Low Velocity Center Mount Unit Cooler. Technical Guide. Models LWA - Air Defrost LWE - Electric Defrost LWG - Hot Gas Defrost.

Similar documents
Center Mount Unit Coolers

Lo-Aire Unit Coolers. Technical Guide. bn-lftb May Models LO Air Defrost LOD Electric Defrost LOG Hot Gas Defrost.

LOW PROFILE UNIT COOLER. Technical Guide. Models RLC Air Defrost ELC/EFC Electric Defrost GLC Hot Gas Defrost. CH-LOPTB May,

Low Flow Unit Coolers

Low Profile Unit Coolers

Low Profile Unit Coolers

Slim Contour Unit Cooler

Reach-In Unit Coolers. Technical Guide. Models TA TL C VA BBM BBL KMK RAMK BTO U. LK-RITB June

LOW PROFILE UNIT COOLER

LOW PROFILE UNIT COOLER

Super-Flo Low Profile Unit Cooler

Packaged refrigeration system Technical Guide

Low Profile Unit Cooler. ECM Motors. All-Temp²B. Small to Medium Walk - Ins. Coolers & Freezer Applications. Now available with optional

A Series T 3. Unit Coolers - Technical Catalog. Product Benefits: Comdustrial TM Refrigeration. Adaptability- Durability- Serviceability-

LK-TSSTB July 2009 FPO HP Two Stage Condensing Units and Systems Technical Guide. with Bitzer Compressors.

PRODUCT. TWB Two-Way Air Defrost Unit Coolers PRODUCT DATA & INSTALLATION. High Temperature (35 o F / 1.7 o C or Higher) Applications

High Profile Evaporator

WIBR SERIES. Unit Coolers - Technical Catalog Hunt St - Pryor, OK Fax

Air-Cooled Condensing Units with Screw Compressors. Technical Bulletin Low Temperature Models SSV DSV

Compak Unit Coolers. LCA - Air Defrost LCE - Electric Defrost LCH - Hot Gas Defrost. Bulletin LC-03A August 2004 (Replaces LC-03 3/03)

KTL Two-Way Low Profile Evaporators

SM/SV Series PRODUCT COOLERS. Technical Bulletin: SMSV_001_ Products that provide lasting solutions.

SM/SV Series PRODUCT COOLERS. Technical Bulletin: SMSV_005_ Products that provide lasting solutions.

LH and GH/GL Series UNIT COOLERS. Technical Bulletin. Products that provide lasting solutions.

MS Series UNIT COOLERS. Technical Bulletin: MSUC_005_ Products that provide lasting solutions.

PRO 3 TOP MOUNT & SIDE MOUNT PACKAGED REFRIGERATION SYSTEMS Technical Guide

Reach-In Unit Coolers: ASL 2 Slim-Temp 2 Wedge-Temp 3 Flex-Temp 3 Mullion-Temp 3 T-Temp 4 Twin-Temp 4 Mini-Twin-Temp 4 Wall-Temp 5

Installation, Operation, and Maintenance Information

SM/SV Series PRODUCT COOLERS. Technical Bulletin. Products that provide lasting solutions.

KR Series COMPACT UNIT COOLERS. Technical Bulletin: KRUC_005_ Products that provide lasting solutions.

Air-Cooled Condensers

KTL Two-Way Low Profile Unit Coolers

BTL Two-Way Low Profile Evaporators

Packaged Refrigeration Systems

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

T H I N K I N S I D E T H E B o x

Air-Cooled Condensing Units with Compact Screw Compressors

Page ` RLP R1. Supersedes all earlier versions LIST PRICES April, 2018

LH and GH/GL Series UNIT COOLERS. Technical Bulletin: LHGH_002_ Products that provide lasting solutions.

1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series

Commercial High-Efficiency Condensing Units

Page ` RLP A. Supersedes all earlier versions LIST PRICES Prices effective 7/2/18

RLP Page. Prices effective January 1, Supersedes all earlier versions LIST PRICES

MACH N-407 Heat Pump Air-Cooled Chiller

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

LK-PL Jan Price List

FF1DNA, FF1DNE FAN COIL UNITS. Sizes 018, 024, 030. Form No. PDS FF1D.18.3 FEATURES FF1D

Price List. BN-PL Oct. 2017

Price List. BN-PL Jan. 2018

KR Series Air Defrost Unit Coolers Operating and Installation Manual

Reach-In Unit Coolers: ASL 2 Slim-Temp 2 Wedge-Temp 3 Flex-Temp 3 Mullion-Temp 3 T-Temp 4 Twin-Temp 4 Mini-Twin-Temp 4 Wall-Temp 5

Air-Cooled Condensers

Rooftop Units 60HZ. PACKAGED HEAT PUMPS 13HPP / rhp13 PRODUCT SPECIFICATIONS 13 HPP 36 A P - 1 A RHP 13 A 36 T - 1 A MODEL NUMBER IDENTIFICATION

Product Data. FF1DNA, FF1DNE Fan Coil Units. Sizes 018 thru 030 FEATURES/BENEFITS

BN-HGDTB June Replaces BN-HGDTB, March Mohave. Technical Guide

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT

Price List. CC-PC-PL Jan. 2019

KR Electrical Defrost Unit Coolers (PN E108318_E)

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

RSG16**S1M. Split System Air Conditioner 16 SEER

LIST PRICES SEE THE BACK COVER FOR "CONDITIONS OF SALE AND WARRANTY"

HEATING & COOLING COIL PRODUCTS

BN-ACCMX MAR 2016 Replaces BN-TB-ACCMX MAR Air-Cooled Condenser. with Microchannel Coil Technology Models NRG NRJ

Unit Coolers Evaporator & Condenser Coils Aluminum Extrusion Heat Transfer Products

TLV Low Velocity Evaporators

Unit Dimension. Unit Nomenclature DEHUMIDIFIER NOMENCLATURE UNIT VOLTAGE: 2: 240/1/60 5: /3/60 9: 480/3/60 8: 600/3/60

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Unit Data - RCA 051 RATED IN ACCORDANCE TO AHRI STANDARD

13 GEP A L P - 1 A

T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 236,000 Btuh AIR CONDITIONERS TS

CONDENSING UNITS-AIR SUBMITTED BY : Poppy Hudson PROJECT : Brooks Landing REV DATE : 07 Dec 2017 ORDER # : A00

T P A 120 S 4 S N 1 Y

Specifications and Performance S2H

072, 090, 120, 180 & 240 MODELS C SERIES CONDENSING UNITS P SERIES HEAT PUMPS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

R4H4. Product Specifications

Product Data PF1MNC DIRECT EXPANSION FAN COIL SIZES 018 THRU 061 FEATURES/BENEFITS AVAILABLE SIZES: 18,000 to 61,000 BTU unit ELECTRICAL RANGE:

LIST PRICES SEE THE BACK COVER FOR "CONDITIONS OF SALE AND WARRANTY"

Today s Value-Added Performers. The DRY-30 Series Dehumidifiers from DryAire Systems.

Product Data PF4MNA DIRECT EXPANSION FAN COIL FOR R -410A REFRIGERANT SIZES 018 THRU 061 FEATURES/BENEFITS AVAILABLE SIZES:

PACKAGE AIR CONDITIONER

Today s Value-Added Performers. The DRY-40A Series Dehumidifiers from DryAire Systems.

SMALL AIR COOLED CONDENSERS

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

Installation, Start-Up and Service Instructions

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

48GS HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS

RGE 13 A T - 1 A

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

MERIT Series R-410A - Upflow / Horizontal

INTERLINK PARTS RECOMMENDED STOCKING LIST 2018

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS

Transcription:

LK-LVTB May 2008 Replaces LW-03, February 2003 FPO Low Velocity Center Mount Unit Cooler Technical Guide s LWA - Air Defrost LWE - Electric Defrost LWG - Hot Gas Defrost www.larkinproducts.com

Table of Contents Nomenclature...2 Features & Benefits...3 Performance Data & Specifications Air Defrost...4-5 Electric Defrost...6-7 Hot Gas Defrost...8-9 Dimensional Data...10 Replacement Parts by InterLink...10 Physical Data...11 Standard Nozzle Selection...11 We have made a commitment to customer needs, innovation and environmental stewardship and have dedicated ourselves to delivering energy-efficient choices. PSC and EC motors will reduce costs, improve the bottom line and enhance equipment performance and service life. Choose the most energy-efficient motor available for evaporators. The EC motor is an Energy Solutions option on new Larkin Low Velocity Center Mount evaporators. Available on all new equipment or as an easyto-install, drop-in replacement aftermarket part from InterLink Commercial Refrigeration Parts. Because they re a drop-in replacement for existing shaded pole and PSC motors, installation is quick and easy. It s a high impact, quick payback solution for reducing costs and achieving green initiatives without replacing the entire system. EC motors by InterLink are up to 75% efficient - that s a 51-59% increase over shaded pole motors and a 30-35% increase over permanent-split capacitor (PSC) motors. With all of this added efficiency, you can count on more energy savings and lower operational costs while taking a step in the right direction toward conserving our planet s resources. To learn more about EC motors, visit www.interlinkparts.com/ec. Nomenclature LW A 100 A C Series Type Capacity Electrical Code Design Revision LW = Larkin Low Velocity Center Mount A = Air Defrost E = Electric Defrost G = Hot Gas Defrost # x 100 = BTUH A = 115/1/60 B = 208-230/1/60 AH = 115/1/60 (PSC) BH = 208-230/1/60 (PSC) AE = 115/1/60 (EC) BE = 208-230/1/60 (EC) 2008 Heatcraft Refrigeration Products LLC

Features & Benefits Cabinet Low height makes it ideal for low ceiling coolers - larger models are only 15 inches tall, allowing for maximum headroom and more product storage Unit designed to be mounted flush against the ceiling or suspended on rods Heavy gauge grained aluminum cabinet cleans easily and looks attractive Stainless steel screws prevent rust streaks Liquid line solenoid wire harness is factory-installed for quick installation Wire fan guards with PVC coating for durability All electrical components factory wired to terminal board and identified, making it easy to field wire the unit Cabinet design features access panels on each end for easy access to electrical and refrigeration components Fan panel is lightweight and can easily be lowered for easy servicing and installation Expansion valve mounts inside the cabinet Coils Sweat connections to reduce potential for leaks Coils are dehydrated and sealed at the factory Internally enhanced tubing and fin design for higher efficiency Electric defrost models incorporate high quality tubular heaters and a standard fixed defrost termination thermostat Hot gas defrost models come with a shipped-loose adjustable fan delay and defrost termination thermostat Drain Pan Double drain pan eliminates drain pan sweating Motors Motor rail is designed for maximum strength and durability Motors are life lubricated and thermal overload protected EC Motors (optional) available factory-installed or as a drop-in replacement through InterLink Commercial Refrigeration Parts in 115/1/60 and 208-230/1/60 voltages PSC are optional for 115/1/60 and 208-230/1/60 voltages PSC are required for 50 Hz operation Options Unit Configurations: mounted components, pre-assembled, pre-charged and Beacon II. - Units available with mounted TXV and mounted TXV / solenoid valve. - Pre-assembled units come with mounted TXV, liquid line solenoid valve and room thermostat. - Pre-charged units come with mounted TXV, liquid line solenoid valve, room thermostat and quick connect fittings (limited availability). - Mounted room thermostat option. - Beacon II units come with electronic expansion valves, pressure transducer, temperature sensors and Beacon control board Most models available with glycol circuiting (see glycol product brochure) Units available with stainless steel housing and drain pan Units available with copper fins. Air defrost units also available with polyester coated fins or various coil coatings options All LW Series units are UL-listed for US and Canada and meet NSF standards 3

Performance Data LWA Air Defrost 60 Hz 10 F TD 6 C TD -4 C SST 15 F TD Capacity 8 C TD -4 C SST Total 50-55 F DB 55% RH 20 F TD Sensible BTUH Watts BTUH Watts BTUH Watts BTUH Watts Fan Data No. CFM m 3 h LWA050 5,000 1,460 7,500 2,200 10,000 2,930 8,500 2,490 1 725 1,233 LWA075 7,500 2,200 11,250 3,300 15,000 4,390 12,750 3,730 1 730 1,241 LWA100 10,000 2,930 15,000 4,390 20,000 5,860 17,000 4,980 2 1,450 2,465 LWA130 13,000 3,810 19,500 5,710 26,000 7,620 22,100 6,470 2 1,470 2,499 LWA155 15,500 4,540 23,250 6,810 31,000 9,080 26,350 7,720 2 1,460 2,482 LWA180 18,000 5,270 27,000 7,910 36,000 10,540 30,600 8,960 3 2,130 3,621 LWA210 21,000 6,150 31,500 9,230 42,000 12,300 35,700 10,460 4 2,840 4,828 LWA270 27,000 7,910 40,500 11,860 54,000 15,820 45,900 13,440 4 2,800 4,760 LWA340 34,000 9,960 51,000 14,940 68,000 19,920 57,800 16,930 5 3,500 5,950 LWA Air Defrost 50 Hz 10 F TD 6 C TD -4 C SST 15 F TD Capacity 8 C TD -4 C SST Total 50-55 F DB 55% RH 20 F TD Sensible BTUH Watts BTUH Watts BTUH Watts BTUH Watts Fan Data No. CFM m 3 h LWA050 4,800 1,410 7,100 2,080 9,500 2,780 8,100 2,370 1 660 1,122 LWA075 7,100 2,080 10,700 3,130 14,300 4,190 12,100 3,540 1 660 1,122 LWA100 9,500 2,780 14,300 4,190 19,000 5,570 16,200 4,740 2 1,310 2,227 LWA130 12,400 3,630 18,500 5,420 24,700 7,230 21,000 6,150 2 1,330 2,261 LWA155 14,700 4,310 22,100 6,470 29,500 8,640 25,000 7,320 2 1,320 2,244 LWA180 17,100 5,010 25,700 7,530 34,200 10,020 29,100 8,520 3 1,920 3,264 LWA210 20,000 5,860 29,900 8,760 39,900 11,690 33,900 9,930 4 2,560 4,352 LWA270 25,700 7,530 38,500 11,280 51,300 15,030 43,600 12,770 4 2,530 4,301 LWA340 32,300 9,460 48,500 14,210 64,600 18,920 54,900 16,080 5 3,160 5,372 For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at 50 Hz will not see a reduction in performance due to the electronic control of the motor) 4

Specifications LWA Air Defrost 60 Hz Shaded Pole Motor PSC Motor EC Motor 115/1/60 230/1/60 115/1/60 230/1/60 115/1/60 230/1/60 Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts LWA050 2.1 135 1.1 135 0.9 90 0.5 90 0.9 55 0.5 55 LWA075 2.1 135 1.1 135 0.9 90 0.5 90 0.9 55 0.5 55 LWA100 4.2 270 2.2 270 1.8 180 1.0 180 1.8 110 1.0 110 LWA130 4.2 270 2.2 270 1.8 180 1.0 180 1.8 110 1.0 110 LWA155 4.2 270 2.2 270 1.8 180 1.0 180 1.8 110 1.0 110 LWA180 6.3 405 3.3 405 2.7 270 1.5 270 2.7 165 1.5 165 LWA210 8.4 540 4.4 540 3.6 360 2.0 360 3.6 220 2.0 220 LWA270 8.4 540 4.4 540 3.6 360 2.0 360 3.6 220 2.0 220 LWA340 10.5 675 5.5 675 4.5 450 2.5 450 4.5 275 2.5 275 LWA Air Defrost 50 Hz PSC Motor EC Motor 110/1/50 220/1/50 110/1/50 220/1/50 Amps Watts Amps Watts Amps Watts Amps Watts LWA050 0.8 80 0.4 80 0.9 55 0.5 55 LWA075 0.8 80 0.4 80 0.9 55 0.5 55 LWA100 1.7 160 0.8 160 1.8 110 1.0 110 LWA130 1.7 160 0.8 160 1.8 110 1.0 110 LWA155 1.7 160 0.8 160 1.8 110 1.0 110 LWA180 2.5 240 1.2 240 2.7 165 1.5 165 LWA210 3.3 320 1.6 320 3.6 220 2.0 220 LWA270 3.3 320 1.6 320 3.6 220 2.0 220 LWA340 4.2 400 2.0 400 4.5 275 2.5 275 5

Performance Data LWE Electric Defrost 60 Hz 10 F TD 6 C TD -4 C SST Capacity 15 F TD BTUH Watts BTUH Watts Fan Data 8 C TD -4 C SST No. CFM m 3 h LWE050 5,000 1,460 7,500 2,200 1 725 1,233 LWE075 7,500 2,200 11,250 3,300 1 730 1,241 LWE100 10,000 2,930 15,000 4,390 2 1,450 2,465 LWE130 13,000 3,810 19,500 5,710 2 1,470 2,499 LWE155 15,500 4,540 23,250 6,810 2 1,460 2,482 LWE180 18,000 5,270 27,000 7,910 3 2,130 3,621 LWE210 21,000 6,150 31,500 9,230 4 2,840 4,828 LWE270 27,000 7,910 40,500 11,860 4 2,800 4,760 LWE340 34,000 9,960 51,000 14,940 5 3,500 5,950 LWE Electric Defrost 50 Hz 10 F TD 6 C TD -4 C SST Capacity 15 F TD BTUH Watts BTUH Watts Fan Data 8 C TD -4 C SST No. CFM m 3 h LWE050 4,800 1,410 7,100 2,080 1 660 1,122 LWE075 7,100 2,080 10,700 3,130 1 660 1,122 LWE100 9,500 2,780 14,300 4,190 2 1,310 2,227 LWE130 12,400 3,630 18,500 5,420 2 1,330 2,261 LWE155 14,700 4,310 22,100 6,470 2 1,320 2,244 LWE180 17,100 2,010 25,700 7,530 3 1,920 3,264 LWE210 20,000 2,860 29,900 8,760 4 2,560 4,352 LWE270 25,700 7,530 38,500 11,280 4 2,530 4,301 LWE340 32,300 9,460 48,500 14,210 5 3,160 5,372 For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at 50 Hz will not see a reduction in performance due to the electronic control of the motor) 6

Specifications LWE Electric Defrost 60 Hz Shaded Pole Motor PSC Motor EC Motor Defrost Heater 230/1/60 230/1/60 230/1/60 230/1/60 Watts Amps Watts Amps Watts Amps Watts Total Amps LWE050 1.1 135 0.5 90 0.5 55 2,000 8.7 LWE075 1.1 135 0.5 90 0.5 55 2,400 10.5 LWE100 2.2 270 1.0 180 1.0 110 2,800 12.2 LWE130 2.2 270 1.0 180 1.0 110 4,000 17.4 LWE155 2.2 270 1.0 180 1.0 110 4,000 17.4 LWE180 3.3 405 1.5 270 1.5 165 4,000 17.4 LWE210 4.4 540 2.0 360 2.0 220 5,200 22.6 LWE270 4.4 540 2.0 360 2.0 220 5,200 22.6 LWE340 5.5 810 2.5 450 2.5 275 7,000 30.4 LWE Electric Defrost 50 Hz PSC Motor EC Motor Defrost Heater 220/1/50 220/1/50 220/1/50 Watts Amps Watts Amps Watts Total Amps LWE050 0.4 80 0.5 55 1,830 8.3 LWE075 0.4 80 0.5 55 2,200 10.0 LWE100 0.8 160 1.0 110 2,560 11.6 LWE130 0.8 160 1.0 110 3,660 16.6 LWE155 0.8 160 1.0 110 3,660 16.6 LWE180 1.2 240 1.5 165 3,660 16.6 LWE210 1.6 320 2.0 220 4,760 21.6 LWE270 1.6 320 2.0 220 4,760 21.6 LWE340 2.0 400 2.5 275 6,400 29.1 7

Performance Data LWG Hot Gas Defrost 60 Hz Capacity Fan Data 10 F TD 6 C TD 15 F TD 8 C TD -4 C SST -4 C SST No. CFM m 3 h BTUH Watts BTUH Watts LWG100 10,000 2,930 15,000 4,390 2 1,450 2,465 LWG130 13,000 3,810 19,500 5,710 2 1,470 2,499 LWG155 15,500 4,540 23,250 6,810 2 1,460 2,482 LWG180 18,000 5,270 27,000 7,910 3 2,130 3,621 LWG210 21,000 6,150 31,500 9,230 4 2,840 4,828 LWG270 27,000 7,910 40,500 11,860 4 2,800 4,760 LWG340 34,000 9,960 51,000 14,940 5 3,500 5,950 LWG Hot Gas Defrost 50 Hz Capacity Fan Data 10 F TD 6 C TD 15 F TD 8 C TD -4 C SST -4 C SST No. CFM m 3 h BTUH Watts BTUH Watts LWG100 9,500 2,780 14,300 4,190 2 1,310 2,227 LWG130 12,400 3,630 18,500 5,420 2 1,330 2,261 LWG155 14,700 4,310 22,100 6,470 2 1,320 2,244 LWG180 17,100 5,010 25,700 7,530 3 1,920 3,264 LWG210 20,000 5,860 29,900 8,760 4 2,560 4,352 LWG270 25,700 7,530 38,500 11,280 4 2,530 4,301 LWG340 32,300 9,460 48,500 14,210 5 3,160 5,372 For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at 50 Hz will not see a reduction in performance due to the electronic control of the motor) Optional Liquid Line Bypass Kit For Hot Gas Defrost The LWG may be field piped for hot gas defrost using the optional bypass kit. When compressor vapor, in reverse cycle defrosting, is directed back into the evaporator at the suction connection, it condenses into liquid. The field-installed liquid line bypass kit directs the condensed liquid around the thermostatic expansion valve and back into the liquid line. Bypass kits include bypass piping, check valve and instructions. Adjustable fan control is shipped loose with hot gas units. 8

Specifications LWG Hot Gas Defrost 60 Hz Shaded Pole Motor PSC Motor EC Motor Drain Pan Heater 115/1/60 208-230/1/60 115/1/60 208-230/1/60 115/1/60 208-230/1/60 115/1/60 230/1/60 Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Total Amps LWG100 4.2 270 2.2 270 1.8 180 1.0 180 1.8 110 1.0 110 350 3.0 1.5 LWG130 4.2 270 2.2 270 1.8 180 1.0 180 1.8 110 1.0 110 500 4.4 2.2 LWG155 4.2 270 2.2 270 1.8 180 1.0 180 1.8 110 1.0 110 500 4.4 2.2 LWG180 6.3 405 3.3 405 2.7 270 1.5 270 2.7 165 1.5 165 500 4.4 2.2 LWG210 8.4 540 4.4 540 3.6 360 2.0 360 3.6 220 2.0 220 650 5.7 2.8 LWG270 8.4 540 4.4 540 3.6 360 2.0 360 3.6 220 2.0 220 650 5.7 2.8 LWG340 10.5 675 5.5 675 4.5 450 2.5 450 4.5 275 2.5 275 875 7.6 3.8 LWG Hot Gas Defrost 50 Hz PSC Motor EC Motor Drain Pan Heater 110/1/50 220/1/50 110/1/50 220/1/50 110/1/50 220/1/50 Watts Amps Watts Amps Watts Amps Watts Amps Watts Total Amps LWG100 1.7 160 0.8 160 1.8 110 1.0 110 320 2.9 1.5 LWG130 1.7 160 0.8 160 1.8 110 1.0 110 460 4.2 2.1 LWG155 1.7 160 0.8 160 1.8 110 1.0 110 460 4.2 2.1 LWG180 2.5 240 1.2 240 2.7 165 1.5 165 460 4.2 2.1 LWG210 3.3 320 1.6 320 3.6 220 2.0 220 595 5.4 2.7 LWG270 3.3 320 1.6 320 3.6 220 2.0 220 595 5.4 2.7 LWG340 4.2 400 2.0 400 4.5 275 2.5 275 800 7.3 3.6 9

Dimensional Data L 29-3/16" 742 mm 5-3/4" 146 mm G D 3/8 DIA. MTG. HOLES F 3-13/16" 97 mm 1-1/4" 31 mm 27-15/16" 711 mm 1-1/4" 31 mm A E B AIR OUT AIR OUT C ELECTRICAL CONNECTION All s Dimensional Data 10 Numbers by Defrost Types AIR IN Dimensions A B C D E F G L Air Electric Hot Gas in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm LWA050 LWE050-6-7/8 175 8-7/8 225 6-1/16 154 - - 4-5/8 118 3-1/4 83 1-5/8 41 53-1/2 1,359 LWA075 LWE075-6-7/8 175 8-7/8 225 6-1/16 154 - - 4-5/8 118 3-1/4 83 1-5/8 41 75-1/2 1,918 LWA100 LWE100 LWG100 9-3/8 238 11-3/8 289 8-9/16 218 - - 7-1/8 181 3-1/4 83 1-5/8 41 75-1/2 1,918 LWA130 LWE130 LWG130 13-1/8 333 15-1/8 384 12-1/8 308 - - 8-1/2 216 2-11/16 68 1-1/8 29 75-1/2 1,918 LWA155 LWE155 LWG155 13-1/8 333 15-1/8 384 12-1/8 308 - - 8-1/2 216 2-11/16 68 1-1/8 29 75-1/2 1,918 LWA180 LWE180 LWG180 13-1/8 333 15-1/8 384 12-1/8 308 - - 8-1/2 216 2-11/16 68 1-1/8 29 75-1/2 1,918 LWA210 LWE210 LWG210 13-1/8 333 15-1/8 384 12-1/8 308 44 1,118 8-1/2 216 2-11/16 68 1-1/8 29 97-1/2 2,477 LWA270 LWE270 LWG270 13-1/8 333 15-1/8 384 12-1/8 308 44 1,118 8-1/2 216 2-11/16 68 1-1/8 29 97-1/2 2,477 LWA340 LWE340 LWG340 13-1/8 333 15-1/8 384 12-1/8 308 55 1,397 8-1/2 216 2-11/16 68 1-1/8 29 119-1/2 3,035 Replacement Parts Commercial Refrigeration Parts AIR IN Right source. Right parts. Right now.. InterLink is your link to a complete line of dependable and certified commercial refrigeration parts, accessories and innovative electronic controls for all Larkin equipment. At InterLink, we provide our wholesalers with a comprehensive selection of product solutions and innovative technologies for the installed customer base. And every product is built to ensure the same high performance standards with which all Heatcraft Refrigeration Products (HRP) brands are built backed by a dedicated team to serve every customer need, delivering at the best lead times in the industry. Dependable. Versatile. Courteous.. Finally, one simple source for all your replacement needs from a name you can trust. For parts, please contact (800) 686-7278 or visit www.interlinkparts.com. No. Fans Air Defrost Electric Defrost Hot Gas Defrost 1 050-075 050-075 2 100-155 100-155 100-155 3 180 180 180 4 210-270 210-270 210-270 5 340 340 340 Electrical Components/Miscellaneous Part # Description No. Fans 22512601 Terminal Strip 1-5 5521R Defrost Termination 1-5 2891040 Room Thermostat 1-5 5708L Heater Safety 1-5 4550G Filters 1-5 DRAIN REFRIGERANT CONNECTION ( OPPOSITE SIDE ) REFRIGERANT CONNECTION Motor/Fan Blade/Fan Guards Part # Description No. Fans 5036SS Motor 115/1/60 Shaded Pole 1-5 5036TS Motor 208-230/1/60 Shaded Pole 1-5 5036NS Motor 115/1/60/50 PSC 1-5 5036PS Motor 208-230/1/60/50 PSC 1-5 25305901 Motor 460/1/60/50 PSC 1-5 25318001 Motor 115/1/60 EC 1-5 25317901 Motor 208-230/1/60 EC 1-5 5110E Fan Blade 1-5 5055F Fan Guard - Wire 1-5 40003001 Motor Mount 1-5 Cabinet Components Part # Description No. Fans C26769A2 Drain Pan-Stucco 1 C26771A2 Drain Pan-Stucco 2 C26361A2 Drain Pan-Stucco 3 C26362A2 Drain Pan-Stucco 4 D20817A2 Drain Pan-Stucco 5 C26769A4 Drain Pan-White 1 C26771A4 Drain Pan-White 2 C26361A4 Drain Pan-White 3 C26362A4 Drain Pan-White 4 D20817A4 Drain Pan-White 5 Electric Defrost Part # Description No. Fans Consult Factory Coil Heater 1 4544B Coil Heater 2 4544B Coil Heater 3 4545B Coil Heater 4 4546B Coil Heater 5

Physical Data LWA Air Defrost No. of Fans Connections (in.) Liquid Suction OD OD Aprox. Net Wt. lbs. Standard Nozzle Selection LWA Air Defrost kg LWA050 1 1/2 7/8 70 32 LWA075 1 1/2 7/8 103 47 LWA100 2 1/2 7/8 106 48 LWA130 2 1-1/8 1-1/8 145 66 LWA155 2 1-1/8 1-1/8 149 68 LWA180 3 1-1/8 1-1/8 160 73 LWA210 4 1-1/8 1-1/8 193 88 LWA270 4 1-3/8 1-3/8 200 91 LWA340 5 1-3/8 1-3/8 242 110 No. of Distributor Tube (in.) No. of Fans OD Length Circuits R-404A* R-22 LWA050 1 3/16 18 2 L-1/2 L-1/3 LWA075 1 3/16 18 4 L-3/4 L-1/2 LWA100 2 3/16 18 6 L-1 L-3/4 LWA130 2 3/16 24 12 E-1-1/2 E-1 LWA155 2 3/16 24 10 E-2 E-1 LWA180 3 3/16 24 12 E-2 E-1-1/2 LWA210 4 3/16 24 12 E-2-1/2 E-1-1/2 LWA270 4 3/16 24 20 C-3 C-2 LWA340 5 3/16 24 20 C-4 C-2-1/2 LWE Electric Defrost No. of Distributor Tube (in.) No. of Fans OD Length Circuits R-404A* R-22 LWE050 1 3/16 18 2 L-1/2 L-1/3 LWE075 1 3/16 18 4 L-1 L-3/4 LWE100 2 3/16 18 6 L-1-1/2 L-3/4 LWE130 2 3/16 24 12 E-1-1/2 E-1 LWE155 2 3/16 24 10 E-2 E-1-1/2 LWE180 3 3/16 24 12 E-2 E-1-1/2 LWE210 4 3/16 24 12 E-2-1/2 E-2 LWE270 4 3/16 24 20 C-3 C-2 LWE340 5 3/16 24 20 C-4 C-2-1/2 LWG Hot Gas Defrost LWE Electric Defrost No. of Distributor Tube (in.) No. of Fans OD Length Circuits R-404A* R-22 LWG100 2 3/16 18 6 L-1-1/2 L-3/4 LWG130 2 3/16 24 12 E-1-1/2 E-1 LWG155 2 3/16 24 10 E-2 E-1-1/2 LWG180 3 3/16 24 12 E-2 E-1-1/2 LWG210 4 3/16 24 12 E-2-1/2 E-2 LWG270 4 3/16 24 20 C-3 C-2 LWG340 5 3/16 24 20 C-4 C-2-1/2 *Also suitable for R-507, R-502, R-134A, R-401A, R-402A NOTE: Nozzles sized for 95 F liquid temp. at expansion valve. Refer to manual H-IM-64 if liquid temp. is not 95 F Room temperature of 35 F for air defrost models and 28 F for electric/hot gas models Consult Larkin Application Engineering if evaporator TD is not 10-15 F, (room temp. - saturated suction temp.) No. of Fans Connections (in.) Liquid Suction OD OD Aprox. Net Wt. lbs. kg LWE050 1 1/2 7/8 75 34 LWE075 1 1/2 7/8 108 49 LWE100 2 1/2 7/8 111 50 LWE130 2 1-1/8 1-1/8 150 68 LWE155 2 1-1/8 1-1/8 154 70 LWE180 3 1-1/8 1-1/8 157 71 LWE210 4 1-1/8 1-1/8 203 92 LWE270 4 1-3/8 1-3/8 208 94 LWE340 5 1-3/8 1-3/8 250 113 NOTE: All units have 1/4" OD external equalizer and 3/4" FPT drain connection LWG Hot Gas Defrost No. of Fans Connections (in.) Liquid Suction OD OD Aprox. Net Wt. lbs. kg LWG100 2 1/2 7/8 131 59 LWG130 2 1-1/8 1-1/8 170 77 LWG155 2 1-1/8 1-1/8 174 79 LWG180 3 1-1/8 1-1/8 185 84 LWG210 4 1-1/8 1-1/8 223 101 LWG270 4 1-3/8 1-3/8 228 103 LWG340 5 1-3/8 1-3/8 270 122 Caution: Refrigeration system will not perform properly without correct nozzle! 11

For more information on Larkin refrigeration products, contact your Sales Representative or visit our web site at www.larkinproducts.com. Mastering the Art of Cold A Brand of Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd. Stone Mountain, GA 30087 800.848.9889 Fax: 770.465.5990 www.larkinproducts.com Since product improvement is a continuing effort, we reserve the right to make changes in specifications without notice. LK-LVTB-0508 Version 000