Control panel B/B2. Package FM126 - Control panel B Package FM159 - Control panel B2. Technical instructions. Installation instructions

Similar documents
Package FT 74. X control panel. Installation and Service Manual

Control panel B - FM126 B2 - FM159. Installation and Service Manual

S3 standard control panel

Control panel (MD3) to be placed on the boiler (MD140) lateral control panel

Control panel K3. Package MD2. Technical instructions. Installation instructions. English 08/02/06

DIEMATIC 3 - FM129 DIEMATIC 3 CH - FM133

Control panel. Package RC 6. Installation and Service Manual A

Range GT GTU C GT 220

DTG X.. N. Low temperature gas furnace. Instructions for use. English 14/11/2005

B 150p to B 500p. Independent domestic hot water tanks. Installation instructions. Instructions for use. Technical instructions.

Wall-hung gas boilers. Instructions for use. English 31/08/05

C 310 ECO - C 610 ECO

TRIO DT 350/3 DIETRISOL. Solar domestic hot water tanks. Installation instructions. Instructions for use. Technical instructions.

WHE 2.24 / WHE 2.24 FF

Oil-fired condensing boiler GTU C 330. User Guide B

C 230 ECO. Control panel. DIEMATIC-m3 (GV6) Installation and Service Manual E

Gas-fired boilers DTG 230. User Guide D

installation and servicing

BSC...E - BSP...E - BESC...E

Low temperature gas boiler DTG 330 S. User Guide

DTG Eco / V130

ES 140/H ES 160/H ES 180/H ES 200/H ES 220/H ES 260/H ES 300/H ES 340/H ES 380/H

Installation, operating and servicing instructions

Elitec. DTG 1300 Eco.NOx/V. English 23/06/05. Gas-fired boilers. Technical instructions

Buccaneer G.T. Installation, Assembly and Servicing. Oil or Dual Gas Fired Boilers

EUROFLAT SERIES TYPES C... S... M...

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5

installation and servicing

ES 140/H ES 160/H ES 180/H ES 200/H ES 220/H ES 260/H ES 300/H ES 340/H ES 380/H

Installation and Instruction Manual

Service manual. Riva Plus HE. M296.28SR/C System boiler. Wall hung, fanflue, roomsealed, high efficiency gas boiler

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

DIEMATIC VM isystem WALL-MOUNTED CONTROL SYSTEM. DIMENSIONS Length: 320 mm Height: 260 mm Depth: 130 mm. POWER SUPPLY 230 V, 50 Hz, 6 A

Solar station DKP 6-8 / DKP Installation and Service Manual C

MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI

KIT UNITÀ AMBIENTE E INTERFACCIA A LED KIT ROOM UNIT AND LED INTERFACE RAUMGERÄT UND LED-SCHNITTSTELLE KIT APPAREIL D'AMBIANCE ET INTERFACE À LEDS

Service manual RIVA ADVANCE HE M110.24SM/C M110.32SM/C Wall hung, fan flue, room sealed, high efficiency gas boiler

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE:

SERVICE MANUAL RIVA COMPACT M90E.24S M90E.28S M90E.32S Wall hung, fan flue, room sealed gas boiler

Forced draught gas burner

EUROBOX SERIES TYPES CM... SM... MM...

CONTENTS PRODUCT GAS TYPE CONVERSION ADJUSTMENTS FAULT & FAILURE. Product Notation Safety Systems Technical Data Main Components Operating Functions

Gas fired condensing boiler C 230 ECO. User Guide C

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80

CORREX MP Anode with external voltage source. Installation & Operation Manual

Buccaneer G.T. Installation, Assembly and Servicing. Oil or Dual Gas Fired Boilers

Vivadens. Wall-hung gas condensing boilers MCR 24/28 BIC. User Guide B

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

HORIZONTAL COOKING SERIES: 700 / 900 S.A.V MAINTENANCE & AFTER SALES WORK PPS-3WE711911CH

USER'S INFORMATION MANUAL

LAE10 LFE10. Use. Series 02

Service manual GARDA HE MK2. M96A.24SM/B Combi boiler M96A.28SM/B Combi boiler

MICROFLAT SERIES TYPES C.../U T X

Instructions for installation and use RE/I. Industrial electric heater for swimming pool

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division

Baxi Maxflow Combi WM

Logic+ Combi

Quickheat 30 weather compensated boiler control

USERS GUIDE 24, 30. For installation guide see reverse of book

USERS GUIDE. LOGIC+ Combi 24, 30, 35

USER'S INFORMATION MANUAL

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

DOMESTIC HOT WATER Follow operational sequence

Wood-burning boiler CBB. User Guide E

USER'S INFORMATION MANUAL

1. GENERAL INSTRUCTIONS Carefully read the instructions contained in this instruction booklet and store booklet in a safe place.

Oil Burner Controls LOA3... Building Technologies HVAC Products

Installation Instructions VITOTRONIC 200

SERVICE MANUAL. Ecoboiler Model range: T20 ( ) T30 ( )

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model MICROGENUS PLUS. R EN - Edition 02-01/04/2007

EUROBOX SERIES TYPES CM...N SM...N MM...N

Energy-Efficient, Environmentally-Friendly Heating Solutions. Baxi Luna HT Residential Troubleshooting Guide

Wall-mounted compact indirect heat interface unit SATK30 series Safety instructions Dimensions Technical specifications Installation Commissioning

Solar regulator DIEMASOL C. Installation and Service Manual. User Guide G

Installation instructions. For the competent person. Installation instructions VRT 350 VRT 350 GB, IE

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

Flame Safeguards LFE10. Building Technologies HVAC Products

Service Instructions

LC3000 Level Controller Installation and Maintenance Instructions

Ecoboiler T20 & T30 SERVICE MANUAL. Marco Beverage Systems Ltd. 63d Heather Road, Sandyford Industrial Estate, Dublin 18, Republic of Ireland

INSTALLATION AND OPERATING INSTRUCTIONS KLIMA

AQUARIUS 45 MARINE SERVICE MANUAL

Brivis Service Manual

EX-TECH SIGNALLING SAS SD100-1 WEATHERPROOF SOUNDER/HORN TECHNICAL MANUAL

ADVANCE EASYLIFE PROJECT

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

2 Zone Kit code

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

LC2610 Level Controller Installation and Maintenance Instructions

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

Service manual. Riva Plus HE. M296.28SM/C Combi boiler. Wall hung, fanflue, roomsealed, high efficiency gas boiler

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

System Installation. multi-zone heating

1. COMMISSIONING OF THE BOILER en DESCRIPTION FUNCTION BUTTON DESCRIPTION SYMBOL DISPLAY

Rheem Australia Pty Ltd ABN

Transcription:

Control panel B/B2 Package FM126 - Control panel B Package FM159 - Control panel B2 English 17/01/06 Installation instructions Technical instructions

Contents Symbols used................................................................................3 Important recommendations...................................................................3 Description..................................................................................4 1 Introduction...............................................................................................4 2 Presentation..............................................................................................4 3 Technical characteristics....................................................................................5 Presentation.................................................................................6 Commissionning.............................................................................7 Assembly, electrical connections and installer's settings...........................................8 1 Control panel assembly.....................................................................................8 2 Connecting the boiler sensor.................................................................................8 3 Electrical connections.......................................................................................8 3.1 Basic connections................................................................................10 3.2 Connecting the options............................................................................12 4 Installer's settings.........................................................................................14 5 Deactivating hot water priority...............................................................................15 6 Heating accelerator timing..................................................................................16 7 Principle electrical diagram.................................................................................17 Alarm messages............................................................................19 Spare parts.................................................................................20 2 Control panel B/B2 17/01/06-300002725-001-C

Symbols used Caution danger Risk of injury and damage to equipment. Attention must be paid to the warnings on safety of persons and equipment Specific information Information must be kept in mind to maintain comfort Reference Refer to another manual or other pages in this instruction manual DHW: Domestic hot water Important recommendations For a proper operating of the boiler, follow carefully the instructions. Any intervention on the appliance and heating equipment must be carried out by a qualified technician. The manufacturer is not liable for any improper use of the appliance or failure to maintain or install the unit correctly (the user shall take care to ensure that the system is installed by a qualified fitter). Keep to the polarity shown on the terminals : phase (L), neutral (N) and earth. To guarantee protection against the corrosion of domestic hot water calorifiers fitted with a titanium anode (Titan Active System protection system), always leave the control panel switched on. To switch off the heating or the domestic hot water, use the Summer or Antifreeze mode. 17/01/06-300002725-001-C Control panel B/B2 3

Description 1 Introduction Electrical board for heating which includes the production of domestic hot water as a priority. The control panel B equips the boilers De Dietrich GT 120 / GT 220. The control panel B2 equips the boilers De Dietrich GT 220. 2 Presentation The control panel B, for controlling a 1-stage burner, includes: - 1 Boiler thermostat - 1 domestic hot water thermostat - The Titan Active System function for tank with titanium anode - 1 electronic thermostat - 1 Safety thermostat If 2 ambient thermostats are also added (option), the board allows 2 direct circuits to be controlled. The control panel B2, for controlling a 2-stage burner, includes: - 1 Boiler thermostat for 2-stage burner The 1st stage is controlled in relation to the setting of the electronic thermostat. The 2nd stage is controlled in relation to the setting of the electronic thermostat, offset by -4 C. If producing domestic hot water, the 2 stages are activated. - 1 domestic hot water thermostat - The Titan Active System function for tank with titanium anode - 1 electronic thermostat - 1 Safety thermostat By adding 1 room thermostat, it is possible to control 1 direct circuit. The boiler thermostat regulates the boiler operating temperature. The safety thermostat with manual reset ensures that the boiler operates safely. The standard delivery of panel B/B2 includes : - 1 Panel B/B2-1 boiler sensor measuring the temperature in the boiler The following options can be ordered : - Non settable ambient thermostat (Package AD 140) - Settable ambient thermostat (Package AD 137) - Wireless settable ambient thermostat (Package AD 200) - DHW sensor with Titan Active System simulation connector for the connection of a domestic hot water calorifier without titanium anode (Package AD 212) In the event that there is an abnormal rise in the temperature in the boiler 110 C. Advise your installation engineer. If domestic hot water is being heated, the domestic hot water thermostat allows the average temperature of the stored domestic hot water to be regulated giving priority to the preparation of domestic hot water. Whenever there is a demand for domestic hot water, the domestic hot water priority starts the burner and the dhw pump stops the heating pumps. On the summer setting, the boiler temperature is not maintained between two domestic loads. The temperature of the domestic hot water is measured with the dhw sensor. 4 Control panel B/B2 17/01/06-300002725-001-C

3 Technical characteristics Electricity supply : 230V (-10%, +10%) - 50 HZ Value of the water probes (Boiler and Domestic hot water) Temperature in C Resistance in ohm Temperature in C Resistance in ohm 0 C 32 014 Ω 50 C 3 661 Ω 10 C 19 691 Ω 60 C 2 535 Ω 20 C 12 474 Ω 70 C 1 794 Ω 30 C 8 080 Ω 80 C 1 290 Ω 40 C 5 372 Ω 90 C 941 Ω Compliance / Stamp This product complies to the requirements to the European Directives and following standards: - 73/23/EEC Low Voltage Directive - Reference Standard : EN 60.335.1-89/336/EEC Electromagnetic Compatibility Directive - Generic standards : EN1000-6-3 ; EN 61000-6-1 17/01/06-300002725-001-C Control panel B/B2 5

Presentation 1. General ON / OFF switch Position : Start Position : Stop 2. Alarm indicator This indicator lights up when the burner is on safety (faulty). 3. Summer / Winter switch "WINTER" position : Heating and domestic hot water working. "SUMMER" position : Only domestic hot water operating. If no accumulator is connected, the boiler remains off. The stopping of the heating accelorator is set at 12 minutes after moving to "Summer" mode. 4. Test-STB button Button kept pressed down, safety thermostat test cutting the pump(s). 5. Safety thermostat with manual reset Set at 110 C 6. Control panel B: Timed circuit breaker (4 A) Control panel B2: Timed circuit breaker (6 A) 7. Electronic thermostat Set the boiler temperature between 30 C and 90 C using manual setting 8. Indicator lights up Boiler temperature display When preparing domestic hot water 9. Indicator lights up Domestic hot water display 10. Electronic thermostat Regulating the storage temperature of domestic hot water between 10 C and 80 C After switching on, the system performs an automatic purge of the accumulator interchanger for one minute by intermittently operating the domestic load pump and the heating pump. This purge sequence is deactivated if the temperature in the accumulator is above 25º C 6 Control panel B/B2 17/01/06-300002725-001-C

Commissionning The first start-up is to be performed by your installation engineer Before starting the boiler, check if the installation is filled with water Start the boiler in the following order : - Place the boiler thermostat 7 in the required position. If necessary, change the position of the maximim temperature. - When preparing domestic hot water: Place thermostat 10 on the required setting. Setting 6 (approx 60 C) recommended. This value must always be below the temperature limiter for the domestic hot water load. - Check that safety thermostat 5 is properly set. To do so, Unscrew the safety thermostat cover and press the reset button using a screwdriver. - Place the Summer / Winter switch 3 on Winter. - Place the Stop /Start 1 switch on Start. 17/01/06-300002725-001-C Control panel B/B2 7

Assembly, electrical connections and installer's settings 1 Control panel assembly Refer to the technical and assembly instructions delivered with the boiler. 2 Connecting the boiler sensor Refer to the technical and assembly instructions delivered with the boiler. 3 Electrical connections Only qualified professionnals may carry out electrical connections, always with the power off. As the electrical wiring has been carefuly checked in the factory, the internal connections on the control panel must not be changed in any way. Electrical connections must match the electrical diagrams delivered with the equipment and comply with the instructions in the manual. The equipment must have a power supply equipped with a omnipolar switch with an opening distance above 3 mm. The earth must comply with the NFC 15.100 (France) or the RGPT (Belgium) standards. GT 120 Power supply 230 V Sensors Cable clamps All connections are made with the terminal boxes designed for that purpose on the back of the boiler's command board. The connection cables enter the boiler via the openings on the back panel, these openings may be used later for cable guides. These cables will be fixed on to the control panel with cable clips (supplied in a separate bag). GT 220 8 Control panel B/B2 17/01/06-300002725-001-C

The available output per outlet is 450 W (with cos ϕ = 0,7) and the inrush current must be lower than 16 A. The sensor cables have to be separated from the 230V circuit cables. In the boiler : use the 2 wire guides on either side of the boiler. Outside the boiler : use 2 pipes or cable guides at least 10 cm apart. All electrical connections are made on the marked bars located under the boiler's card screen. Power supply connection is made using a 3 wire cable with a 1,5 mm² diameter on the 3 plot bar (terminals 1, 2, 3) located under the boiler's card card. For other electrical connections, use the 3 wire cable with a diameter of 0,75 mm². Keep to the polarity shown on the terminals : phase (L), neutral (N) and earth. 17/01/06-300002725-001-C Control panel B/B2 9

3.1 Basic connections Control panel B 1 Power supply 230 V 2 Heating pump Circuit A 3 Dhw pump 4 Boiler sensor 5 Domestic hot water sensor 6 Titane anode 7 Boiler with or without accumulator 8 Boiler with accumulator 9 Heating pump Circuit B 10 Control panel B/B2 17/01/06-300002725-001-C

Control panel B2 1 Power supply 230 V 2 Heating pump Circuit A 3 Dhw pump 4 Boiler sensor 5 Domestic hot water sensor 6 Titane anode 7 Boiler with or without accumulator 8 Boiler with accumulator The sensor cables have to be separated from the 230V circuit cables. In the boiler : use the 2 wire guides on either side of the boiler. Outside the boiler : use 2 pipes or cable guides at least 10 cm apart. 17/01/06-300002725-001-C Control panel B/B2 11

3.2 Connecting the options Control panel B 1 Remove bridge 2 Safety contact 3 Alarm indicator 4 Room thermostat Circuit A 5 Boiler with or without accumulator 6 Room thermostat Circuit B If only one circuit is used, connect the ambient thermostat to circuit A and do not bridge this connector. Connection to a flue gas thermostat (TF) When used in combination with a wood fired boiler : the flue gas thermostat is connected on the terminals (CS) after having removed the existing bridge. Safety contact connection (CS) Terminals (CS) after having removed the bridge : allows the connection of a safety device (e.g. low water pressostat, fire safety,...). 12 Control panel B/B2 17/01/06-300002725-001-C

Control panel B2 1 Remove bridge 2 Safety contact 3 Alarm indicator 4 Room thermostat Circuit A 5 Boiler with or without accumulator Connection to a flue gas thermostat (TF) When used in combination with a wood fired boiler : the flue gas thermostat is connected on the terminals (CS) after having removed the existing bridge. Safety contact connection (CS) Terminals (CS) after having removed the bridge : allows the connection of a safety device (e.g. low water pressostat, fire safety,...). The sensor cables have to be separated from the 230V circuit cables. In the boiler : use the 2 wire guides on either side of the boiler. Outside the boiler : use 2 pipes or cable guides at least 10 cm apart. 17/01/06-300002725-001-C Control panel B/B2 13

4 Installer's settings The settings below have different functions and configure the installation. They may only be changed by a qualified professionnal. Access to the potentiometers for setting the domestic hot water pump timer and the domestic hot water load temperature limiter. Take out the 2 nuts and bolts from the back of the boiler. Remove the upper panel from the boiler. 60 90 The potentiometer ( ) on the boiler's flat bar allows the temperature of the boiler to be regulated whilst the hot water is being heated. The load temperature setting may be between 60 and 90 C (factory setting 75 C). Setting the timer for the domestic hot water pump The potentiometer ( ) on the boiler's flat bar allows the timing of the domestic hot water pump to be set. 0 10 The timer has a setting range from 0 to 10 minutes (factory setting 4 minutes). Assembly When the setting has finished, assemble the protective cover for the bars and the upper panel in the reverse order as disassembly. Do not leave out the toothed washers. Loosen the protection for the flat bars on either side. Disassemble the protective cover from the flat bars. Set the domestic hot water load temperature limiter 14 Control panel B/B2 17/01/06-300002725-001-C

5 Deactivating hot water priority When the domestic hot water priority is deactivated, the heating is not cut off during the hot water heating phases. GT 120 Cut the power supply to the boiler. Lift up the glass. Unscrew the 2 holding screws located on the side panels. Take out the front panel from the clips and from the notches, by pulling it towards you. Take oput the panel from the notches at the bottom of the side panels. Turn the panel. Take out the shunt (bridge). Reclose the command box and replace the front panel in the reverse order.. Turn the screw on the front panel of the command box. 17/01/06-300002725-001-C Control panel B/B2 15

GT 220 Remove the front panel (lift and pull). Lift up the glass. Turn the screw on the front panel of the command box. Turn the panel. Take out the shunt (bridge). Reclose the command box and replace the front panel in the reverse order. 6 Heating accelerator timing The timer for the heater accelorator is set at 12 minutes after the ambient thermostat closing or when moving into summer mode. If there are two accelerators connected with two ambient thermostats, the timer is deactivated while the circulation pump is working. 16 Control panel B/B2 17/01/06-300002725-001-C

7 Principle electrical diagram Control panel B θ 2 1 DJ4A 1a 1 TS 3 Â Ã 1 1a 2 ZG 2a 1 TEST STB ZT 1a 1b 1b 1a 2b ZEH 2a 1b VA ZT 2 TEST STB 1 2 1a 2a 2b J3 1 J3 2 J3 3 J3 4 J3 5 J3 8 J3 7 J3 6 J3 9 J2 2 J2 1 J2 3 J2 4 J2 5 J3 10 FA T RL BR RL ECS RL PA RL PB Alim 230 V-50Hz L N Ä Ã L N Ä A Ä B TAM A L N L N À Á TAM B À Á VA CS N L J1 6 J1 4 J1 3 J1 5 J1 1 J1 2 S CH 1 2 S ECS 1 2 T A + - θ C θ C B4 N S3 T2 T1 L1 Ë Ä A ACCELERATEUR CIRCUIT A Ä Ã POMPE DE CHARGE Ä B ACCELERATEUR KESSELKREISPUMPE KREIS A SPEICHERLADEPUMPE KESSELKREISPUMPE RL PA RELAIS DE COMMANDE ACCELERATEUR CIRCUIT A RL PB RELAIS DE COMMANDE ACCELERATEUR CIRCUIT B S CH SONDE CHAUDIERE HEIZUNGSPUMPE STEUERRELAIS KREIS A HEIZUNGSPUMPE STEUERRELAIS KREIS B KESSELFÜHLER Ä A HEATING PUMP CIRCUIT A Ä Ã LOAD PUMP Ä B HEATING PUMP VERWARMINGSPOMP KRING A LAADPOMP VERWARMINGSPOMP RL PA HEATING PUMP CONTROL RELAY CIRCUIT A RL PB HEATING PUMP CONTROL RELAY CIRCUIT B S CH BOILER SENSOR VERWARMINGSPOMPE RELAIS KRING A VERWARMINGSPOMPE RELAIS KRING B KETEL VOELERS CS CONTACT DE SECURITE DJ4A DISJONCTEUR Ë BRULEUR SICHERHEITSKONTAKT LEISTUNGSSCHALTER BRENNER S ECS SONDE EAU CHAUDE WARMWASSERFÜHLER SANITAIRE T A ANODE A COURANT IMPOSE FREMDSTROMANODE TAM. THERMOSTAT D' AMBIANCE RAUMTHERMOSTAT CS SAFETY CONTACT DJ4A CIRCUIT BREAKER Ë BURNER VEILIGHEIDSCONTACT THERMISCHE BEVEILIGING BRANDER S ECS DOMESTIC HOT WATER SENSOR T A ELECTRIC ANODE TAM. ROOM THERMOSTAT SANITAIR WARM WATER VOELERS CORROSIEBESCHERMINGSAN ODE KAMERTHERMOSTAAT FA J. L N FILTRE ANTIPARASITE CONNECTEUR CIRCUIT IMPRIME PHASE NEUTRE FUNKENENSTÖRUNGSFILTER LEITERPLATTE STECKER PHASE NULLEITER TS VA ZEH ZG THERMOSTAT DE SECURITE SICHERHEITSTEMPERATURB EGRENZER VOYANT ALARME ALARMLEUCHTE INTERRUPTEUR ETE-HIVER SOMMER-WINTERSCHALTER INTERRUPTEUR GENERAL HAUPTSCHALTER FA J. L N EMI SUPPRESSOR PRINTED CIRCUIT BOARD PLUG PHASE NEUTRAL ONSTORINGS-FILTER AANSLUITKLEM FASE NULLEIDER TS VA ZEH ZG SAFETY THERMOSTAT ALARM INDICATOR SUMMER-WINTER SWITCH MAIN SWITCH VEILIGHEIDSTHERMOSTAAT ALARM LAMPJE ZOMMER-WINTER SCHAKELAAR ALGEMENE SCHAKELAAR RL BR RELAIS DE COMMANDE BRULEUR RL RELAIS DE COMMANDE ECS POMPE DE CHARGE BRENNER STEUERRELAIS SPEICHERLADEPUMPE STEUERRELAIS ZT INTERRUPTEUR TEST TESTSCHALTER RL BR BURNER CONTROL RELAY BRANDER RELAIS RL LOAD PUMP CONTROL RELAY RELAIS STURING LAADPOMP ECS ZT TEST SWITCH TEST SCHAKELAAR Plan n : 300001532-001-B 17/01/06-300002725-001-C Control panel B/B2 17

Control panel B2 Â Ã DJ 6A θ 2 2 1 ZG 1 1a 1 TEST STB ZT ZEH 1 1 TS 3 2 TEST STB ZT 2a 1a 1a 1b 1a 2a 2b 2 1 J1 J1 J1 3 J1 7 J1 8 J1 5 J1 6 J1 9 J1 11 J1 10 J1 4 RL BR1 RL PA RL ECS RL BR2 Alim 230 V-50Hz N L N Ä A L Ä Ã N L TAM A À Á J2 6 J2 7 N VA L J2 4 J2 2 J2 1 CS J2 3 J3 1 J3 2 J3 3 T A + - S ECS 1 2 S CH 1 2 VA 1a 1b θ C θ C B N B4 B5 S3 L1 T1 T2 T6 T7 T8 1 2 Ä A Ä Ã ALI B CS DJ6A J- L N RL BR1 RL BR2 RL ECS RL PA S CH S ECS T A TAM A TS VA ZEH ZG ZT ACCELERATEUR CIRCUIT A POMPE DE CHARGE ALIMENTATION BRULEUR CONTACT DE SECURITE DISJONCTEUR CONNECTEUR CIRCUIT IMPRIME PHASE NEUTRE RELAIS DE COMMANDE BRULEUR 1ere ALLURE RELAIS DE COMMANDE BRULEUR 2e ALLURE RELAIS DE COMMANDE POMPE DE CHARGE RELAIS DE COMMANDE ACCELERATEUR SONDE CHAUDIERE SONDE EAU CHAUDE SANITAIRE ANODE A COURANT IMPOSE THERMOSTAT D'AMBIANCE THERMOSTAT DE SECURITE VOYANT ALARME INTERRUPTEUR ETE-HIVER INTERRUPTEUR GENERAL INTERRUPTEUR TEST KESSELKREISPUMPE KREIS A SPEICHERLADEPUMPE NETZANSCHLUSS BRENNER SICHERHEITSKONTAKT LEISTUNGSSCHALTER LEITERPLATTE STECKER PHASE NULLEITER BRENNER STEUERRELAIS 1.STUFE BRENNER STEUERRELAIS 2.STUFE SPEICHERLADEPUMPE STEUERRELAIS HEIZUNGSPUMPE STEUERRELAIS KESSELFÜHLER WARMWASSERFÜHLER FREMDSTROMANODE RAUMTHERMOSTAT SICHERHEITSTEMPERATURBEGRENZER ALARMLEUCHTE SOMMER-WINTERSCHALTER HAUPTSCHALTER TESTSCHALTER Ä A Ä Ã ALI B CS DJ6A J- L N RL BR1 RL BR2 RL ECS RL PA S CH S ECS T A TAM A TS VA ZEH ZG ZT HEATING PUMP CIRCUIT A LOAD PUMP MAIN SUPPLY BURNER SAFETY CONTACT CIRCUIT BREAKER PRINTED CIRCUIT BOARD PLUG PHASE NEUTRAL BURNER 1st STAGE CONTROL RELAY BURNER 2nd STAGE CONTROL RELAY LOAD PUMP CONTROL RELAY HEATING PUMP CONTROL RELAY BOILER SENSOR DOMESTIC HOT WATER SENSOR ELECTRIC ANODE ROOM THERMOSTAT SAFETY THERMOSTAT ALARM INDICATOR SUMMER-WINTER SWITCH MAIN SWITCH TEST SWITCH VERWARMINGSPOMP KRING A VUL POMP VOEDING BRANDER VEILIGHEIDSCONTACT THERMISCHE BEVEILIGING AANSLUITKLEM FASE NULLEIDER BRANDER RELAIS 1st TRAP BRANDER RELAIS 2nd TRAP RELAIS STURING VUL POMP VERWARMINGSPOMPE RELAIS KETEL VOELERS SANITAIR WARM WATER SENSORS CORROSIEBESCHERMINGSANODE KAMERTHERMOSTAAT VEILIG HEIDS THERMOSTAAT ALARM LAMPJE ZOMMER-WINTER SCHAKELAAR ALGEMENE SCHAKELAAR TEST SCHAKELAAR PLAN n 300007073-001-B 18 Control panel B/B2 17/01/06-300002725-001-C

Alarm messages In the event of a fault, the display may show the following messages : Message Faults Probable causes Solution AL 50 AL 52 Boiler sensor Domestic hot water sensor The sensor is cut or has short circuit. Advise the installer. See comments below. AL td AL tc Titane anode The titanium anode is on an open circuit or the tank is empty. A short circuit has occurred on the titanium anode or connection reversed. Check that the titane anode is properly connected or fill the dhw tank. Check that there is no short circuit or an inversion of the wires of the titane anode. Operation mode in the event of a fault : AL 50 : The installation is stopped. AL 52 : In the event of a fault with the domestic hot water probe, the installation continues to operate, but heating the domestic hot water is no longer guaranteed. AL td and AL tc : Production of domestic hot water is stopped. This may be reactivated for 24 hours by disconnecting and reconnecting the power supply to the boiler. There are 2 options : - With a domestic hot water tank protected by a titane anode : the tank is no longer protected against corrosion. This will mean that the accumulator is no longer protected. Contact NECESSARELY your installation engineer. - With a domestic hot water tank protected by a magnesium anode : check that the connector delivered with AD212 package is placed on the sensor p.c.b.. Check that the AD212 container connector, with the 22 kohm resistance and a 100 nf capacitor, is properly connected to terminals 25 26. 17/01/06-300002725-001-C Control panel B/B2 19

Spare parts To order a spare part, quote the reference number next to the part required. Control panel B with Titan Active System function for GT120 / GT220 17/01/06-300002725-002-C DE DIETRICH THERMIQUE S.A.S. - Spare parts centre 4, rue d Oberbronn - F-67110 REICHSHOFFEN - Tél. : (+33) 03 88 80 26 50 - Fax : (+33) 03 88 80 26 98 cpr dedietrichthermique.com

Control panel B Rep Code no. Description 1 100001620 Standard complete control panel 2 200001651 Standard card cover 3 9786-4038 Plastic coated panel 4 9532-5027 Green S/S bipolar switch 5 8500-0035 Bipolar switch 6 9532-5028 Bipolar inversor switch 7 8500-0032 Safety thermostat 110 C 8 9534-0288 Circuit breaker 4A TS710/4A 9 8559-5507 Setting button 10 9521-6220 Red indicator 11 200000243 Basic UC display card 12 9752-5378 Card support 13 8575-4945 Burner cable 14 9531-7395 Burner connector 15 8806-5564 Basic relay card 16 200001789 Standard beam 17 9532-0187 Cable clamps 18 200000625 Connector assembly with label 19 9536-2446 KVT sensor 60 l. 1 m 20 8575-4905 3-bridge pwer supply connector, assembled 21 8575-4922 4-bridge VA+CS connector, assembled 22 8575-4924 Connector 3 pt assembled pump A/VS 23 8575-4926 Connector 3 pt assembled auxiliary pump 24 8575-4920 Connector 2 pt assembled TAM 25 8575-4949 Connector 2 pt assembled TAM B 17/01/06-300002725-001-C Control panel B/B2 21

Control panel B2 with Titan Active System function for GT220 22 Control panel B/B2 17/01/06-300002725-001-C

Control panel B2 Rep Code no. Description 1a 100004376 Standard complete control panel 2a 200004950 Standard card cover 3 9786-4038 Plastic coated panel 4 9532-5027 Green S/S bipolar switch 5 8500-0035 Bipolar switch 6a 8500-0034 Test Switch 7 8500-0032 Safety thermostat 110 C 8a 9534-0285 Circuit breaker 6A 9 8559-5507 Setting button 10 9521-6220 Red indicator 11a 200005084 Basic UC display card 12 9752-5378 Card support 13a 200004753 Burner cable 1 stage 14 9531-7395 Burner connector 15a 200004948 Basic relay card 16a 200004772 Standard beam 17 9532-0187 Cable clamps 18 200000625 Connector assembly with label 19 9536-2446 KVT sensor 60 l. 1 m 20 8575-4905 3-bridge pwer supply connector, assembled 21 8575-4922 4-bridge VA+CS connector, assembled 22 8575-4924 Connector 3 pt assembled pump A/VS 24 8575-4920 Connector 2 pt assembled TAM 27 200004754 Burner cable 2nd stage 28 9531-7384 4-pin plug 29 9532-0532 Feed through 30 9655-0352 Beam mounting FTH15 17/01/06-300002725-001-C Control panel B/B2 23

FR DE DIETRICH THERMIQUE S.A.S. www.dedietrich.com Direction des Ventes France 57, rue de la Gare F- 67580 MERTZWILLER +33 (0)3 88 80 27 00 +33 (0)3 88 80 27 99 AT DE DIETRICH HEIZTECHNIK www.dedietrich.com Am Concorde Park 1 - B 4 / 28 A-2320 SCHWECHAT / WIEN +43 (0)1 / 706 40 60-0 +43 (0)1 / 706 40 60-99 office@dedietrich.at In the interest of customers, De Dietrich Thermique SAS are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice DE BE CH DE DIETRICH HEIZTECHNIK www.dedietrich.com Rheiner Strasse 151 D- 48282 EMSDETTEN +49 (0)25 72 / 23-5 +49 (0)25 72 / 23-102 info@dedietrich.de VAN MARCKE www.vanmarcke.be Weggevoedenlaan 5 B- 8500 KORTRIJK +32 (0)56/23 75 11 VESCAL S.A. www.chauffer.ch / www.heizen.ch Z.I de la Veyre, St-Légier 1800 VEVEY 1 +41 (0)21 943 02 22 +41 (0)21 943 02 33 LU RU CN NEUBERG S.A. www.dedietrich.com 39 rue Jacques Stas L- 2010 LUXEMBOURG +352 (0)2 401 401 DE DIETRICH www.dedietrich.com 8 Gilyarovskogo Str. 7 R- 129090 MOSCOW +7 495.974.16.03 +7 495.974.66.08 dedietrich@nnt.ru DE DIETRICH www.dedietrich.com Room 512, Tower A, Kelun Building 12A Guanghua Rd, Chaoyang District C-100020 BEIJING +86 (0)106.581.4017 +86 (0)106.581.4018 +86 (0)106.581.7056 +86 (0)106.581.4019 contactbj@dedietrich.com.cn AD001Z 02.2006 DE DIETRICH THERMIQUE 57, rue de la Gare F- 67580 MERTZWILLER - BP 30 www.dedietrich.com