User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

Similar documents
CMF, CMX & CMA series

User Manual. PolyGard SPC Carbon monoxide (CO) gas detection and control system serial no. SPC April 01, 2004

Carbon Monoxide CO Transmitter ADT-X3-1110

User Manual. PolyGard AT-3300 V3. Transmitter for Combustible Gases. Serial No. ET April 2009

User Manual. PolyGard Single Point Controller SPC3-11XX. Single Point Gas Controller Serial Number _E_1007. May 2009

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Carbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output

User Manual. PolyGard Gas Controller MGC3. Two-Channel Analog Gas Controller Serial Number _E _0907. September 2007

RK Carbon Monoxide Transmitter Operator s Manual

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006

Oxygen (O2) Single-Point Gas Detection System

Two-Channel Gas Controller

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

RK Carbon Monoxide Transmitter Operator s Manual

CT-7 Series Toxic Gas Transmitter Operator s Manual

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

RK Carbon Monoxide Transmitter Operator s Manual

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

RK Transmitter Technical Notice

RK Combustible Gas Transmitter Operator s Manual

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

MODEL QTS-1800 SERIES WALL MOUNT DIGITAL AND ANALOG TRANSMITTER/SENSOR

User Manual. PolyGard Single Point Controller SPC Single Point Gas Controller for Combustible Gases Serial Number _E_1008.

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

EC24. Operation Manual. (Type MWG 2411, MWG 2412, MWG 2413 and MWG 2414)

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

RK-05 Combustible Gas Transmitter Operator s Manual

QAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases

CARBON MONOXIDE CO SS SOLID STATE ELECTROCHEMICAL SENSORS

RK-05 Carbon Monoxide Transmitter Operator s Manual

RK CO 2 Transmitter Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

Carbon Monoxide (CO) Gas Detector, 4-20mA GCO. Automatikprodukter. Oct. 15. Features. Technical Data. Design Features. Application.

1228s Multidrop INSTRUCTIONS. Installation and Operation of the AMC-1228s Electrochemical Sensor Module For Use With Multidrop AMC Monitors

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

RK-02 Multi Point Detector Operator s Manual

TOXIC GAS AND OXYGEN DETECTOR DTX 420 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS DTX420_MAN01_EN_V1R2

RK/ RK Carbon Monoxide Detector Operator s Manual

! "! # Please read these installation and operating instructions completely and carefully before starting.

RK/ RK Oxygen Detector Operator s Manual

GAS MONITOR Model Model

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

Duct and Rough Service Carbon Monoxide Sensor

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

RK-05 Carbon Monoxide Detector Operator s Manual

User Manual. PolyGard Single Point Controller SPC-43-20XX. Single Point Gas Controller for Refrigerant Gases Serial Number _E_.

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

Overview of Standards for CO Detection Products

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

RK/ RK Oxygen Detector Operator s Manual

QAS-101 SERIES SINGLE CHANNEL CONTROLLERS

Combustible Gas Detection and Control System

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

Warranty Registration

Combustible Gas Sample-Draw Detector Operator s Manual

Carbon Monoxide (CO) Gas Detector, 4-20mA or 2-10Vdc

Carbon Monoxide Sample-Draw Detector Operator s Manual

PolyGard Digital Gas Controller DGC-05 RS-485 Bus

RK Multi Point Detector Operator s Manual

Stand Alone DYNAGARD SP Operation Manual

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

RKA-03 Sample-Draw Detector Head

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

Models TX-KE and TX-KP Toxic Gas Transmitters

Sensepoint. Fit For Purpose Flammable, toxic and Oxygen versions available High performance, low cost Suitable for new and retro fit applications

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

Warranty Registration

Nitrogen Dioxide Stand-Alone Detector - Analog, ModBus

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

Sensepoint. Fit For Purpose Flammable, toxic and oxygen versions available High performance, low cost Suitable for new and retro fit applications

Warranty Registration

MACURCO INC. CONTROLLERS & CARBON MONOXIDE DETECTORS SS103-3A, SS103-10A SS102H, SS102HC-1 INSTALLATION & OPERATING INSTRUCTIONS

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

Combustible Gas/Carbon Monoxide Sample-Draw Detector Operator s Manual

Gas Detection Sensor type GDA, GDC, GDHC, GDHF, GDH REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Operation Manual. Rev. I SCC Self Contained Controller.

Operation Manual. Rev. D GEM-II Self-Contained Gas Detector.

Macurco Single-Gas XL Series Monitor, CM-1XL Carbon Monoxide (CO), HS-1XL Hydrogen Sulfide (H2S) User Instructions

RK-OXY Oxygen Sample-Draw Detector Operator s Manual Part Number: RK Revision: P1 Released: 7/18/02

Carbon Dioxide Sample-Draw Detector Operator s Manual

Combustible Gas/Hydrogen Sulfide Sample-Draw Detector Operator s Manual

MODEL: O ELECTROCHEMICAL O2 DETECTOR (Used with ST1400 O2 Sensor) Part Number: MAN Rev. 0

SEC Signature Process Gas Analyzer

4P-90 CiTipeL Combustible Gas Sensor Part Number: PM

Operation Manual. Rev. E GEM-II Self Contained Gas Detector.

PolyGard 2-channel Gas Controller MGC-03

Transcription:

PolyGard CO LC-1112 V3 Electrochemical analog carbon monoxide transmitters serial no. EC-S 002 User Manual August 29, 2006 January 04, 2016 Revision

Specifications subject to change without notice. USA 160104 Page 2 of 13 Electrochemical analog carbon monoxide transmitters 1 General Overview... 3 2 Description... 3 3 Installation... 4 3.1 Assembly information... 4 3.2 Enclosure... 4 4 Electrical Connection... 5 4.1 Instructions... 5 4.2 Wiring connection... 5 5 Start-up operation... 6 5.1 Calibration... 6 5.2 Control span voltage calculation... 7 6 Inspection and Service... 8 6.1 Inspection... 8 6.2 Calibration... 8 6.3 Replacing of the sensor element... 8 7 Troubleshooting... 8 7.1 Diagnostics of the transmitter... 8 8 Cross-sensitivity Data... 9 9 Specifications... 10 10 Wiring Configuration and Enclosure Dimensions... 11 11 Notes and General Information... 13 11.1 Intended product application... 13 11.2 Installers` responsibilities... 13 11.3 Maintenance... 13 11.4 Limited warranty... 13

Specifications subject to change without notice. USA 160104 Page 3 of 13 Electrochemical analog carbon monoxide transmitters 1 General Overview The PolyGard CO analog gas transmitter is used for detection of carbon monoxide in the ambient air to warn of the presence of Carbon Monoxide gas. 2 Description The sensor portion of the PolyGard LC-1112 analog gas transmitter is a micro-fuel cell, which is completely sealed. The measurement is a gas-in-liquid chemical reaction rather than a surface area measurement. With no surface area to coat, this sensor retains its sensitivity to carbon monoxide even after prolonged exposure to clean air. The cell consists of a diffusion barrier, O-ring seal, electrolyte reservoir and two electrodes. The target gas, carbon monoxide, enters the cell through a diffusion barrier. The chemical process of the measurement is one of oxidation where one molecule of the target gas is exchanged for one molecule of oxygen. The reaction drives the oxygen molecule to the counter electrode, generating a DC microampere signal between the sensing and counter electrodes. This signal is linear to the volume concentration of the sensed gas rather than the partial pressure. The integrated two-wire transformer converts this DC microampere signal to a standard 4-20 ma signal. Most sensors produce a small amount of baseline current in clean air. This is adjusted out with the zero potentiometer on the transmitter. This oxidation at the electrodes causes wear of the sensor. Typical life for this sensor is approximately five years in normal operation. This will vary somewhat from sensor to sensor, with some working lifetimes less than five years and some greater than 5 years. This wear also changes the characteristics of the sensor, requiring periodic re-calibration. It is recommended that the sensor accuracy be verified every six months and recalibrated as necessary.

Specifications subject to change without notice. USA 160104 Page 4 of 13 3 Installation Note: Avoid any force (e.g. by thumb) during operation or installation on the sensor element. This could destroy the element. Electronics can be destroyed through static electricity. Therefore, do not work on the equipment without a wrist strap connected to earth ground or standing on conductive floor. 3.1 Assembly information The specific weight of carbon monoxide is almost the same as that of air (factor 0.967). Location of the sensor must conform to the layout of the area being monitored. Disregard the ventilation ratio! Do not mount sensor in the center of the airflow. In larger rooms, it might be necessary to install two or more transmitters where there is not adequate air movement. Do not mount in corners or directly in front of air inlets (e.g. doors, windows, open ramps, dampers, etc.). In areas with undefined air movement, it might be necessary to distribute several transmitters in a vertical and horizontal direction over the whole area to be monitored. Avoid locations where water, oil etc. may influence proper operation and where mechanical damage might be possible. Mounting height is five feet above floor (max. 6 feet). Provide adequate space around sensor for maintenance and calibration work. 3.2 Enclosure Un-screw cover of enclosure. Carefully unplug the basic PCB mounted on fixed terminal blocks. Screw the base vertically on wall or on a single gang electrical box. (see Fig. 3, page 12). Plug in the basic PCB and replace the cover after wiring connection is completed (see 4.2 wiring connection).

Specifications subject to change without notice. USA 160104 Page 5 of 13 4 Electrical Connection 4.1 Instructions Note: Electrostatic discharge (ESD) may damage electronic components. During wiring, open the cover only when completely grounded via grounding strap or standing on conductive floor. Connections should be made without any power applied to conductors. Installation of the electrical wiring should be according to the connection diagram and only performed by a trained specialist. Avoid any influence from external interference by using a shielded cable. Recommended cable: 18 AWG shielded, maximum resistance 20.8 Ω/1000 ft (73 Ω/1000 m) Cable insulation: Since the PCB mounts on top of the wiring terminations, it is important to ensure that the wire shields or any bare wires do not short to the PCB. Terminal strip X4 Connector 1 Connector 2 Connector 4 Power supply (+) 24 VDC, 17 28 VDC 0 VDC (DC common, not needed) Signal 4 20 ma 4.2 Wiring connection Unscrew cover of enclosure. Unplug basic PCB from terminal blocks. For single gang electrical box mounting: Pull through cable via hole in base; connect cable leads on terminal block X4. For surface mounting (cable entry always from the top Remove cover to access cable. Connect cable leads on terminal block X4. Plug the PCB on fixed terminal blocks on base. Screw cover on base.

Specifications subject to change without notice. USA 160104 Page 6 of 13 5 Start-up operation Only trained technicians should perform the following: Check mounting location. Check power voltage. Check PCB for proper mounting at X4 and X5. Verify transmitter operation (sensor/transmitter was factory calibrated). Note: If calibration is necessary, the sensor element must be powered and be fully stabilized for at least 1 hour. Required instruments to calibrate the transmitter: Test gas bottle with synthetic air. Test gas bottle with 200 ppm CO. Gas pressure regulator with flow meter to control the gas flow to 150 ml/min. Calibration set CONKIT-E/CH-LC. See fig. 4. Digital voltmeter with range 0 2 VDC, accuracy 1% and a small screwdriver. Note: Please observe proper handling procedures for test gas bottles! 5.1 Calibration Zero adjustment Zero-point calibration (4mA): (After sensor warm-up) Connect digital voltmeter to test pins and + (with a range selected that will display 2 VDC max.). Connect the calibration adapter to sensor element. Apply sensor element zero calibration gas, (150 ml/min; 14.5 psi ± 10%), or other clean air source. Wait two minutes until the signal is stable, adjust signal with zero potentiometer Zero until the signal is 40 mv ± 3 mv and stable. Remove calibration adapter carefully by turning lightly.

Specifications subject to change without notice. USA 160104 Page 7 of 13 Span adjustment Notes: CO calibration gas is toxic, never inhale the gas! Symptoms: Dizziness, headache and nausea. Procedure if exposed: Bring into fresh air at once, consult doctor. Connect calibration adapter to the sensor element. Apply sensor element span calibration gas (200 ppm CO), (150 ml/min; 14.5 psi ± 10%). Wait two minutes until the signal is stable, adjust signal with span potentiometer Gain until the signal reads the appropriate mvdc (± 3 mv, see calculation for control voltage 5.2) and is stable. Remove calibration adapter with a careful light turn. Inspect the seating of the sensor element! 5.2 Control span voltage calculation 160 (mv) x test gas concentration (ppm) + 40 (mv) Measuring range CO (ppm) Example Measuring range CO concentration Test gas concentration Control voltage 250 ppm 200 ppm 168 mv 160 (mv) x 200 (ppm) + 40 (mv) = 168 mv 250 (ppm)

Specifications subject to change without notice. USA 160104 Page 8 of 13 6 Inspection and Service 6.1 Inspection Inspection and service of the transmitters should be done by a trained technician and executed on a periodic interval. It is recommended that the sensor operation be verified every 12 months. 6.2 Calibration (See part 5.1 and 5.2) Service at periodic intervals is to be decided by the person responsible for the gas detection system. If span calibration voltage of 168 mv (see note below) is no longer attainable when applying 200 ppm Carbon Monoxide in air, then the sensor element has to be replaced. After the sensor element has been replaced a calibration is required. Note: If using a different level of span test gas ppm, or different sensor range, then the mv needs to be calculated. 6.3 Replacing of the sensor element Static electricity (see section 4.1). Sensor should always be installed without power applied: Unplug basic PCB carefully from the terminal blocks on the base. Unplug old sensor element out from the PCB. Take new sensor element out of original packing Plug sensor element in the PCB. Plug the PCB in terminal block X4, X5 carefully. Calibrate after sensor warm-up (see section 5.1). 7 Troubleshooting 7.1 Diagnostics of the transmitter Trouble Reason Solution Output signal 0 ma and control voltage 0 V Output signal less then 4 ma Control current signal not correct Power not applied Basic PCB X4 and X5 not plugged in correctly Sensor element not calibrated Sensor span not attainable Measure power voltage terminal block X4 terminal 1 (+) and 4 for 17 28 VDC Plug in the basic PCB into X4 and X5 correctly Calibrate sensor element output Replace sensor element

Specifications subject to change without notice. USA 160104 Page 9 of 13 8 Cross-sensitivity Data This table shows the typical response to be expected from the sensor when exposed to the following gases. Gas Chemical mark Gas concentration Tolerance ppm CO Acetone (CH 3 )CO(CH 3 ) 1000 ppm 0 ppm Acetylene C 2 H 2 40 ppm 80 ppm Ammonia NH 3 100 ppm 0 ppm Carbone dioxide CO 2 5000 ppm 0 ppm Chlorine CL 2 2 ppm 0 ppm Ethanol C 2 H 5 OH 2000 ppm 5 ppm Hydrogen H 2 100 ppm 20 ppm Hydrogen sulphide H 2 S 25 ppm 0 ppm Iso propanol C 2 H 7 OH 200 ppm 0 ppm Nitric oxide NO 50 ppm 8 ppm Nitrogen dioxide NO 2 50 ppm 1 ppm Sulphur dioxide SO 2 50 ppm 0 ppm

9 Specifications Specifications subject to change without notice. USA 160104 Page 10 of 13 Electrical Power supply: 17-28 VDC (polarity protected) Power consumption: 22 ma, (0.6 VA), max. RFI/EMI protection 5.0 W @1 ft. (0.31 m) radiated Sensor Performance Gas detected Carbon monoxide (CO) Sensor element Electrochemical, diffusion Range 0 250 ppm factory set 0-200 to 0 300 ppm, adjustable via calibration Stability & resolution ± 3.0 ppm of reading Repeatability ± 3.0 % of reading Long term output drift 0.4% signal loss/month Response time t 90 50 sec. Sensor life expectancy 3-5 year, normal operating environment Sensor coverage 5,000 sq.ft., (465 m 2 ), to10,000 sq.ft. (930 m 2 ) under ideal conditions Mounting height 5 to 6 ft. (1.5 to 1.8 m) above floor Type of Control Analog output signal Proportional, 4 20 ma, load 450 Operating Environment Working temperature 14 F to 122 F (-10 C to + 50 C) Intermitted temperature -4 F to 122 F (-20 C to 50 C) Storage temperature 41 F to 86 F (5 C to + 30 C) Working humidity 15 to 95% RH non-condensing Intermitted humidity 0 to 99% RH non-condensing Pressure range Atmospheric ±10% Physical characteristics Enclosure material High impact, GW-Plast, IEC 60695-2-12, GWFI-650 C, fire-retardant Enclosure color Light gray Protection NEMA12 (IP 55) Installation Wall (surface) mounted or single gang electrical box Dimensions (HxWxD) 5.0 x 3.4 x 2.2 in. (127 x 87 x 56 mm) Cable entry 1 hole for ½ in. conduit for wall (surface) mounting, and 1 hole on back side of base plate for single gang electrical box mounting Wire connection Terminal blocks, screw type for lead wire Wire size Min. 24 AWG (0.25 mm 2 ), max. 14 AWG (2.5 mm 2 ) Wire distance Max. loop resist. 500 (= wire resist. + controller input resist.) Weight 0.6 Ibs. ( 0.25 kg ) Approvals/Listings - Unit rating NRTL Performance Tested & Certified, Conforms to STD ANSI/UL 2075 City of Los Angeles CE VDI 2053, air treatment systems for garages and tunnels EMV-Compliance 89/336/EWG, low voltage directives 73/23/EWG - Enclosure UL Listed, E208470 CSA Certified, E208470

Specifications subject to change without notice. USA 160104 Page 11 of 13 10 Wiring Configuration and Enclosure Dimensions Wiring Configuration Fig. 1 Power supply 17-28V/DC - 0V/DC 4-20mA + Controller X4 Transmitter LC-1112 7 BUS B 6 BUS A 5 4-20 ma_inp 4 Output (V/mA) 3 24 VDC_Out 2 0 VDC 1 24 VDC_Inp X5 1 2 3 4 5 Printed circuit board Fig. 2 Calibration adapter Fig. 4 Type: CONKIT-E/CH-LC 7 Bus_B 6 Bus_A 5 INP 4 OUT 3 <24VDC 2 GND 1 >24VDC 7 1 2 3 4 5 6 - X6 + Test P1 P2 Gain Zero Sensor 4 3 2 1 X5 1 NO1 2 NC1 3 COM1 4 NO2 5 COM2 EC-S-002 240703

Specifications subject to change without notice. USA 160104 Page 12 of 13 Dimensions Fig. 3 d = 0.16 in. (4 mm) 0.87 in. (22 mm) 3.19 in. (81 mm) 3.3 in. (84 mm) d = 0.16 in. (4 mm) d = 0.88 in. (22,5 mm) 4.9 in. (125 mm) 1 2 3 4 5 6 7 1 2 3 4 5 3.35 in. (85 mm) 2.2 in. (55 mm)

Specifications subject to change without notice. USA 160104 Page 13 of 13 11 Notes and General Information It is important to read this user manual thoroughly and clearly understand the information and instructions. The PolyGard transmitters must be used within product specification capabilities. The appropriate operating and maintenance instructions and recommendations must be followed. Due to ongoing product development, MSR reserves the right to change specifications without notice. The information contained herein is based upon data considered to be accurate. However, no guarantee is expressed or implied regarding the accuracy of this data. 11.1 Intended product application The PolyGard CO LC-1112 transmitters are designed and manufactured for control applications for energy savings and OSHA air quality compliance in commercial buildings and manufacturing plants (i.e.,detection and automatic exhaust fan control for automotive maintenance facilities, enclosed parking garages, engine repair shops, warehouses with forklifts, fire stations, tunnels, etc.). 11.2 Installers` responsibilities It is the installer`s responsibility to ensure that all PolyGard transmitters are installed in compliance with all national and local codes and OSHA requirements. Installation should be implemented only by individuals familiar with proper installation techniques and with codes, standards and proper safety procedures for control installations and the latest edition of the National Electrical Code (ANSI/NFPA70). It is also essential to strictly follow all instructions as provided in the user manual. 11.3 Maintenance It is recommended that the PolyGard transmitter performance check is done on a routine schedule. Any performance deviations may be serviced based on needed requirements. Re-calibration and part replacement may be implemented in the field by a qualified individual and with the appropriate tools. Alternatively, the easily removable plug-in transmitter card with the sensor may be returned for service to INTEC Controls. 11.4 Limited warranty MSR-Electronic-GmbH and INTEC Controls warrants the PolyGard transmitter for a period of two years, 12 months normal exposure for the sensor, from the date of shipment against defects in material or workmanship. Should any evidence of defects in material or workmanship occur during the warranty period, INTEC Controls will repair or replace the product at their own discretion, without charge. This warranty does not apply to units that have been altered, had attempted repair, or been subject to abuse, accidental or otherwise. The warranty also does not apply to units in which the sensor element has been overexposed or gas poisoned. The above warranty is in lieu of all other express warranties, obligations or liabilities. This warranty applies only to the PolyGard transmitter. MSR-Electronic-GmbH and/or INTEC Controls shall not be liable for any incidental or consequential damages arising out of or related to the use of the PolyGard transmitter. If the PolyGard transmitter needs to be returned to INTEC Controls for service, an RMA number must be obtained prior to sending.