Refrigerant Leak Detector Manual

Similar documents
Ammonia Leak Detector Manual

Inc Series Digital Gas Detector/Controller. Operation Manual

Version Inc Series Digital Gas Detector/Controller. Operation Manual

Carbon Monoxide Transmitter

Version Digital Gas Dector/Controller. Operation Manual

Version Digital Gas Detector/Controller. Operation Manual

MT-374B/364B Operation User s Guide. The Anti-Sweat Energy Saving Controller user s manual

MT Alliance Refrigeration Technician s Manual

Danfoss gas detection units

Anti-sweat Energy Saver Installation guide

Danfoss gas detection units

SEC 2000 Millenium Infrared Gas Detector

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

Analog Room Pressure Monitor RPC Series

Pioneer-R16 Gas Monitor Operator s Manual

Danfoss gas detection unit Type GD Heavy Duty

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Recalibrate the way you look at gas detection

Universal Gas Detector

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

INSTALLATION AND OPERATING INSTRUCTIONS

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors)

GLD-30 Gas Leak Detector

Oxygen (O2) Single-Point Gas Detection System

OVEN INDUSTRIES, INC.

Ax60+ Multi-Gas. Service Manual

Product Manual SZ1144

Two-Channel Gas Controller

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual

Product Manual SZ1145

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 800 Gas Monitor Operator s Manual

Duct and Rough Service Carbon Monoxide Sensor

User Manual. PolyGard Gas Controller MGC3. Two-Channel Analog Gas Controller Serial Number _E _0907. September 2007

CLEANROOM MONITOR CR3A Network - Installation Instructions

ZSC100 Gas Detection and Alarm System Controller

! "! # Please read these installation and operating instructions completely and carefully before starting.

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006

SECTION 1 (Page 2) Introduction, standard accessories and mounting specifications.

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

AIR MONITOR & ALARM SYSTEM Installation and Operating Guidelines Version 7.2 Series Software

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

MagnaValve Shot Flow Controller

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

Operations Manual TS400. Test Station for G450/G460 Gas Detector

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

Operations Manual TS400. Test Station for G450/G460 Gas Detector

Operation Manual. Rev. E GEM-II Self Contained Gas Detector.

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

DI220 Using the Optional Docking Station The maintenance and operating functions of the Micro IV can be automated with the Micro IV Docking Station.

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours

Paradox Integration Module Settings Guide

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

IMR 5000 Operating Manual S/N: SAMPLE For information only! IMR Environmental Equipment Inc.

Gas Detection Sensor type GDA, GDC, GDHC, GDHF, GDH REFRIGERATION AND AIR CONDITIONING. Technical leaflet

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

Safe T Net 210. Instruction Manual Part Number Mar2010

Gas detecting sensor Types GDA, GDC, GDHC, GDHF, GDH

DS3MX-E-I. Installation Guide. 3 Zone Mini Control Panel

CN7232 Advanced Garage Ventilation Controller

20 Light Remote Annunciator

RCS Residential Control Systems Inc.

Warranty Registration

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Planning Elevator Relay Groups Programming Millenium for Windows Software

Toxic Gas Detection. Model F12. Toxic Gas Detection

SAM-MAX Refrigerant Monitors

EasyTronic III MANUAL SERVICE

Beacon 410A Gas Monitor Operator s Manual

Operation Manual. Rev. D GEM-II Self-Contained Gas Detector.

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Beacon 110 Gas Monitor Operator s Manual

HALOGUARD IR MULTI-POINT, COMPOUND SPECIFIC MONITOR INSTRUCTION MANUAL

Air Check O 2 Sample Draw Monitor

Controllers. Instruction Manual WARNING

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

Networkable Fan Coil Controller Specification and Installation Instructions

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

Frequently asked questions: Intelligent Transmitter Series

Air Check Ex O 2 Deficiency Monitor

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. SIL1 reliability. Gas Detection Control Panel

Air Check O 2 Deficiency Monitor 0-25%

RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL. USER MANUAL Read carefully before use

Model 4001 Series Single Channel Controller

PureAire Combo O 2 / CO 2 Monitor

Air Check O 2 Deficiency Monitor 0-25%

WM3000 WIRELESS MODULES

Warranty Registration

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

M2 Rig Monitor Operator s Manual

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter

Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Transcription:

Refrigerant Leak Detector Manual Document No. 70-PHW-1018-R2.4 No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written permission of Micro Thermo Technologies. 1997-2015 by Micro Thermo Technologies. All rights reserved worldwide. Local Phone: (450) 668-3033 Fax: (450)668-2695 Toll Free Canada: 1-888-664-1406 Toll Free USA: 1-888-920-6284 www.sporlanonline.com/micro-thermo

Table of Contents 1 Description... 1 2 Specifications, series 023-034X Gas sensor... 2 3 Physical installation:... 3 4 Operation... 4 5 User Settings Configuration... 5 6 MT Alliance installation... 6 7 Test... 8 70-PHW-1018-R2.4 023-034X Refrigerant Leak Detector Manual.doc i

1 Description The series 023-034X are entirely solid state electronic sensors that have proven to be the most reliable method of detecting refrigerant leaks for the price. The catalytic semiconductor responds quickly to refrigerant in very low concentrations. Sensor life is in excess of five years and routine calibration is needed usually once per year. A low wattage heater element in the cell performs two functions; continuous decontamination of the sensing element, and the creation of a convection air current that pulls air into the unit. This series uses an inexpensive plug-and-play replaceable sensor tip that memorized the gas type, scale and calibration settings. So you can change the sensor tip instead of having the unit calibrated. Units are factory calibrated when delivered but they get their best accuracy after 24 hours warm-up. The unit can operate in stand-alone mode with 3 adjustable output relays, or with a group as part of a twisted pair network for shared functions. Any of the sensors connected can be assigned the task of controlling alarms and fans so a dedicated central controller is not necessary. An alphanumeric display located on the front panel shows the actual reading or program values. An analog signal (2-10V) is output from the sensor for the reading to be monitored remotely. The enclosure is splash proof in the event of walls being washed with hoses. 023-0342, 023-0343 Standard Ranges for Gas Concentration Model Number Type of refrig. Sensor Range (0-100%) 023-0342 HFC R23 0-1000 ppm R134a 0-2000 ppm R152a 0-600 ppm R402a (HP-80) 0-600 ppm R404a (HP-62) 0-800 ppm R407a 0-1400 ppm R408a 0-800 ppm R409a 0-600 ppm R410a 0-1400 ppm R500 0-800 ppm R502 0-800 ppm R507 (AZ-50) 0-800 ppm 023-0343 HCFC R21 0-600 ppm R22 0-1000 ppm R141b 0-900 ppm R142b 0-800 ppm R401a (MP-39) 0-1200 ppm (023-0342 recomended) R402a (HP-80) 0-1500 ppm (023-0342 recomended) R408a 0-1500 ppm (023-0342 recomended) R409a 0-1500 ppm (023-0342 recomended) R502 0-1500 ppm 70-PHW-1018-R2.4 023-034X Refrigerant Leak Detector Manual.doc 1

2 Specifications, series 023-034X Gas sensor Gas sensors O=optional, S=standard Sample frequency, one sensor continuous, maximum 1 second S Sample frequency, (in house network) maximum 1 second, 1-99 units S Response time to gas less than 30 seconds to 90% reading S Type of sensing element electro-chemical for toxic gases S Semiconductor for refrigerants S fuel cell for oxygen S Coverage maximum 50 feet each side of sensor, with no obstructions Sensor Memory Module type of gas, scale, sensor calibration points, S zero, gain Output Analog output (2) 4-20 ma or 2-10 v (per jumper) S Digital output In house network, twisted pair S BACnet MS/TP network (optional) O RS485 Switching capacity 3 relays SPDT, 1/8 HP @ 125 vac S 5 amp @ 125 vac non inductive Delay, relay on (3) 0-999 seconds (16 minutes) S Delay, relay off (run on) (3) 0-999 seconds (16 minutes) S User controls and indicators LCD display gas concentration, ppm or percentage S Alarm indicators 1, 2, 3 LCD S User keyboard 4 push buttons S to access and view options to modify options Security access control 6 key strokes, user set S Internal audio alarm on relay 3, adjustable S Physical Characteristics Energy consumption Supply voltage Electrical conduit entry Dimensions Operating temperature range varies with type of sensor, 150 ma maximum at 24 vac, (3.6 va) 16 to 29 vac, 20 to 31 vdc 3.6 va 4 X 0.875 two on top, one on bottom One in rear, all with hermetic seals 7 in. high, 4.5 in. wide, 1.7 in. deep. 17.5 cm. high, 11 cm. wide, 4.2 cm. deep. Local display -25 to 50 C (-13 to 122 F) Other component -40 to 50 C (-40 to 122 F) Maintenance guide Visual verification recommended frequency: once per week. The system incorporates monitoring software which checks the operation of the circuits. This software is always running when the unit is powered on. Ensure that the unit is installed on an independent circuit. It is recommended that the unit be checked once per week to ensure that it is on, by the presence of reading on the display. Verification of communication and calibration of sensors recommended frequency: once per year. It is recommended that sensor be verified with standardized bottled gas mixtures by the manufacturer or other qualified specialist or the sensor plugin module be replaced with a new or factory calibrated module. The communication between the sensor and control systems should be tested. A report of compliance should be supplied and available on the site. 70-PHW-1018-R2.4 023-034X Refrigerant Leak Detector Manual.doc 2

3 Physical installation: This device is normally used with a Manual Pull Station, MTT number 961-0001 To Sensor Node Sensor GND Sensor U Input NO 1 NO 2 NO 3 To Pull Station Panel Option To Ext Audio Device Option 24Vac 3.6VA Power 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 4-20mA 2-10V EOL Relay Contacts Active relay number - + G SA SB 24Vac Analog Power Output Gas Leak Detector R141b 123 900 Alarms Value Alarm 1 Alarm 2 Alarm 3 Local Audio Alert Sensor A Sensor B PPM reading Affix the panel on the wall according to the following chart Open a nock-out hole for wiring. 023-0341 Diesel 50% of ceiling height 023-0342 HFC Refrigerant 10-30cm from floor 023-0343 HCFC Refrigerant 10-30cm from floor 023-0344 Ammonia 10-30cm from ceiling Apply the power on 24V+ and the common on 24V- Take the Sensor A signal output from SA and the signal ground on the G terminal 70-PHW-1018-R2.4 023-034X Refrigerant Leak Detector Manual.doc 3

Make sure the SA jumper is towards down to send 2-10V signal on the SA output Place the SB jumper towards down to send 2-10V signal on the SB output Place the appropriate jumper towards up in the case you need to send 4-20mA signal on the output. Dry contact wiring on the terminal block NF/C COM NO to be connected to the manual pull station. NC - Close contact when not in alarm Common terminal NO - Open contact when not in alarm IMPORTANT! 120V: If you commute 120V equipment with the relay contact, connect the ground to the chassis terminal. Use User settings P00 to determine the threshold of SA at which the relay should operate. P01 is the set time, P02 is the reset time. Alarm reset by its own, there is no need to acknowledge an alarm. See section 5 User settings. The jumper EOL is not used in this application and don t have any effect. Replace the cover and screws. Default display scale is R22 or R507 and it can be changed by the user. To view the current settings on the model 023-034X, press the right arrows. To modify press up/down. See section 5 for more information. To save, press up and left buttons at the same time. The word **OK** will appear. Example: To set the reading scale for R141b you have to change the gas type as follow: Press the right arrows to display the value for P57 (hold arrow to speed up) then press the up arrow to change gas type (see available gas type and their ppm range at section 1). 4 Operation The power supplied should be between 16 to 29 vac or between 20 to 31 vdc. If the power is too high or too low the sensor will not work properly. Each time the unit is powered on with proper power, the relays are disabled and the analog outputs operate normally during the warm up period. This is to allow time for the sensor to warm up and to avoid false alarm relay flip due to high readings of the cold sensor. The warm up timer may be cancel by pressing any arrow. The output may take a few more minutes to stabilize as the sensor may need more warm-up time if it was not powered for many days. The warm up time can be changed to up to 255 sec with the P52 user setting. After power up it will take 48 hours for maximum accuracy to be obtained, although accuracy is very good after an hour. When the gas concentration is higher than the threshold set by A1 for the time A1D the relay 1 is energized. The active relay number (Alarms 123) will be displayed at the bottom left of the display. The relay will de-energized A1R seconds after the gas concentration drops below the threshold. A1 is for relay 1 settings, A2 is for relay 2 settings and A3 is for relay 3 and buzzer settings. Press the right arrow to change settings then up and left arrow simultaneously to save changes. See section 5 User settings. The buzzer may sounds when relay 3 activates. To silence the buzzer press any arrow. See section 7 Test for overrides and test commands. 70-PHW-1018-R2.4 023-034X Refrigerant Leak Detector Manual.doc 4

5 User Settings Configuration To view the current settings on the model 023-034X, press the right arrows. To modify the current setting press up/down arrow. To save, press up and left arrows at the same time. The word **OK** will appear. Program Code Definition Display maximum value default ============================================================================= Sensor A (first module, plugged into the left side) Firmware rev 1C08 Sensor B (second module, plugged into the right side) P00 P18 Alarm 1 level A1 sensor scale 400ppm P01 P19 Alarm 1 Delay on (seconds) A1D 999 5s P02 P20 Alarm 1 Delay off (run on) (seconds) A1R 999 300s P03 P21 Alarm 2 level A2 sensor scale 400ppm P04 P22 Alarm 2 Delay on A2D 999 5s P05 P23 Alarm 2 Delay off (run on) A2R 999 300s P06 P24 Alarm 3 level A3 sensor scale 400ppm P07 P25 Alarm 3 Delay on A3D 999 5s P08 P26 Alarm 3 Delay off A3R 999 5s P09 P27 Alarm 1 external command A A1X 255 1 P10 P28 Alarm 1 external command B A1X 255 0 P11 P29 Alarm 1 external command C A1X 255 0 P12 P30 Alarm 2 external command A A2X 255 2 P13 P31 Alarm 2 external command B A2X 255 0 P14 P32 Alarm 2 external command C A2X 255 0 P15 P33 Alarm 3 external command A A3X 255 3 P16 P34 Alarm 3 external command B A3X 255 0 P17 P35 Alarm 3 external command C A3X 255 0 P36 external command for relay 1 XR1 255 1 P37 external command for relay 2 XR2 255 2 P38 external command for relay 3 XR3 255 3 P39 sensor identification address for network ADR 255 0 P40 sensor A analog output zero (factory set) ZA 255 P41 sensor A analog output span (factory set) SA 255 P42 sensor B analog output zero (factory set) ZB 255 P43 sensor B analog output span (factory set) SB 255 P44 C temperature display 0=off 1=on TMP 0/1 0 P45 audio alarm off/on AUD 0/1 1 P49 Keyboard security lock, 0=off, 1=on SEC 0/1 0 P50 Temperature modify/correct TMO -9/+9 C P51 High temperature alarm limit (alarm 1) ATH 0-99 C 60 P52 Warm up delay, disables alarms on power up DEL 0-99 mins 60 P55 Low temperature alarm limit (alarm 3) ATB 0-99 C 0 P56 Network Display on/off (non BACnet version) NET 0/1 0 P57 sensor A refrigerant ppm scale RFA Refrig list Rx P58 sensor B refrigerant ppm scale RFB Refrig list Rx Where Rx is R507 for 023-0342 and R22 for 023-0343 Calibration To calibrate the sensor, adjust the zero and span using standardized gas mixtures. Press the right arrow to enter the program mode (as above) then press up and right at the same time to enter the calibration mode. You will see SAZ and the current gas reading on the first line plus the zero factor on the second line. Adjust the factor with the up and down arrows. To save it press up and left at the same time. Press the right arrow to proceed with the span factor SAS and repeat last two steps When finished press and hold the left arrow Note: these calibrations setting are stored on the sensor plug in module and will follow the module if plugged into another gas sensor unit. 70-PHW-1018-R2.4 023-034X Refrigerant Leak Detector Manual.doc 5

6 MT Alliance installation Log into MT Alliance. You must have technician refrigeration configuration permissions. Enter configuration Mode. Select and zoom in the view where the sensor is located. Pick and drop a Custom Sensor Then select Absolute Gas Concentration Type, Local source, Micro Thermo manufacturer and the sensor and gas type you are going to monitor Click OK then click on the new button. In the Detail tab enter a sensor name in the Identification field 70-PHW-1018-R2.4 023-034X Refrigerant Leak Detector Manual.doc 6

In the Alarm Settings tab Set the limit values and the Alarm set time inside which the monitoring should run without any alarm 70-PHW-1018-R2.4 023-034X Refrigerant Leak Detector Manual.doc 7

In the Hardware tab you can review the sensor manufacturer and model and you can select the node and input where this sensor is connected. If you need help to make the wire connections click on Diagram. Click on OK to complete the connection. If the node is connected you should get a green status right away even if the sensor is not powered. 7 Test Analog output To test the output signal, power the sensor and wait for the warm-up period to expire Use P40 to force sensor A output to 2V (4mA) (min range 0 ppm) Use P41 to force sensor A output to 10V (20mA) (max range) Use P42 to force sensor B output to 2V (4mA) (min range 0 ppm) Use P43 to force sensor B output to 10V (20mA) (max range) You can also calibrate the Zero and Span of the signal through these parameters. Relay output To force the relay output 1 for 5 minutes press the up arrow for more than 5 sec then press it another time. Add 5 minutes each time you press the up arrow. MAN or M at the left of the display will tell that the relay is overridden. To cancel the relay override, press the down arrow. 70-PHW-1018-R2.4 023-034X Refrigerant Leak Detector Manual.doc 8

8 Revision History REV Description Revised by Date 0.0 Creation of the document KR 20-Mar-99 0.1 Revision RL 9-Apr-04 0.2 Fusion spec, installation and startup RL 5-May-04 0.3 Revision RL 7-May-04 0.4 Header and Physical installation added RL 10-May-04 0.5 Alliance installation added RL 13-May-04 0.6 Title page Revision, First Draft Publication RL 14-May-04 1.0 Publication 70-GEN-1005 for MTA 4 JG 19-May-04 1.1 Section 1 and 3.2 revised, new gas added RL 6-Dec-04 1.2 Publication of a temporary version 70-GEN-1005 MTA 4.1 CP 31-Oct-06 1.3 Update & PUID changed to 70-PHW-1018 for 023-0014, 0071 RL 31-Mar-08 2.A Updated for 023-034X and MTA 5.2 RL 25-Aug-09 2.B Recovered file sent to Alain Richer RL 1-Sept-09 2.C Temporary version RL 2-Sept-09 2.0 Published for 1C03 023-034X and MTA 5.2 RL 11-Sept-09 2.D Revised temporary version RL 15-Sept-09 2.E Revised again RL 16-Sept-09 2.1 Published for ver 1C08 and 023-034X and MTA 5.2 RL 2-Oct-09 2.F Revised (Operating temp HFC HCFC) RL 21-Jan-10 2.2 Published again RL 2-Mar-10 2.3 Logo changed RL 8-Jul-11 2.3 Address changed RL 30-Nov-11 2.4 Cover page and formatting ER 11-FEB-2015 70-PHW-1018-R2.4 023-034X Refrigerant Leak Detector Manual.doc 9