SUBMITTAL M4MCW1509A-SUB-1C. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

Similar documents
SUBMITTAL M4MCW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

SUBMITTAL M4MHW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MHW1509A1N0A M4THS1509A11NA TAG:

SUBMITTAL M4MLW1809A-SUB-1A. Specifications 18 SERIES. Single Zone Mini-Split Inverter System M4MLW1809A1N0A M4TLS1809A11NA TAG:

READ ONLY. American Standard Ductless Systems Product Catalog. A Comfortable, Convenient Solution Built To A Higher Standard.

TECHNICAL GUIDE MODELS: DCPM/DHPM PREMIUM SERIES DUCTLESS SINGLE-SPLIT AIR CONDITIONERS AND HEAT PUMPS 22 SEER 1 PHASE 3/4 THRU 3 NOMINAL TONS

Product Data Split System (R-410A) Air Handler for Multi Split Inverter System 9,000 to 24,000 BTU/Hr

Submittal Sheet AIR-CON MULTI-SPLIT II. High-Wall Cassette Duct Floor and Ceiling AMTCM4H4R18

Submittal. Split System Cooling 4A7A6024J-SUB-1B-EN. January A7A6024J1000B TAG:

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To

Commercial High-Efficiency Condensing Units

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To

Specifications. (Model) KSIB009-H /2500 (W) 10600/9000(Btu/h) 13000/9500(Btu/h) 1250/ / SEER 16 HSPF 9.

TECHNICAL GUIDE MODELS: DCMF/DHMF LX SERIES DUCTLESS SINGLE-SPLIT AIR CONDITIONERS AND HEAT PUMPS 16 SEER 1 PHASE 3/4 THRU 2 NOMINAL TONS DESCRIPTION

Thank you for selecting LENNOX air conditioners.

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Submittal. 5 Ton Convertible Air Handler TEM3A0C60S51SA TEM3A0C60-SUB-1C-EN. July 2014 TAG:

Commercial High-Efficiency Condensing Units

Submittal. Split System Cooling 5.0 Ton 4A7A3060D1000P TAG:

15A Operating Range Communication Wire Size 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Submittal Data: UMAT48HP230V1AF. Job Name Location Date. Submitted To

TECHNICAL SPECIFICATIONS

PACKAGE AIR CONDITIONER

13 SEER CONDENSING UNITS & AIR HANDLERS

MAC-120HE-03 Air-Cooled Chiller

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Variable Speed Convertible Air Handler 5 Ton

Variable Speed Convertible Air Handler 2 1/2 Ton

Variable Speed Convertible Air Handler 4 Ton

Submittal. 1 1/2 Ton Convertible Air Handler TEM3A0B18S21SA TEM3A0B18-SUB-1C-EN. July 2014 TAG:

Submittal. 2 Ton Convertible Air Handler TEM3A0B24S21SA TEM3A0B24-SUB-1C-EN. July 2014 TAG:

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Innovative Ductless Mini Split Solution Submittal Data: GUHD24ND3FO/GKH24D3FI Job Name Location Date

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control...

Klimaire 16 SEER CENTRAL DUCTED YEAR. Central Air Conditioning & Heat Pump Systems Multi Position Air Handling Units LIMITED GUARANTEE

SUBMITTAL DATA - OUTDOOR UNIT VEP075N432G VRF HEAT PUMP

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

15A 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

PAJ3. Product Specifications

Condensing Units & Air Handlers

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MACH N-407 Heat Pump Air-Cooled Chiller

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

Samsung 360 Cassette, Single Zone, Split System

Submittal Data Sheet

18-2 AWG / 300V THHN Operating Range MCA 2.0A Cooling (Max) 118 F (48 C) MOCP/Breaker Size 15A (Min) 0 F (-18 C)

Product Data. Features/Benefits All in one package cooling efficiency, installation convenience and ease of accessibility allow for timesaving

Product Data. Split System Heat Pump B-EN. February A6H6024H1000A

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

Specifications, Performance & Submittal

Power Input (Max) 1,500 W Dehumidification 1.7 pt/hr HSPF 10.5 COP 4.2 Compressor Type DC Inverter Driven 2-Stage Rotary Heating at 17 F FLA 8.

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

MHH. 13 SEER High Efficiency R410a. SPECIFICATION sheet

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Product Data. Split System Heat Pump D-EN. February 2016

RSG16**S1M. Split System Air Conditioner 16 SEER

Model: Ceiling Cassette V 9k-24k

Ruud Achiever Series Dedicated Horizontal Package Heat Pump

Ruud Achiever Series Dedicated Horizontal Package Heat Pump

Single - Zone Systems

MAC N-407 Air-Cooled Chiller

Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz Technical Manual

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Submittal. Date: January 8, Customer P.O. Number: Customer Project Number: CARROLLTON, TX 75006

Specifications and Performance S2H

Advance Product Data

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

16 SEER TWO-STAGE AIR CONDITIONERS

PAR5. Product Specifications

1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series

Advance Product Data

Technical Product Guide

Product Data. Split System Heat Pump A-EN. March 2016

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

Product Data INDUSTRY LEADING FEATURES / BENEFITS

PERFORMANCE SERIES Single Zone & Multi-Zone Ductless Systems

Product Data. Fig. 1 - Unit 50VR -A

Unit Data - RCA 051 RATED IN ACCORDANCE TO AHRI STANDARD

WJH4 Product Specifications

Lennox 8 Series Single Zone - R-410A

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

Service Manual. Models WAH48115MB WAH412230MB WH48YMB WH412ZMB

R4H4. Product Specifications

Advance Release September 2009

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

Unit Features & Benefits RQPM/RQRM Series

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

Product Data. FF1DNA, FF1DNE Fan Coil Units. Sizes 018 thru 030 FEATURES/BENEFITS

Product Data. Split System Cooling D-EN. August 2016

T P A 120 S 4 S N 1 Y

Product Data. 50ZP (60Hz) Single-Package. Air Conditioners 3-5 Nominal Tons

Transcription:

M4MCW1509A-SUB-1C TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA MODEL - Cooling Only RATED Volts/PH Frequency (Hz) Rated Cooling Capacity (Btu/h): Minimum Cooling Capacity (@95F) (Btu/h): Maximum Cooling Capacity (@95F) (Btu/h): Total Capacity (W) (High/Standard/Low): Rated Power Input (W) Nominal Input Current (A) SEER Air Flow Volume (CFM) (SH/H/M/L) Dehumidifying Volume (pt./h) EER (Btu/W hr) Indoor Unit Fan Motor Speed (r/min) (SH/H/M/L) Fan Motor RLA(A) Evaporator Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (D) x coil width (W) (inch) Output of Swing Motor (W) Fuse (A) Sound Power Level db (A)(SH/H/M/L) Sound PRESSURE Level db (A)(SH/H/M/L) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Outdoor Unit Compressor Type Compressor Oil L.R.A. (A) Compressor RLA(A) Compressor Power Input(W) Throttling Method Working Temp Range ( F) Condenser Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (H) x coil width (W) (inch) Fan Motor Speed (rpm) Output of Fan Motor (W) Fan Motor RLA (A) Air Flow Volume of Outdoor Unit (CFM) Fan Diameter (inch) Defrosting Method Sound Power Level db (A) Sound PRESSURE Level db (A) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Refrigerant Charge (oz) MCA MOP Connection Pipe Gas additional charge(oz/ft) Outer Diameter Liquid Pipe (inch) Outer Diameter Gas Pipe (inch) Max Height Distance (ft) Max Length Distance (ft) M4MCW1509A / M4TCS1509A 208 / 230 / 1 60Hz 9000 3100 9600 2800 / 2600 / 900 900 4.0 15.0 310 / 280 / 240 / 170 1.69 10.0 M4MCW1509A1N0A 1350 / 1200 / 1050 / 750 0.20 Aluminum Fin-Copper Tube 1/5 2-1/18 23 7/8 10 1/2 1.5 3.15 53 / 49 / 45 / 39 43 / 38 / 34 / 28 31 1/9 x 10 5/6 x 7 7/8 34 x 10 2/3 x 14 4/9 19.8 / 24.2 M4TCS1509A11NA Swing Rotary DAPHNE FVC50K (PVE Oil) 16.5 6.60 845 Capillary 0-115 Aluminum Fin-Copper Tube 2/7 1-1/18 28 3/4 20 820±20 30 0.37 942 15 3/4 Automatic Defrosting 62 52 30 5/9 x 21 1/4 x 12 3/5 33 1/2 x 14 2/7 x 23 3/7 66.2 / 71.7 24.7 9.0 15.0 0.2 1/4 3/8 65 100 2018 Ingersoll Rand All Rights Reserved 1 Sound PRESSURE Level @ 3.3 ft. db(a)

Unit Dimensions W D H 6 5/8 18 3/16 6 5/16 9K 09K Φ2 3/16 Φ2 3/16 2 1/8 2 1/8 6 3 1/2 Unit: inch MODEL W H D 09K 31 1/8 10 5/6 7 7/8 12K 33 1/4 11 3/8 8 1/4 10 1/8 28 21 1/4 12 3/5 30 9/16 11 1/4 20

Clearance Requirements Space to the ceiling 6 in. 6 in. 6 in. 118 in. Air outlet side 66 in. Space to the floor The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent structures Space to the obstruction 12 in. Space to the wal l 9 7 n. i 20 in. Air inlet side 12 in. 20 in. Air outlet side valve cover NOTE: The maximum recommended height from the floor to the bottom of the indoor unit is 11.5 ft. (3.5 m). Air Velocity Patterns for High Wall Max Horizontal Distance Unit: ft. (m) Model Cooling Mode Heating Mode M4MCW1509A 13.1 (4) N/A

Performance Data Cooling Capacity 9,000 (Bthu/h) M4MCW1509A1/M4TCS1509A Indoor Entering Air Temperature (Dry Bulb/Wet Bulb) Outdoor Ambient Air Temperature ( F) 68/57 F 73/61 F 80/67 F 82/68 F TC* SHC** TC SHC TC SHC TC SHC 0 1300 1100 1400 1100 1600 1300 1700 1300 10 1600 1300 1700 1300 1900 1500 2000 1600 20 1800 1400 1900 1500 2200 1800 2300 1800 30 1900 1500 2000 1600 2300 1800 2400 1900 40 2000 1600 2100 1700 2400 1900 2400 2000 50 2100 1600 2200 1700 2500 2000 2600 2000 60 2300 1800 2400 2000 2600 2100 2900 2300 70 2500 2100 2700 2200 2900 2400 3100 2500 80 2500 2000 2600 2200 2800 2300 3000 2500 90 2300 1900 2500 2100 2700 2300 2900 2400 100 2200 1800 2300 2000 2600 2200 2800 2400 110 2100 1800 2200 1900 2500 2100 2700 2300 120 1900 1700 2100 1800 2400 2000 2600 2200 *Total Capacity **Sensible Heat Capacity Capacities in these performance tables reflect normal operation at the temperatures indicated. See specification tables above for certified values under prescribed test conditions.

Mechanical Specifications Mini-Split Outdoor Unit General This unit is fully charged from the factory for up to 25 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115 F. Cooling capacities with the mini-split air handler shown in the catalog are AHRI certified. The unit is ETL listed for outdoor application. Unit Casing The unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Refrigerant Controls Refrigeration system controls include condenser fan and compressor relay. High and low pressure controls are inherent to the compressor. A suction line multi function service valve is standard Compressor The compressor features internal over temperature and pressure protection; total dipped hermetic motor windings. Other features include: centrifugal oil pump and low vibration and noise. Condenser Coil The coil shall consist of aluminum finned coils brazed to copper tubing. The coil provides air flow resistance and efficient heat transfer. The coil is protected by the casing. Low Ambient Cooling Matched Ameristar ductless products, have cooling capabilities at outdoor ambient temperatures as low as 0 F. Mini-Split Indoor High Wall General The High Wall mounted type air handler shall be completely factory assembled including coil, condensate drain pan, fan motor, washable filter, air purifying filter and electric controls to be used with a wireless remote controller. Unit shall be shipped with a unit mounting plate. Unit shall be matched with an Ameristar outdoor unit, rated and tested in accordance with AHRI standard. Unit shall be ETL listed. Unit Casing Casing shall be provided with knockouts on the right, and left of the unit to facilitate piping and electrical connection on either side of the unit. An electrical service cover shall be provided to permit easy access to the electrical terminal strip. Discharge Airflow and Distribution System Unit shall have auto swing, dual horizontal blades to optimize the aperture outlet for vertical airflow and air distribution. Blade shall close automatically when the air conditioner is turned off to minimize dust entering the unit. Five-Step preset program on the remote controller shall be available to control the blade angle. Manually adjusted wide-angle louvers shall be provided to adjust the coverage and direction of airflow. Controls Units shall have the capability to be controlled remotely through wall-mounted wired options (sold separately) as well as a wireless remote option. Remote Controller The unit shall have a wireless infrared remote controller with easy reading digital display panel to start, stop and regulate the air conditioner from a distance. The wireless controller is included with all units. Healthy Filters The unit shall have an active carbon and catechin filter with the unit.the filters need to be cleaned at least once a year. 01/18 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

M4MCW1512A-SUB-1C TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MCW1512A1N0A M4TCS1512A11NA MODEL - Cooling Only RATED Volts/PH Frequency (Hz) Rated Cooling Capacity (Btu/h): Minimum Cooling Capacity (@95F) (Btu/h): Maximum Cooling Capacity (@95F) (Btu/h): Total Capacity (W) (High/Standard/Low): Rated Power Input (W) Nominal Input Current (A) SEER Air Flow Volume (CFM) (SH/H/M/L) Dehumidifying Volume (pt./h) EER (Btu/W hr) Indoor Unit Fan Motor Speed (r/min) (SH/H/M/L) Fan Motor RLA(A) Evaporator Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (D) x coil width (W) (inch) Output of Swing Motor (W) Fuse (A) Sound Power Level db (A)(SH/H/M/L) Sound PRESSURE Level db (A)(SH/H/M/L) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Outdoor Unit Compressor Type Compressor Oil L.R.A. (A) Compressor RLA(A) Compressor Power Input(W) Throttling Method Working Temp Range ( F) Condenser Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (H) x coil width (W) (inch) Fan Motor Speed (rpm) Output of Fan Motor (W) Fan Motor RLA (A) Air Flow Volume of Outdoor Unit (CFM) Fan Diameter (inch) Defrosting Method Sound Power Level db (A) Sound PRESSURE Level db (A) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Refrigerant Charge (oz) MCA MOP Connection Pipe Gas additional charge(oz/ft) Outer Diameter Liquid Pipe (inch) Outer Diameter Gas Pipe (inch) Max Height Distance (ft) Max Length Distance (ft) M4MCW1512A / M4TCS1512A 208 / 230 / 1 60Hz 12000 3700 12500 3600 / 3500 / 1100 1300 5.8 15.0 390 / 310 / 240 / 190 2.96 9.25 M4MCW1512A1N0A 1350 / 1200 / 1000 / 800 0.31 Aluminum Fin-Copper Tube 1/5 2-1/18 25 7/8 12 1/16 1.5 3.15 55 / 49 / 45 / 39 45 / 39 / 35 / 29 33 1/4 x 11 3/8 x 8 2/9 36 1/4 x 11 x 15 23.1 / 28.7 M4TCS1512A11NA Swing Rotary DAPHNE FVC50K (PVE Oil) 16.5 6.60 845 Capillary 0-115 Aluminum Fin-Copper Tube 2/7 2-1/18 28 1 1/2 20 820±20 30 0.37 942 15 3/4 Automatic Defrosting 63 53 30 5/9 x 21 1/4 x 12 3/5 33 1/2 x 14 2/7 x 23 3/7 70.6 / 76.1 30.0 9.0 15.0 0.2 1/4 3/8 65 100 2018 Ingersoll Rand All Rights Reserved 1 Sound PRESSURE Level @ 3.3 ft. db(a)

Unit Dimensions W D H 4 11/16 21 5/16 7 1/4 12K 12K Φ2 3/16 Φ2 3/16 1 3/8 1 3/8 5 3 5/16 Unit: inch MODEL W H D 09K 31 1/8 10 5/6 7 7/8 12K 33 1/4 11 3/8 8 1/4 10 1/8 28 21 1/4 12 3/5 30 9/16 11 1/4 20

Clearance Requirements Space to the ceiling 6 in. 6 in. 6 in. 118 in. Air outlet side 66 in. Space to the floor The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent structures Space to the obstruction 12 in. Space to the wal l 9 7 n. i 20 in. Air inlet side 12 in. 20 in. Air outlet side valve cover NOTE: The maximum recommended height from the floor to the bottom of the indoor unit is 11.5 ft. (3.5 m). Air Velocity Patterns for High Wall Max Horizontal Distance Unit: ft. (m) Model Cooling Mode Heating Mode M4MCW1512A 29.5 (9) N/A

Performance Data Cooling Capacity 12,000 (Bthu/h) M4MCW1512A1/M4TCS1512A Indoor Entering Air Temperature (Dry Bulb/Wet Bulb) Outdoor Ambient Air Temperature ( F) 68/57 F 73/61 F 80/67 F 82/68 F TC* SHC** TC SHC TC SHC TC SHC 0 5100 4000 5400 4200 6700 5200 6600 5100 10 7000 5500 7400 5800 8500 6700 8800 6900 20 7800 6100 8300 6500 9400 7400 9800 7700 30 8300 6500 8900 6900 10100 8000 10600 8300 40 10000 7900 10700 8400 11800 9200 12800 10000 50 11600 9100 12300 9600 13100 10300 14100 11100 60 11400 8900 12100 9500 13000 10200 13900 10900 70 11100 8700 11800 9300 12800 10100 13700 10700 80 10800 8500 11500 9000 12600 9900 13500 10600 90 10500 8200 11200 8800 12300 9600 13300 10400 100 10000 7900 10700 8400 11900 9300 12900 10100 110 9500 7400 10200 8000 11400 8900 12300 9700 120 8900 7000 9600 7500 10900 8500 11800 9200 *Total Capacity **Sensible Heat Capacity Capacities in these performance tables reflect normal operation at the temperatures indicated. See specification tables above for certified values under prescribed test conditions.

Mechanical Specifications Mini-Split Outdoor Unit General This unit is fully charged from the factory for up to 25 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115 F. Cooling capacities with the mini-split air handler shown in the catalog are AHRI certified. The unit is ETL listed for outdoor application. Unit Casing The unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Refrigerant Controls Refrigeration system controls include condenser fan and compressor relay. High and low pressure controls are inherent to the compressor. A suction line multi function service valve is standard Compressor The compressor features internal over temperature and pressure protection; total dipped hermetic motor windings. Other features include: centrifugal oil pump and low vibration and noise. Condenser Coil The coil shall consist of aluminum finned coils brazed to copper tubing. The coil provides air flow resistance and efficient heat transfer. The coil is protected by the casing. Low Ambient Cooling Matched Ameristar ductless products, have cooling capabilities at outdoor ambient temperatures as low as 0 F. Mini-Split Indoor High Wall General The High Wall mounted type air handler shall be completely factory assembled including coil, condensate drain pan, fan motor, washable filter, air purifying filter and electric controls to be used with a wireless remote controller. Unit shall be shipped with a unit mounting plate. Unit shall be matched with an Ameristar outdoor unit, rated and tested in accordance with AHRI standard. Unit shall be ETL listed. Unit Casing Casing shall be provided with knockouts on the right, and left of the unit to facilitate piping and electrical connection on either side of the unit. An electrical service cover shall be provided to permit easy access to the electrical terminal strip. Discharge Airflow and Distribution System Unit shall have auto swing, dual horizontal blades to optimize the aperture outlet for vertical airflow and air distribution. Blade shall close automatically when the air conditioner is turned off to minimize dust entering the unit. Five-Step preset program on the remote controller shall be available to control the blade angle. Manually adjusted wide-angle louvers shall be provided to adjust the coverage and direction of airflow. Controls Units shall have the capability to be controlled remotely through wall-mounted wired options (sold separately) as well as a wireless remote option. Remote Controller The unit shall have a wireless infrared remote controller with easy reading digital display panel to start, stop and regulate the air conditioner from a distance. The wireless controller is included with all units. Healthy Filters The unit shall have an active carbon and catechin filter with the unit.the filters need to be cleaned at least once a year. 01/18 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

M4MCW1518A-SUB-1C TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MCW1518A1N0A M4TCS1518A11NA MODEL - Cooling Only RATED Volts/PH Frequency (Hz) Rated Cooling Capacity (Btu/h): Minimum Cooling Capacity (@95F) (Btu/h): Maximum Cooling Capacity (@95F) (Btu/h): Total Capacity (W) (High/Standard/Low): Rated Power Input (W) Nominal Input Current (A) SEER Air Flow Volume (CFM) (SH/H/M/L) Dehumidifying Volume (pt./h) EER (Btu/W hr) Indoor Unit Fan Motor Speed (r/min) (SH/H/M/L) Fan Motor RLA(A) Evaporator Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (D) x coil width (W) (inch) Output of Swing Motor (W) Fuse (A) Sound Power Level db (A)(SH/H/M/L) Sound PRESSURE Level db (A)(SH/H/M/L) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Outdoor Unit Compressor Type Compressor Oil L.R.A. (A) Compressor RLA(A) Compressor Power Input(W) Throttling Method Working Temp Range ( F) Condenser Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (H) x coil width (W) (inch) Fan Motor Speed (rpm) Output of Fan Motor (W) Fan Motor RLA (A) Air Flow Volume of Outdoor Unit (CFM) Fan Diameter (inch) Defrosting Method Sound Power Level db (A) Sound PRESSURE Level db (A) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Refrigerant Charge (oz) MCA MOP Connection Pipe Gas additional charge(oz/ft) Outer Diameter Liquid Pipe (inch) Outer Diameter Gas Pipe (inch) Max Height Distance (ft) Max Length Distance (ft) M4MCW1518A / M4TCS1518A 208 / 230 / 1 60Hz 18000 7100 20000 5800 / 5200 / 2100 1800 8.0 15.0 470 / 400 / 340 / 280 3.8 9.0 M4MCW1518A1N0A 1350 / 1200 / 1050 / 900 0.30 Aluminum Fin-Copper Tube 2/7 2-1/18 28 1/7 1 12 2.5 3.15 56 / 52 / 49 / 45 46 / 42 / 39 / 35 38 1/5 x 11 4/5 x 8 5/6 41 x 15 x 12 3/5 29.8 / 36.4 M4TCS1518A11NA Rotary RB68EP (POE Oil) 16.5 12.08 1440 Capillary 0-115 Aluminum Fin-Copper Tube 2/7 1-1/18 34 5/7 6/7 26 800 60 0.52 1883 20 1/2 Automatic Defrosting 66 56 37 3/5 x 27 5/9 x 15 3/5 40 1/2 x 18 x 29 1/2 90.4 / 100.3 35.3 16.0 25.0 0.2 1/4 1/2 65 130 2018 Ingersoll Rand All Rights Reserved 1 Sound PRESSURE Level @ 3.3 ft. db(a)

Unit Dimensions W D H 18K 4 27 7 3/16 Φ2 3/16 Φ2 3/16 1 1/2 7 1/2 5 1/2 Unit: inch Models W H D 18K 38 1/4 11 13/16 8 7/8 24K 42 1/2 12 13/16 9 11/16 13 3/8 35 27 9/16 15 5/8 38 22 14 5/16 Unit: inch

Clearance Requirements Space to the ceiling 6 in. 6 in. 6 in. 118 in. Air outlet side 66 in. Space to the floor The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent structures Space to the obstruction 12 in. Space to the wal l 9 7 n. i 20 in. Air inlet side 12 in. 20 in. Air outlet side valve cover NOTE: The maximum recommended height from the floor to the bottom of the indoor unit is 11.5 ft. (3.5 m). Air Velocity Patterns for High Wall Max Horizontal Distance Unit: ft. (m) Model Cooling Mode Heating Mode 4MYW1618 30.2 (9.2) N/A

Performance Data Cooling Capacity 18,000 (Bthu/h) M4MCW1518A1/M4TCS1518A Indoor Entering Air Temperature (Dry Bulb/Wet Bulb) Outdoor Ambient Air Temperature ( F) 68/57 F 73/61 F 80/67 F 82/68 F TC* SHC** TC SHC TC SHC TC SHC 0 9500 7400 9900 7700 11200 8800 11900 9300 10 11200 8800 11900 9300 13400 10500 13800 10800 20 12700 10000 13600 10600 15500 12100 15900 12500 30 13500 10600 14400 11300 16500 13000 17000 13400 40 14100 11000 15000 11800 17200 13500 17700 13900 50 14600 11500 15700 12300 17900 14100 18500 14500 60 16100 12600 17200 13500 18800 14800 19400 15200 70 18000 14100 19100 15000 20400 16000 21000 16500 80 17500 13700 18600 14600 20100 15700 20700 16200 90 16500 12900 17300 13600 19300 15100 19900 15600 100 15600 12200 15900 12500 18000 14100 18500 14500 110 14700 11500 15200 11900 16600 13000 17100 13400 120 13800 10900 14600 11400 15200 11900 15600 12300 *Total Capacity **Sensible Heat Capacity Capacities in these performance tables reflect normal operation at the temperatures indicated. See specification tables above for certified values under prescribed test conditions.

Mini-Split Outdoor Unit Mechanical Specifications General This unit is fully charged from the factory for up to 25 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115 F. Cooling capacities with the mini-split air handler shown in the catalog are AHRI certified. The unit is ETL listed for outdoor application. Unit Casing The unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Refrigerant Controls Refrigeration system controls include condenser fan and compressor relay. High and low pressure controls are inherent to the compressor. A suction line multi function service valve is standard Compressor The compressor features internal over temperature and pressure protection; total dipped hermetic motor windings. Other features include: centrifugal oil pump and low vibration and noise. Condenser Coil The coil shall consist of aluminum finned coils brazed to copper tubing. The coil provides air flow resistance and efficient heat transfer. The coil is protected by the casing. Low Ambient Cooling Matched Ameristar ductless products, have cooling capabilities at outdoor ambient temperatures as low as 0 F. Mini-Split Indoor High Wall General The High Wall mounted type air handler shall be completely factory assembled including coil, condensate drain pan, fan motor, washable filter, air purifying filter and electric controls to be used with a wireless remote controller. Unit shall be shipped with a unit mounting plate. Unit shall be matched with an Ameristar outdoor unit, rated and tested in accordance with AHRI standard. Unit shall be ETL listed. Unit Casing Casing shall be provided with knockouts on the right, and left of the unit to facilitate piping and electrical connection on either side of the unit. An electrical service cover shall be provided to permit easy access to the electrical terminal strip. Discharge Airflow and Distribution System Unit shall have auto swing, dual horizontal blades to optimize the aperture outlet for vertical airflow and air distribution. Blade shall close automatically when the air conditioner is turned off to minimize dust entering the unit. Five-Step preset program on the remote controller shall be available to control the blade angle. Manually adjusted wide-angle louvers shall be provided to adjust the coverage and direction of airflow. Controls Units shall have the capability to be controlled remotely through wall-mounted wired options (sold separately) as well as a wireless remote option. Remote Controller The unit shall have a wireless infrared remote controller with easy reading digital display panel to start, stop and regulate the air conditioner from a distance. The wireless controller is available for all units. Healthy Filters The unit shall have an active carbon and catechin filter with the unit.the filters need to be cleaned at least once a year. 01/18 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

M4MCW1524A-SUB-1C TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MCW1524A1N0A M4TCS1524A11NA MODEL - Cooling Only RATED Volts/PH Frequency (Hz) Rated Cooling Capacity (Btu/h): Minimum Cooling Capacity (@95F) (Btu/h): Maximum Cooling Capacity (@95F) (Btu/h): Total Capacity (W) (High/Standard/Low): Rated Power Input (W) Nominal Input Current (A) SEER Air Flow Volume (CFM) (SH/H/M/L) Dehumidifying Volume (pt./h) EER (Btu/W hr) Indoor Unit Fan Motor Speed (r/min) (SH/H/M/L) Fan Motor RLA(A) Evaporator Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (D) x coil width (W) (inch) Output of Swing Motor (W) Fuse (A) Sound Power Level db (A)(SH/H/M/L) Sound PRESSURE Level db (A)(SH/H/M/L) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Outdoor Unit Compressor Type Compressor Oil L.R.A. (A) Compressor RLA(A) Compressor Power Input(W) Throttling Method Working Temp Range ( F) Condenser Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (H) x coil width (W) (inch) Fan Motor Speed (rpm) Output of Fan Motor (W) Fan Motor RLA (A) Air Flow Volume of Outdoor Unit (CFM) Fan Diameter (inch) Defrosting Method Sound Power Level db (A) Sound PRESSURE Level db (A) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Refrigerant Charge (oz) MCA MOP Connection Pipe Gas additional charge(oz/ft) Outer Diameter Liquid Pipe (inch) Outer Diameter Gas Pipe (inch) Max Height Distance (ft) Max Length Distance (ft) M4MCW1524A / M4TCS1524A 208 / 230 / 1 60Hz 22000 8600 23200 6600 / 6400 / 2500 2260 10.0 15.0 700 / 640 / 580 / 520 5.3 9.75 M4MCW1524A1N0 1250 / 1100 / 900 / 800 0.32 Aluminum Fin-Copper Tube 2/7 2-1/17 33 1/4 1 13 1/2 2.5 3.15 58 / 54 / 50 / 46 48 / 44 / 40 / 36 42 4/9 x 12 4/5 x 9 2/3 45 1/5 x 16 1/4 x 13 7/9 37.5 / 45.2 M4TCS1524A11N Rotary RB68EP (POE Oil) 25 11.29 1440 Capillary 0-115 Aluminum Fin-Copper Tube 3/8 2-1/18 33 1/3 1 3/4 26 800 60 0.4 1883 20 1/2 Automatic Defrosting 69 59 37 3/5 x 27 5/9 x 15 3/5 40 1/2 x 18 x 29 1/2 103.6 / 113.6 56.45 15.0 25.0 0.2 1/4 5/8 65 130 2018 Ingersoll Rand All Rights Reserved 1 Sound PRESSURE Level @ 3.3 ft. db(a)

Unit Dimensions W D H 8 1/8 27 7 5/16 24K Φ2 3/4 Φ2 3/4 1 11/16 6 3 1/8 Unit: inch Models W H D 18K 38 1/4 11 13/16 8 7/8 24K 42 1/2 12 13/16 9 11/16 13 3/8 35 27 9/16 15 5/8 38 22 14 5/16 Unit: inch

Clearance Requirements Space to the ceiling 6 in. 6 in. 6 in. 118 in. Air outlet side 66 in. Space to the floor The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent structures Space to the obstruction 12 in. Space to the wal l 9 7 n. i 20 in. Air inlet side 12 in. 20 in. Air outlet side valve cover NOTE: The maximum recommended height from the floor to the bottom of the indoor unit is 11.5 ft. (3.5 m). Air Velocity Patterns for High Wall Max Horizontal Distance Unit: ft. (m) Model Cooling Mode Heating Mode M4MCW1524 31.2 (9.5) N/A

Performance Data Cooling Capacity 24,000 (Bthu/h) M4MCW1524A1/M4TCS1524A Indoor Entering Air Temperature (Dry Bulb/Wet Bulb) Outdoor Ambient Air Temperature ( F) 68/57 F 73/61 F 80/67 F 82/68 F TC* SHC** TC SHC TC SHC TC SHC 0 10900 8500 11400 8900 12900 10100 13100 10300 10 13200 10400 14000 10900 15700 12300 16200 12700 20 15000 11700 15900 12500 18200 14300 18700 14700 30 15900 12400 17000 13300 19400 15200 20000 15700 40 16500 13000 17700 13900 20300 15900 20900 16400 50 17200 13500 18400 14400 21100 16500 21700 17000 60 19000 14900 20300 15900 22100 17400 22800 17900 70 21100 16600 22400 17600 24000 18800 24700 19400 80 20600 16100 21900 17200 23600 18500 24300 19100 90 19400 15200 20300 15900 22700 17800 23300 18300 100 18300 14400 18700 14700 21200 16600 21800 17100 110 17300 13600 17900 14000 19500 15300 20100 15700 120 16300 12800 17100 13400 17900 14000 18400 14400 *Total Capacity **Sensible Heat Capacity Capacities in these performance tables reflect normal operation at the temperatures indicated. See specification tables above for certified values under prescribed test conditions.

Mini-Split Outdoor Unit Mechanical Specifications General This unit is fully charged from the factory for up to 25 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115 F. Cooling capacities with the mini-split air handler shown in the catalog are AHRI certified. The unit is ETL listed for outdoor application. Unit Casing The unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Refrigerant Controls Refrigeration system controls include condenser fan and compressor relay. High and low pressure controls are inherent to the compressor. A suction line multi function service valve is standard Compressor The compressor features internal over temperature and pressure protection; total dipped hermetic motor windings. Other features include: centrifugal oil pump and low vibration and noise. Condenser Coil The coil shall consist of aluminum finned coils brazed to copper tubing. The coil provides air flow resistance and efficient heat transfer. The coil is protected by the casing. Low Ambient Cooling Matched Ameristar ductless products, have cooling capabilities at outdoor ambient temperatures as low as 0 F. Mini-Split Indoor High Wall General The High Wall mounted type air handler shall be completely factory assembled including coil, condensate drain pan, fan motor, washable filter, air purifying filter and electric controls to be used with a wireless remote controller. Unit shall be shipped with a unit mounting plate. Unit shall be matched with an Ameristar outdoor unit, rated and tested in accordance with AHRI standard. Unit shall be ETL listed. Unit Casing Casing shall be provided with knockouts on the right, and left of the unit to facilitate piping and electrical connection on either side of the unit. An electrical service cover shall be provided to permit easy access to the electrical terminal strip. Discharge Airflow and Distribution System Unit shall have auto swing, dual horizontal blades to optimize the aperture outlet for vertical airflow and air distribution. Blade shall close automatically when the air conditioner is turned off to minimize dust entering the unit. Five-Step preset program on the remote controller shall be available to control the blade angle. Manually adjusted wide-angle louvers shall be provided to adjust the coverage and direction of airflow. Controls Units shall have the capability to be controlled remotely through wall-mounted wired options (sold separately) as well as a wireless remote option. Remote Controller The unit shall have a wireless infrared remote controller with easy reading digital display panel to start, stop and regulate the air conditioner from a distance. The wireless controller is included with all units. Healthy Filters The unit shall have an active carbon and catechin filter with the unit.the filters need to be cleaned at least once a year. 01/18 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.