportional band setting high limit setting PV PV Integral time setting PV Derivative time setting PV Proportional cycle setting PV PV Manual reset setting PV Alarm 1 (A1) setting PV Alarm 2 (A2) setting PV Loop break alarm time setting PV Loop break alarm span setting PV Main setting value low limit setting PV Sensor correcting value setting Instrument number setting PV Transfer rate selection PV Communication protocol selection PV 1

OPERATIONS : Options + : Press the key while the key is being pressed. + s: Press the key for approx. seconds while the key is being pressed. + + s: Press the key for approx. seconds while the and keys are being pressed. + s : Pressing the key, press the key for approx. seconds. *1: Step rest time is indicated only during program control. *2: If the Auto-tuning is performed, the mode reverts to the PV/SV display. If the Auto-tuning is released, the mode will move to Proportional band setting. *: In the mode Program control change, if is selected and the key is pressed, the display reverts to the PV/SV display mode. Set the temperature setting of program in the Sub setting mode, Auxiliary fuction setting mode 1 and 2. + + s + s [Auxiliary function setting mode 2] [Program mode] Scaling high limit Alarm 1 (A1) hysteresis Program control change * setting setting PV PV PV Scaling low limit Alarm 2 (A2) hysteresis Step 1 time setting setting setting PV PV PV PV filter time constant Alarm 1 (A1) action Step 2 time setting setting delayed timer setting PV PV PV Main output high limit Alarm 2 (A2) action Step time setting setting delayed timer setting PV PV PV Main output low limit Display selection when Step time setting setting control output off PV PV PV Main output ON/OFF Main setting value Step 5 time setting action hysteresis setting rising rate setting PV PV PV Alarm 1 (A1) action Main setting value Step 6 time setting Energized/Deenergized falling rate setting PV PV PV Alarm 2 (A2) action Energized/Deenergized PV Step time setting PV 1

OPERATIONS (PV/SV display mode).2 Operations The PV display indicates the sensor type and the SV display indicates the rated value selected by Sensor input designation (page 10, 11) for approx. 2 seconds after the power is turned on. See [table.2-1]. During this time, all outputs and LED indicators are in their off status. After that, the actual temperature is displayed on the PV display, main setting value on the SV display and starts control. (1) PV/SV display mode Instrument power ON Warm-up status (For 2s) [Table.2-1] Rated value [Table.2-1] Input K J R B PL-ll N S E T C Pt100 JPt100 Pt100 PV display SV display PV display SV display PV/SV display mode Mode during control. Actual Main The contents of setting items nor setting values Temperature setting value cannot be changed. 15

OPERATIONS (Main, Sub setting mode) (2) Main setting mode In the PV/SV display mode, if the key is pressed, the Main setting mode will be selected. The setting value can be increased or decreased by pressing the and keys. If the key is pressed, the setting value will be registered and the controller will revert to the PV/SV display. PV/SV display mode Actual Main setting Temperature value Main setting Setting value Mode to set the setting value of the main control. Setting range: From Main setting value low limit to Main setting value high limit [Factory adjusted as 0 ] () Sub setting mode In the PV/SV display mode, if the key is pressed while the key is being pressed, Sub setting mode will be selected. The setting value can be increased or decreased by pressing the and keys. If the key is pressed, the setting value is registered and the next setting item will be selected. PV/SV display mode Actual Main setting temperature value + Setting value memory Mode to select the memory number (file) number selection to be set or to be called. Selected Selecting items: 1 to value [Factory adjusted as Memory number 1.] Auto-tuning Perform/ Mode to designate the auto-tuning Perform or Cancel. Cancel If Auto-tuning Perform is designated, and the Designation key is pressed, the controller reverts to PV/SV display mode. (When Perform) To set the other values, cancel the Auto-tuning. When the ON/OFF action or PD action is selected in the Control action designation (page 10), this display is not available. 16

OPERATIONS (Sub setting mode) SV (Auto-tuning Cancel) SV (Auto-tuning Perform) [Factory adjusted as Auto-tuning Cancel] If the Auto-tuning is released during the process, the PID value reverts to the former value. Proportional band setting Mode to set the proportional band. Setting value Setting range: 0.1 to 999.9% [Factory adjusted as 2.5%] When the ON/OFF action is selected in control action designation (Page 10), this display is not available. Integral time setting Mode to set the integral time. Setting value Setting range: 0 to 600s [Factory adjusted as 200s] Setting the value to 0 disables the function. This display is not available when the ON/OFF action or PD action is selected in Control action designation (page 10). Derivative time setting Mode to set the derivative time. Setting value Setting range: 0 to 600s [Factory adjusted as 50s] Setting the value to 0 disables the function. This display is not available when the ON/OFF action is selected in Control action designation (page 10). Proportional cycle setting Mode to set the proportional cycle Setting value Setting range: 1 to 120s [Factory adjusted as 0s to Relay contact output type, and s to Non-contact voltage output type] When the ON/OFF action is selected in Control action designation (page 10), this display is not available. This setting item is not available to Current output type. With the Relay contact output type, if the proportional cycle time is decreased, the frequency of the relay action increases, and the life of the relay contact is shortened. 1

OPERATIONS (Sub setting mode) Manual reset setting Mode to set the reset value to correct the offset Setting value (Deviation between SV and PV when equilibrium status). Setting range: proportional band converted value [However, in the range, 199.9 to 999.9 ( )] [Factory adjusted as 0.0 ] This display is indicated only when PD action is designated in the Control action designation (page 10). Manual reset setting method: When SV>PV, set the positive + value (SV PV). When SV<PV, set the negative value (SV PV). Alarm 1 (A1) setting Setting value Mode to set the action point of the Alarm 1 (A1) output. This item is not displayed if setting the rotary switch to No. 0 or No. (See page 12.) Setting range: See [table.2-2]. [Factory adjusted as 0 ] Alarm 2 (A2) setting Setting value Mode to set the action point of the Alarm 2 (A2) output. This item is not displayed if the option [A2] is not applied or even if it is applied, when setting the rotary switch to No. 0 or No. (See page 12.) Setting range: See [table.2-2]. [Factory adjusted as 0 ] 18

OPERATIONS (Sub setting mode) Setting range of Alarm 1 and 2 (The setting range is the same when the standby function is added.) [Table.2-2] Alarm type Setting range High limit alarm Input span to Input span Low limit alarm Input span to Input span High/Low limits alarm 1 to Input span High/Low limit range alarm 1 to Input span Process high alarm Input range minimum to Input range maximum Process low alarm Input range minimum to Input range maximum For RTD input, the minimum value of the negative side is 199.9. Loop break alarm time setting Setting value Loop break alarm span setting Setting value Mode to set the time for Loop break alarm activation assessment. Setting range: 0 to 200 minutes [Factory adjusted as 0 minutes.] This display is indicated only when the option [LA] is applied. Mode to set the span for Loop Break Alarm activation assessment. Setting range: 0 to 150 (Thermocouple, except T and RTD without a decimal point) 0.0 to 150.0 (Thermocouple T and RTD with a decimal point) [Factory adjusted as 0 ] This display is indicated only when the option [LA] is applied. PV/SV display mode Actual Main setting Temperature value 19

OPERATIONS (Auxiliary function setting mode 1) () Auxiliary function setting mode 1 In PV/SV display mode, if the key is pressed for approx. seconds while the key is being pressed, Auxiliary function setting mode 1 can be selected. The setting value can be increased or decreased by pressing the and keys. If the key is pressed, the setting value is registered and the next setting item is selected. PV/SV display mode Actual Main setting Temperature value + for approx. s Setting value lock Mode to lock the setting value to prevent error. designation The setting item to be locked depends on the Designation designation. [Factory adjusted as Unlock status.] Unlock status. All setting values are changeable. None of the setting items can be changed. Only main setting value is changeable. All setting items can be changed, however, the value returns to the former value after the power off because the value is not written on the nonvolatile memory. This mode is used when changing the value temporarily. Fuzzy self-tuning or Auto-tuning PID action will not function if [ ] or [ ] is designated. When designating Lock, designate Lock 1, 2 or after setting the necessary items in the status Unlock. 20

OPERATIONS (Auxiliary function setting mode 1) As to the Lock mode When using the as a Fixed value controller. The setting values can temporarily be changed by the selected setting value memory number, however, when the number is changed, the setting values changed by the previous number are canceled and returns to the former values. When using the as a Program controller. The setting values can temporarily be changed by the step number performing, however, when the step number is changed, the setting values are canceled and returns to the former values. Setting value change is null when the controller is waiting for running. The running starts by the values memorized. Main setting value high limit setting Setting value Main setting value low limit setting Setting value Mode to set the high limit of main setting value. (If scaling high limit value is changed, this setting value will be changed as well.) Setting range: Main setting value low limit to scaling high limit value [Factory adjusted as 00 ] Mode to set the low limit of main setting value. (If scaling low limit value is changed, this setting value will be changed as well.) Setting range: Scaling low limit value to main setting value high limit [Factory adjusted as 0 ] Sensor correction setting Mode to set the correct value of the sensor. Setting value Setting range: 100.0 to 100.0 [Factory adjusted as 0.0 ] Instrument number setting Setting value Mode to set the Instrument number individually to each instrument when communicating by connecting multiple instruments in serial communication. Setting range: 0 to 95 [Factory adjusted as 0] This display is available only when the option [C or C5] is applied. 21

OPERATIONS (Auxiliary function setting mode 1) Transfer rate selection Selection Mode to select a communication transfer rate to meet the rate of the host computer. [Factory adjusted as 9600bps] 200bps 800bps 9600bps 19200bps This display is available only when the option [C or C5] is applied. Communication protocol Mode to select a communication protocol selection between the and the host computer. Selection [Factory adjusted as ] Shinko standard protocol Based on Modbus, ASCII mode This display is available only when the option [C or C5] is applied. PV/SV display mode Actual Main setting Temperature value 22

OPERATIONS (Auxiliary function setting mode 2) (5) Auxiliary function setting mode 2 In PV/SV display mode, if the key is pressed for approx. seconds while the and keys are being pressed, Auxiliary function setting mode 2 can be selected. The setting value can be increased or decreased by pressing the and keys. If the key is pressed, the setting value is registered and the next setting item is selected. PV/SV display mode Actual Main setting Temperature value + + for approx. s Scaling high limit setting Mode to set the high limit value of the scaling. Setting value If scaling high limit value is changed, main setting high limit value will be changed to the scaling high limit value as well. Setting range: Scaling low limit value to input range maximum value [Factory adjusted as 10 ] Scaling low limit setting Setting value Mode to set the low limit value of the scaling. If scaling low limit value is changed, main setting low limit value will be changed to the scaling low limit value as well. Setting range: Input range minimum value to scaling high limit value [Factory adjusted as 200 ] PV filter time constant Setting Setting value Mode to suppress the PV fluctuation caused by such as disturbance. Set the value larger by degrees, and find the setting value at which the value does not fluctuate. If the value is set too large, it affects control result due to the delay of response. Setting range: 0.0 to 10.0s [Factory adjusted as 0.0s] 2

OPERATIONS (Auxiliary function setting mode 2) Main output high limit setting Mode to set the high limit value of the main output. Setting value Setting range: Main output low limit value to 105% Setting greater than 100% is effective to the type Current output. [Factory adjusted as 100%] This display is not available for the ON/OFF action. Main output low limit setting Setting value Mode to set the low limit value of the main output. Setting range: 5% to Main output high limit value Setting less than 0% is effective to the type Current output. [Factory adjusted as 0%] This display is not available for the ON/OFF action. Main output ON/OFF Mode to set the ON/OFF action hysteresis of the action hysteresis setting main control output. Setting value Setting range: 0.1 to 100.0 [Factory adjusted as 1.0 ] This display is indicated only when the ON/OFF action is designated in Control action designation (page10). Alarm 1 (A1) action Mode to select the action Energized or Deenergized Energized/Deenergized for Alarm 1. Selection [Factory adjusted as Energized] This display is not indicated when the rotary switch is set to No. 0 or No. in Alarm 1 action designation (page 12). Energized Deenergized 2

OPERATIONS (Auxiliary function setting mode 2) Alarm 2 (A2) action Mode to select the action Energized or Deenergized Energized/Deenergized for Alarm 2. Selection [Factory adjusted as Energized] This display is not indicated when the rotary switch is set to No. 0 or No. in Alarm 2 action designation (page 1), or the option [A2] is not applied. Selection items: The same as those of the alarm 1 (A1) action Energized/Deenergized selection. Alarm 1 hysteresis setting Mode to set the hysteresis value for Alarm 1. Setting value Setting range: 0.1 to 100.0 [Factory adjusted as 1.0 ] This display is not indicated when the rotary switch is set to No. 0 or No. in Alarm 1 action designation (page 12). Alarm 2 hysteresis setting Mode to set the hysteresis value for Alarm 2. Setting value Setting range: 0.1 to 100.0 [Factory adjusted as 1.0 ] This display is not indicated when the option [A2] is not applied and when the rotary switch is set to No. 0 or No. in Alarm 2 action designation (page 12) even if the option [A2] is applied. Alarm 1 (A1) action Mode to set the action delayed timer for Alarm 1. delayed timer setting Setting range: 0 to 9999s Setting value [Factory adjusted as 0s] Alarm output is turned on when the setting time has passed after the input gets into the alarm output range. This display is not indicated if the rotary switch is set to No. 0 or No. in Alarm 1 action designation (page 12). 25

OPERATIONS (Auxiliary function setting mode 2) Alarm 2 (A2) action Mode to set the action delayed timer for Alarm 2. delayed timer setting Setting range: 0 to 9999s Setting value [Factory adjusted as 0s] Alarm output is turned on when the setting time has passed after the input gets into the alarm output range. This display is not indicated when the option [A2] is not applied and when the rotary switch is set to No. 0 or No. in Alarm 2 action designation even if the option [A2] is applied (P.12). Display selection when control output is off Selection Mode to select the display when the control output is off. [Factory adjusted as indicating OFF on the PV display] OFF is indicated on the PV display. No indication (all unlit). Only PV is indicated. Main setting value rising rate setting Setting value Mode to set the rising rate of the main setting value. (Rising value per minute) Setting the value to 0 or 0.0 disables the function. Setting range: 0 to 9999 /min. Thermocouple, except T and RTD without a decimal point 0.0 to 999.9 /min. Thermocouple T and RTD with a decimal point [Factory adjusted as 0 /min.] 26

OPERATIONS (Auxiliary function setting mode 2) Main setting value falling rate setting Setting value Mode to set the falling rate of the main setting value. (Falling value per minute) Setting the value to 0 or 0.0 disables the function. Setting range: 0 to 9999 /min. Thermocouple, except T and RTD without a decimal point 0.0 to 999.9 /min. Thermocouple T and RTD with a decimal point [Factory adjusted as 0 /min.] PV/SV display mode Actual Main setting temperature value 2

OPERATIONS (Program mode) (6) Program mode In PV/SV display mode, if the key is pressed for approximately seconds while the key is being pressed, the Program mode can be selected. The setting value can be increased or decreased by pressing the and keys. If the key is pressed, the setting value is registered and the next setting item is selected. As to the setting values of the step 1 to, each setting value for setting value memory number 1 to set during the Fixed value control is assigned respectively. For example, values in memory number 1 are assigned to the values for step 1, and number 2 for step 2. If the Pattern end output is designated and the program control is performed, the Pattern end output is turned on when the program is completed. When the Pattern end output is on and if the key is pressed, the Pattern end output is turned off. If the key is pressed again, the program will be performed. If some steps are unnecesary, set the times 00.00 for the step numbers not used. Program Example Step number (Setting value memory number) 1 2 5 6 Main setting value 500 500 1000 1000 200 200 100 Proportional band 2.0 1.8 2.0 1.8 2.5 1.8 2.0 Integral time 180 80 180 80 200 80 200 Derivative time 0 20 0 20 50 20 50 Proportional cycle 0 0 0 0 0 0 0 Alarm 1 2 5 2 5 10 0 5 Alarm 2 2 5 2 5 10 0 5 Step time 00:0 01:00 00:0 01:00 02:00 00:0 01:00 1000 500 0 28

OPERATIONS (Program mode) PV/SV display mode Actual Main setting temperature value + for approx. s Program control change Control form is changed between Fixed value Setting value of and Program. (Fixed value control) fixed value control In Fixed value control, if the key is pressed, the mode will revert to the PV/SV display. Fixed value control Following dislay is available only when Program control. Program control [Factory adjusted as Fixed value control] Step 1 Time setting Mode to set the Time for step 1. Setting value 00.00 Minute indication Hour indication For example, when setting 1 hour 58 minutes, set as [ ]. Setting range: 00.00 to 99.59 [Factory adjusted as 00.00] Step 2 Time setting Mode to set the Time for step 2. Setting value [The setting range and the factory adjusted value are the same as Step 1.] Step Time setting Mode to set the Time for step. Setting value [The setting range and the factory adjusted value are the same as Step 1.] Step Time setting Mode to set the Time for step. Setting value [The setting range and the factory adjusted value are the same as Step 1.] 29

OPERATIONS (Program mode) Step 5 Time setting Mode to set the Time for step 5. Setting value [The setting range and the factory adjusted value are the same as Step 1.] Step 6 Time setting Mode to set the Time for step 6. Setting value [The setting range and the factory adjusted value are the same as Step 1.] Step Time setting Mode to set the Time for step. Setting value [The setting range and the factory adjusted value are the same as Step 1.] PV/SV display mode Actual Main setting temperature value 0

OPERATIONS (Control output OFF function) () Control output OFF function A function to turn the control output OFF even if the power to the instrument is supplied. The function is used when required to halt the control action or when the is not being used in multiple controllers. Control output OFF function can be selected from any mode by pressing the key for approx. 1 second. The display is the same as when [Display selection when control output is off] is selected. (See page 26.) PV/SV display mode Actual Main setting temperature value for approx. 1s [From any mode, as an example] Control output OFF function 1s Manual reset setting (*) [Unlit] Setting value for approx. 1s (*): PV display indicates [OFF indication], [No indication] or [Only PV] selected in Display selection when control output is off (page 26). Notice Once the Control output OFF function is enabled, the function cannot be released even if the power to the instrument is turned OFF and turned ON again. To cancel the function, press the key again for approx. 1 second. In the program control, the Control output OFF function cannot be used because the key functions as Program Start/Stop key. 1

OPERATIONS (Manipulating value and Step time indication ) (8) Output manipulating value and Step rest time indication mode In the PV/SV display mode, press the key for approx. seconds. The display will be changed to main setting mode in the process, however, keep pressing it until the Output manipulating value is displayed. If the key is pressed again, the mode reverts to the PV/SV display. During program control, if the key is pressed in Output manipulating value indication, the Step rest time indication will be selected. If the key is pressed again, the mode reverts to the PV/SV display. PV/SV display mode Actual Main setting temperature value for approx. s Output manipulating value indication mode Actual manipulating Manipulating value is indicated on the SV display temperature value by the blinking the decimal point. (Fixed value (Program control) control) Step rest time indication Actual Step Step rest time is indicated on the SV display. temperature rest time 2

SETTING VALUE MEMORY FUNCTION 5. Setting value memory number external selection [Option code: SM] If the option SM is applied, setting value memory number 2 can be selected by external operation. The option SM cannot be applied in combination with option A2, LA, C or C5. Wiring connection of setting value memory number external selection 1 6 ( ) 2 2(NC) 1( ) 8 NC (Color of wire: Red) 2 (Color of wire: Blue) 1 9 5 10 The Setting value memory number 2 can be selected by shorting between 1 and. If Setting value memory number 2 is selected by the Open collector, connect the pin No.1 to the collector and the pin No. to the emitter. When the Setting value memory number 2 is selected by external operation, the number cannot be selected by front key operation. Memory number cannot be changed during setting mode or PID auto-tuning.

RUNNING 6. Running After the controller has been mounted to the control panel and wiring is completed, it can be started in the following manner. 6.1 When using the as a Temperature controller (1) Turn the power supply to the ON. For approx. 2s after the power is switched ON, the type of sensor and the unit designated in Sensor input designation (page 11) will be indicated on the PV display, and the rated maximum value will be indicated on the SV display. See [table 6.1-1]. During this time, all outputs and LED indicators are in their OFF status. After that, the display turns to the PV/SV display. When the Control output OFF function is working, the item selected in the [Display selection when control output is off] is displayed on the PV display. (See page 26.) [Table 6.1-1] Input K J R B PL-ll N S E T C Pt100 JPt100 Pt100 PV display SV display PV display SV display (2) Input the setting value, referring to Chapter. Operations (page 1ff). When controlling by Fuzzy self-tuning PID action, designate [Perform] in the Auto-tuning Perform/Cancel function to start the control in optimum conditions. () Turn the load circuit power ON. Starts the control action so as to keep the controlled object at the main setting value.

RUNNING 6.2 When using the as a Simplified program controller (1) Turn the power supply to the ON. For approx. 2s after the power is turned ON, the type of sensor and the unit designated in Sensor input designation (page 11) are indicated on the PV display, and the rated maximum value is indicated on the SV display. See [table 6.1-1]. During this time, all outputs and LED indicators are in their OFF status. After that, the display reverts to the PV/SV display. When the Control output OFF function is working, the item selected in Display selection when control output is off is displayed on the PV display. (See page 26.) (2) Input each setting value and each step time referring to Chapter. Operations (page 1ff). Then the PV display will indicate the actual temperature and the status turns standby. () Turn the load circuit power ON. () Program control start If Automatic start is designated in the Program start Auto/Manual designation (page 10), it will switch to warm-up status for approx. 2 seconds after the power is turned on, and then will automatically start the program control from step 1. If Manual start is designated in Program start Auto/Manual designation (page 10), it will switch to warm-up status for approx. 2 seconds after the power is turned on, and then it reverts to standby status. In this status, if the key is pressed, it starts the program control from the step 1. While the program control is being performed, the change of Step number (Setting value memory number) is ineffective. To end the program control during the process. The program control is ended if the key is pressed for approx. 1 second or longer. To change the displays. In the PV/SV display, if the key is pressed for approximately seconds, the Output manipulating value display mode is activated, and if the key is pressed again, the Step rest time display will be indicated (see page 29.). Instrument status when power failure is restored. When power is restored after a power failure occurs during program control, the performs the program continuously. The PV display blinks until the step at which the power failure occurs is finished. 5

ACTION EXPLANATIONS. Action explanations.1 Standard action Action Heating (reverse) action Cooling (direct) action Control action ON OFF Proportional band Proportional band ON OFF Setting Setting Relay contact 6 6 6 6 6 (*1) (*1) 6 Output Non-contact voltage 6 + 12Vdc 6 + 12/0Vdc (*1) 6 + 0Vdc 6 + 0Vdc 6 + 0/12Vdc (*1) 6 + 12Vdc Current Indicator [OUT] Green 6 + 20mAdc 6 + 20 to madc (*2) 6 + madc + madc + to 20mAdc (*2) 6 + 20mAdc Lit Unlit Unlit Lit 6 6 (*1) Cycle action is performed according to deviation. (*2) Changes continuously according to deviation. 6

ACTION EXPLANATIONS.2 ON/OFF action Action Control action ON OFF Heating (reverse) action Hysteresis Cooling (direct) action Hysteresis ON OFF Main setting Main setting Relay contact 6 6 6 6 Output Non-contact voltage 6 + 12Vdc 6 + 0Vdc 6 + 0Vdc 6 + 12Vdc Current 6 + 20mAdc 6 + madc 6 + madc 6 + 20mAdc Indicator [OUT] Green Lit Unlit Unlit Lit : Either ON or OFF. Pattern end action Program control end ON OFF [Time] Pattern end output is released by pressing OUT the OFF key. Unlit Lit Unlit Pattern end output is turned ON when the program control is ended, and it is not released until the key is pressed.

ACTION EXPLANATIONS. Alarm 1 (A1) and 2 (A2) actions High limit alarm Hysteresis Temperature alarm action Output Indication Temperature alarm action Output Indication Temperature alarm action Output Indication ON OFF ON OFF Main setting Alarm setting Unlit Lit High limit alarm with standby Hysteresis ON OFF Alarm setting Main setting Unlit Lit High/Low limits alarm Hysteresis Main setting Alarm setting Standby function works at part. and shows the action point of the alarm output. Output terminals for Alarm 2: 5 Alarm setting Lit Unlit Lit ON OFF ON OFF Low limit alarm Hysteresis Lit Unlit Low limit alarm with standby Hysteresis ON OFF Alarm setting Main setting Lit Unlit High/Low limit range alarm Hysteresis Unlit Alarm setting Alarm setting Lit Main setting Main setting Alarm setting Unlit 8

ACTION EXPLANATIONS Temperature alarm action Output Indication Temperature alarm action Output Indication Temperature alarm action Output Indication High/Low limits alarm with standby ON OFF Alarm setting Lit Unlit Lit Process high alarm Hysteresis ON OFF Alarm setting Unlit Lit Process high alarm with standby Hysteresis ON OFF Unlit Hysteresis Main setting Alarm setting Alarm setting Lit High/Low limit range alarm with standby Hysteresis ON OFF Unlit Alarm setting Process low alarm Hysteresis Alarm setting Main setting Lit Alarm setting ON OFF Unlit Lit Unlit Process low alarm with standby Hysteresis Lit Alarm setting Unlit ON OFF Standby function works at part. and shows the action point of the alarm output. Output terminals for Alarm 2: 5 9

CONTROL ACTIONS 8. Control actions 8.1 Fuzzy self-tuning Fuzzy self-tuning is a function to perform a fine adjustment of PID values automatically. The stable control can be carried out even if the conditions of the process are changed due to things like change in types and rates of production. (1) When the control is rising, the controller performs the control by the PID values tuned in advance. (2) When the control result is disordered by the disturbance or a change in the process, the controller checks the converging status, and performs a fine adjustment of PID values if necessary. (a) If the convergence is performed smoothly, the PID values are not changed. (b) If the convergent speed is slow, the controller corrects the PID values to accelerate the convergence. (c) When overshoot is generated during the convergence, the controller corrects the PID values so as not to generate the overshoot. (d) When hunting is generated, the controller checks the waveform and performs fine adjustment of PID values. () The controller can be used without Fuzzy self-tuning by designating the internal switch. () When using the controller for the first time, perform the PID auto-tuning or set the proper PID values by key operation. The instrument is always in self-tuning status itself, and when deviation is created, it starts the tuning. Even if in Fuzzy self-tuning status, when very large hunting is caused and the control is not stabilized, it starts auto-tuning automatically. When the auto-tuning performance is designated by the key operation, tuning is initiated, and when the control is stabilized, the auto-tuning is released and returns to self-tuning status. When lock mode [ ] or [ ] is designated, Fuzzy self-tuning or Auto-tuning PID action cannot work. With the control system in which load fluctuation periodically occurs, the Fuzzy self-tuning may fall into malfunction. In such a case, use the controller with the PID auto-tuning mode. 0

CONTROL ACTIONS 8.2 Explanations of PID (1) Proportional band (P) Proportional action is the action which the control output varies in proportion to the deviation between the setting value and the processing temperature. If the proportional band is narrowed, even if the output changes by a slight variation of the processing temperature, better control results can be obtained as the offset decreases. However, if the proportional band is narrowed too much, even slight disturbances may cause variation in the processing temperature, and control action changes to ON/OFF action and the so called hunting phenomenon occurs. Therefore, when the processing temperature comes to the balanced position near the setting value and a constant temperature is maintained, the most suitable value is selected by gradually narrowing the proportional band while observing the control results. (2) Integral time (I) Integral action is used to eliminate offset. When the integral time is shortened, the returning speed to the setting point is quickened. However, the cycle of oscillation is also quickened and the control becomes unstable. () Derivative time (D) Derivative action is used to restore the change in the processing temperature according to the rate of change. It reduces the amplitude of overshoot and undershoot width. If the derivative time is shortened, restoring value becomes small, and if the derivative time is made longer, an excessive returning phenomenon may occur and the control system may be oscillated. 1

CONTROL ACTIONS 8. PID auto-tuning of this controller In order to set each value of P, I, D and ARW automatically, the auto-tuning process should be made to fluctuate to obtain an optimal value. (1) When the difference between setting value and processing temperature is large when the temperature rises. The AT process will fluctuate at the temperature 1.5% of scaling span lower than the setting value. Setting value 1.5% of scaling span Temperature Controlling action is performed with the values set by PID auto-tuning. Time [Figure 8.-1] (2) When the control is stable or when control temperature is within ±1.5% of scaling span. The AT process will fluctuate around the setting value. Starting point of auto-tuning Setting value Temperature Controlling action is performed with the values set by PID auto-tuning. Time [Figure 8.-2] () When the control temperature is 1.5% or greater of scaling span higher than the setting value. The AT process will fluctuate at the temperature 1.5% of scaling span higher than the setting value. 1.5% of scaling span Setting value Temperature Controlling action is performed with the values set by PID auto-tuning. Time 2 [Figure 8.-]