Metasys Connectivity Technical Manual. Metasys Integrator Section Application Note Issue Date 000 APPLICATION NOTE Metasys Integrator York Application lntroduction Page * Application Details * Component Requirements * Vendor Contact Information Design Considerations * Cable Connections Cable Pinouts Connecting the Cable Metasys Integrator Setup * Point Mapping Tables Translator and XL Login YT Centrifugal Dual or Mono Shell Chiller YK Centrifugal Super Chiller * YS -00 Ton Rotary Screw Chiller 0 LS 000-0 Ton Rotary Screw Chiller YP Absorption Chiller C U.S. Reciprocating Intelligent Chiller - Master C U.S. Reciprocating Intelligent Chiller - Slave B U.K. Basildon Reciprocating Intelligent Chiller - Master B U.K. Basildon Reciprocating Intelligent Chiller - Slave *Indicates those sections where changes have occurred since the last printing. 000 Johnson Controls, Inc. No. LIT-0 www.johnsoncontrols.com
YR Sunline 000 Rooftop Chiller Page A Air-cooled Screw Chiller - Master A Air-cooled Screw Chiller - Slave YI Isoflow Absorption Chiller * YG Gas Engine Drive Chiller Metasys Network Setup * Mapping to a CS Object * Custom Integration * *Indicates those sections where changes have occurred since the last printing. Metasys Integrator Metasys Integrator York Application
lntroduction This document explains Metasys Integrator York applications. Use this document with the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN.), which provide information on installing and commissioning the Metasys Integrator unit. For information on York equipment, see York documentation (obtainable from a York representative). Note: If you use a Universal Packaging Module (UPM) enclosure, you must install the Metasys Integrator 00 Series in a two high enclosure (EN-EWC-0) rather than the one high enclosure (EN-EWC-0) as shown in the figures in this application note. Application Details The Metasys Integrator unit allows York Millennium chillers and Sunline 000 rooftop units to become an integral part of the Metasys and Metasys Companion Networks. Once York controllers are connected to Metasys or Companion Networks via the Metasys Integrator unit, their data is available to the full complement of Metasys Building Automation System (BAS) features, including Change-of-State (COS) monitoring, alarm notification, scheduling, trend, and totalization. The York YorkTalk Translator and YorkTalk XL are the interfaces between York chiller controllers and non-york devices (such as the Metasys Integrator unit). Each Metasys Integrator vendor port can connect to one YorkTalk Translator. Each YorkTalk Translator can connect to up to four York chiller controllers. If you use reciprocating chillers, the maximum number of pairs in master/slave configuration (C/C or B/B) is two. If you use only master reciprocating chillers (C or B), the maximum number of chillers allowed is four. Also, with a YorkTalk Translator interface, reciprocating chillers may not be mixed with other types of chillers due to a difference in baud rates. Each Metasys Integrator vendor port can connect to one YorkTalk XL, which can then connect to York controllers. Figure shows York and Metasys System integration. Figure shows York and Metasys Companion integration. Metasys Integrator Metasys Integrator York Application
N LAN A A YS YI Linc Chiller Linc Chiller Linc Chiller RS- ISN Network Standard NCU YorkTalk XL Metasys Integrator RS- YorkTalk Translator UNT YK Chiller YS Chiller YP Chiller YT Chiller N Bus Note: If you use a UPM enclosure, you must install the Metasys Integrator 00 Series in a two high enclosure (EN-EWC-0) rather than the one high enclosure (EN-EWC-0) as shown in the figures in this application note. Figure : York and Metasys System Integration York Metasys Integrator Metasys Integrator York Application
Panel Unit Workstation A A YS YI Linc Chiller Linc Chiller Linc Chiller RS- ISN Network Metasys Integrator RS- YorkTalk XL YorkTalk Translator UNT N Bus YK Chiller YS Chiller YP Chiller YT Chiller Note: Note: A PC version and converter may be substituted for the Panel unit. If you use a UPM enclosure, you must install the Metasys Integrator 00 Series in a two high enclosure (EN-EWC-0) rather than the one high enclosure (EN-EWC-0) as shown in the figures in this application note. york Figure : York and Metasys Companion Integration Metasys Integrator Metasys Integrator York Application
Component Requirements Metasys Network Release Requirements Metasys Companion Release Requirements Vendor Component Requirements To integrate York equipment, you need the following components: properly installed York YorkTalk Translator (Revision A, firmware Revision.00 or above) or YorkTalk XL version and York chiller controllers Note: The Metasys Integrator unit supports only the U.S. version of the translator, which has two Advanced Processor Cards. Versions with only one Advanced Processor Card (such as the U.K. version) are not supported. RS- cable (for connecting the YorkTalk Translator or YorkTalk XL to the Metasys Integrator unit) Metasys Integrator unit N Bus (for connecting the Metasys Integrator unit to the Metasys or Companion Networks) portable Personal Computer (PC) for downloading vendor communication tables (.VCT files) and network setup information into the Metasys Integrator unit, and for running diagnostics cable for connecting portable PC to the Metasys Integrator unit the correct vendor communication table (.VCT file) to download into the Metasys Integrator unit (supplied on Metasys Integrator CD-ROM) To integrate York equipment into the Metasys Network, you need: Metasys Operator Workstation (OWS) software Release.0 or higher Metasys Integrator software/firmware Release.0 or higher To integrate York equipment into the Metasys Companion Network, you need: Metasys Companion Release.0 or higher Metasys Integrator software/firmware Release.0 or higher Integration between the Metasys Integrator unit and York has been tested with the YorkTalk Translator (Part Number -0-00, Revision A) or the YorkTalk XL (Part Number -0-0, Revision ). Changes to this equipment or integration of York products not discussed in this document will require additional software development and testing by Systems Products. For information on integrating other products, refer to the Custom Integration section in this document. Metasys Integrator Metasys Integrator York Application
Vendor Contact Information Design Considerations York International Corporation Applied Systems P.O. Box -Z York, PA 0- Phone: () -0 FAX: () -0 When integrating York equipment, consider the following: Make sure all York equipment is set up and running properly before attempting to integrate with Metasys or Companion Network. (The York representative is responsible for operation of YorkTalk Translator, YorkTalk XL, and controllers.) Make sure the YorkTalk Translator or YorkTalk XL baud rate is set to 00. (The York representative is responsible for setting the YorkTalk baud rate.) The York representative must configure the YorkTalk Translator or the YorkTalk XL to talk to the Metasys Integrator unit, provide passwords, and commission the chillers via YorkTalk. York must also configure the YorkTalk Translator and the YorkTalk XL to report statuses as Off and On. (The defaults in the Translator at this time are No and Yes.) The YorkTalk Translator or YorkTalk XL must be configured for: trm= (cr, prompt) txt= (field text) The YorkTalk Translator or the YorkTalk XL must have its logon password set to. Otherwise, the Metasys Integrator unit will not be able to bring it online. IMPORTANT: Make sure the YorkTalk Translator or YorkTalk XL table is defined as an N address so that the Metasys Integrator unit can establish the logon procedure. This will ensure the quickest recovery to online status of all York equipment. RS- cable distance between the Metasys Integrator unit and the YorkTalk Translator or YorkTalk XL can be a maximum of 0 feet. Cable distance between the YorkTalk Translator and the last controller can be a maximum of 000 feet. IMPORTANT: The YorkTalk Translator does not provide offline notification when the chiller is disconnected from the Translator. Metasys Integrator Metasys Integrator York Application
York must configure the YorkTalk XL failure output to report statuses as NOR, and FLT to allow the XL to report if the chiller is offline to the XL. Ensure battery backup is enabled to save baud rate settings on the YorkTalk Translator or YorkTalk XL. York chiller model names sometimes differ from the two character codes Johnson Controls uses (refer to Table ). Table : Chiller Names Standard Name Also Known As: C, C (B, B) YCA, YDA, YEA, YCW, YCR A, A DYCAS YI YP YIA YPC Metasys Integrator Metasys Integrator York Application
Cable Connections Cable Pinouts Use the following cable pinouts for the RS- connection between the Metasys Integrator unit and the YorkTalk Translator and XL: Vendor Port A or B on Metasys Integrator DB- Female RS- Port on Translator or XL Screw Terminal Signal RD TD GND Pin RS- (0 ft maximum) Pin Signal TX RX GND york Figure : Cable Pinouts Connecting the Cable Connect the female end of the RS- cable to either Vendor Port A or Vendor Port B on the Metasys Integrator unit. Connect the male end to Port A on the YorkTalk Translator or YorkTalk XL. Metasys Integrator YorkTalk Translator or XL Vendor Port A or B RS- Cable RS- Terminal Block york Figure : Port-to-Port Connection Metasys Integrator Metasys Integrator York Application
0 Metasys Integrator Metasys Integrator York Application
Metasys Integrator Setup To set up the Metasys Integrator unit, use a portable PC connected to the Metasys Integrator Terminal Port. Metasys Integrator setup involves: downloading the correct vendor communication table (.VCT file) setting up the ports assigning network addresses to the controllers Table provides information specific to York applications. For detailed procedures, see the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN.). Table : Metasys Integrator Setup for York Controllers Vendor Communication Table (.VCT File) Login and Chillers Translator XL Login YK_TRAN.VCT YK_XL.VCT YT Chiller (Centrifugal Dual Shell or Mono Shell) YK_YTCH.VCT YK_YTXL.VCT YK Chiller (Centrifugal Super Chiller ) YK_YKCH.VCT YK_YKXL.VCT YS Chiller (-00 Ton Rotary Screw) YK_YSCH.VCT YK_YSXL.VCT LS Chiller (000-0 Ton Rotary Screw) YK_LSCH.VCT YK_LSXL.VCT YP Chiller (Absorption Chiller) YK_YPCH.VCT YK_YPXL.VCT C Chiller (U.S. Reciprocating Intelligent Chiller-Master) C Chiller (U.S. Reciprocating Intelligent Chiller-Slave) B Chiller (U.K. Basildon Reciprocating Intelligent Chiller-Master) B Chiller (U.K. Basildon Reciprocating Intelligent Chiller-Slave) YK_CCH.VCT YK_CCH.VCT YK_BCH.VCT YK_BCH.VCT YK_CXL.VCT YK_CXL.VCT YK_BXL.VCT YK_BXL.VCT YR Chiller (Sunline 000 Rooftop Chiller) YK_S000.VCT YK_S0XL.VCT A Chiller (Air-cooled Screw Chiller- Master) A Chiller (Air-cooled Screw Chiller- Slave) N/A N/A YK_AXL.VCT YK_AXL.VCT YI Chiller (Isoflow Absorption Chiller) N/A YK_YIXL.VCT YG Chiller (Gas Engine Drive Chiller) N/A YK_YGXL.VCT Port Setup Baud Rate 00 Word Length Stop Bits Parity Continued on next page... None Metasys Integrator Metasys Integrator York Application
Network Setup for Login of Translator or XL (Cont.) Interface Vendor Address 0 Timeout Value Poll Delay Network Setup for Translator Vendor Address - Timeout Value Poll Delay Network Setup for XL Vendor Address* Timeout Value Poll Delay RS- 000 ms 0 ms 000 ms 0 ms net, node 000 ms 0 ms Performance Guide Chillers Translator XL Approximate Scan Time (For a single N address) Login Table seconds seconds YT Chiller 0 seconds seconds YK Chiller seconds seconds YS Chiller seconds seconds LS Chiller seconds seconds YP Chiller seconds seconds C Chiller seconds seconds C Chiller 0 seconds 0 seconds B Chiller seconds seconds B Chiller 0 seconds 0 seconds YR Chiller seconds seconds A Chiller XL N/A seconds A Chiller XL N/A 0 seconds YI Chiller XL N/A seconds YG Chiller XL N/A seconds * Example: If network is 0 and node is, then enter 00,0 for the vendor address. The format is two digits each for the network address and the node address, with leading zeros if necessary. Metasys Integrator Metasys Integrator York Application
Network Modify/Add/Delete N Address Interface Type Vendor Address Port Timeout Poll Delay Retry 0 [ ] [ ] [A] [ ] [ ] [ ] [ ] [ ] [A] [ ] [ ] [ ] [ ] [ ] [A] [ ] [ ] [ ] [YorkTalk Translator] [0 ] [A] [ 000] [ 0] [ ] [York C Chiller ] [ ] [A] [ 000] [ 0] [ ] [ ] [ ] [A] [ ] [ ] [ ] [ ] [ ] [A] [ ] [ ] [ ] [ ] [ ] [A] [ ] [ ] [ ] Available Vendor Interface Types YorkTalk Translator York C Chiller F Cancel F Save F More F Goto Select a vendor interface type from the list Figure : Example--Proper Setup of York C Chiller on YorkTalk Translator Network Modify/Add/Delete N Address Interface Type Vendor Address Port Timeout Poll Delay Retry 0 [ ] [ ] [A] [ ] [ ] [ ] [YorkTalk XL ] [0 ] [A] [ 000] [ 0] [ ] [York YT Chiller XL] [00,0 ] [A] [ 000] [ 0] [ ] [York YT Chiller XL] [00,0 ] [A] [ 000] [ 0] [ ] [York YT Chiller XL] [00,0 ] [A] [ 000] [ 0] [ ] [ ] [ ] [A] [ ] [ ] [ ] [ ] [ ] [A] [ ] [ ] [ ] [ ] [ ] [A] [ ] [ ] [ ] Available Vendor Interface Types York Talk XL York YT Chiller XL F Cancel F Save F More F Goto Select a vendor interface type from the list Figure : Example--Proper Setup of Three York YT Chillers on ISN YorkTalk XL Metasys Integrator Metasys Integrator York Application
Metasys Integrator Metasys Integrator York Application
Point Mapping Tables The following tables (one for each application) show the points available for mapping in the York controllers: Translator and XL Login Table : YorkTalk Translator Login NPT NPA Unit Description Translator Ready 0-no, -yes Network Point Type Network Point Address Table : YorkTalk XL Login NPT NPA Unit Description XL Ready 0-no, -yes Network Point Type Network Point Address Metasys Integrator Metasys Integrator York Application
YT Centrifugal Dual or Mono Shell Chiller To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Condenser Pressure point is 0. Table : YT Centrifugal Dual or Mono Shell Chiller (Translator and XL Configuration) NPT NPA Unit Description 0 0 * * Amperes Amperes Amperes Volt Volt Volt FLA DegC Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Evaporator Saturation Temperature Condenser Saturation Temperature Discharge Temperature Oil Temperature Evaporator Pressure Condenser Pressure Oil Differential Pressure Purge Pressure Full Load Amperes Phase A Amperes Phase B Amperes Phase C Amperes Phase A-B Volts Phase B-C Volts Phase C-A Volts Leaving Water Temperature Actual Setpoint Current Actual Setpoint Feedback Compressor 0-open, -made Vent Solenoid 0-open, -made Chill Water Pump 0-open, -made Start Switch 0-open, -made Flow Switch 0-open, -made ACC Valid Surge Map 0-open, -made ACC New Surge Point 0-open, -made VSD Cooling Pump Running 0-open, -made Leaving Chill Water Setpoint (0 to 0) Current Limit Setpoint (0 to 00) Leaving Chill Water Setpoint (- to ) BO Chiller Start/Stop 0-stop, -start Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. Continued on next page... Metasys Integrator Metasys Integrator York Application
NPT (Cont.) BD BD NPA Unit Description 0 0 Hour Volt kw MWh Volt Amps Hz kva Deg Deg Hz Anti-Recycle Timer Operational Mode Operational Safety Cycling Runtime Hours Number Of Starts Adaptive Capacity Control Frozen Delta p/p VSD Output Voltage VSD Input kw VSD Input MWh VSD DC Link Voltage VSD DC Link Current VSD Surge Count VSD Output Frequency VSD Maximum Voltage THD VSD Maximum Current TDD VSD Input kva VSD Internal Temperature VSD Converter Heatsink Temperature ACC PRV Position ACC Frozen Output Frequency VSD IEEE Filter Present 0-Not Installed Surge Detection Type 0-Delta_p/p, -Current Network Point Type Network Point Address Metasys Integrator Metasys Integrator York Application
YK Centrifugal Super Chiller To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Condenser Pressure point is 0. Table : YK Centrifugal Super Chiller (Translator and XL Configuration) NPT NPA Unit Description 0 0 * * Amperes Amperes Amperes Volt Volt Volt FLA DegC Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Evaporator Saturation Temperature Condenser Saturation Temperature Discharge Temperature Oil Temperature Evaporator Pressure Condenser Pressure Oil Differential Pressure Refrigerant Level Full Load Amperes Phase A Amperes Phase B Amperes Phase C Amperes Phase A-B Volts Phase B-C Volts Phase C-A Volts Low Oil Pressure High Oil Pressure Leaving Water Temperature Actual Setpoint Current Actual Setpoint Feedback Compressor 0-open, -made Vent Solenoid 0-open, -made Chill Water Pump 0-open, -made Start Switch 0-open, -made Flow Switch 0-open, -made ACC Valid Surge Map 0-open -made ACC New Surge Point 0-open -made VSD Cooling Pump Running 0-open -made Leaving Chill Water Setpoint (0 to 0) Current Limit Setpoint (0 to 00) Leaving Chill Water Setpoint (- to ) BO Chiller Start/Stop 0-stop, -start Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. Continued on next page... Metasys Integrator Metasys Integrator York Application
NPT (Cont.) BD BD NPA Unit Description 0 0 Hour Volt kw MWh Volts Amps Hz kva Deg Deg Hz Network Point Type Network Point Address Anti-Recycle Timer Operational Mode Operational Safety Cycling Runtime Hours Number of Starts Adaptive Capacity Control Frozen Delta p/p VSD Output Voltage VSD Input kw VSD Input MWh VSD DC Link Voltage VSD DC link Current VSD Surge Count VSD Output Frequency VSD Maximum Voltage THD VSD Maximum Current TDD VSD Input kva VSD Internal Temperature VSD Converter Heatsink Temperature ACC PRV Position ACC Frozen Output Frequency Refrigerant Level Setpoint VSD IEEE Filter Present 0-Not Installed Surge Detection Type 0-Delta_p/p, -Current Metasys Integrator Metasys Integrator York Application
YS -00 Ton Rotary Screw Chiller To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Discharge Temperature point is. Table : YS -00 Ton Rotary Screw Chiller (Translator and XL Configuration) NPT NPA Unit Description 0 0 * * Amperes Amperes Amperes Volt Volt Volt FLA DegC Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Evaporator Saturation Temperature Condenser Saturation Temperature Discharge Temperature Oil Temperature Evaporator Pressure Condenser Pressure Oil Differential Pressure Filter Differential Pressure Full Load Amperes Phase A Amperes Phase B Amperes Phase C Amperes Phase A-B Volts Phase B-C Volts Phase C-A Volts Leaving Water Temperature Actual Setpoint Current Actual Setpoint Feedback Compressor 0-open, -made Oil Solenoid 0-open, -made Chill Water Pump 0-open, -made Start Switch 0-open, -made Flow Switch 0-open, -made Eductor Solenoid 0-open, -made Separator Solenoid 0-open, -made Leaving Chill Water Setpoint (0 to 0) Current Limit Setpoint (0 to 00) Leaving Chill Water Setpoint (- to ) BO Chiller Start/Stop 0-stop, -start Hour Anti-Recycle Timer Operational Mode Operational Safety Cycling Runtime Hours Number of Starts Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. 0 Metasys Integrator Metasys Integrator York Application
LS 000-0 Ton Rotary Screw Chiller To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Discharge Temperature point is. Table : LS 000-0 Ton Rotary Screw Chiller (Translator and XL Configuration) NPT NPA Unit Description 0 * * FLA DegC Leaving Chill Water Temperature Suction Temperature Discharge Temperature Oil Temperature Separator Temperature Evaporator Pressure Condenser Pressure Oil Pressure Filter Pressure Full Load Amperes Slide Valve Liquid Level Vapor Pressure Ratio Leaving Water Temperature Actual Setpoint Current Actual Setpoint Feedback Heater 0-open, -made Oil Pump 0-open, -made Separator Switch 0-open, -made Compressor 0-open, -made Leaving Chill Water Setpoint ( to 0) Current Limit Setpoint (0 to 00) Leaving Chill Water Setpoint ( to 0) BO Chiller Start/Stop 0-stop, -start Anti-Recycle Timer Compressor Mode Slide Mode Operational Safety Cycling Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. Metasys Integrator Metasys Integrator York Application
YP Absorption Chiller To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Purge Tank Pressure point is. Table : YP Absorption Chiller (Translator and XL Configuration) NPT NPA Unit Description 0 0 * * * * DegC DegC Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Leaving Hot Water Temperature Entering Hot Water Temperature First Gen Temperature First Gen Temperature Refrigerant Temperature Solution Temperature First Gen Pressure First Gen Pressure Purge Pump Pressure Purge Tank Pressure Leaving Water Temperature Actual Setpoint Leaving Hot Water Temperature Actual Setpoint Remote Loading Setpoint Feedback Refrigerant Pump 0-open, -made Condenser Pump 0-open, -made Chill Water Pump 0-open, -made Start Switch 0-open, -made Hot Water Pump 0-open, -made Solution Pump 0-open, -made Solution Pump 0-open, -made Purge Pump 0-open, -made Chill Water Flow Switch 0-open, -made Hot Water Flow Switch 0-open, -made Condenser Water Flow Switch 0-open, -made Leaving Chill Water Setpoint ( to ) Hot Water Setpoint (0 to ) Leaving Chill Water Setpoint ( to ) Hot Water Setpoint ( to ) BO Chiller Start/Stop 0-stop, -start Network Point Type Network Point Address Continued on next page... Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description 0 Mode Hour Operational Mode Operational Safety Shutdown Cycling Shutdown Accumulated Operating Hours Accumulated System Starts Lifetime Purge Count Max Loading Seven Day Purge Total Pulldown utes Setpoint Pulldown utes Left Pulldown Loading Start Setpoint Pulldown Loading Stop Setpoint Present Calculated Pulldown Loading Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. The same is true for points and. Metasys Integrator Metasys Integrator York Application
C U.S. Reciprocating Intelligent Chiller - Master To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is. Table 0: C U.S. Reciprocating Intelligent Chiller - Master (Translator and XL Configuration) NPT NPA Unit Description 0 0 FLA FLA Network Point Type Network Point Address Continued on next page... Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Outdoor Air Temperature Compressor Suction Pressure Compressor Discharge Pressure Compressor Oil Pressure Compressor Full Load Amperes Compressor Suction Pressure Compressor Discharge Pressure Compressor Oil Pressure Compressor Full Load Amperes Leaving Chill Water Setpoint Feedback Low Water Temperature Cutout Feedback Low Ambient Cutout Feedback High Ambient Cutout Feedback Low Pressure Cutout Feedback High Pressure Cutout Feedback Remote Temperature Setpoint Remote Cooling Range Local Barrel Setpoint Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description 0 0 * * FLA DegC Chiller Run 0-open, -made Chiller Alarm 0-open, -made Evaporator Heater 0-open, -made Evaporator Pump Starter 0-open, -made Condenser Pump Starter 0-open, -made Load Permissive 0-open, -made Comp Liquid Line Valve 0-open, -made Comp Hot Gas Bypass Valve 0-open, -made Comp Condenser Fan Reverse 0-open, -made Comp Liquid Line Valve 0-open, -made Comp Hot Gas Bypass Valve 0-open, -made Comp Condenser Fan Reverse 0-open, -made Sw (0-Comfort Cooling, -Brine) Sw (0-Standard Ambient, -Low Ambient) Sw (0-Local, -Remote) Sw (0-RWT Control, -LWT Control) Sw (0-English Units, -Metric Units) Sw (0-Standard Fan Control, -Shared Fan Control) Sw (0-Manual Lead/Lag, -Auto Lead/Lag) Sw (0- Ambient Pressure Control, - Discharge Pressure Control) Leaving Chill Water Setpoint (0 to 0) Load Limit Setpoint (0 to 00) Leaving Chill Water Setpoint (- to ) BO Chiller Start/Stop 0-stop, -start Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. Continued on next page... Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description Hour Sec Compressor : Operational Fault Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Compressor : 0 Hour Sec Operational Fault Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Network Point Type Network Point Address Master Anti-Coincidence Timer Load Steps Available Lead Compressor Metasys Integrator Metasys Integrator York Application
C U.S. Reciprocating Intelligent Chiller - Slave To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Mixed Chill Water Temperature point is. Table : C U.S. Reciprocating Intelligent Chiller - Slave (Translator and XL Configuration) NPT NPA Unit Description 0 0 0 FLA FLA Network Point Type Network Point Address Continued on next page... Leaving Chill Water Temperature Entering Chill Water Temperature Mixed Chill Water Temperature Outdoor Air Temperature Compressor Suction Pressure Compressor Discharge Pressure Compressor Oil Pressure Compressor Full Load Amperes Compressor Suction Pressure Compressor Discharge Pressure Compressor Oil Pressure Compressor Full Load Amperes Leaving Chill Water Setpoint Feedback Low Water Temperature Cutout Feedback Low Ambient Cutout Feedback High Ambient Cutout Feedback Low-Pressure Cutout Feedback High-Pressure Cutout Feedback Remote Temperature Setpoint Remote Cooling Range Local Barrel Setpoint Chiller Run Chiller Alarm Evaporator Heater Evaporator Pump Starter Condenser Pump Starter Comp Liquid Line Valve Comp Hot Gas Bypass Valve Comp Pressure Equalization Valve Comp Condenser Reversing Valve Comp Liquid Line Valve Comp Hot Gas Bypass Valve Comp Pressure Equalization Valve Comp Condenser Reversing Valve Load Permissive 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description hrs Sec Compressor : Operational Fault Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Compressor : 0 Hour Sec Operational Fault Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Network Point Type Network Point Address Slave Anti-Coincidence Timer Load Steps Available Lead Compressor Metasys Integrator Metasys Integrator York Application
B U.K. Basildon Reciprocating Intelligent Chiller - Master To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is. Table : B U.K. Basildon Reciprocating Intelligent Chiller - Master (Translator and XL Configuration) NPT NPA Unit Description 0 0 0 0 FLA FLA Network Point Type Network Point Address Continued on next page... Leaving Chill Water Temperature Leaving Condenser Water Temperature Outdoor Air Temperature Compressor Oil Temperature Compressor Oil Pressure Compressor Suction Pressure Compressor Discharge Pressure Compressor Full Load Amperes Compressor Oil Temperature Compressor Oil Pressure Compressor Suction Pressure Compressor Discharge Pressure Compressor Full Load Amperes Leaving Chill Water Setpoint Feedback Low Water Temperature Cutout Feedback Low Ambient Cutout Feedback High Ambient Cutout Feedback Low Pressure Cutout Feedback High Pressure Cutout Feedback Remote Temperature Setpoint Remote Cooling Range Local Barrel Setpoint Chiller Run 0-open, -made Chiller Alarm 0-open, -made Evaporator Heater 0-open, -made Evaporator Pump Starter 0-open, -made Condenser Pump Starter 0-open, -made Load Permissive 0-open, -made Comp Liquid Line Valve 0-open, -made Comp Hot Gas Bypass Valve 0-open, -made Comp Pressure Equalization Valve 0-open, -made Comp Liquid Line Valve 0-open, -made Comp Hot Gas Bypass Valve 0-open, -made Comp Pressure Equalization Valve 0-open, -made Sw (0-Water Cooling, -Brine) Sw (0-Stand Ambient, -Low Ambient) Sw (0-Local, -Remote) Sw (0-Star/Delta, -Part Wind) Sw (0-English Units, -Metric units) Sw (0-Comm Enable, -Comm Disable) Sw (0-Manual Lead/Lag, -Auto Lead/Lag) Sw (0-RA Refrigerant, -R) Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description * * FLA DegC Leaving Chill Water Setpoint (0 to 0) Load Limit Setpoint (0 to 00) Leaving Chill Water Setpoint (- to ) BO Chiller Start/Stop 0-stop, -start Mode Hour Sec Compressor : Operational Fault Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Compressor : 0 Hour Sec Operational Fault Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Master Panel Anti-Coincidence Timer Load Steps Available Lead Compressor Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. 0 Metasys Integrator Metasys Integrator York Application
B U.K. Basildon Reciprocating Intelligent Chiller - Slave To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is. Table : B U.K. Basildon Reciprocating Intelligent Chiller - Slave (Translator and XL Configuration) NPT NPA Unit Description 0 0 0 FLA FLA Network Point Type Network Point Address Continued on next page... Leaving Chill Water Temperature Mixed Chill Water Temperature Outdoor Air Temperature Compressor Oil Temperature Compressor Oil Pressure Compressor Suction Pressure Compressor Discharge Pressure Compressor Full Load Amperes Compressor Oil Temperature Compressor Oil Pressure Compressor Suction Pressure Compressor Discharge Pressure Compressor Full Load Amperes Leaving Chill Water Setpoint Feedback Low Water Temperature Cutout Feedback Low Ambient Cutout Feedback High Ambient Cutout Feedback Low Pressure Cutout Feedback High Pressure Cutout Feedback Remote Temperature Setpoint Remote Cooling Range Local Barrel Setpoint Chiller Run Chiller Alarm Evaporator Heater Evaporator Pump Starter Condenser Pump Starter Comp Liquid Line Valve Comp Hot Gas Bypass Valve Comp Pressure Equalization Valve Comp Condenser Reversing Valve Comp Liquid Line Valve Comp Hot Gas Bypass Valve Comp Pressure Equalization Valve Comp Condenser Reversing Valve Load Permissive 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made 0-open, -made Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description Hour Sec Compressor : Operational Fault Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Compressor : 0 Hour Sec Operational Fault Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Network Point Type Network Point Address Slave Panel Anti-Coincidence Timer Load Steps Available Lead Compressor Metasys Integrator Metasys Integrator York Application
YR Sunline 000 Rooftop Chiller To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Building Air Pressure point is. Table : YR Sunline 000 Rooftop Chiller (Translator and XL Configuration) NPT NPA Unit Description 0 0 0 Hour Hour Network Point Type Network Point Address Continued on next page... Space Temperature Discharge Air Temperature Return Air Temperature Outside Air Temperature Duct Static Pressure Building Air Pressure Outside Air Damper Position 0-00 Heating Coil Valve Position 0-00 Supply Fan Run Hours Exhaust Fan Run Hours Supply Fan Inlet Guide Vane Position 0-00 Exhaust Fan Inlet Guide Vane Position 0-00 Compressor Oil Pressure Compressor Suction Pressure Compressor Discharge Pressure Compressor Oil Pressure Compressor Suction Pressure Compressor Discharge Pressure Low Ambient Cutout High Ambient Cutout Low Pressure Cutout High Pressure Cutout Discharge Air Temperature Cutout Unit Run Permissive 0-open, -made Air Handling Unit Alarm 0-open, -made Local/Remote Selected 0-local, -remote Supply Fan Run 0-open, -made Return (Exhaust) Fan Run 0-open, -made OA/RA Selected 0-OA, -RA Refrigeration System Locked Out 0-open, -made Compressor Contractor 0-open, -made System Liquid Line Solenoid Valve 0-open, -made Compressor Unloader Solenoid Valve 0-open, -made Compressor Unloader Solenoid Valve 0-open, -made Compressor Hot Gas Bypass Sol. Valve 0-open, -made Refrigeration System Locked Out 0-open, -made Compressor Contractor 0-open, -made System Liquid Line Solenoid Valve 0-open, -made Compressor Unloader Solenoid Valve 0-open, -made Compressor Unloader Solenoid Valve 0-open, -made Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description * * DegC Return Air Setpoint (0, 0) 0=Vent, =Heating, =Cooling, =Local Setpoints Return Air Setpoint (- to ) BO Start/Stop Command 0-stop, -start 0 Hour Hour Anti-Coincidence Timer Compressor Run Hours Compressor Anti-Recycle Timer Compressor No. of Operating Stages Compressor Run Hours Compressor Anti-Recycle Timer Compressor No. of Operating Stages Air Handling Unit Shutdown Compressor Operational Compressor Fault Compressor Operational Compressor Fault Number of Condenser Fans Running Cooling Load Steps Available Actual Heating Setpoint Actual Cooling Setpoint Actual Discharge Air Temperature Setpoint Actual Static Pressure Setpoint Actual Building Pressure Setpoint Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. Metasys Integrator Metasys Integrator York Application
A Air-cooled Screw Chiller - Master To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is. Table : A Air-cooled Screw Chiller - Master (XL Configuration only) NPT NPA Unit Description 0 0 0 FLA FLA Network Point Type Network Point Address Continued on next page... Leaving Chill Water Temperature Entering Chill Water Temperature Mixed Chill Water Temperature Compressor Suction Temperature Compressor Discharge Temperature Compressor Saturated Suction Temperature Compressor Saturated Discharge Temperature Compressor Oil Temperature Compressor Suction Temperature Compressor Discharge Temperature Compressor Saturated Suction Temperature Compressor Saturated Discharge Temperature Compressor Oil Temperature Outdoor Air Temperature Compressor Suction Pressure Compressor Discharge Pressure Compressor Oil Pressure Compressor Full Load Amperes Compressor Suction Pressure Compressor Discharge Pressure Compressor Oil Pressure Compressor Full Load Amperes Compressor SVCALC Compressor SVCALC Leaving Chill Water Setpoint Low Water Temperature Cutout Low Ambient Temperature Cutout High Ambient Temperature Cutout Low Pressure Cutout High Pressure Cutout Remote Temperature Setpoint Local Cooler Barrel Setpoint Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description 0 * * FLA DegC Chiller Run 0-open, -made Chiller Alarm 0-open, -made Evaporator Heater 0-open, -made Evaporator Pump Starter 0-open, -made Comp Liquid Line Solenoid Valve 0-open, -made Comp Condenser Fan Reverse 0-open, -made Comp Liquid Line Solenoid Valve 0-open, -made Comp Condenser Fan Reverse 0-open, -made Switch (0=Comfort Cooling, =Brine Cooling) Switch (0=Standard Ambient, =Low Ambient) Switch (0=Local, =Remote) Switch (0=eev, =Thermal Expansion Valves) Switch (0=English Units, =Metric Units) Switch (0=x-Line Start, =wye delta start) Switch (0=Manual Lead/Lag, =Auto Lead/Lag) Switch (0=Ra, =R) Load Permissive 0-open, -made Leaving Chill Water Setpoint (0 to 0) Load Limit Setpoint (0 to 00) Leaving Chill Water Setpoint (- to ) BO Chiller Start/Stop 0-stop, -start Hour Compressor : Operational Fault Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Compressor : Operational Fault Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts 0 Hour Master Anti-Coincidence Timer Lead Compressor Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. Metasys Integrator Metasys Integrator York Application
A Air-cooled Screw Chiller - Slave To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is. Table : A Air-cooled Screw Chiller - Slave (XL Configuration only) NPT NPA Unit Description 0 0 0 FLA FLA Network Point Type Network Point Address Continued on next page... Leaving Chill Water Temperature Entering Chill Water Temperature Mixed Chill Water Temperature Compressor Suction Temperature Compressor Discharge Temperature Compressor Saturated Suction Temperature Compressor Saturated Discharge Temperature Compressor Oil Temperature Compressor Suction Temperature Compressor Discharge Temperature Compressor Saturated Suction Temperature Compressor Saturated Discharge Temperature Compressor Oil Temperature Outdoor Air Temperature Compressor Suction Pressure Compressor Discharge Pressure Compressor Oil Pressure Compressor Full Load Amperes Compressor Suction Pressure Compressor Discharge Pressure Compressor Oil Pressure Compressor Full Load Amperes Compressor SVCALC Compressor SVCALC Leaving Chill Water Setpoint Low Water Temperature Cutout Low Ambient Temperature Cutout High Ambient Temperature Cutout Low Pressure Cutout High Pressure Cutout Remote Temperature Setpoint Local Cooler Barrel Setpoint Chiller Run 0-open, -made Chiller Alarm 0-open, -made Evaporator Heater 0-open, -made Evaporator Pump Starter 0-open, -made Comp Liquid Line Solenoid Valve 0-open, -made Comp Condenser Fan Reverse 0-open, -made Comp Liquid Line Solenoid Valve 0-open, -made Comp Condenser Fan Reverse 0-open, -made Load Permissive 0-open, -made Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description Hour Compressor : Operational Fault Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Compressor : 0 Hour Operational Fault Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Network Point Type Network Point Address Master Anti-Coincidence Timer Lead Compressor Metasys Integrator Metasys Integrator York Application
YI Isoflow Absorption Chiller To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Refrigerant Temperature point is. Table : YI Isoflow Absorption Chiller (XL Configuration only) NPT NPA Unit Description 0 0 Network Point Type Network Point Address Continued on next page... Leaving Chilled Water Temperature Entering Chilled Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Automatic Decrystallization Temperature Refrigerant Temperature Leaving the Condenser Steam/Hot Water Supply Temperature Refrigerant Temperature Strong Solution Temperature Generator Shell Pressure Steam Supply Pressure (Steam Units Only) Steam/Hot Water Actuator Value Position (0-00) Local Leaving Chilled Water Setpoint Purge Pump Service Interval Setpoint - Hours Active Leaving Chilled Water Setpoint Remote Loading Setpoint Maximum Steam/Hot Water Valve Load Setpoint Pulldown Demand Setpoint - utes Pulldown Demand Setpoint -Start Load Limit Pulldown Demand Setpoint -Stop Load Limit Remote Temperature Range Setpoint Maximum Entering Condenser Water Temperature Setpoint Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description 0 0 * * DegC Chilled Water Pump Status 0-Off, -On Condenser Water Pump Status 0-Off, -On Refrigerant Pump Motor Status 0-Off, -On Solution/Absorber Pump Motor Status 0-Off, -On Purge Pump Motor Status 0-Off, -On Generator Pump Motor Status 0-Off, -On Refrigerant and Solution Pump Motor 0-Off, -On Coolant Solenoid Valve Status Refrigerant Stabilizer Solenoid Valve 0-Off, -On Status Refrigerant Level Solenoid Valve 0-Off, -On Status Chilled Water Flow Switch Status 0-Open, -Closed Condenser Water Flow Switch Status 0-Open, -Closed Refrigerant Level Float Switch Status 0-Open, -Closed Unit Switch Status 0-Stop, -Run J0 Status 0-AutoRe, -Manual J Status 0-LOA, -No_LOA J Status 0-Englsh, -Metric J Status 0-Limitd, -FullCn J Status 0-DiagEn, -DiaDis J Status 0-RTCDis, -RTCEnb J Status(Expansion I/O Board) 0-Englsh -German Dilution Cycle Status 0-Open, -Made Low Entering Condenser Water 0-No, -Yes Temp Limit Active Automatic Decrystallization Active 0-No, -Yes Remote Load Limiting Active 0-No, -Yes Pulldown Limiting Active 0-No, -Yes Leaving Chill Water Setpoint (0 to 0) Leaving Chill Water Setpoint (- to ) BO Chiller Start/Stop 0-Stop, -Start Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. Continued on next page... 0 Metasys Integrator Metasys Integrator York Application
NPT (Cont.) BD BD BD NPA Unit Description 0 Mode Hour Network Point Type Network Point Address Operational Mode (0-Service, -Local, -Remote) Operational Safety Shutdown Cycling Shutdown Warning Message Total Operating Hours Total System Starts Lifetime Purge Count Weekly Purge Counter Pulldown Demand - utes Left Pulldown Demand - Present Limit Dilution Cycle Maximum Steam/Hot Water Valve Unload Setpoint JP Status 0-Steam, -Hwater JP Status 0-Stndrd, -0Hz JP (Expansion I/O Board) 0-Rotary, -Cage Metasys Integrator Metasys Integrator York Application
YG Gas Engine Drive Chiller To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Engine Speed point is. Table : YG Gas Engine Drive Chiller (XL Configuration only) NPT NPA Unit Description 0 0 * * rpm mils mils rpm FLA DegC Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Evaporator Saturation Temperature Condenser Saturation Temperature Discharge Temperature Oil Temperature Evaporator Pressure Condenser Pressure Oil Differential Pressure Percent Engine Load Percent Vanes Open Engine Jacket Water Temperature Engine Speed Engine Oil Pressure Engine Manifold Pressure Low Oil Transducer Pressure High Oil Transducer Pressure Leaving Water Temperature Actual Setpoint Remote/Local Actual Engine Load Setpoint Proximity Sensor - Actual Position Proximity Sensor - Reference Position Drain Line Thermocouple Temperature Delta P over P Surface Speed Engine Panel Shutdown Status 0-open, -made Vent Valve Status 0-open, -made Chilled Water Pump Status 0-open, -made Start Switch Status 0-open, -made Chilled Water Flow Switch Status 0-open, -made Leaving Chill Water Setpoint (0 to 0) Demand Limit Setpoint (0 to 00) Leaving Chill Water Setpoint (- to ) BO Chiller Start/Stop 0-stop, -start Network Point Type Network Point Address * Points and are the same point and will have the same value. Two points are provided because of the different ranges for and DegC. Continued on next page... Metasys Integrator Metasys Integrator York Application
NPT (Cont.) NPA Unit Description Hour Anti-Recycle Time Left Operating Mode Operation Safety Shutdown Cycling Shutdown Accumulated Operating Hours Accumulated System Starts ADI Engine Type 0-G0, -G, -G0, -G, -G, -G0 Network Point Type Network Point Address Metasys Integrator Metasys Integrator York Application
Metasys Integrator Metasys Integrator York Application
Metasys Network Setup Metasys Network setup is described in the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN.). This section contains details specific to York applications. Mapping to a CS Object Table : Software Model and CS Object Details Application Software Model (on Tables and Models CD-ROM) Display Attribute (recommended) NT Command Attribute (recommended) Login YK_TRAN.DDL * YT Chiller YK_YTCH.DDL BO YK Chiller YK_YKCH.DDL BO YS Chiller YK_YSCH.DDL BO LS Chiller YK_LSCH.DDL BO YP Chiller YK_YPCH.DDL BO C Chiller YK_CCH.DDL BO C Chiller YK_CCH.DDL * B Chiller YK_BCH.DDL BO B Chiller YK_BCH.DDL * YR Chiller YK_S000.DDL BO A Chiller YK_AXL.DDL BO A Chiller YK_AXL.DDL * YI Chiller YK_YIXL.DDL BO YG Chiller YK_YGXL.DDL BO * The NT Command attribute must be defined; it cannot be null. However, since the points are not commandable, you will not be able to command the attribute. Metasys Integrator Metasys Integrator York Application
Metasys Integrator Metasys Integrator York Application
Custom Integration For information on integrating products that are not discussed in this document, first refer to the Metasys Compatible Global Catalog, an online list of released Connectivity products. If this list does not provide the information you require, consider using the System Integration Project Data Sheet to request a custom contract from the System Integration Team. Both the Metasys Compatible Global Catalog and the System Integration Project Data Sheet can be accessed from The Advisor by performing the following steps:. Click on the Systems Products button located on the left side of The Advisor home page.. Click on the Product Literature link.. Click on the Manuals-FANS link.. Click on the.0 Metasys Connectivity Sales Resource Manual link.. Find the System Integration Project Data Sheet link in the table of contents. Click on this link to view an online copy of the System Integration Project Data Sheet, or click on the Metasys Compatible Global Catalog link below it to view a list of released Connectivity products. The System Integration Project Data Sheet (LIT-00) also can be found in the Metasys Connectivity Sales Resource Manual (FAN ). If you need further assistance, contact Johnson Controls Field Support Center. Metasys Integrator Metasys Integrator York Application
Notes www.johnsoncontrols.com Controls Group FAN. 0 E. Michigan Street Metasys Connectivity Technical Manual P.O. Box Metasys Integrator Release.0 Milwaukee, WI 0 Printed in U.S.A. Metasys Integrator Metasys Integrator York Application