Version Inc Series Digital Gas Detector/Controller. Operation Manual

Similar documents
Inc Series Digital Gas Detector/Controller. Operation Manual

Version Digital Gas Dector/Controller. Operation Manual

Version Digital Gas Detector/Controller. Operation Manual

Ammonia Leak Detector Manual

Refrigerant Leak Detector Manual

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Two-Channel Gas Controller

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

Warranty Registration

Danfoss gas detection units

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Carbon Monoxide Transmitter

SIL 2. Ultima X Series Gas Monitors CERTIFIED

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

User Manual. PolyGard Gas Controller MGC3. Two-Channel Analog Gas Controller Serial Number _E _0907. September 2007

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

GLD-30 Gas Leak Detector

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Danfoss gas detection units

Combustible Gas Detection and Control System

Product Manual SZ1144

Product Manual SZ1145

Carbon Monoxide CO Transmitter ADT-X3-1110

Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases

Oxygen (O2) Single-Point Gas Detection System

Carbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features.

GAS DETECTION SYSTEMS

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Macurco DVP-120 / DVP-120M Detection and Ventilation Control Panel User Instructions

Toxic Gas Detection. Model F12. Toxic Gas Detection

Danfoss gas detection unit Type GD Heavy Duty

CN7232 Advanced Garage Ventilation Controller

GAS PLUS ALARM SYSTEM

Operation Manual. Rev. D GEM-II Self-Contained Gas Detector.

Macurco DVP-120 Detection and Ventilation Control Panel

EXAMPLES OF HOW TO ORDER

EXAMPLES OF HOW TO ORDER

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

MODEL 4300-PG CENTRAL ACCESS PANEL FOR EC-GOLD TRANSMITTERS. User Manual

Detection, Protection, Innovation

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. SIL1 reliability. Gas Detection Control Panel

Model D12-IR. Digital Gas Transmitter...

INSTALLATION AND OPERATING INSTRUCTIONS

Universal Gas Detector

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

GasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability

Analog Room Pressure Monitor RPC Series

Operation Manual. Rev. E GEM-II Self Contained Gas Detector.

Air Check O 2 Deficiency Monitor 0-25%

PureAire Combo O 2 / CO 2 Monitor

ALTAIR 5X Multigas Detector Product Specification

ZSC100 Gas Detection and Alarm System Controller

ESD3000 ESD200 Combustible / Toxic Gas Detector

GAS DETECTION SYSTEMS

Air Check O 2 Sample Draw Monitor

Air Check O 2 Remote Monitor 25%

3M Oldham MX 43 Controller

Frequently Asked Questions

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006

Air Check Ex O 2 Deficiency Monitor

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

CLEANROOM MONITOR CR3A Network - Installation Instructions

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

Air Check O 2 Deficiency Monitor 0-25%

Gas Detection System TOX ALARM DG2000-Garage

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

EAGLE 2. 6 Channel Capacity. Inlet fitting. Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility

SEC 2000 Millenium Infrared Gas Detector

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual

ESD500. ESD500 Combustible / Toxic Gas Detector

Introduction. What is the W2W Open controller?

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

APPLICATION DATA SHEET

Gas detecting sensor Types GDA, GDC, GDHC, GDHF, GDH

INSTALLATION AND OPERATION INSTRUCTIONS Before Installing or Operating, Read and Comply with These Instructions

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

GAS DETECTION MANUFACTURED BY. Aerionics, Inc. Sioux Falls, SD Phone:

Guidelines for the Design Engineer

Air Check O 2 Deficiency Monitor

RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL. USER MANUAL Read carefully before use

User Manual. PolyGard Single Point Controller SPC-43-20XX. Single Point Gas Controller for Refrigerant Gases Serial Number _E_.

Ventostat Wall Mount. Amphenol Advanced Sensors. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. Features:

Operation Manual. Rev. I SCC Self Contained Controller.

Networkable Fan Coil Controller Specification and Installation Instructions

Air Check O 2 Sample Draw Monitor

AT-G-SENSE Gas Sensing System

Pioneer-R16 Gas Monitor Operator s Manual

FIXED POINT SINGLE OR DUAL GAS MONITOR WITH DUAL ANALOG OUTPUTS

Oxygen Monitor Operating Manual

Table of Contents. WSHP Open v3

Fixed Gas Detector User Manual Installation Operation Configuration Troubleshooting

M2 Transmitter Operator s Manual

Transcription:

6000 Series Digital Gas Detector/Controller Version 000.02 Operation Manual

TABLE OF CONTENTS 1.0 2.0 3.0 4.0 5.0 6.0 General Description 1.1 Applications 1.2 Features 1.3 Outputs 1.4 User Interface Model Selection Guide Installation 3.1 Wiring 3.2 Installation Guide Operation 4.1 Screen Display 4.2 Default Settings 4.3 Changing Settings 4.4 List of Settings Network Configuration 5.1 Using Central Controller 5.2 Using No Central Controller 5.3 Defaults Configuration 5.4 Addresses 5.5 Creating Zones or Groups 5.6 Output Relays Maintenance Guide 6.1 Quick Test Caution 6.2 Calibration Procedure

1.0 General Description 1.0 GENERAL DESCRIPTION The Opera series 6000 gas detectors offer commercial building owner s the precision to assure the health and safety to occupants with the tightest possible controls on energy consumption. It is a versatile, self-contained dual gas sensor that is ready for either peer-to-peer (master slave) operation or central control for a smooth integration into new or existing energy management systems. 1.1 Applications: Vehicle Emissions Combustible Gases Refrigerant Gas Leak Detection Industrial Health and Safety 1.2 Features: Stand-alone operation with 1 or 2 adjustable alarm relays, indicators and strobe BTL listed Smart Sensor BACnet MS/TP RS485 interface CAN interface for master-slave operation or central control Pre-calibrated plug-and-play sensor modules Impact resistant water proof enclosure

1.0 General Description 1.3 Outputs Digital s CAN for central control or peer-to-peer BACnet MS/TP RS485 (BTL listed) Relays (2 on model 6000-B, 1 on model 6000-A) On delay; seconds (16 minutes) Off delay; seconds (16 minutes) 1.4 User Interface: Back lit LCD display shows gas concentration, user settings, calibration controls Red LED alarm indicators, level 1 and 2 High intensity white LED strobe on level 3 Audible alarm, 85 db at 1 meter 4 pushbutton user keypad Password control for settings

2.0 Model Selection Gudie 2.0 MODEL SELECTION GUIDE Example: Complete part number 6 0 0 2-1 4 - B Gas Type If second sensor installed Controller 6000 Gas Type B = (BACnet Version) A = (Analog Version) NH 3 Ar C 4 H 10 CO 2 CO 2 CO CO CO H 2 nil CL 2 C 2 H 4 (OH) 2 C 2 H 5 OH He H 2 O in air H 2 H 2 S C 4 H 10 C 3 H 7 OH CH 4 CH 3 OH NO 2 VOCs O 2 C 3 H 8 Ammonia Argon (O 2 depletion) Butane Carbon Dioxide Carbon Dioxide Carbon Monoxide Carbon Monoxide Carbon Monoxide Chlorine Ethylene glycol Ethanol HCFCs HFCs Helium (O 2 depletion) Humidity (relative) Hydrogen Hydrogen sulfide Iso-butane Iso-propyl Alcohol Methane Methanol Nitrogen (oxygen depletion) Nitrogen dioxide Organic Vapors Oxygen Propane Gas Type 04 23 05 15-2000 15-5000 02 02-250 02H2nil 17 01 01 13 20 23 25 08 16 05 01 05 01 23 14 01 22 06 Range 0-250 ppm 0-50% O 2 0-50% LEL 0-2000 ppm 0-5000 ppm 0-100 ppm 0-250 ppm 0-100 ppm 0-10 ppm 0-1000 ppm 0-1000 ppm 0-25% O 2 0-100% RH 0-50% LEL 0-50 ppm 0-50% LEL 0-1000 ppm 0-50% LEL 0-1000 ppm 0-50% O 2 0-10 ppm 0-1000 ppm 0-50% O 2 0-50 % LEL

3.0 Installation 3.0 INSTALLATION 3.1.1 Wiring Model 6000-B Bacnet Version EOL EOL AL1 AL2 NO C NC NO C NC G AC+ AC- S L H S + - 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 BACnet MSTP communication - BACnet MSTP communication + BACnet MSTP communication shield (no connect) 24V or 120V N L Transformer 120/24v Use class 2 type 5 va for each unit N L Independant circuit 120 vac CAN communication high CAN communication low CAN communication shield (on first unit only) To other detectors To magnetic starter coil or control relay coil for local control

3.0 Installation 3.1.2 Installation, Wiring Model 6000-A Analogue Version 4-20 4-20 EOL EOL AL1 NO C NC AN1 G AN2 AC+AC- BI S L H S + - 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 BACnet MSTP communication - BACnet MSTP communication + BACnet MSTP communication shield (no connect) Transformer 120/24v Use class 2 type CAN communication high CAN communication low CAN communication shield (on first unit only) Input for limit switch 24 vac or 120 vac 5 va for each unit N L Independant circuit 120 vac To other detectors OUTPUT 4-20 ma (2-10V) to controller, Sensor A Ground 4-20 ma (2-10V) to controller, Sensor B N L To magnetic starter coil or control relay coil for local control

3.0 Installation 3.2 Installation Guidelines All wiring must conform to local building codes, regulations and laws. 1. 2. 3. 4. 5. Use ½ in EMT conduit for all wiring. Install enclosed 120/24 vac transformer, 5 va per sensor or controller, using 18 to 20 AWG two conductor wire. Do not tie the secondary to ground. Connect multiple sensors. Ensure that the polarity of the connections are the same at each sensor or controller. Connect relay contacts (usually relay 1) to ventilation system. Use a magnetic starter so that the sensor contacts energize the starter coil and not the fan motor directly. For multiple sensors, chain a shielded twisted pair cable 20 to 24 AWG from screw 6 and 7 on one sensor, to the next and continue chain to the last sensor. Maintain the same polarity on each unit. Do not use star configuration. T connections should be less than 3 meters (10 feet) from the chain. Best to make all chain connections at the sensors to avoid T connections. Move the end-of-line jumper (the first one on the left) to the on position (UP) on the first sensor, or controller, on the chain and the last sensor/controller on the chain. A controller can be located anywhere on the chain. Ensure its EOL jumper is off if it is in the middle. Any address assigned to a sensor/controller can be in any location on the chain.

3.0 Installation 3.2 Installation Guidelines (Continued) 6. 7. Power on the units. They will display the gas type and reading. To verify if the sensors are communicating correctly, change setting no. 56 from 0 to 1 to turn on the display. Press and simultaneously to save then press and hold for a few seconds. The unit will display each sensor connected. If the unit does not display the other sensors scrolling by, check the following; each unit has a unique address, setting 39, with no duplicates end-of-line jumpers are set on units at ends of cable only polarity of the communication cable and the 24 vac wire connections for shorts, etc. To test communication, press and hold the up button on sensor for 5 seconds to start manual mode (5 minutes). This will close the relay 1 on that unit and all of the other units on the.

4.0 Operation 4.0 OPERATION 4.1 Screen Display The LCD shows the type of gas and the current gas concentration, depending on the model of sensor module plugged in. If two sensor modules are installed, the display will alternate between them. Address (See setting 56) State of the alarms Type of gas Concentration The bottom left corner will also display the alarm status; 1 indicates alarm 1 on, according to the settings 0, 1, 2 or activated by another sensor on the CAN via setting 36. This is usually the low gas level alarm. 2 indicates alarm 2 on. Per settings 3, 4, 5 or if activated by another sensor on CAN per setting 37. 3 indicates alarm 3 on. Per settings 6, 7, 8 or if activated by another sensor on CAN per setting 38.

4.0 Operation M indicates manual override mode active. Useful to start ventilation system without the risk of leaving it on (and freezing the space in winter). Press and hold for 5 seconds to start manual mode. Then click again to increase time from 5 to 60 minutes. This activates alarm 1, 2, or 3 (per setting 69) and sends alarm transmit messages in settings 9-17. The unit will return to automatic operation after the time runs down. To cancel manual mode press several times to reduce time left to run. It will take a few seconds to stop. T indicates alarm 1 on due to high ambient temperature, setting 51. Useful for summer ventilation. 4.2 Default Settings User settings are factory pre-loaded with default values to facilitate set up and can be changed at any time. Upgrading firmware will not affect user settings. Alarm thresholds should be set to suit local regulations. Default values for these are general guidelines only. 4.3 Changing Settings Press and to move through the settings. If the keypad lock is on then enter the password first. The screen will display the setting number 0, 1, 2, etc plus the short description (eg; AL1) and the current setting value. Press the or buttons to increase or decrease the setting. To save, press and buttons at the same time. The word OK will appear. If you do not see OK and the new value it is because the buttons were not pressed simultaneously. Try again.

4.0 Operation 4.4 List of Settings Sensor A (top socket) settings No. Name 0 AL1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 A1Del A1Off AL2 AL2Del AL2Off AL3 A3Del A3Off A1Tx A1Tx A1Tx A2Tx A2Tx A2Tx A3Tx A3Tx A3Tx Description Alarm 1 threshold, activates relay 1 Alarm 1 Delay on (seconds) Alarm 1 Delay off (seconds) Alarm 2 threshold, activates relay 2 Model 6000-B only Alarm 2 Delay on (seconds) Alarm 2 Delay off (seconds) Alarm 3 threshold, sounder and strobascope Alarm 3 Delay on (seconds) Alarm 3 Delay off (seconds) Alarm 1 transmit message, CAN Alarm 1 transmit message, CAN Alarm 1 transmit message, CAN Alarm 2 transmit message, CAN Alarm 2 transmit message, CAN Alarm 2 transmit message, CAN Alarm 3 transmit message, CAN Alarm 3 transmit message, CAN Alarm 3 transmit message, CAN Range per sensor scale per sensor scale per sensor scale Default 30 20 30 20 180 20 1 2 3

4.0 Operation 4.4 List of Settings (Continued) Sensor B (bottom socket) settings No. Name 18 AL1-B 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 A1Del A1Off AL2-B A2Del A2Off AL3-B A3Del A3Off A1x AL1Tx A1Tx A2Tx A2Tx A2Tx A3Tx A3Tx A3Tx Description Alarm 1 threshold, activates relay 1 Alarm 1 Delay on (seconds) Alarm 1 Delay off (seconds) Alarm 2 threshold, activates relay 2 Model 6000-B only Alarm 2 Delay on (seconds) Alarm 2 Delay off (seconds) Alarm 3 threshold, sounder and strobe Alarm 3 Delay on (seconds) Alarm 3 Delay off (seconds) Alarm 1 transmit message, CAN Alarm 1 transmit message, CAN Alarm 1 transmit message, CAN Alarm 2 transmit message, CAN Alarm 2 transmit message, CAN Alarm 2 transmit message, CAN Alarm 3 transmit message, CAN Alarm 3 transmit message, CAN Alarm 3 transmit message, CAN Range Default per sensor scale per sensor scale per sensor scale 30 20 30 20 180 20 1 2 3

4.0 Operation 4.4 List of Settings (Continued) General Settings No. Name 36 R1Rx 37 38 39 40 41 42 43 44 45 46 47 48 49 R2Rx R3Rx Adr AnZA AnSA AnZB AnSB Temp Aud BAC BMA BBR KLB Description Receive message to activate relay 1, CAN Receive message to activate relay 2, CAN. Model 6000-B only Receive message to activate sounder and strobe CAN Sensor identification address, CAN Adjustment to analogue zero (4ma or 2v) to tweak for wire losses and controller input inaccuracies. Also forces zero output. Sensor A as option 40 but for span adjustment (20ma or 10v). Forces output high as option 40 but for sensor B as option 41 but for sensor B Temperature display enable off/on Local audio alarm enable on alarm 3 BACnet MSTP mode select 0 = BACnet communication disabled 1 = BACnet communication enabled 2 = BACnet communication enabled and display all sensors on CAN BACnet MAC address. Device ID displayed as 50,000 plus BMA BACnet baud rate 0 = 9600 1 = 19200 2 = 38400 3 = 76800 Keyboard lock. Locked keyboard require password to access options Range Default 1 0-32 0/1 0/1 0/1/2 127 3 0/1 2 3 0 0 1 0 0 0

4.0 Operation 4.4 List of Settings (Continued) General Settings (Continued) No. Name 50 TMod 51 ATHi 52 53 54 55 56 57 W/U BMM BDiag ATLo Net Ref-A Description Temperature modify/calibrate High temperature alarm limit used for summer ventilation (Alarm 1 is activated when temperature exceeds option) Deg C Warm up delay disables alarms (mins) until sensor is stableized after power outage BACnet maximum MAC address BACnet diagnostic display while accessing this option. In format XXXXYYZZ. Where YY is MAC address (in HEX) of the sensor that just passed the token to the current one. ZZ is the sensor to which the token was passed to. Example 0305 would display on sensor 04 Low temperature alarm limit (alarm 3) Deg C Enable local display of all sensors on home screen CAN Refrigerant scale and type of gas for sensor A For model 5520: R507, R23, R134a, R152a, R492a, R404a, R407a, R408a, R410a, R500, R502, R507 For model 5513: R22, R21, R141b, R142b, R401a, R402a, R408a, R409a, R502a Press up arrow to select desired gas then save. Range Default -9/+9 0 0-99 60 0-99 0-127 0-99 0/1 1 127 0

4.0 Operation 4.4 List of Settings (Continued) General Settings (Continued) No. Name 58 Ref-B 59 60 61 62 64 65 66 68 69 FltTx ADTxA AMinA AMaxA ADTxB AMinB AMaxB Baud Man Description Press up arrow to select desired gas then save. Fault alarm transit message, CAN Analogue drive transmit message, sensor A (top) CAN. Used to communicate a percentage drive signal to other sensors or controller via CAN. Example 8 sensors on CAN send messages to controller whose analogue is output to modulate a damper or variable speed drive. Analogue drive. Minimum percent of scale for zero output. Sensor A Analogue drive. Maximum percent of scale for full scale output. Sensor A Analogue drive transmit message, CAN sensor B Enable display of all sensor connected via CAN on this unit. For example see section 4.1 Analogue drive. Maximum percent of scale for full scale output. Sensor B Baud rate for CAN CAN baud rate. Maximum wire length is 1500 feet at rate 0 and 3000 feet at rate 1. Set Baud rate = 1 when used with model 5000 Manual mode activates alarms 1, 1+2 or 1+2+3. See screen display section. Range Default 0 0 0 0-100 100 0-100 100 0 0-100 0 0-100 100 0-1 0

4.0 Operation 4.4 List of Settings (Continued) General Settings (Continued) No. Name Description 70 BDI Bacnet device instance replaces default 5,000 + BMA (parameter) BACnet device instance replace default 5,000 + BMA (setting) Range Default 1-3 1

5.0 Network Configuration 5.0 NETWORK CONFIGURATION 5.1 Using a Central Controller A basic model 6000 controller serves as the central connection point for the ventilation system. Model 60XX gas sensors transmit alarm messages to the central controller. A controller will display up to 32 sensors on the (64 for dual units). It also displays their address, gas types, gas concentration, and alarm status for each. The two relays on board can be configured for different levels of gas or to operate different ventilation systems, zones or groups. Zone 1 Controller 6000 60xx 60xx 60xx 60xx Zone 2 60xx 60xx 60xx 60xx

5.0 Network Configuration 5.2 Using No central controller (master/slave operation) One of the 60XX series gas sensors can perform the same function as the controller. It can activate the ventilation for all the sensors, or a group. The use of a dedicated controller is optional, - to add a display in some specific location, such as before entering a mechanical room or interface with several fan starters which are located in one place. The low cost of a basic controller makes it easy to use them to reduce costly field wiring where needed. 60xx 60xx 60xx 60xx Zone 1 60xx 60xx 60xx 60xx Zone 2

5.0 Network Configuration 5.3 Default Configuration Sensors are shipped pre-loaded with a default settings which can be changed in the field to suit the desired sequence with simple keypad input. Using the default settings, when one sensor goes into alarm level 1, 2 or 3 it activates its relays and transmits a message to all other sensors to activate their relays also. The ventilation system can be connected to any of the relays (usually level 1). This is essentially a one zone configuration. 5.4 Addresses Set each sensor and controller to a different address (setting 39). 1, 2, 3, 4 etc. It is important to have no duplicates on the same cable. Addresses are independent of groupings. 5.5 Creating Zones or groups To control multiple zones, set the transmit message on sensors to different messages for different zones. The default transmit messages are 1, 2, 3 for alarm levels 1, 2, 3 for zone 1. Set zone 2 sensors to transmit messages to 4, 5, 6 Set zone 3 sensors to transmit 7, 8, 9 and so on. 5.6 Output Relays Relay number 1 and 2 will activate if the gas on that sensor goes into alarm level 1, or 2. It will also activate when it sees it s receive code (setting 36, 37) go by on the, sent by other sensors. The 6000 basic controller has no sensors on board so the relays will only activate if it sees it s receive codes. The 6000 controller could control two zones via its two relays. When no controller is used, the master needs to be a member of the group it is controlling.

6.0 Maintenance Guide 6.0 MAINTENANCE GUIDE All sensors are shipped from the factory pre-calibrated. To maintain accuracy and conformity with standards it is essential that they be calibrated by a qualified technician at least once per year using certified bottled gas mixtures. 6.1 Quick Test Caution Opera does not approve the use of the so called bump test. Here, a gas of a higher concentration than the alarm level is simply injected into the sensor to cause the alarm to trigger. The gas in these bottles is a higher concentration than what is used for proper calibration. This only test the operation of the alarm with no regard for the intended alarm settings, similar to simply pressing a test button. Use certified precision mixtures to adjust the sensitivity of the sensor due to normal wear and aging and guarantee that the designed alarm set points are respected. It will also indicate the general condition of a sensor that is due for replacement. So called automatic calibration or self-test will not provide this level of security.

6.0 Maintenance Guide 6.2 Calibration Procedure 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Use certified bottled calibration gas mixtures only. Ensure that sensors are powered on for a minimum of the break-in period for the sensor. For electro-chemical sensors this is only a few minutes. Press the right arrow to enter settings. Press the and at the same time to enter calibration mode. SAZ (sensor A zero) will display and the current gas reading on the top line. Inject bottled zero gas into first sensor. Adjust gas reading to zero with the and buttons. Press and at the same time to save. Press The display will show SAS (sensor A span) and the current gas reading. Inject bottled span gas into first sensor and wait until the gas reading stops going up. Adjust the reading to match the concentration in the bottle. Press and at the same time to save. If second sensor installed press and repeat steps 3 to 10 for sensor B. Press left arrow to return to settings.