INSTALLATION ADJUSTMENT SERVICE THERMOSTATIC WATER MIXING VALVE SERIES LV-981 & LV-982

Similar documents
INSTALLATION ADJUSTMENT SERVICE HIGHLOW THERMOSTATIC WATER MIXING VALVE SERIES XL-32, XL-82

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION ADJUSTMENT SERVICE

OUTLET HOT INLET COLD INLET INSTALLATION

INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20, TM-20-LF (As furnished with models TM-554, TM-356, TM-356-W/HA)

INSTALLATION SETUP AND OPERATING INSTRUCTIONS THERMOSTATIC WATER MIXING VALVE SYSTEM TM-500, TM-550

INSTALLATION ADJUSTMENT SERVICE

TA-300, TA-300-LF, TA-350, TA-350-LF

MODEL TA. TA-SB 117.5mm mm HOT INLET. TA mm mm mm mm

INSTALLATION SETUP AND OPERATING INSTRUCTIONS THERMOSTATIC WATER MIXING VALVE SYSTEM * TM-500A, TM-550A

INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20* (As furnished with models TM-554, TM-356, TM-356-W/HA Valve is ASSE 1017 listed

Installation, Operation and Maintenance Guide AP3900 Series Thermostatic Mixing Valves

MEGATRON MODEL 2, 3, 4, and 5

Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Tempered Water Outlet. Hot Water Inlet.

Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Thermometer. Hot Water Inlet. Cold Water Inlet G3600LF

Installation, Operation and Maintenance Guide G3600 Series Thermostatic Mixing Valves

OUTLET LEONARDH THERMOSTATIC INSTALLATION

INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20 (As furnished with models TM-554, TM-356, TM-356-W/HA, TM PRV, 8015, 12520, 15020)

SS-7600 THERMOSTATIC MODEL INSTALLATION INSTRUCTIONS

INSTALLATION ADJUSTMENT SERVICE NEXT-GENERATION MANIFOLD SYSTEMS TM-520B-LF, TM-820B-LF, TM-920B-LF, TM-1520B-LF

INSTALLATION SETUP AND OPERATING INSTRUCTIONS THERMOSTATIC WATER MIXING VALVE SYSTEMS TYPE *TM-600, TM-650, *TM-800, *TM-850, TM-5100, TM-5125

HOT INLET COLD INLET INSTALLATION

DOMESTIC OUTLET. kg/cm 2 11 psi LEONARD LEONARD -10 C F LEONARD R THERMOSTATIC LEONARD LEONARD C F C F 60 COLD INLET HOT INLET

INSTALLATION ADJUSTMENT SERVICE TM-1520A-DT, TM-2020A-DT PARALLEL SYSTEMS

INSTALLATION ADJUSTMENT SERVICE THERMOSTATIC WATER MIXING VALVE TM-200 (NEW STYLE) TMS-200 (VALVE ONLY)

30 R -10 C F H C INSTALLATION. Maximum Operating Pressure 125PSI (860 KPA) for Hot and Cold Water. CAUTION

OUTLET LEONARD THERMOSTATIC INSTALLATION

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD SYSTEMS TM-520, TM-820, TM-920, TM-1520A TM-520-LF TM-820-LF, TM-920-LF, TM-1520A-LF

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B

MEGATRON MODEL 2NB-LF, 3NB-LF, 4NB-LF, 5NB-LF NEXT GENERATION MANIFOLD SYSTEMS TM-520B-LF, 820B-LF, 920B-LF, 1520B-LF

MODEL 210, 210-LF THERMOSTATIC WATER MIXING VALVES INSTALLATION SETUP AND OPERATING INSTRUCTIONS

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD SYSTEMS TM-420A Valve assemblies are ASSE 1017 listed

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD SYSTEMS TM-420A Valve assemblies are ASSE 1017 listed

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B, TM-2020B-LF

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B, TM-2020B-LF

MEGATRON MODEL TA, TA-LF

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B, TM-2020B-LF

INSTALLATION ADJUSTMENT SERVICE MEGATRON MODEL 8N-LF. Valve assemblies are ASSE 1017 listed

INSTALLATION ADJUSTMENT SERVICE 2PS TM-2020B-2P, TM2020B-2PS-LF PARALLEL SYSTEMS

INSTALLATION ADJUSTMENT SERVICE 2P TM-2020B-2P, TM2020B-2P-LF PARALLEL SYSTEMS

INSTALLATION ADJUSTMENT SERVICE TM-1520A-2P, TM-1520A-2P-LF TM-2020B-2P, TM2020B-2P-LF PARALLEL SYSTEMS

LEONARD -10 LEONARD VALVE CO. CRANSTON RI USA. TYP TM US. P aten ts 2.970, 3,06 1, , " Maximum Operating Pressure 125PSI (8.6 Bar).

Installation Manual. Models 99168, 99169, 99170

MODEL 270-LF ECO-MIX THERMOSTATIC MIXING LEAD FREE THERMOSTATIC POINT OF USE MIXING VALVE. Submittal Data Sheet S-827-LF February 2013

INSTALLATION, OPERATION AND MAINTENANCE

FFP S700 SERIES. Pull-Out Spray Faucet. Installation guide

MEGATRON MODEL 2N, 3N, 4N, 5N HIGH-LOW MANIFOLD SYSTEMS TM-520, TM-820, TM-920, TM-1520A TM-520-LF, TM-820-LF, TM-920-LF, TM-1520A-LF

SEISCO SUPERCHARGER EXTENDER/BOOSTER INSTALLATION GUIDE & OWNERS MANUAL

Installation S

Installation S

Installation S

Model NOTE TO INSTALLER: Please leave this information with the Maintenance Department. LIMITED WARRANTY

Installation Instructions PP-AS20 Anti-Scale System

INSTALLATION & TESTING MANUAL

Installation S

INSTALLATION & TESTING MANUAL

CLASSIC HIGH LOW MANIFOLD SYSTEMS

Model 9201EFE Tempered Water Blending System

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION MEGATRON MODEL 10NB-LF 4 HOT & COLD INLETS 4 MIXED OUTLET 2 RETURN PIPING

TUB AND SHOWER FAUCET

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

Installation Instructions / Warranty

Installation S

Instruction Manual. Carmel Apple-Dip Warmer

AeroVent 3X Product Manual

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

Instruction Manual. Nacho Cheese Dispenser and Warmer

Installation Instructions

Installation Instructions / Warranty. PuraVida 15775XX1

Instruction Sheet LTR - Low Water Cutoff for Hot Water Boilers

Model 8780 INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS. Tempering Skid General Area Classification & Class I Division 2. No.

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

ECCOTEMP. Point of Use Tankless Water Heaters EP-2.4 / EP-7.0. Installation and Operating Instruction Manual. Shop Online.

TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER TECHNICAL ASSISTANCE FAX:

Model T-45NL: Certified in compliance with ASSE 1017, 1069, 1070, and ANSI/NSF 61 PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING AND OPERATING!

Model TWBS.EW.H Tempered Water Blending System

Installation & Operation Manual

AeroVent 1 Product Manual

TRU-TEMP VALVE. Tru-Temp Pressure Balance 1/2" Rough-In Valve Owner's Manual 3001-RIV-PB-ORB 3001-RIV-PB-BN 3001-RIV-PB-CH 3003-RIV-PB-ORB

RK/ RK Oxygen Detector Operator s Manual

NEW GENERATION HIGH LOW SYSTEMS

Model TWBS.SHE Tempered Water Blending System

SEABREEZE. SeaBreeze Rain Shower System Model #1086-CH Owner's Manual

Model 9201EW Tempered Water Blending System

Installation S HL2X2 High Capacity Manifold System. Table of Contents Rev. B; ECN Bradley Page 1 of 8 11/10/2014

Installation Instructions / Warranty. Massaud

Owner s Manual. Pelican Custom Premium WHWF 1354/1665

Troubleshooting the MPH 24FP Series Pedestal Hydrant

Part No Revised: June TS1 TOASTER SYSTEM Instruction Manual Models # 5700 AND # 5700SF

Thermostatic mixing valves with interchangeable cartridges

INSTRUCTION MANUAL HS-229G

Model 7656WCC Eye/face Wash

Transcription:

Bulletin LV-98 March 010 INSTALLATION ADJUSTMENT SERVICE THERMOSTATIC WATER MIXING VALVE SERIES & LV-98 IMPORTANT! Provide valve serial number, (located on valve cover) when ordering parts!! ASSE 1017 Certified INSTALLATION 1. Valve should be installed at a location where it can easily be cleaned, adjusted or repaired.. The inlets are clearly marked on the valve body. Union angle strainer checkstops furnished must be installed on both supply lines as shown above.. A shutoff valve must be installed on the outlet pipe. Type LV valves do not have a built-in shutoff. 4. Use solder, or thread sealant sparingly. Supply pipes should be flushed before the valve is connected. Flush outlet pipe and valve as soon as it is connected. 1 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE CAUTION All thermostatic water-mixing valves have limitations. They will not provide the desired accuracy outside of their flow capacity range. Consult the flow capacity chart on page. Minimum flow must be no less than as shown. REMEMBER! THIS IS A CONTROL SYSTEM WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD MGR-1000). 160 Elmwood Avenue, Cranston, RI 0910 USA Phone: 401.461.100 Fax: 401.941.10 Email: info@leonardvalve.com Web Site: http://www.leonardvalve.com 1

METHOD #1 INSTALLATION REQUIRED METHODS OF PIPING LV SERIES Required when TEMPERED WATER is NOT CIRCULATED. Only the hot water supply to the mixing valve can be circulated with this piping arrangement. FIXTURES, SUPPLIED BY TEMPERED WATER THERMOMETER T HOT WATER SUPPLY COLD WATER SUPPLY METHOD W Required when TEMPERED WATER IS CIRCULATED. CIRCULATE HOT WATER FROM END OF LINE BACK TO TANK FIXTURES, SUPPLIED BY TEMPERED WATER THERMOMETER T C CIRCULATOR A AQUASTAT HOT WATER SOURCE COLD SUPPLY BALANCE VALVE OPERATION 1. Verify that the temperature of the hot water source is properly set and maintained. Shutoff and isolate the circulator pump.. Loosen LTR set screw located on temperature adjustment knob with allen wrench.. Turn on enough fixtures to flow approximately GPM, turn knob clockwise until it stops (full cold) then counterclockwise until it stops (full hot), three times to exercise the thermostatic element. 4. Set mixing valve to the desired temperature, (See warning tag for temperature set point). Tighten LTR set screw.. Shut off all fixtures. Setup is complete. 6. Turn on circulator. With all fixtures still off, (no water flowing) observe the circulation temperature until it stabilizes. 7. If temperature rises, close balance valve until desired temperature is reached

INSTALLATION CONTINUED WARNING WARNING! This Thermostatic Mixing Valve has an Locking Temperature Regulator (LTR) which must be checked. If the temperature is too high, the installer MUST RESET this adjustment immediately. Always check the temperature of the mixed water after installation. Excessively hot water is DANGEROUS AND MAY CAUSE SCALDING! SERVICE Leonard Type LV Thermostatic Water Mixing Valves are simple in design and may be easily cleaned, adjusted and repaired. If the installation is accessible, servicing may be completed without disconnecting the valve. NOTE: Thermostatic Water Mixing Valves are REGULATING mechanisms, which must be regularly maintained to provide best performance. Frequency of cleaning depends on quality of local water conditions and usage. (See Maintenance Guide and Record MGR-1000). TROUBLESHOOTING INSTRUCTIONS ITEM: PROBLEM: RECOMMENDED REPAIR KITS: RECOMMENDED REPAIR KITS: LV-98 PACKINGS & GASKETS 1. Leak at stem.. Leak between valve cover and base. KIT 1/XL KIT 1/XL8 SHUTTLE ASSEMBLY. Valve delivers either all hot or all cold water, or will not mix consistently. KIT R/LV981 OR /LV981 KIT R/LV98 OR 1/LV98 CHECKSTOPS 4. Hot water bypass into cold line.. Supplies cannot be shut off completely. 6. Leak at checkstop bonnet. KIT /0 KIT /0 REMEMBER! THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS. (SEE MAINTENANCE GUIDE AND RECORD, MGR-1000).

1 1 11 0 18 17 16 19 8 14 10 4 9 7 6 KIT KIT TYPE KIT INCLUDES LV-98 R/LV981 R/LV98 COMPLETE REPAIR 1,,,4,,6,7,8,10 1/XL 1/XL8 O-RING,6,7,8 /LV981 /LV98 SHUTTLE 1,,,4 76800 76800 KNOB 11,1,1 /0 /0 CHECK 1,16,17,19,1, 1 1 1 4 ITEM # DESCRIPTION QTY. PART # / KIT # PART # / KIT # LV-98 1 SPRING, RETURN 1 /LV981, R/LV981 /LV98, R/LV98 THERMOSTATIC ELEMENTS AND SPACER 1 /LV981, R/LV981 /LV98, R/LV98 SHUTTLE 1 /LV981, R/LV981 /LV98, R/LV98 4 ELEMENT HOLDER 1 /LV981, R/LV981 /LV98, R/LV98 O'RING, LOWER SHUTTLE 1 1/XL, R/LV981 1/XL-8, R/LV98 6 O'RING, UPPER SHUTTLE 1 1/XL, R/LV981 1/XL-8, R/LV98 7 O'RING, COVER 1 1/XL, R/LV981 1/XL-8, R/LV98 8 O'RING, STEM 1 1/XL, R/LV981 1/XL-8, R/LV98 9 STEM ASSEMBLY (DO NOT REMOVE SNAP RING) 1 741900 761900 10 RETAINING RING, COVER 1 7411, R/LV981 7611, R/LV98 11 KNOB 1 76800 76800 1 SCREW, KNOB 1 76800 76800 1 LTR SET SCREW 1 76800 76800 14 COVER 1 740 7604 1 LOWER STEM & PACKING 0, KIT /0 0, KIT /0 16 SPRING,CHECK 011, KIT /0 011, KIT /0 17 PACKING, BONNET 0, KIT /0 0, KIT /0 18 STEM, UPPER CHECK 010 010 19 O'RING, UPPER STEM MU-A, KIT /0 MU-A, KIT /0 0 BONNET 0 0 1 SCREEN 01, KIT /0 01, KIT /0 PACKING, STRAINER CAP 014, KIT /0 014, KIT /0 STRAINER CAP 06 06 4 SWIVEL NUT 09/0 09/0 SWIVEL 74-04-1 04/0 4

FLOW CAPACITIES VALVE LV-98 MIN FLOW. 9 11 0. 14 1 79 PRESSURE DROP 10 1 0 0 0.7 1 1.4 1.7.1 0 4 8 76 91 106 11 1 1 7 4 48 117 140 16 18 01.4 8 144 6 11 40.8 41 1 60 7 4.1 4 16 6 8 PSI BAR GPM l/min GPM l/min 6 (46) 60 (7) (08) LV-98 0 (189) 4 (170) 40 (11) (1) FLOW RATE GPM(l/min) 0(114) (9) 0(76) 1(7) 10(8) (19) 0 0 (0.) 10 (0.7) 1 (1.0) 0 (1.4) (1.7) 0 (.1) (,4) 40 (.8) PRESSURE DROP PSI(BAR) 4 (.1) 0 (.4) LIMITED WARRANTY Leonard Valve Company warrants the original purchaser that products manufactured by them (not by others) will be free from defects in materials and workmanship under normal conditions of use, when properly installed and maintained in accordance with Leonard Valve Company's instructions, for a period of one year from date of shipment. During this period the Leonard Valve Company will at its option repair or replace any product, or part thereof, which shall be returned, freight prepaid, to the Leonard factory and determined by Leonard to be defective in materials or workmanship. There are no warranties, express or implied, which extend beyond the description contained herein. There are no implied warranties of merchantability or of fitness for a particular purpose. In no event will Leonard be liable for labor or incidental or consequential damages. Any alteration or improper installation or use of the product will void this limited warranty. 00 Leonard Valve Company Printed in USA 160 Elmwood Avenue, Cranston, RI 0910 USA Phone: 401.461.100 Fax: 401.941.10 Email: info@leonardvalve.com Web Site: http://www.leonardvalve.com