Engine Control Unit, ECU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

Similar documents
Generator Control Unit, GCU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

Compact Genset Controller, CGC 400 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL

Protection and Power Management, PPM-3 Display and push-button functions Alarm handling Log list Failure mode and effect analysis

CAN bus-based I/O module, CIO relays Mounting Terminals and wiring Commissioning, using the utility software

DEIF A/S. Operator s Manual. Multi-line 2/version 2-GS E (UK) SW version 2.4X.X. Display readings. Push-button functions.

DEIF A/S. Operator s Manual. Basic Gen-set Controller. Display readings. Push-button functions. Alarm handling. Log list C (UK)

Engine Control Unit, ECU 100 Functional description Additional functions Parameter list

DEIF A/S. Description of options. Option A4, Loss of mains protection package Automatic Gen-set Controller. Description of option

Option M16.x Configurable I/O extension cards, four multi-inputs (4-20 ma/0-5 V/Pt100) Description of option Functional description

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option

Generator Paralleling Controller, GPC-3 Hydro Start and stop sequences, water level control

DELOMATIC 400, DM-400 HYDRO

INSTALLATION INSTRUCTIONS. Anti Knocking System, AKR 3. Document no.: A SW version:

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

User Manual. Dryer Controller M720

Manual# User s Manual. DCU 410/408 Engine Control Unit RP 410 Remote Panel FW 2.3

Dryer Controller M720

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

Tri-Stack Smart System

Procidia iware AlarmWorX32. AlarmWorX32 Viewer January 2010

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

Halton SAFE / 7.14 user guide and installation instructions

Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A

User s Manual DCU 305 R3 DCU 305 R3 LT. Diesel Engine Control Unit. Auto-Maskin

Flopurge TS. Operation Manual

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

DEIF A/S. Technical Manual. Type EC-2 Engine Control Unit D. Technical Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

CSP-204 CSP-208 CSP-104 CSP-108

Intelligent Security & Fire Ltd

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Diplomat Inverter/Diplomat Duo Inverter

with internal sensor (channel 1) with an external sensor (channel 2) A-Editor software, Professional AK20 version (not for version AK4)

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Dryer Master DM510 Commissioning Guide

HERCULES 6 GRAPHICS SYSTEM

Entero Voice Alarm system.

ZITON RADIO LOOP MODULE

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

THX-DL Data Logger USER & INSTALLATION MANUAL V

Flostop TS D7E and A8E. Operation Manual

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

Lift Station Level Controller

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

Sensor Control Panel

Electro-Sentry. Users Manual

Ontech GSM 9040/50. Reference Manual English -1 -

Fridge-tag 2 OPERATION MANUAL ENGLISH PAGE 1-35 GEBRAUCHSANWEISUNG DEUTSCH SEITE with external sensor

EXcon zone control. Control for up to 4 individual zones _ fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov

Emergency power automatics MS-2. High resistance to shock, vibrations and transients. All output are 2A relay contacts

Chore-Tronics Load Cell Indicator

Fridge-tag 2 L. with external sensor OPERATION MANUAL

Tasman Sea Control System

M2500 Engine Controller Installation Manual

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

PROGRAMMABLE 7-DAY RF THERMOSTAT

EXPERT TRI-STAR. Temperature controller. User s Manual

DS7446KP. User Guide. Keypad

CONTROL UNIT: REFERENCE MANUAL

Master User Guide Premier Elite Series

TPOne-B. Electronic Programmable Room Thermostat. Installation Guide. Danfoss Heating

User instructions DHP-AT

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

FLOW CONTROLLER TYPE S/601

Laptop / PC Programming Manual

Application description

Control of the system, MLP RO pump station

Table of Contents. Part I SAFETY MESSAGE TO INSTALLERS OF EMERGENCY WARNING EQUIPMENT 2 Part II Vehicle Operation 4. Part III Safety Messages 13

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

U ser's Guide PC6010

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

VISY-X. Technical Documentation. VISY-SoftView V 1.7 User Guide for VISY-Command GUI and VISY-View Touch. Edition: Version: 6 Art.

QuadraTouch Pro Software Manual Dryer Control System

BeneVision Central Monitoring System. Quick Reference Guide

Fridge-tag 2 L OPERATION MANUAL ENGLISH PAGE 1-34 GEBRAUCHSANWEISUNG DEUTSCH SEITE with internal sensor

GLD-30 Gas Leak Detector

Dashboard for Windows V1.1.0

User Guide IM/SM3000 EN Rev. L. SM3000 Multipoint Videographic Recorder

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

DYGIZONE GJD910 Lighting Controller & Enunciator

ZERIO PLUS EDA-Z5008, Z5020 & Z5100

WiFi Hints & Tips. Contents. WiFi Hints and Tips 1. Page No. Section No. Title

M2000 Engine Controller

MPT Electric Fire Pump Controller

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert)

3D_ISS. Integrated Software System. User Guide Manual

Memcom Emergency Telephone

Operator's Handbook. Release 3. Fire Alarm Control Panel, BS-310 / 320 / Operator Panel BS-330. System Program Version 3.8.0

Operating Instructions READ AND SAVE THESE INSTRUCTIONS

Patriot Systems Limited

INSTRUCTION FOR THE USER THC V E OIL BLU

Temperature Controller CC24-7 UNIBOX USER S MANUAL Legion Dr. Mason, MI USA October 2010 Ph. (517) Fax (517)

INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

Version 1.03 January-2002 USER S MANUAL

Transcription:

OPERATOR'S MANUAL Engine Control Unit, ECU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4189340797A SW version:

1. General information 1.1. Warnings, legal information and safety...3 1.1.1. Warnings and notes...3 1.1.2. Legal information and disclaimer...3 1.1.3. Safety issues...3 1.1.4. Electrostatic discharge awareness...3 1.1.5. Factory settings...3 1.2. About the operator's manual...4 1.2.1. General purpose...4 1.2.2. Intended users...4 1.2.3. Contents and overall structure...4 2. Push-buttons and LEDs 2.1. Unit...5 2.1.1. Push-button functions...5 2.1.2. LED functions...6 3. Display and menu structure 3.1. Menu...7 3.1.1. Menu system...7 3.1.2. View menu...7 3.1.3. Menu structure example...8 3.2. Display functions...8 3.2.1. Functional examples...8 4. Standard text 4.1. Status line text...10 4.1.1. Status texts...10 4.1.2. Information text...10 5. Running modes 5.1. Running mode overview...11 5.1.1. Overview...11 6. Alarm handling and log list 6.1. Alarm handling...12 6.2. Log list...12 DEIF A/S Page 2 of 13

General information 1. General information 1.1 Warnings, legal information and safety 1.1.1 Warnings and notes Throughout this document, a number of warnings and notes with helpful user information will be presented. To ensure that these are noticed, they will be highlighted as follows in order to separate them from the general text. Warnings Notes Warnings indicate a potentially dangerous situation, which could result in death, personal injury or damaged equipment, if certain guidelines are not followed. Notes provide general information, which will be helpful for the reader to bear in mind. 1.1.2 Legal information and disclaimer DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the installation or the operation of the set must be contacted. The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost. Disclaimer DEIF A/S reserves the right to change any of the contents of this document without prior notice. 1.1.3 Safety issues Installing and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment. Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death. 1.1.4 Electrostatic discharge awareness Sufficient care must be taken to protect the terminal against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary. 1.1.5 Factory settings The Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average values and are not necessarily the correct settings for matching the engine/generator set in question. Precautions must be taken to check the settings before running the engine/generator set. DEIF A/S Page 3 of 13

General information 1.2 About the operator's manual 1.2.1 General purpose This Operator's Manual mainly includes general product information, display readings, push-button and LED functions, alarm handling descriptions and presentation of the log list. The general purpose of this document is to give the operator important information to be used in the daily operation of the unit. Please make sure to read this document before starting to work with the Multi-line 2 unit and the generator set to be controlled. Failure to do this could result in human injury or damage to the equipment. 1.2.2 Intended users This Operator's Manual is mainly intended for the daily user. On the basis of this document, the operator will be able to carry out simple procedures such as start/stop and control of the generator set. 1.2.3 Contents and overall structure This document is divided into chapters, and in order to make the structure simple and easy to use, each chapter will begin from the top of a new page. DEIF A/S Page 4 of 13

Push-buttons and LEDs 2. Push-buttons and LEDs 2.1 Unit 2.1.1 Push-button functions The push-buttons on the unit have the following functions: 1 2 3 4 5 6 7 11 10 9 8 No. Function No. Secondary functionality 1: Scroll the display down once 1: Programming: Decrease setpoint value 2: Scroll the display up once 2: Programming: Increase setpoint value 3: Reset horn relay 3: Press and hold for 2 seconds to see alarm list 4: Enter menus/enter value/acknowledges alarm 5: Return function 6: Initiates the test sequence 7: Lamp test/dimmer 8: Remote running mode selector 9: Local running mode selector 10: Start engine 11: Stop engine DEIF A/S Page 5 of 13

Push-buttons and LEDs 2.1.2 LED functions The display unit holds 10 LED functions. Dependent on the situation, the colour of the LEDs is green, red or a combination. The table below describes the functionality of the LEDs on the ECU 100: 1 2 3 6 5 4 LED no. LED function 1: Power LED indicates that the auxiliary supply is switched on. If it is green, the ECU 100 is operational. If it is red, the self-check has failed. 2 : Alarm LED steady light indicates that all alarms are acknowledged, but some are still present. LED flashing indicates that unacknowledged alarms are present. 3: 4 x LEDs with selectable indication function. Selection is made in M-Logic. 4: Indicates that Remote mode is active. 5: Steady light indicates that Local mode is active. 6: Indicates that Engine is running DEIF A/S Page 6 of 13

Display and menu structure 3. Display and menu structure 3.1 Menu 3.1.1 Menu system The display includes the menu systems listed below which can be used/viewed without password entry: View menu system: This is the commonly used menu system, which contains displaying of the measured values. Log menu: This menu contains event, alarm and battery logs. Setup menu (not commonly used by the operator): This menu is used for setting up the unit, and if the operator needs detailed information that is not available in the view menu system. Changing of parameter settings is password-protected. Alarm list: This list shows active acknowledged and unacknowledged alarms. It is also in this list that alarms can be acknowledged by pressing Service menu: This menu contains input-, output-, M-Logic status and data about the unit. 3.1.2 View menu The view menus are the daily use menus for the operator. There are 20 configurable display views, with up to three configurable display lines in each view. View configuration is done through the PC utility software (USW). In the view menus, various measured values are on the display. First display line: status and information text. Second display line: information relating to operational status Third display line: information relating to operational status Fourth display line: information relating to operational status Fifth display line: running hours DEIF A/S Page 7 of 13

Display and menu structure 3.1.3 Menu structure example The figure below is an example of how the menu structure is arranged, and it also shows the meaning of the entry symbols.... (up to 20 views) ENGINE RUNNING Serv 4d 0h Serv 4d 0h Start attempts 53 Running hours 0hrs ENGINE RUNNING Serv 4d 0h Serv 4d 0h Start attempts 53 Running hours 0hrs ENGINE RUNNING Serv 4d Serv 4d Start attempts 5 Running hours Use arrows to toggle betweeen menus LOG MENU Event log Alarm log Battery test log SETUP MENU 2500 Regulation 3000 Digital input 4000 Analogue input 5000 output Alarm list: Emergency Stop Ch 3490 UNAK 2/2 alarm(s) Service menu Status digital input Status relay output Status analog input M-logic Line Status Event log: 2012-10-01 08:15:00 POWER UP 1/50 Log(s) SETUP MENU 2770 EIC control 2790 EIC Speed Dem. Sw. Alarm list: Over Speed 1 Ch 4510 UNAK 1/2 alarm(s) Service menu Remote Start 1 Remote Stop 0 Digital in 12 0 Digital in 13 0 2770 EIC control Droop: 4.0% Speedsel: Scania rpm Cummins gain: 5.00 Use the arrows to change the setpoint 3.2 Display functions 3.2.1 Functional examples The display indicates both readings and alarms. The examples below are with icons and English language. DEIF A/S Page 8 of 13

Display and menu structure View examples The software version can be found in the Service menu Alarm acknowledge Press or hold down to enter the list of active alarms. The alarm list shows the active alarms. Press alarms to ackowledge Parameter settings Press to enter the parameter setting. Select menu group with to edit. Edit value with or arrows and save the value by pressing All alarm explanations are found in the parameter list. The channel numbers are individual for all alarms. The available parameters depend on the version of the ECU. Some parameters can only be changed using the PC utility software (USW). The parameter list will automatically be abandoned, if no button is pressed during a 30 sec. period. For detailed information about functionality, parameters and setup, please see the Designer's Reference Handbook DEIF A/S Page 9 of 13

Standard text 4. Standard text 4.1 Status line text 4.1.1 Status texts The following table explains the different status messages in the display. Status messages are automatically shown during and under operation without any interaction of the operator. Condition COOLING DOWN ENGINE STOPPING EXT STOP TIMER IDLE RUN SHUTDOWN OVERRIDE SIMPLE TEST START PREPARE START RELAY OFF ENGINE RUNNING Comment Cooling-down period is activated Engine is stopping Trailing timer for external equipment The timer in the "Idle run" function is active The configurable input is active Test mode is activated The start prepare relay is activated The start relay is deactivated during the start Engine is running 4.1.2 Information text This table explains the different information text messages on the display. The information messages are active for three seconds after a push-button has been pressed. Condition ALREADY RUNNING NOT IN REMOTE NOT IN LOCAL NOT READY NOT RUNNING Comment Engine is already running Auto mode not selected Manual mode not selected Engine not ready Engien not running DEIF A/S Page 10 of 13

Running modes 5. Running modes 5.1 Running mode overview 5.1.1 Overview The unit has three different running modes. The different running modes are selected by use of push-buttons, digital inputs on the display or the PC utility software. For detailed information, please see the Designer's Reference Handbook. Remote In remote mode, the unit will operate on external control input, and the operator cannot initiate any sequences manually on the display. Local Local means that the unit will not be able to be controlled from external signals, but only from display. Test The simple test sequence will start when the test mode is selected. Test mote can be selected by digital input, Modbus commands and display. DEIF A/S Page 11 of 13

Alarm handling and log list 6. Alarm handling and log list 6.1 Alarm handling When an alarm occurs, the unit will automatically go to the alarm list for display of the alarm. If reading of the alarms is not desired, press to exit the alarm list. If you decide to enter the alarm list later, press the HORN push-button for 2 seconds to jump directly to the alarm list reading. The alarm list contains both acknowledged and unacknowledged alarms provided that they are still active (i.e. the alarm condition is still present). Once an alarm is acknowledged and the condition has disappeared, the alarm will no longer be displayed in the alarm list. This means that if there are no alarms, the alarm list will be empty. This display example below indicates an unacknowledged alarm. The display can show only one alarm at a time. Therefore, all other alarms are hidden. Alarm list: BB U> 1 Ch 1270 UNACK 1/1 alarm(s) To see the other alarms, use the and push-buttons to scroll in the display. To acknowledge an alarm press. 6.2 Log list The log is divided into three different lists: 1. Event log 2. Alarm log 3. Battery test log The log list contains up to 50 events, the alarm list contains up to 30 historical alarms, and the battery test list contains up to 52 historical battery tests. An event is e.g. closing of breaker and starting of engine. An alarm is e.g. overcurrent or high cooling water temperature. A battery test is e.g. test OK or test failed. DEIF A/S Page 12 of 13

Alarm handling and log list To enter the log list: 1. Select from the setup menu For detailed information about the alarms, please see the parameter list. DEIF A/S Page 13 of 13