ISC-PDL1-W18G-H. Installation Instructions Professional Series Dual Detector

Similar documents
DS9370-BEL. Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector

Commercial Series TriTech+ Motion Detector with Anti-mask

DS860 Surface or Corner Mount TriTech PIR/Microwave Detector

Commercial Series TriTech Motion Detector. Reference Guide

Microwave/PIR Intrusion Detector with POPIT Interface ZX970

DT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions

Extended Range DUAL TEC Motion Sensor

DT900 Series Sensors TECHNOLOGY FOR LARGE COMMERCIAL AND INDUSTRIAL APPLICATIONS. Impressive Performance, Impressive Coverage

English. Italiano. Português. Françias. Español

Description. Optex Incorporated

Professional Series TriTech+ Motion Detectors with Anti mask

DT8016AF4 / DT8016AF5 DUAL TEC Motion Sensor with Anti-Mask Installation Instructions

design line performance line Guardall DesignLine & PerformanceLine detector series 2015 Peace of mind

Blue Line Gen2 TriTech Motion Detectors

Photobeam 5000 ISC-FPB1-W60QS, ISC-FPB1-W120QS, ISC-FPB1-W200QS. en Installation and Operation Guide

Blue Line Gen2 TriTech Motion Detectors

LC-151 Dual-Tech Motion Sensor (Single PIR & Microwave) with adjustable Pet Immunity INSTALLATION INSTRUCTIONS & USER MANUAL P/N: ver.

STANDARD FEATURES SPECIFICATIONS

Quick Selection Guide Intrusion Detectors

DS7465i. Installation Instructions. Input/Output Module

DS7400Xi Addressable Control/ Communicator

Advanced DIGITAL Wired PIR Motion Detector

M O T I O N DETECTORS. The Paradox series of motion detectors. combines advanced features and patented. technologies to provide a high level of

INTERNAL DETECTORS. Wired and two-way wireless grade 2 and 3 internal detectors

D7053. Installation Instructions Multiplex Input/Output Module

DS160/161 Request To Exit PIR sensors Installation Instructions

alarm shop Outdoor PIR + MW Detector with Double Dual Mirror Optics INSTALLATION INSTRUCTIONS & USER MANUAL ELECTRONIC ENGINEERING LTD.

1126 Series Ceiling Mount PIR Motion Detector

D7052. Installation Instructions Multiplex Dual Input Module

Occupancy Sensor LS Descriptions. Product Profile. Technical Specifications

D7044. Installation Instructions Multiplex Single Input Module

Integrated Security Solutions. B and G Series Control Panels

High Mount. Low Mount. High security wired tri-technology external detectors with anti-masking

DD205RF/TX Detector Installation Sheet

ISC PPR1 WA16x Professional Series PIR Detectors with Anti mask

Notification Appliance Circuit Module

D-TECT Dual Tech. GJD360 Triple Technology External Detector

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Photobeam 5000 ISC-FPB1-W60QF, ISC-FPB1-W120QF, ISC-FPB1-W200QF. en Installation and Operation Guide

Model 17A00 Expansion Enclosure

Commercial Series TriTech+ Motion Detectors with Anti-mask

Duct smoke housing, 2-wire D340/D340P

D8125MUX. Operation and Installation Guide. Multiplex Bus Interface

DS160/DS161 Request To Exit PIR sensors Installation Instructions

Multiplex Eight Input Remote Modules

D-TECT Introduction. Connecting the Unit. Quick Installation. Multi Beam Alignment & Masking. Mounting the Unit

TriTech Ceiling Mount PIR/Microwave Detector DS9360. en Installation Guide

General Description. Industrial LuNAR DT AM Grade 3 Features

D250A/D253/D261AW/D280A/D290 Series

D-Tect 2 GJD300 Quad PIR Movement Detector

DS3MX-E-I. Installation Guide. 3 Zone Mini Control Panel

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

Immunity. P/N: ver.b

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

D1255RB/D1256RB/D1257RB

Addressable NAC Output Module D327A

Intrusion Outdoor Protection Perimeter

NetworX NX-548E Receiver Installation Instructions

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors

Occupancy Sensor LS Descriptions. Product Profile. Technical Specifications

FMR Installation Instructions. Addressable Fire System Controller

MO144. Operators Guide. Universal Timer Module

Installation Instructions

WIRELESS OUTDOOR DUAL TECHNOLOGY MOTION DETECTOR AOD-200

HX-40/40AM/ 40DAM. High Mount Outdoor Detector

Designed for integration. B Series and G Series Control Panels

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

1125 PIR Motion Detector

F220-B6PS/M. Installation Guide. Addressable Detector Bases

Motion Detectors Made by Bosch Quality You Can Trust. Rely on Bosch for superior intrusion detection for your commercial and residential applications.

TABLE OF CONTENTS TABLE OF CONTENTS 1

DI601AM Outdoor PIR/AM Detector Installation Sheet

RCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Guide

RADION. Transmitter. en Reference Guide

XHS1-TY / MP-841 ZigBee Home Automation 1.2 Wireless Digital Pet Immune PIR Detector

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

D-TECT 3 IP. GJD260 IP Motion Detector

Professional Series LSN TriTech+ Motion Detectors with Anti mask

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

MANUAL RESET ALARM RELEASE

RILEVATORI DI MOVIMENTO DA INTERNO serie unum

Independent Zone Control (I.Z.C.)

Flash 3 times per 3 seconds: Under voltage indication, please

Open-area Smoke Imaging Detection (OSID)

Sentrol. ShatterPoint Glassbreak Sensor. Installation Instructions DESCRIPTION. Models (3 Volt) (6 Volt) STEP 1 MOUNTING

HX-80NRAM. High Mount Outdoor Detector

5800-OD Wireless Outdoor Motion Sensor Installation Instructions

2 x CR123A Lithium batteries. White night-light LED. Blue alarm LED - also glows behind the lens. Ambient light sensor behind lens.

Elite. GJD022 /GJD023 35m External PIR. Multi Beam Lens Data

Flair 500 Series Annunciators

Wireless Sensors. Security unplugged. Interlogix wireless sensors deliver reliable detection and flexible installation for multiple applications.

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

Motion Detectors. Whatever the application, there s a Paradox motion detector that will suit your needs and surpass your expectations.

SECURITY PRODUCTS CATALOGUE

SOFTWARE VERSION 2.20 CONTROL PANEL RESET:

INSTALLATION MANUAL PC15OO

Transcription:

ISC-PDL1-W18G-H EN Installation Instructions Professional Series Dual Detector

1.0 General Information 1.1 Unlock and remove the cover The ISC-PDL1-W18x Professional Series TriTech Detectors are exceptionally suited for commercial indoor applications. Sensor data fusion technology ensures that the detectors send alarm conditions based on precise information. Tri-focus optics eliminate coverage gaps and respond efficiently to intruders. The powerful combination of unique features in the Professional Series delivers superior catch performance and virtually eliminates false alarms. The self-locking two-piece enclosure, built-in bubble level, flexible mounting height, and three optional mounting brackets simplify installation and reduce service time. 2.0 Installation Procedure Do Not: Mount outdoors Point toward windows Install facing direct sunlight Point towards fireplaces or air conditioners Install near moving objects such as ceiling fans The ISC-PDL1 is immune to small animals weighing less than 10 lb. (4.5 kg). The small animal immunity feature was not investigated by UL. Mount the detector so that it is between 7 ft and 10 ft from the floor (2.1 m - 3 m). The cover lock snaps back to the locked position when the cover is removed. The cover must be reattached with the lock in the locked position. 2.2 Mounting Level The detector has a built-in level which can be moved to measure on two axes. Mount the detector so that a person walks across the detection pattern. Typical mounting locations 2 2009 Bosch Security Systems, Inc.

2.3 Mounting the detector Use the hardware provided. The plastic mounting anchors require a 3/16 (5 mm) hole. Surface mounting 2.5 Wiring the terminal blocks The detector has two terminal blocks. One block is used for primary wiring; the other has two spare terminals. The two spare terminals are normally used as tie points for the EOL resistor. 1 Tamper Screw Corner Mounting 2.4 Wiring the detector Wire sizes between 16 AWG and 26 AWG (0.2 mm 2 and 1 mm 2 ) are permitted. Install the wiring using the approprate knock-outs and tie-downs. Do not attempt to remove the terminal blocks from the cover. This could result in permanent damage to the detector. 2009 Bosch Security Systems, Inc. 3

3.0 Switch Settings 3.3 Switch 3 - Short Range/ Long Range 3.1 Switch 1 - Walk Test Switch 3 Range Distance Switch 1 Voltage on WT Terminal Walk Test ON 0 ON ON +12 OFF OFF 0 OFF OFF +12 ON ON Short 25 ft (8 m) OFF Long 60 ft (18 m) 3.4 Switch 4 - Antimask ON/ Antimask OFF The Remote Self Test automatically occurs when the walk test changes from a disabled to enabled by a change in the voltage on the WT terminals. A passing Remote Self Test responds with an alarm signal. The Remote Self Test must be connected to 0 or +12 VDC on UL listed Control Panels. 3.2 Switch 2 - Alarm Memory Polarity Switch 4 ON OFF Antimask ON OFF When Antimask is ON, items placed witihin 1 ft (30 cm) of the detector are detected. The detector closes the Trouble contact (terminals marked TR ) 30 sec after the detector is blocked. 4.0 LED Indicators Switch 2 Voltage on S/U Terminal Alarm Memory ON +12 ON (Locked) ON 0 OFF (Unlocked) OFF 0 ON (Locked) OFF +12 OFF (Unlocked) The Alarm Memory must be connected to 0 or +12 VDC on UL listed control panels. Color Indication Function Blue Steady ON New alarm detected Yellow Steady ON Microwave detection Red Steady ON PIR Detection Blue Blue Flashing Flashing 1/4 sec ON, 1/4 sec OFF Detector warming up. (Up to 2 minutes) Alarm Memory Blue 3 Flashes Antimask Detected Blue 4 Flashes Self Test/ Self Test failure Blue 5 Flashes Low Input Power 4 2009 Bosch Security Systems, Inc.

5.0 Setup 5.1 Walk Test If Switch 1 is ON and no connections are made to the WT terminal, the local Walk Test is always on. For switch settings refer to Section 3.1 Switch 1 - Walk Test on page 4. To perform the Walk Test, walk across the detection pattern. 5.4 Short Range/Long Range For switch settings refer to Section 3.3 Switch 3 - Short Range/Long Range on page 4. If Switch 3 is in the ON position the coverage pattern is 25 ft x 32 ft (8 m x 10 m). If Switch 3 is in the OFF position the coverage pattern is 60 ft x 80 ft (18 m x 24 m). If necessary, adjust the microwave range a minimal amount until the required coverage is met. 5.2 Alarm Memory If Switch 2 is ON and no connections are made to the S/U terminal, the Alarm Memory is OFF. For switch settings refer to Section 3.2 Switch 2 - Alarm Memory Polarity on page 4. Alarm memory flashes the alarm LED to indicate stored alarms for use in multiple unit applications. A switched voltage from the control panel controls the alarm memory. The Alarm Memory function is used when more than one detector is connected to an alarm loop. The Alarm Memory identifies the units experiencing an alarm in the last armed period. The detector stores the alarm event in memory during the armed period. It shows the stored alarm when the system is disarmed. The LED flashes to indicate the stored alarm. Alarm Memory clears when the system is rearmed. 5.3 Trouble Memory Pulsing the WT Terminals recalls the last trouble condition from the memory. Refer to Section 4.0 LED Indicators on page 4 for the trouble conditions. When the memory is recalled, it clears automatically after 12 hours. 2009 Bosch Security Systems, Inc. 5

5.5 Antimask ON/Antimask OFF For switch settings refer to Section 4.4 Switch 4 - Antimask On/Antimask OFF. When antimask is ON, items placed within 1 ft (30 cm) of the detector are detected. The detector closes the Trouble contact (terminals marked TR ) 30 sec after the detector is blocked. 5.6 Clearing Antimask Trouble If the Walk Test input is not wired and the Walk Test LED is disabled, the process for clearing Antimask Trouble conditions on Version 3.x of the ISC-PPR1-WA16G/H and ISC- PDL1-WA18G/H Motion Detectors is as follows: Cycle power to the motion detectors from the control panel, or Cycle power at the detector by removing and reattaching the front cover. Version 4.0 and later detectors provide two options for antimask functioning: automatic antimask reset and latched antimask. Refer to Sections 5.6.1 and 5.6.2, below. Version 4.0 and later detectors are identified with a label on the inside of the detector, and the label on the detector s box. To determine if a detector includes these options without examining the label, count the LED flashes at power up. If the LED sequence starts with four or more fast flashes (followed by a pause and then up to 30 slower flashes), the detector includes both options. 5.6.1 Automatic Antimask Reset If the Walk Test Input is not wired, you can clear an Anti- Mask Trouble condition by simply walking in front of the detector after a 10-sec period with no activity. You can also clear the trouble condition using the methods described in Section 5.6 above. 5.6.2 Latched Antimask If the Walk Test Input is wired to the control panel and Walk Test Mode is disabled, the detector latches if there is an Antimask trouble condition. To clear the Antimask trouble condition: 1. From the control panel, place the detector in Walk Test Mode. 2. Remove the object that is masking the detector. 3. Perform the Walk Test after a 10-sec period with no activity. The Antimask condition clears. 4. To ensure that the Antimask condition clears automatically when an alarm occurs, leave the detector in Walk Test Mode. To ensure that the next Antimask event latchs, disable Walk Test Mode from the control panel. 6.0 Specifications Electrical Power Requirements Voltage (Operating): 9 VDC to 15 VDC Current (Maximum): 23 ma. Current (Standby): 13 ma Outputs Relay: Solid state relay, normally-closed (NC) contacts power supervised. 3 W, 125 ma, 25 VDC, resistance < 10 Ω. Tamper: Normally-closed (NC) contacts (with cover on) rated at 25 VDC, 125 ma maximum. Connect tamper circuit to 24-hour protection circuit. Trouble: Solid state relay normally-closed (NC) contacts. Mechanical Enclosure Design Color: White Dimensions: 5.25 in. x 2.75 in. x 2.25 in. (136 mm x 69 mm x 58 mm) Material: High-impact ABS plastic Indicators Alarm Indicators: Blue LED for TriTech+ alarms Yellow LED for microwave alarms Red LED for PIR alarms Detection Zones Zones: 86 Frequency Information Radio Frequency Interference (RFI) immunity: No alarm or setup on critical frequencies in the range from 26 MHz to 1 GHz at 50 V/m. Environmental Relative Humidity: 0 to 95%, non-condensing Temperature (Operating and Storage): -20 F to +130 F (-29 C to +55 C) For UL Certificated installations, +32 F to +120 F (0 C to +49 C) Environmental Class II EN 50130-5 Protection Rating: IP41, IK04 (EN 60529, EN 50102) 2009 Bosch Security Systems, Inc. 3/09 130 Perinton Parkway, Fairport, NY 14450-9199 USA Page 6 of 6 (800) 289-0096