Open-area Smoke Imaging Detector. Engineering Specification

Similar documents
VESDA VLP. Engineering Specification

Open-area Smoke Imaging Detection (OSID)

OSID Smoke Detector. Product Guide. July 2011 Document No.: Revision: A Build: 4 Part No. LF42339

LaserFOCUS VLF-250 Engineering Specification

ADPRO PRO Series by Xtralis

Open-area Smoke Imaging Detection (OSID)

Open-area Smoke Imaging Detection (OSID)

OSID Smoke Detector. Product Guide OSI-10 OSI-45 OSI-90 OSE-SP OSE-SPW OSE-SP-01 OSE-HPW

OSID in Challenging Environments

Open-area Smoke Imaging Detection (OSID)

Engineering Specification Guide VESDA-E VEP

Reflective Optical Beam Smoke Detector User Guide

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

Buys Time. Aspirating Smoke Detection

Why choose Fireray? Why use a Beam Smoke Detector? Product Range.

Motorised Infrared Optical Beam Smoke Detector. User Guide

1.1 SCOPE 1.2 APPROVALS. A. The Aspirating Smoke Detector shall be tested, approved and/or listed by: 1.3 CODE, STANDARDS, AND REGULATION

VESDAnet Interface Card Product Guide. Document Number: 10672_05 Part Number: 30071

Fiber Optic Cable Fence Disturbance Sensor

Flexible Air-sampling Smoke Detection

TITLE SLIDE. FIRERAY2000 EExd OPTICAL BEAM SMOKE DETECTOR. Doc. No: Copyright Fire Fighting Enterprises Ltd.

Integrated Security Solutions

ALK-V PHOTOELECTRIC SMOKE SENSOR

FIRERAY 5000 range USER GUIDE

Aspiration Systems for Smoke Detection

Motorised Infrared Optical Beam Smoke Detector. User Guide

The World s No. 1 Brand of Aspirating Smoke Detection

TITLE SLIDE FIRERAY50/100R OPTICAL BEAM SMOKE DETECTOR. Doc. No: Copyright Fire Fighting Enterprises Ltd.

Installation and Operation Manual

End To End Optical Beam Smoke Detector. Additional Information

Apollo Intelligent Auto Aligning Beam Detector. User Guide

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500 AND 6500S REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR

TX7130. Conventional Reflective Beam Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

3NT SERIES FIXED TEMPERATURE THERMOSTATS Introduction

The World's No. 1 Brand of Air-sampling Smoke Detector

AnaLASER II Detector. Protection Systems. A UTC Fire & Security Company. High-Sensitivity Smoke Detector (HSSD ) FEATURES DESCRIPTION

The World's No. 1 Brand of Aspirating Smoke Detector

The World's No. 1 Brand of Aspirating Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS NFXI-BEAM AND NFXI-BEAM-T REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR

TrueAlarm Analog Sensing

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

Integrated Security Solutions. A Complete Portfolio

Beam Detectors. The 6500 Series

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

TrueAlarm Analog Sensing

Range brochure. Beam detection. others look up to.

D296/D297. Application Guide. Projected Beam Smoke Detectors

Beam detector DBD-DL40 KBD-DL80 KBD-DL100

Intrusion Outdoor Protection Perimeter

Fact File 66. Guide to Beam Smoke Detectors

ADPRO PRO-45D / PRO-45DH by Xtralis. Installation Manual

RF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors

FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a

CL3 HYBRID MULTI-LINE LASER INSTRUCTION MANUAL

COMPANY PROFILE Technoswitch with its headquarters, manufacturing and training facilities in Johannesburg, has been supplying and providing technical

and Aspirating Smoke Detection

TrueAlarm Analog Sensing

IFD-E Flame Detector User Manual

Smoke Detection Solutions for Challenging Environments

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

FIRERAY 2000 EExd Hazardous Area Smoke Detector Installation Guide

6600 SERIES 8-Pin DIP, Subminiature Bimetal Disc Thermostat

Fireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds

alarm shop Outdoor PIR + MW Detector with Double Dual Mirror Optics INSTALLATION INSTRUCTIONS & USER MANUAL ELECTRONIC ENGINEERING LTD.

IFD-E Flame Detector User Manual

TrueAlarm ES Analog Sensing

FDA241, FDA221 Siemens ASD

WFDE Series Waterflow Detector

Case Study. INTEGRATING Fire & GAS SAFETY WITH PROCESS CONTROL SYSTEMS

FDA241, FDA221 Siemens ASD

VESDA. Accessories Guide. May 2011 Document: 10258_06 Part Number: 30012

Photobeam 5000 ISC-FPB1-W60QF, ISC-FPB1-W120QF, ISC-FPB1-W200QF. en Installation and Operation Guide

CONVENTIONAL FIRE ALARM CONTROL PANEL

Multi-Point Peripherals

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

I am Rick Jeffress and I handle sales for Fike Video Image Detection. We thank the AFAA for coordinating the venue for this presentation, and we

The Next Generation of VESDA Aspirating Smoke Detection Technology

Fireray 2000 Linear Smoke Detector

Customized LIDARs. Research Pollution Climate. Raman, Depolarization, Backscatter, DIAL

Wilcom. Model FR2 Fiber Ranger Optical Fault Locator OPERATING INSTRUCTIONS

good things in small packages

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Accessories ADPRO PRO E-400H SLR Superior Long-Range PRO E-Series Extraordinary Features Complete New Housing Design

MR300 OPTICAL SMOKE DETECTOR RANGE PRODUCT APPLICATION & DESIGN INFORMATION

FAAST. Fire Alarm Aspirating Sensing Technology

Reflective Beam Smoke Detector

Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015

Dräger PIR 7000 Flammable Gas Detection

SECTION FIRE ALARM SYSTEMS

SP METHOD 5320 Issue No: Test method for fire detection systems installed in engine compartments of heavy vehicles

Notifier by Honeywell: FAAST TM Fire Alarm Aspiration Sensing Technology

Intelligent Detection Devices

Optical Beam Smoke Detector RK90R - RK90RS

This training course discusses the correct use of Infrared (IR) Optical Beam Smoke Detectors for the protection of lives, equipment and property.

Dräger Flame 2500 Flame Detection

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

TrueAlarm Smoke Detectors

Passive Infrared Perimeter Intrusion Detector

Notifier by Honeywell: FAAST TM Fire Alarm Aspiration Sensing Technology

Transcription:

Open-area Smoke Imaging Detector 15273_02 October 2011

Table of Contents 1. Scope... 3 2. System Information... 3 2.1 General... 3 2.2 Approvals... 3 2.3 Codes, Standards or Regulations... 3 2.4 System Description... 4 2.4.1 The Imager (receiving component)... 4 2.4.2 The Emitters (emitting component)... 4 3. Product... 5 3.1 Manufacturer... 5 3.2 Product Specific... 5 3.3 Signal Annunciation, Inputs and Outputs... 5 4. Installation... 6 4.1 The Detection system... 6 4.2 Environmental... 6 4.3 Alignment... 6 4.4 Building Flex... 6 4.5 Commissioning... 6 4.6 Maintenance... 6 4.7 Testing... 6 Page 2 of 7

1. Scope This document provides specification details of the Open-area Smoke Imaging Detector (OSID) product to assist in their installation and commissioning. 2. System Information 2.1 General An open-area smoke imaging detector will be installed for the protection of nominated areas in the building plans. The system will actively measure the attenuation in these areas and be able to distinguish between smoke, intruding objects (e.g. obstructions, insects), and non-smoke particles (e.g. dust). The detector will have at least two beams with different wavelengths. The system will have high alignment tolerances that enable it to compensate for natural shifts in the building structure, and be easily installed and maintained. 2.2 Approvals The Open-area Smoke Imaging Detector must be of a type submitted to, tested, approved, and/or listed by a Nationally Recognized Testing Laboratory (NRTL) as follows: CPD VdS UL (Underwriters Laboratories Inc), USA ULC (Underwriters Laboratories Canada), Canada FM (Factory Mutual) ActivFire, Australia AFNOR, France 2.3 Codes, Standards or Regulations The Open-area Smoke Imaging Detector (OSID) shall be installed to comply with all local codes and standards for beam detectors such as: AS 1670.1, AUS BS5839.1, UK NFPA72, US GB50166, China The design of the system, including all spacing and mounting locations of components, shall fulfil all protection goals and local requirements. Page 3 of 7

2.4 System Description The system shall consist of a receiving (Imager) and emitting (Emitters) components for installation along the perimeter of the protected space. It shall use dual wavelength imaging principles to determine the smoke obscuration at known locations, while providing a high resistance to false alarms and obstructions. Intruding objects that sufficiently reduce the ability of the system to measure smoke obscuration will be identified as a Trouble (Fault). 2.4.1 The Imager (receiving component) 1. The system will be primarily configured through DIP switches located on the Imager that allow for a number of settings to provide the best possible parameters for the particular site in which it will be installed. The parameters will be least: 3 sensitivity settings for fire alarm threshold Selection for particle size discrimination (dust rejection on or off) Alarm latching or non-latching. 2. Different Imagers will be available covering different horizontal viewing angles. 3. There will be at least Imagers for 7, 38 and 80. 4. The vertical viewing angle shall be at least 50% of the horizontal one. 5. Depending on the angles chosen, the respectively covered distances will vary from 150 m/492 ft to 34 m/110 ft. 6. For the 38 and 80 viewing angles, the system will allow a configuration of 1 up to 7 Emitters on a single Imager so the system designer can project the most cost-effective, yet complying area coverage. 7. This set-up will allow installing Emitters on different heights and as such providing an optimum 3D coverage of the area. 8. The Imager shall be powered from an external power supply at a nominal value of 24 VDC 2.4.2 The Emitters (emitting component) 1. The Emitters may be powered from an external power supply, or by an internal battery. 2. When choosing the external power supply, the nominal value will be 24 VDC. 3. The system designer shall have a choice between Emitters with two intensities, for long range or short range coverage. 4. A battery-powered component shall indicate when its battery power is low. 5. The Emitters shall activate automatically once aligned and their position fixed and secured Page 4 of 7

3. Product 3.1 Manufacturer Open-area Smoke Imaging Detector: Acceptable Manufacturer: Xtralis 4 North Drive, Virginia Park 236 262 East Boundary Road East Bentleigh VIC 3165 Australia Telephone: +61 3 9936 7000 Fax: +61 3 9936 7200 3.2 Product Specific The housing will be constructed of a robust plastic material meeting all relevant flammability requirements. 3.3 Signal Annunciation, Inputs and Outputs 1. Locations of alarms and troubles (faults) shall be identified through the user interface. 2. It will be possible to remotely reset the unit by applying 24 VDC to a dedicated input. 3. There will be a choice between automatic reset and manual reset. Faults are always reset automatically when the fault has disappeared. 4. There will be an initiating device circuit (IDC) interface, C/O contacts, to report Alarms and Trouble (Fault) to connected four-wire control panels. 5. A connection to a remote indicator (remote LED) shall be provided, which will activate when a Fire alarm is initiated. 6. An internal heater shall be provided to prevent condensation build-up in the detector when installed in low temperatures. 7. Optional equipment may be installed to provide addressability to a third-party control panel. Such installations must comply with the control panel manufacturer s specifications. Page 5 of 7

4. Installation 4.1 The Detection system The contractor shall install the system in accordance with the manufacturer's Product Guide. 4.2 Environmental The units will have an IP44 rating for the Electronics and IP66 rating for the optics enclosure. The system will be able to operate at an ambient temperature range of at least -10 C to 55 C (14 F to 131 F) at a maximum relative humidity 90% (non-condensing). 4.3 Alignment 1. Both Imager and Emitter will be constructed in such that they can be simply rotated left, right, up and down and easily aligned and secured by the use of a simple tool, i.e. a laser screwdriver. The adjustment angles will be at a minimum ±60 horizontal and ±15 vertical. 2. It will possible to install and align Imagers and Emitters by a single person. 4.4 Building Flex The system will tolerate building flex up to at least 2 in all directions. 4.5 Commissioning 1. After installation and power up, the system will automatically learn the locations of the Emitters and initialise itself. The installation engineer shall not be required to remain at the detector while the initiation is going on. 2. The user interface will indicate when the learning phase is over. At the end of this phase the detector shall be active without any further required action or programming except for a test. 3. The whole initiation phase will not take longer than 10 minutes for a detector with 7 Emitters. 4.6 Maintenance 1. The system shall be highly resistant to dirt and dust and auto-adjust. 2. Maintenance will be limited to clean the Imager and Emitter front by wiping the optical surface with a dry cloth. 4.7 Testing Optical filters shall be available from acceptable manufacturers that enable a calibrated test to be performed. Page 6 of 7

www.xtralis.com The Americas +1 781 740 2223 Asia +852 2916 8894 Australia and New Zealand +61 3 9936 7000 Europe, Middle East & Africa +44 1442 242 330 The contents of this document are provided on an as is basis. No representation or warranty (either express or implied) is made as to the completeness, accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or specifications without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any implied warranties of merchantability and fitness for a particular purpose are expressly excluded. This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of their respective owners. Your use of this document does not constitute or create a licence or any other right to use the name and/or trademark and/or label. Doc. No. 15273_02 Page 7 of 7