SUBMITTAL M4MCW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

Similar documents
SUBMITTAL M4MCW1509A-SUB-1C. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

SUBMITTAL M4MHW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MHW1509A1N0A M4THS1509A11NA TAG:

SUBMITTAL M4MLW1809A-SUB-1A. Specifications 18 SERIES. Single Zone Mini-Split Inverter System M4MLW1809A1N0A M4TLS1809A11NA TAG:

READ ONLY. American Standard Ductless Systems Product Catalog. A Comfortable, Convenient Solution Built To A Higher Standard.

TECHNICAL GUIDE MODELS: DCPM/DHPM PREMIUM SERIES DUCTLESS SINGLE-SPLIT AIR CONDITIONERS AND HEAT PUMPS 22 SEER 1 PHASE 3/4 THRU 3 NOMINAL TONS

Product Data Split System (R-410A) Air Handler for Multi Split Inverter System 9,000 to 24,000 BTU/Hr

Submittal Sheet AIR-CON MULTI-SPLIT II. High-Wall Cassette Duct Floor and Ceiling AMTCM4H4R18

Specifications. (Model) KSIB009-H /2500 (W) 10600/9000(Btu/h) 13000/9500(Btu/h) 1250/ / SEER 16 HSPF 9.

TECHNICAL GUIDE MODELS: DCMF/DHMF LX SERIES DUCTLESS SINGLE-SPLIT AIR CONDITIONERS AND HEAT PUMPS 16 SEER 1 PHASE 3/4 THRU 2 NOMINAL TONS DESCRIPTION

Thank you for selecting LENNOX air conditioners.

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To

Submittal. Split System Cooling 4A7A6024J-SUB-1B-EN. January A7A6024J1000B TAG:

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To

Commercial High-Efficiency Condensing Units

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

SUBMITTAL DATA - OUTDOOR UNIT VEP075N432G VRF HEAT PUMP

Submittal. 5 Ton Convertible Air Handler TEM3A0C60S51SA TEM3A0C60-SUB-1C-EN. July 2014 TAG:

Submittal. Split System Cooling 5.0 Ton 4A7A3060D1000P TAG:

15A Operating Range Communication Wire Size 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

Submittal Data: UMAT48HP230V1AF. Job Name Location Date. Submitted To

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Commercial High-Efficiency Condensing Units

Variable Speed Convertible Air Handler 5 Ton

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Variable Speed Convertible Air Handler 2 1/2 Ton

Variable Speed Convertible Air Handler 4 Ton

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

Submittal. 1 1/2 Ton Convertible Air Handler TEM3A0B18S21SA TEM3A0B18-SUB-1C-EN. July 2014 TAG:

Submittal. 2 Ton Convertible Air Handler TEM3A0B24S21SA TEM3A0B24-SUB-1C-EN. July 2014 TAG:

Innovative Ductless Mini Split Solution Submittal Data: GUHD24ND3FO/GKH24D3FI Job Name Location Date

MAC-120HE-03 Air-Cooled Chiller

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

13 SEER CONDENSING UNITS & AIR HANDLERS

Product Data. Split System Heat Pump B-EN. February A6H6024H1000A

Klimaire 16 SEER CENTRAL DUCTED YEAR. Central Air Conditioning & Heat Pump Systems Multi Position Air Handling Units LIMITED GUARANTEE

15A 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

PACKAGE AIR CONDITIONER

Condensing Units & Air Handlers

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MACH N-407 Heat Pump Air-Cooled Chiller

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

Samsung 360 Cassette, Single Zone, Split System

18-2 AWG / 300V THHN Operating Range MCA 2.0A Cooling (Max) 118 F (48 C) MOCP/Breaker Size 15A (Min) 0 F (-18 C)

Product Data. Split System Heat Pump D-EN. February 2016

TECHNICAL SPECIFICATIONS

PAJ3. Product Specifications

Power Input (Max) 1,500 W Dehumidification 1.7 pt/hr HSPF 10.5 COP 4.2 Compressor Type DC Inverter Driven 2-Stage Rotary Heating at 17 F FLA 8.

Submittal Data Sheet

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control...

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

Product Data. Split System Heat Pump A-EN. March 2016

MHH. 13 SEER High Efficiency R410a. SPECIFICATION sheet

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz Technical Manual

MAC N-407 Air-Cooled Chiller

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

Submittal. Date: January 8, Customer P.O. Number: Customer Project Number: CARROLLTON, TX 75006

Lennox 8 Series Single Zone - R-410A

Specifications and Performance S2H

Product Data. Features/Benefits All in one package cooling efficiency, installation convenience and ease of accessibility allow for timesaving

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

16 SEER TWO-STAGE AIR CONDITIONERS

Product Data. Split System Cooling D-EN. August 2016

Technical Product Guide

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Advance Product Data

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

Product Data. Split System Cooling A. November 2013

Advance Product Data

PAR5. Product Specifications

Product Data. Split System Cooling H-EN. January 2017

1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series

RSG16**S1M. Split System Air Conditioner 16 SEER

Product Data. Split System Cooling E-EN. November 2016

Service Manual. Models WAH48115MB WAH412230MB WH48YMB WH412ZMB

Product Data INDUSTRY LEADING FEATURES / BENEFITS

Product Data. Fig. 1 - Unit 50VR -A

13 SEER CONDENSING UNITS

Specifications, Performance & Submittal

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Product Data. 38GJQ MULTI-ZONE DUCTLESS SYSTEM MATCHED WITH 40GRQ / 40GJB / 40GJC / 40GJD / 40GJF Indoor Units Sizes 18, 24, 30, 36, 42, 48 and 56

WJH4 Product Specifications

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

Market District Commons. Black Oak Engineering. Daikin Ductless Heat Pump Split Systems N/A N/A M001. Plans. Fujitsu ductless heat pump systems

R4H4. Product Specifications

TECHNICAL GUIDE MODELS: INDOOR-DHPM/OUTDDOR-DHMF LX SERIES DUCTLESS MULTI-ZONE SPLIT HEAT PUMPS 16 SEER 1 PHASE 1.5 THRU 3.5 NOMINAL TONS DESCRIPTION

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

Ruud Achiever Series Dedicated Horizontal Package Heat Pump

Ruud Achiever Series Dedicated Horizontal Package Heat Pump

Unit Data - RCA 051 RATED IN ACCORDANCE TO AHRI STANDARD

Transcription:

M4MCW1509A-SUB-1B TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA MODEL - Cooling Only RATED Volts/PH Frequency (Hz) Rated Cooling Capacity (Btu/h): Minimum Cooling Capacity (@95F) (Btu/h): Maximum Cooling Capacity (@95F) (Btu/h): Total Capacity (W) (High/Standard/Low): Rated Power Input (W) Nominal Input Current (A) SEER Air Flow Volume (CFM) (H/M/L) Dehumidifying Volume (pt./h) EER (@95F) Indoor Unit Fan Motor Speed (r/min) (SH/H/M/L) Fan Motor RLA(A) Evaporator Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (D) x coil width (W) (inch) Output of Swing Motor (W) Fuse (A) Sound Power Level db (A)(SH/H/M/L) Sound PRESSURE Level db (A)(SH/H/M/L) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Outdoor Unit Compressor Type Compressor Oil L.R.A. (A) Compressor RLA(A) Compressor Power Input(W) Throttling Method Working Temp Range ( F) Condenser Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (H) x coil width (W) (inch) Fan Motor Speed (rpm) Output of Fan Motor (W) Fan Motor RLA (A) Air Flow Volume of Outdoor Unit (CFM) Fan Diameter (inch) Defrosting Method Sound Power Level db (A) Sound PRESSURE Level db (A) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Refrigerant Charge (oz) MCA MOP Connection Pipe Gas additional charge(oz/ft) Outer Diameter Liquid Pipe (inch) Outer Diameter Gas Pipe (inch) Max Height Distance (ft) Max Length Distance (ft) M4MCW1509A / M4TCS1509A 208 / 230 / 1 60Hz 9000 3100 9600 2800 / 2600 / 900 900 4.0 15.0 310 / 280 / 240 / 170 1.69 10.0 M4MCW1509A1N0A 1350 / 1200 / 1050 / 750 0.20 Aluminum Fin-Copper Tube 1/5 2-1/18 23 7/8 10 1/2 1.5 3.15 53 / 49 / 45 / 39 43 / 38 / 34 / 28 31 1/9 x 10 5/6 x 7 7/8 34 x 10 2/3 x 14 4/9 19.8 / 24.2 M4TCS1509A11NA Swing Rotary DAPHNE FVC50K (PVE Oil) 16.5 6.60 845 Capillary 0-115 Aluminum Fin-Copper Tube 2/7 1-1/18 28 3/4 20 820±20 30 0.37 942 15 3/4 Automatic Defrosting 62 52 30 5/9 x 21 1/4 x 12 3/5 33 1/2 x 14 2/7 x 23 3/7 66.2 / 71.7 24.7 9.0 15.0 0.2 1/4 3/8 65 100 2017 Ingersoll Rand All Rights Reserved 1 Sound PRESSURE Level @ 3.3 ft. db(a)

Unit Dimensions W D H 6 5/8 18 3/16 6 5/16 9K 09K Φ2 3/16 Φ2 3/16 2 1/8 2 1/8 6 3 1/2 Unit: inch MODEL W H D 09K 31 1/8 10 5/6 7 7/8 12K 33 1/4 11 3/8 8 1/4 10 1/8 28 21 1/4 12 3/5 30 9/16 11 1/4 20

Clearance Requirements Space to the ceiling 6 in. 6 in. 6 in. 118 in. Air outlet side 66 in. Space to the floor The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent structures Space to the obstruction 12 in. Space to the wal l 9 7 in. 20 in. Air inlet side 12 in. 20 in. Air outlet side valve cover NOTE: The maximum recommended height from the floor to the bottom of the indoor unit is 11.5 ft. (3.5 m). Air Velocity Patterns for High Wall Max Horizontal Distance Unit: ft. (m) Model Cooling Mode Heating Mode M4MCW1509A 13.1 (4) N/A

Performance Data Cooling Capacity 9,000 (Bthu/h) M4MCW1509A1/M4TCS1509A Outdoor 68F DB (20C) 73F DB (23C) 80F DB (27C) 82F DB (28C) Coil air 57F WB (14C) 61F WB (16C) 67F WB (19C) 68F WB (20C) DB F DB C TC SHC TC SHC TC SHC TC SHC 0 18 4400 3550 4750 3750 5250 4250 5600 4400 5 15 4900 3900 5100 4050 5800 4600 5950 4750 14 10 5600 4400 5950 4750 6800 5450 6950 5600 23 5 6100 4900 6650 5250 7650 6100 8000 6450 32 0 6450 5100 6800 5450 7650 6100 8000 6300 41 5 6650 5250 6950 5600 8000 6300 8350 6650 50 10 6950 5450 7300 5800 8350 6650 8700 6800 59 15 7500 6100 8000 6450 8850 7150 9700 7800 68 20 8500 6950 9000 7500 9700 8000 10400 8500 77 25 8500 6950 9000 7300 9550 7800 10200 8350 86 30 8000 6650 8500 7150 9350 7650 10050 8350 95 35 7650 6300 8150 6800 8850 7500 9700 8150 104 40 7150 6100 7650 6450 8700 7300 9350 7800 113 45 6800 5800 7300 6300 8350 6950 9000 7650 Capacities in these performance tables reflect normal operation at the temperatures indicated. See specification tables above for certified values under prescribed test conditions.

Mechanical Specifications Mini-Split Outdoor Unit General This unit is fully charged from the factory for up to 25 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115 F. Cooling capacities with the mini-split air handler shown in the catalog are AHRI certified. The unit is ETL listed for outdoor application. Unit Casing The unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Refrigerant Controls Refrigeration system controls include condenser fan and compressor relay. High and low pressure controls are inherent to the compressor. A suction line multi function service valve is standard Compressor The compressor features internal over temperature and pressure protection; total dipped hermetic motor windings. Other features include: centrifugal oil pump and low vibration and noise. Condenser Coil The coil shall consist of aluminum finned coils brazed to copper tubing. The coil provides air flow resistance and efficient heat transfer. The coil is protected by the casing. Low Ambient Cooling Matched Ameristar ductless products, have cooling capabilities at outdoor ambient temperatures as low as 0 F. Mini-Split Indoor High Wall General The High Wall mounted type air handler shall be completely factory assembled including coil, condensate drain pan, fan motor, washable filter, air purifying filter and electric controls to be used with a wireless remote controller. Unit shall be shipped with a unit mounting plate. Unit shall be matched with an Ameristar outdoor unit, rated and tested in accordance with AHRI standard. Unit shall be ETL listed. Unit Casing Casing shall be provided with knockouts on the right, and left of the unit to facilitate piping and electrical connection on either side of the unit. An electrical service cover shall be provided to permit easy access to the electrical terminal strip. Discharge Airflow and Distribution System Unit shall have auto swing, dual horizontal blades to optimize the aperture outlet for vertical airflow and air distribution. Blade shall close automatically when the air conditioner is turned off to minimize dust entering the unit. Five-Step preset program on the remote controller shall be available to control the blade angle. Manually adjusted wide-angle louvers shall be provided to adjust the coverage and direction of airflow. Controls Units shall have the capability to be controlled remotely through wall-mounted wired options (sold separately) as well as a wireless remote option. Remote Controller The unit shall have a wireless infrared remote controller with easy reading digital display panel to start, stop and regulate the air conditioner from a distance. The wireless controller is included with all units. Healthy Filters The unit shall have an active carbon and catechin filter with the unit.the filters need to be cleaned at least once a year. 06/17 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

M4MCW1512A-SUB-1B TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MCW1512A1N0A M4TCS1512A11NA MODEL - Cooling Only RATED Volts/PH Frequency (Hz) Rated Cooling Capacity (Btu/h): Minimum Cooling Capacity (@95F) (Btu/h): Maximum Cooling Capacity (@95F) (Btu/h): Total Capacity (W) (High/Standard/Low): Rated Power Input (W) Nominal Input Current (A) SEER Air Flow Volume (CFM) (H/M/L) Dehumidifying Volume (pt./h) EER (@95F) Indoor Unit Fan Motor Speed (r/min) (SH/H/M/L) Fan Motor RLA(A) Evaporator Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (D) x coil width (W) (inch) Output of Swing Motor (W) Fuse (A) Sound Power Level db (A)(SH/H/M/L) Sound PRESSURE Level db (A)(SH/H/M/L) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Outdoor Unit Compressor Type Compressor Oil L.R.A. (A) Compressor RLA(A) Compressor Power Input(W) Throttling Method Working Temp Range ( F) Condenser Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (H) x coil width (W) (inch) Fan Motor Speed (rpm) Output of Fan Motor (W) Fan Motor RLA (A) Air Flow Volume of Outdoor Unit (CFM) Fan Diameter (inch) Defrosting Method Sound Power Level db (A) Sound PRESSURE Level db (A) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Refrigerant Charge (oz) MCA MOP Connection Pipe Gas additional charge(oz/ft) Outer Diameter Liquid Pipe (inch) Outer Diameter Gas Pipe (inch) Max Height Distance (ft) Max Length Distance (ft) M4MCW1512A / M4TCS1512A 208 / 230 / 1 60Hz 12000 3700 12500 3600 / 3500 / 1100 1300 5.8 15.0 390 / 310 / 240 / 190 2.96 9.25 M4MCW1512A1N0A 1350 / 1200 / 1000 / 800 0.31 Aluminum Fin-Copper Tube 1/5 2-1/18 25 7/8 12 1/16 1.5 3.15 55 / 49 / 45 / 39 45 / 39 / 35 / 29 33 1/4 x 11 3/8 x 8 2/9 36 1/4 x 11 x 15 23.1 / 28.7 M4TCS1512A11NA Swing Rotary DAPHNE FVC50K (PVE Oil) 16.5 6.60 845 Capillary 0-115 Aluminum Fin-Copper Tube 2/7 2-1/18 28 1 1/2 20 820±20 30 0.37 942 15 3/4 Automatic Defrosting 63 53 30 5/9 x 21 1/4 x 12 3/5 33 1/2 x 14 2/7 x 23 3/7 70.6 / 76.1 30.0 9.0 15.0 0.2 1/4 3/8 65 100 2017 Ingersoll Rand All Rights Reserved 1 Sound PRESSURE Level @ 3.3 ft. db(a)

Unit Dimensions W D H 4 11/16 21 5/16 7 1/4 12K 12K Φ2 3/16 Φ2 3/16 1 3/8 1 3/8 5 3 5/16 Unit: inch MODEL W H D 09K 31 1/8 10 5/6 7 7/8 12K 33 1/4 11 3/8 8 1/4 10 1/8 28 21 1/4 12 3/5 30 9/16 11 1/4 20

Clearance Requirements Space to the ceiling 6 in. 6 in. 6 in. 118 in. Air outlet side 66 in. Space to the floor The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent structures Space to the obstruction 12 in. Space to the wal l 9 7 in. 20 in. Air inlet side 12 in. 20 in. Air outlet side valve cover NOTE: The maximum recommended height from the floor to the bottom of the indoor unit is 11.5 ft. (3.5 m). Air Velocity Patterns for High Wall Max Horizontal Distance Unit: ft. (m) Model Cooling Mode Heating Mode M4MCW1512A 29.5 (9) N/A

Performance Data Cooling Capacity 12,000 (Bthu/h) M4MCW1512A1/M4TCS1512A Cooling 12K Outdoor 68F DB (20C) 73F DB (23C) 80F DB (27C) 82F DB (28C) Coil air 57F WB (14C) 61F WB (16C) 67F WB (19C) 68F WB (20C) DB F DB C TC SHC TC SHC TC SHC TC SHC 0 18 5100 4000 5350 4200 6650 5200 6550 5100 5 15 6100 4800 6450 5050 7700 6000 7750 6100 14 10 7650 6000 8100 6350 9150 7150 9500 7450 23 5 7850 6150 8300 6500 9500 7450 9900 7750 32 0 8400 6600 9000 7050 10300 8050 10750 8400 41 5 10200 8000 10900 8550 11950 9350 13050 10200 50 10 11550 9050 12250 9600 13100 10300 14050 11050 59 15 11400 8950 12150 9500 13000 10200 13900 10900 68 20 11150 8700 11850 9300 12850 10100 13700 10750 77 25 10850 8500 11550 9050 12650 9900 13550 10600 86 30 10550 8300 11300 8850 12400 9700 13350 10450 95 35 10250 8050 11000 8600 12050 9450 13150 10300 104 40 9750 7650 10500 8200 11700 9200 12650 9900 113 45 9250 7250 10000 7800 11200 8800 12150 9500 Capacities in these performance tables reflect normal operation at the temperatures indicated. See specification tables above for certified values under prescribed test conditions.

Mechanical Specifications Mini-Split Outdoor Unit General This unit is fully charged from the factory for up to 25 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115 F. Cooling capacities with the mini-split air handler shown in the catalog are AHRI certified. The unit is ETL listed for outdoor application. Unit Casing The unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Refrigerant Controls Refrigeration system controls include condenser fan and compressor relay. High and low pressure controls are inherent to the compressor. A suction line multi function service valve is standard Compressor The compressor features internal over temperature and pressure protection; total dipped hermetic motor windings. Other features include: centrifugal oil pump and low vibration and noise. Condenser Coil The coil shall consist of aluminum finned coils brazed to copper tubing. The coil provides air flow resistance and efficient heat transfer. The coil is protected by the casing. Low Ambient Cooling Matched Ameristar ductless products, have cooling capabilities at outdoor ambient temperatures as low as 0 F. Mini-Split Indoor High Wall General The High Wall mounted type air handler shall be completely factory assembled including coil, condensate drain pan, fan motor, washable filter, air purifying filter and electric controls to be used with a wireless remote controller. Unit shall be shipped with a unit mounting plate. Unit shall be matched with an Ameristar outdoor unit, rated and tested in accordance with AHRI standard. Unit shall be ETL listed. Unit Casing Casing shall be provided with knockouts on the right, and left of the unit to facilitate piping and electrical connection on either side of the unit. An electrical service cover shall be provided to permit easy access to the electrical terminal strip. Discharge Airflow and Distribution System Unit shall have auto swing, dual horizontal blades to optimize the aperture outlet for vertical airflow and air distribution. Blade shall close automatically when the air conditioner is turned off to minimize dust entering the unit. Five-Step preset program on the remote controller shall be available to control the blade angle. Manually adjusted wide-angle louvers shall be provided to adjust the coverage and direction of airflow. Controls Units shall have the capability to be controlled remotely through wall-mounted wired options (sold separately) as well as a wireless remote option. Remote Controller The unit shall have a wireless infrared remote controller with easy reading digital display panel to start, stop and regulate the air conditioner from a distance. The wireless controller is included with all units. Healthy Filters The unit shall have an active carbon and catechin filter with the unit.the filters need to be cleaned at least once a year. 06/17 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

M4MCW1518A-SUB-1B TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MCW1518A1N0A M4TCS1518A11NA MODEL - Cooling Only RATED Volts/PH Frequency (Hz) Rated Cooling Capacity (Btu/h): Minimum Cooling Capacity (@95F) (Btu/h): Maximum Cooling Capacity (@95F) (Btu/h): Total Capacity (W) (High/Standard/Low): Rated Power Input (W) Nominal Input Current (A) SEER Air Flow Volume (CFM) (H/M/L) Dehumidifying Volume (pt./h) EER (@95F) Indoor Unit Fan Motor Speed (r/min) (SH/H/M/L) Fan Motor RLA(A) Evaporator Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (D) x coil width (W) (inch) Output of Swing Motor (W) Fuse (A) Sound Power Level db (A)(SH/H/M/L) Sound PRESSURE Level db (A)(SH/H/M/L) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Outdoor Unit Compressor Type Compressor Oil L.R.A. (A) Compressor RLA(A) Compressor Power Input(W) Throttling Method Working Temp Range ( F) Condenser Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (H) x coil width (W) (inch) Fan Motor Speed (rpm) Output of Fan Motor (W) Fan Motor RLA (A) Air Flow Volume of Outdoor Unit (CFM) Fan Diameter (inch) Defrosting Method Sound Power Level db (A) Sound PRESSURE Level db (A) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Refrigerant Charge (oz) MCA MOP Connection Pipe Gas additional charge(oz/ft) Outer Diameter Liquid Pipe (inch) Outer Diameter Gas Pipe (inch) Max Height Distance (ft) Max Length Distance (ft) M4MCW1518A / M4TCS1518A 208 / 230 / 1 60Hz 18000 7100 20000 5800 / 5200 / 2100 1800 8.0 15.0 470 / 400 / 340 / 280 3.8 9.0 M4MCW1518A1N0A 1350 / 1200 / 1050 / 900 0.30 Aluminum Fin-Copper Tube 2/7 2-1/18 28 1/7 1 12 2.5 3.15 56 / 52 / 49 / 45 46 / 42 / 39 / 35 38 1/5 x 11 4/5 x 8 5/6 41 x 15 x 12 3/5 29.8 / 36.4 M4TCS1518A11NA Rotary RB68EP (POE Oil) 16.5 12.08 1440 Capillary 0-115 Aluminum Fin-Copper Tube 2/7 1-1/18 34 5/7 6/7 26 800 60 0.52 1883 20 1/2 Automatic Defrosting 66 56 37 3/5 x 27 5/9 x 15 3/5 40 1/2 x 18 x 29 1/2 90.4 / 100.3 35.3 16.0 25.0 0.2 1/4 1/2 65 130 2017 Ingersoll Rand All Rights Reserved 1 Sound PRESSURE Level @ 3.3 ft. db(a)

Unit Dimensions W D H 18K 4 27 7 3/16 Φ2 3/16 Φ2 3/16 1 1/2 7 1/2 5 1/2 Unit: inch Models W H D 18K 38 1/4 11 13/16 8 7/8 24K 42 1/2 12 13/16 9 11/16 13 3/8 35 27 9/16 15 5/8 38 22 14 5/16 Unit: inch

Clearance Requirements Space to the ceiling 6 in. 6 in. 6 in. 118 in. Air outlet side 66 in. Space to the floor The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent structures Space to the obstruction 12 in. Space to the wal l 9 7 in. 20 in. Air inlet side 12 in. 20 in. Air outlet side valve cover NOTE: The maximum recommended height from the floor to the bottom of the indoor unit is 11.5 ft. (3.5 m). Air Velocity Patterns for High Wall Max Horizontal Distance Unit: ft. (m) Model Cooling Mode Heating Mode 4MYW1618 30.2 (9.2) N/A

Performance Data Cooling Capacity 18,000 (Bthu/h) M4MCW1518A1/M4TCS1518A Cooling 18K Outdoor 68F DB (20C) 73F DB (23C) 80F DB (27C) 82F DB (28C) Coil air 57F WB (14C) 61F WB (16C) 67F WB (19C) 68F WB (20C) DB F DB C TC SHC TC SHC TC SHC TC SHC 0 18 9450 7400 9850 7700 11200 8750 11850 9300 5 15 10300 8050 10850 8500 12250 9600 12650 9900 14 10 11950 9350 12600 9900 14250 11150 14650 11500 23 5 13100 10250 14000 10950 16050 12550 16500 12950 32 0 13550 10650 14500 11400 16650 13050 17150 13450 41 5 14100 11050 15050 11800 17250 13550 17800 13950 50 10 14600 11450 15650 12250 17900 14050 18450 14450 59 15 15850 12450 17000 13300 18600 14550 19150 15000 68 20 18000 14100 19100 14950 20400 16000 21050 16500 77 25 17750 13900 18900 14800 20250 15850 20850 16350 86 30 16900 13250 18000 14100 19650 15400 20250 15850 95 35 16000 12500 16300 12800 18750 14700 19300 15100 104 40 15200 11900 15550 12200 17350 13600 17900 14000 113 45 14450 11300 15000 11750 16150 12650 16600 13000 Capacities in these performance tables reflect normal operation at the temperatures indicated. See specification tables above for certified values under prescribed test conditions.

Mini-Split Outdoor Unit Mechanical Specifications General This unit is fully charged from the factory for up to 25 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115 F. Cooling capacities with the mini-split air handler shown in the catalog are AHRI certified. The unit is ETL listed for outdoor application. Unit Casing The unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Refrigerant Controls Refrigeration system controls include condenser fan and compressor relay. High and low pressure controls are inherent to the compressor. A suction line multi function service valve is standard Compressor The compressor features internal over temperature and pressure protection; total dipped hermetic motor windings. Other features include: centrifugal oil pump and low vibration and noise. Condenser Coil The coil shall consist of aluminum finned coils brazed to copper tubing. The coil provides air flow resistance and efficient heat transfer. The coil is protected by the casing. Low Ambient Cooling Matched Ameristar ductless products, have cooling capabilities at outdoor ambient temperatures as low as 0 F. Mini-Split Indoor High Wall General The High Wall mounted type air handler shall be completely factory assembled including coil, condensate drain pan, fan motor, washable filter, air purifying filter and electric controls to be used with a wireless remote controller. Unit shall be shipped with a unit mounting plate. Unit shall be matched with an Ameristar outdoor unit, rated and tested in accordance with AHRI standard. Unit shall be ETL listed. Unit Casing Casing shall be provided with knockouts on the right, and left of the unit to facilitate piping and electrical connection on either side of the unit. An electrical service cover shall be provided to permit easy access to the electrical terminal strip. Discharge Airflow and Distribution System Unit shall have auto swing, dual horizontal blades to optimize the aperture outlet for vertical airflow and air distribution. Blade shall close automatically when the air conditioner is turned off to minimize dust entering the unit. Five-Step preset program on the remote controller shall be available to control the blade angle. Manually adjusted wide-angle louvers shall be provided to adjust the coverage and direction of airflow. Controls Units shall have the capability to be controlled remotely through wall-mounted wired options (sold separately) as well as a wireless remote option. Remote Controller The unit shall have a wireless infrared remote controller with easy reading digital display panel to start, stop and regulate the air conditioner from a distance. The wireless controller is available for all units. Healthy Filters The unit shall have an active carbon and catechin filter with the unit.the filters need to be cleaned at least once a year. 06/17 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

M4MCW1524A-SUB-1B TAG: 15 SERIES SUBMITTAL Specifications Single Zone Mini-Split Inverter System M4MCW1524A1N0A M4TCS1524A11NA MODEL - Cooling Only RATED Volts/PH Frequency (Hz) Rated Cooling Capacity (Btu/h): Minimum Cooling Capacity (@95F) (Btu/h): Maximum Cooling Capacity (@95F) (Btu/h): Total Capacity (W) (High/Standard/Low): Rated Power Input (W) Nominal Input Current (A) SEER Air Flow Volume (CFM) (H/M/L) Dehumidifying Volume (pt./h) EER (@95F) Indoor Unit Fan Motor Speed (r/min) (SH/H/M/L) Fan Motor RLA(A) Evaporator Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (D) x coil width (W) (inch) Output of Swing Motor (W) Fuse (A) Sound Power Level db (A)(SH/H/M/L) Sound PRESSURE Level db (A)(SH/H/M/L) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Outdoor Unit Compressor Type Compressor Oil L.R.A. (A) Compressor RLA(A) Compressor Power Input(W) Throttling Method Working Temp Range ( F) Condenser Pipe Diameter (inch) Row Fin Gap (inch) Coil length (L) x depth (H) x coil width (W) (inch) Fan Motor Speed (rpm) Output of Fan Motor (W) Fan Motor RLA (A) Air Flow Volume of Outdoor Unit (CFM) Fan Diameter (inch) Defrosting Method Sound Power Level db (A) Sound PRESSURE Level db (A) 1 Uncrated Dimension (W/H/D) (inch) Crated Dimension of Package (L/W/H) (inch) Net Weight /Gross Weight (lbs) Refrigerant Charge (oz) MCA MOP Connection Pipe Gas additional charge(oz/ft) Outer Diameter Liquid Pipe (inch) Outer Diameter Gas Pipe (inch) Max Height Distance (ft) Max Length Distance (ft) M4MCW1524A / M4TCS1524A 208 / 230 / 1 60Hz 22000 8600 23200 6600 / 6400 / 2500 2260 10.0 15.0 700 / 640 / 580 / 520 5.3 9.75 M4MCW1524A1N0 1250 / 1100 / 900 / 800 0.32 Aluminum Fin-Copper Tube 2/7 2-1/17 33 1/4 1 13 1/2 2.5 3.15 58 / 54 / 50 / 46 48 / 44 / 40 / 36 42 4/9 x 12 4/5 x 9 2/3 45 1/5 x 16 1/4 x 13 7/9 37.5 / 45.2 M4TCS1524A11N Rotary RB68EP (POE Oil) 25 11.29 1440 Capillary 0-115 Aluminum Fin-Copper Tube 3/8 2-1/18 33 1/3 1 3/4 26 800 60 0.4 1883 20 1/2 Automatic Defrosting 69 59 37 3/5 x 27 5/9 x 15 3/5 40 1/2 x 18 x 29 1/2 103.6 / 113.6 56.45 15.0 25.0 0.2 1/4 5/8 65 130 2017 Ingersoll Rand All Rights Reserved 1 Sound PRESSURE Level @ 3.3 ft. db(a)

Unit Dimensions W D H 8 1/8 27 7 5/16 24K Φ2 3/4 Φ2 3/4 1 11/16 6 3 1/8 Unit: inch Models W H D 18K 38 1/4 11 13/16 8 7/8 24K 42 1/2 12 13/16 9 11/16 13 3/8 35 27 9/16 15 5/8 38 22 14 5/16 Unit: inch

Clearance Requirements Space to the ceiling 6 in. 6 in. 6 in. 118 in. Air outlet side 66 in. Space to the floor The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent structures Space to the obstruction 12 in. Space to the wal l 9 7 in. 20 in. Air inlet side 12 in. 20 in. Air outlet side valve cover NOTE: The maximum recommended height from the floor to the bottom of the indoor unit is 11.5 ft. (3.5 m). Air Velocity Patterns for High Wall Max Horizontal Distance Unit: ft. (m) Model Cooling Mode Heating Mode M4MCW1524 31.2 (9.5) N/A

Performance Data Cooling Capacity 24,000 (Bthu/h) M4MCW1524A1/M4TCS1524A Outdoor 68F DB (20C) 73F DB (23C) 80F DB (27C) 82F DB (28C) Coil air 57F WB (14C) 61F WB (16C) 67F WB (19C) 68F WB (20C) DB F DB C TC SHC TC SHC TC SHC TC SHC 0 18 10850 8500 11350 8900 12850 10050 13100 10250 5 15 12100 9500 12800 10000 14450 11300 14850 11650 14 10 14050 11000 14850 11650 16750 13150 17250 13500 23 5 15400 12050 16450 12900 18850 14800 19450 15250 32 0 15950 12500 17100 13400 19600 15350 20150 15800 41 5 16550 13000 17700 13900 20300 15900 20900 16400 50 10 17200 13450 18400 14400 21050 16500 21700 17000 59 15 18650 14650 19950 15650 21850 17150 22550 17650 68 20 21150 16550 22450 17600 24000 18800 24750 19400 77 25 20900 16400 22250 17400 23800 18650 24500 19200 86 30 19850 15550 21200 16600 23150 18150 23800 18650 95 35 18800 14750 19200 15050 22050 17250 22700 17800 104 40 17900 14000 18300 14300 20450 16000 21050 16500 113 45 16950 13300 17600 13800 18950 14850 19550 15300 Capacities in these performance tables reflect normal operation at the temperatures indicated. See specification tables above for certified values under prescribed test conditions.

Mini-Split Outdoor Unit Mechanical Specifications General This unit is fully charged from the factory for up to 25 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115 F. Cooling capacities with the mini-split air handler shown in the catalog are AHRI certified. The unit is ETL listed for outdoor application. Unit Casing The unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Refrigerant Controls Refrigeration system controls include condenser fan and compressor relay. High and low pressure controls are inherent to the compressor. A suction line multi function service valve is standard Compressor The compressor features internal over temperature and pressure protection; total dipped hermetic motor windings. Other features include: centrifugal oil pump and low vibration and noise. Condenser Coil The coil shall consist of aluminum finned coils brazed to copper tubing. The coil provides air flow resistance and efficient heat transfer. The coil is protected by the casing. Low Ambient Cooling Matched Ameristar ductless products, have cooling capabilities at outdoor ambient temperatures as low as 0 F. Mini-Split Indoor High Wall General The High Wall mounted type air handler shall be completely factory assembled including coil, condensate drain pan, fan motor, washable filter, air purifying filter and electric controls to be used with a wireless remote controller. Unit shall be shipped with a unit mounting plate. Unit shall be matched with an Ameristar outdoor unit, rated and tested in accordance with AHRI standard. Unit shall be ETL listed. Unit Casing Casing shall be provided with knockouts on the right, and left of the unit to facilitate piping and electrical connection on either side of the unit. An electrical service cover shall be provided to permit easy access to the electrical terminal strip. Discharge Airflow and Distribution System Unit shall have auto swing, dual horizontal blades to optimize the aperture outlet for vertical airflow and air distribution. Blade shall close automatically when the air conditioner is turned off to minimize dust entering the unit. Five-Step preset program on the remote controller shall be available to control the blade angle. Manually adjusted wide-angle louvers shall be provided to adjust the coverage and direction of airflow. Controls Units shall have the capability to be controlled remotely through wall-mounted wired options (sold separately) as well as a wireless remote option. Remote Controller The unit shall have a wireless infrared remote controller with easy reading digital display panel to start, stop and regulate the air conditioner from a distance. The wireless controller is included with all units. Healthy Filters The unit shall have an active carbon and catechin filter with the unit.the filters need to be cleaned at least once a year. 06/17 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.